Iec 62040-5-3-2016
Iec 62040-5-3-2016
®
Edition 1 .0 201 6-1 0
I N TE RN ATI ON AL
S TAN D ARD
N ORM E
I N TE RN ATI ON ALE
colour
i n sid e
C o p yri g h t © 2 0 1 6 I E C , G e n e v a , S wi tz e rl a n d
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about I EC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local I EC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
IEC Central Office Tel.: +41 22 91 9 02 1 1
3, rue de Varembé Fax: +41 22 91 9 03 00
CH-1 21 1 Geneva 20 info@iec.ch
Switzerland www.iec.ch
Ab ou t th e I E C
The I nternational Electrotechnical Commission (I EC) is the leading global organization that prepares and publishes
I nternational Standards for all electrical, electronic and related technologies.
Ab o u t I E C p u b l i ca ti o n s
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
I E C Catal og u e - webstore. i ec. ch /catal og u e E l ectroped i a - www. el ectroped i a. org
The stand-alone application for consulting the entire The world's leading online dictionary of electronic and
bibliographical information on IEC International Standards, electrical terms containing 20 000 terms and definitions in
Technical Specifications, Technical Reports and other English and French, with equivalent terms in 1 5 additional
documents. Available for PC, Mac OS, Android Tablets and languages. Also known as the International Electrotechnical
iPad. Vocabulary (IEV) online.
I E C pu bl i cati on s s earch - www. i ec. ch /search pu b I E C G l os sary - s td . i ec. ch /g l oss ary
The advanced search enables to find IEC publications by a 65 000 electrotechnical terminology entries in English and
variety of criteria (reference number, text, technical French extracted from the Terms and Definitions clause of
committee,…). It also gives information on projects, replaced IEC publications issued since 2002. Some entries have been
and withdrawn publications. collected from earlier publications of IEC TC 37, 77, 86 and
CISPR.
I E C J u st Pu bl i s h ed - webstore. i ec. ch /j u stpu bl i sh ed
Stay up to date on all new IEC publications. Just Published I E C C u stom er S ervi ce C en tre - webstore. i ec. ch /csc
details all new publications released. Available online and If you wish to give us your feedback on this publication or
also once a month by email. need further assistance, please contact the Customer Service
Centre: csc@iec.ch.
A propos d e l 'I E C
La Commission Electrotechnique I nternationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos d es pu bl i cati on s I E C
Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la
plus récente, un corrigendum ou amendement peut avoir été publié.
Catal og u e I E C - webstore. i ec. ch /catal og u e E l ectroped i a - www. el ectroped i a. org
Application autonome pour consulter tous les renseignements Le premier dictionnaire en ligne de termes électroniques et
bibliographiques sur les Normes internationales, électriques. Il contient 20 000 termes et définitions en anglais
Spécifications techniques, Rapports techniques et autres et en français, ainsi que les termes équivalents dans 1 5
documents de l'IEC. Disponible pour PC, Mac OS, tablettes langues additionnelles. Egalement appelé Vocabulaire
Android et iPad. Electrotechnique International (IEV) en ligne.
Rech erch e d e pu bl i cati on s I E C - www. i ec. ch /search pu b
G l oss ai re I E C - s td . i ec. ch /g l ossary
La recherche avancée permet de trouver des publications IEC 65 000 entrées terminologiques électrotechniques, en anglais
en utilisant différents critères (numéro de référence, texte, et en français, extraites des articles Termes et Définitions des
comité d’études,…). Elle donne aussi des informations sur les publications IEC parues depuis 2002. Plus certaines entrées
projets et les publications remplacées ou retirées. antérieures extraites des publications des CE 37, 77, 86 et
CISPR de l'IEC.
I E C J u st Pu bl i s h ed - webstore. i ec. ch /j u stpu bl i sh ed
Restez informé sur les nouvelles publications IEC. Just S ervi ce Cl i en ts - webstore. i ec. ch /csc
Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur cette
Disponible en ligne et aussi une fois par mois par email. publication ou si vous avez des questions contactez-nous:
csc@iec.ch.
I E C 62 0 40 -5-3
®
Edition 1 .0 201 6-1 0
I N TE RN ATI ON AL
S TAN D ARD
N ORM E
I N TE RN ATI ON ALE
colour
i n sid e
P arti e 5-3 : AS I à ten s i on d e s orti e con ti n u e – P erform an ces e t exi g en ce s d 'es sai
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
Atten ti on ! Veu i l l ez vou s as s u rer q u e vou s avez ob ten u cette p u b l i cati on vi a u n d i s tri bu teu r ag ré é.
CONTENTS
FOREWORD . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... ... ... .. 5
1 Scope .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . 7
2 Norm ative references . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 8
3 Terms and definitions . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 8
3. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... .. 8
3. 2 System and component definitions . ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... .. 9
3. 3 Perform ance of systems and com ponents . .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... ... .. ... ... ... .. 1 1
3. 4 Specified values ‒ General .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. .. 1 3
3. 5 I nput values . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... . .. .. 1 6
3. 6 Output values . ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . . 1 7
4 Environm ental conditions . ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... 1 8
4. 1 Test environment . ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... 1 8
4. 2 Normal conditions ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... . .. ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... 1 8
4. 2. 1 Operation . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 1 8
4. 2. 2 Storage and transportation . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. 1 9
4. 3 Unusual conditions.. ... ... ... ... ... ... ... ... ... .. ... ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... 20
4. 3. 1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 20
4. 3. 2 Operation . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 20
4. 3. 3 Storage and transportation . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. 20
5 Electrical conditions, perform ance and declared values .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... . .. ... 20
5. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 20
5. 1 . 1 DC U PS configuration . ... ... ... ... ... ... .. ... ... ... ... ... . .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 20
5. 1 . 2 Markings and instructions ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . .. ... .. ... ... ... ... ... ... .. 21
5. 2 DC U PS input specification .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. .. 21
5. 2. 1 Conditions for normal m ode operation .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. . ... ... . 21
5. 2. 2 I nput characteristics to be declared by the m anufacturer ... ... ... ... .. ... ... ... ... ... .. 21
5. 2. 3 Characteristics and conditions to be identified by the purch aser .. ... ... ... ... ... ... 22
5. 3 DC U PS output specification ... ... .. ... ... ... ... ... ... ... ... ... .. . ... ... ... ... ... .. ... ... ... ... ... ... ... ... .. 22
5. 3. 1 Conditions for the DC U PS to suppl y a load .. ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. 22
5. 3. 2 Characteristics to be declared by the m anufacturer ... ... ... ... ... ... ... ... .. ... ... ... ... . 23
5. 3. 3 Characteristics and conditions to be identified by the purchaser .. ... ... ... ... ... ... 23
5. 3. 4 Performance classification .. ... ... ... ... ... ... ... ... ... ... ... . . ... ... ... ... ... ... ... ... ... ... ... ... ... . 23
5. 4 Stored energ y specification .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. 25
5. 4. 1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 25
5. 4. 2 Battery . ... ... .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... .. . ... .. ... ... . 25
5. 5 DC U PS switch specification ... ... .. ... ... ... ... ... ... ... ... ... .. . ... ... ... ... ... .. ... ... ... ... ... ... ... ... .. 26
5. 6 Comm unication circuits ... ... ... ... ... ... .. ... ... ... ... ... ... ... . .. ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . 26
6 DC U PS tests ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... . 26
6. 1 Summ ary . ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... ... . 26
6. 1 . 1 Venue, instrum entation and load .. ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... .. . ... ... ... ... ... 26
6. 1 . 2 Routine test ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... .. 27
6. 1 . 3 Site test .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... . . ... ... . 27
6. 1 . 4 Witness test ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... .. 28
6. 1 . 5 Type test .. ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... .. . ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 28
6. 1 . 6 Schedule of tests ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . .. ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... 28
6. 2 Routine test procedure . ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 29
I EC 62040-5-3: 201 6 © I EC 201 6 –3–
6. 2. 1 Environmental .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 29
6. 2. 2 Electrical .. ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... .. . ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 29
6. 3 Site test procedure .. ... ... ... ... ... ... ... ... ... .. ... ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... 31
6. 4 Type test procedure (electrical) .. .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... ... .. ... ... ... ... ... ... ... ... .. 31
6. 4. 1 I nput – AC supply compatibility . .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... ... .. ... ... ... ... ... ... .. 31
6. 4. 2 Output characteristics – Resistive load . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... . 33
6. 4. 3 Output characteristics – Constant power load . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. 37
6. 4. 4 Stored and restored energ y ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... .. 37
6. 5 Type test procedure (environm ental) . ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... ... ... ... ... 38
6. 5. 1 Environmental and transportation test methods . ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... 38
6. 5. 2 Storage... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... . 39
6. 5. 3 Operation . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 40
6. 5. 4 Acoustic noise .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 40
6. 6 DC U PS functional unit tests (where not tested as a complete DC U PS) .. ... .. ... ... .. 41
6. 6. 1 DC U PS rectifier tests . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... 41
6. 6. 2 DC U PS converter tests . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 41
6. 6. 3 DC U PS switch tests . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... 41
6. 6. 4 Stored energy/battery tests . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. 41
Annex A (informative) DC UPS configurations . ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... . 43
A. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 43
A. 2 Single DC U PS .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... .. 43
A. 2.1 I ntroduction ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... .. 43
A. 2.2 Basic single DC U PS .. ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. . ... ... ... ... ... .. ... ... ... ... ... . 43
A. 2.3 Scalable single DC U PS .. ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... .. . ... ... ... ... ... ... ... ... ... . 43
A. 3 Parallel DC U PS ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... .. 44
A. 3.1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 44
A. 3.2 Parallel non-redundant DC UPS ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... 44
A. 3.3 Parallel redundant DC U PS ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... .. 45
A. 3.4 Enhanced parallel redundant DC U PS .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. . ... ... . 45
A. 4 Dual bus .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. ... ... . 46
A. 4.1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 46
A. 4.2 Dual bus system 2( N + r) . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... . .. ... ... ... ... ... ... ... ... ... . 46
A. 4.3 Dual bus distribution ( N + r) .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 47
Annex B (informative) Topologies – DC U PS. ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . 48
B. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 48
B. 2 Basic topologies. ... ... ... ... .. ... ... ... ... ... ... ... ... .. . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... .. 48
B. 2.1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 48
B. 2.2 Direct energy storage connect . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 48
B. 2.3 Series converter connect . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 49
B. 2.4 Shunt converter connect .. ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 49
Annex C (inform ative) Purchaser specification guidelines .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . 51
C. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 51
Annex D (norm ative) I nput m ains failure – Test m ethod .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... 55
Annex E (informative) Dynam ic output performance – Measurement techniques . ... ... ... ... ... .. 56
E. 1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 56
E. 2 Graphical validating m ethod . ... ... ... ... ... ... ... ... ... ... ... .. ... ... .. . ... ... ... ... ... ... ... ... ... ... ... .. .. 56
Annex F (norm ative) DC U PS efficiency –Methods of m easurem ent ... ... ... ... ... ... ... .. ... ... ... ... .. 58
F.1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 58
–4– I EC 62040-5-3: 201 6 © I EC 201 6
F.2 Measurem ent conditions . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . 58
F. 2. 1 Environmental conditions . ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... . 58
F. 2. 2 Operational and electrical conditions . ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... . 58
F. 2. 3 I nstrum entation . ... ... ... ... .. ... ... ... ... ... ... .. . ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 58
F.3 Measurem ent m ethod .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... ... ... ... ... ... ... ... ... ... ... ... ... 59
F.4 Test report . ... ... ... ... ... ... ... ... .. ... ... ... ... ... .. . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . 59
Annex G (informative) Clim atic test . ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. ... ... ... ... ... ... ... ... ... ... ... ... .. 61
G.1 General . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... 61
G.2 Testing of com pliance to clim atic requirem ents ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . .. 61
Bibliograph y .. .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... 63
Figure 1 – Exam ples of basic electronic power converters .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 9
Figure 2 – Dynam ic output performance . ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 24
Figure A. 1 – Basic single DC UPS . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 43
Figure A. 2 – System sized for load ( N DC U PS units) – No redundancy ... ... ... ... ... ... ... ... ... ... .. 44
Figure A. 3 – System sized for load (N DC U PS units) – N + 1 redundancy .. ... ... ... ... ... ... ... ... .. 45
Figure A. 4 – System sized for load ( N DC U PS units) – N + r redundancy ... ... ... ... ... ... ... ... ... .. 46
Figure A. 5 – Dual bus DC UPS . ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 46
Figure A. 6 – Dual bus DC UPS variant . ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... .. 47
Figure B. 1 – Direct energy storage connect . ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... 49
Figure B. 2 – Series converter connect . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. 49
Figure B. 3 – Shunt converter connect .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . ... ... ... .. ... ... ... ... ... ... .. 50
Figure D.1 – Connection of test circuit ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . .. ... ... ... ... ... ... ... ... ... .. 55
Figure E. 1 – Example: N arrowband validation of dynam ic voltage response . .. ... ... ... ... ... ... ... . 56
Figure E. 2 – Example: Wideband validation of d ynam ic voltage response .. ... ... ... ... ... ... ... ... ... 57
Table 1 – Exam ple of power derating factors for use at altitudes above 1 000 m ... ... ... ... ... ... . 1 9
Table 2 – Com patibility levels for individual harm onic voltages in low voltage networks . ... ... . 21
Table 3 – DC U PS test schedule .. .. ... ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 28
Table 4 – Free fall testing . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... 39
Table C. 1 – DC U PS technical data – Manufacturer’s declaration . ... ... ... ... ... ... ... ... .. ... ... ... ... .. 51
Table G. 1 – Recom mended tests for I EC 60721 -3-3 – Class 3K2 (continuousl y
temperature-controlled enclosed locations; hum idity not controlled) . ... ... ... ... ... ... ... .. ... ... ... ... .. 61
I EC 62040-5-3: 201 6 © I EC 201 6 –5–
U N I N T E RRU P T I B L E P O WE R S YS T E M S ( U P S ) –
P a rt 5 -3 : D C o u tp u t U P S – P e rfo rm a n c e a n d te s t re q u i re m e n ts
FOREWORD
1 ) The I nternati on al Electrotechni cal Comm ission (I EC) is a worl d wid e organization for stan dardization com prisin g
all n ation al el ectrotechnical comm ittees (I EC National Comm ittees). The object of I EC is to prom ote
internati onal co-operation on all q uestions concerni ng stand ardi zati on in the el ectrical an d electronic fi elds. To
this en d and in additi on to other acti vities, I EC pu blish es I nternational Stan dards, Techn ical Specificati ons,
Technical Reports, Publicl y Avail abl e Specificati ons (PAS) an d Gu ides (h ereafter referred to as “I EC
Publication(s)”). Th ei r preparation is entrusted to tech nical comm ittees; any I EC N ational Comm ittee interested
in the subj ect dealt with m ay partici pate in this preparatory work. I nternational, governm ental an d n on -
governm ental organ izations l iaising with th e I EC also participate i n this preparation. I EC collaborates closel y
with the I ntern ational Organi zation for Stand ardization (I SO) in accordance with con ditions determ ined by
agreem ent between th e two organi zati ons.
2) The form al decisions or ag reem ents of I EC on tech nical m atters express, as n early as possible, an i nternati onal
consensus of opi nion on the rel evant subjects since each technical com m ittee has representati on from all
interested I EC N ational Com m ittees.
3) I EC Publications have the form of recom m endations for international use an d are accepted by I EC National
Com m ittees in that sense. While all reasonable efforts are m ade to ensure that the tech nical content of I EC
Publications is accu rate, I EC cann ot be h eld responsi ble for th e way in which th ey are used or for an y
m isinterpretation by an y en d u ser.
4) I n order to prom ote intern ational u niform ity, I EC National Com m ittees und ertake to apply I EC Publications
transparentl y to the m axim um extent possible i n their national an d regi on al publicati ons. Any d ivergence
between an y I EC Publication and the correspondi ng national or regi on al publicati on sh all be clearl y in dicated in
the latter.
5) I EC itself d oes n ot provi de an y attestation of conform ity. I n dependent certificati on bodies provi de conform ity
assessm ent services and, in som e areas, access to I EC m arks of conform ity. I EC is not responsi ble for an y
services carri ed out by ind ependent certification bodi es.
6) All users shou ld ensure that th ey h ave the l atest editi on of thi s publicati on.
7) No liability shall attach to I EC or its directors, em ployees, servants or ag ents inclu din g in divi du al experts an d
m em bers of its tech nical com m ittees and I EC Nati onal Com m ittees for any person al i nju ry, property d am age or
other dam age of any n ature whatsoever, whether di rect or indirect, or for costs (includ i ng leg al fees) and
expenses arisi ng out of the publ ication, use of, or relian ce upon, this I EC Publicati on or any other I EC
Publications.
8) Attention is drawn to th e N orm ative references cited in th is publ ication. Use of the referenced publ ications is
indispensable for the correct applicati on of this publication.
9) Attention is drawn to the possibility that som e of the elem ents of this I EC Publication m ay be the su bject of
patent rig hts. I EC shall not be held responsibl e for identifyi ng any or all such patent ri ghts.
The text of this docum ent is based on the following docum ents:
Full inform ation on the voting for the approval of this docum ent can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the I SO/I EC Directives, Part 2.
A list of all parts of the I EC 62040 series, under the general title Un in te rrup tib le p o we r
The committee has decided that the contents of th is publication will rem ain unchanged until
the stability date indicated on the I EC website under "http: //webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• am ended.
u n d e rs t a n d i n g of i ts c o n te n ts . U s e rs s h ou l d t h e re fo re p ri n t th i s d o cu m en t u sin g a
c o l o u r p ri n t e r.
I EC 62040-5-3: 201 6 © I EC 201 6 –7–
U N I N T E RRU P T I B L E P O WE R S YS T E M S ( U P S ) –
P a rt 5 -3 : D C o u tp u t U P S – P e rfo rm a n c e a n d te s t re q u i re m e n ts
1 S cop e
This part of I EC 62040 establishes the perform ance and test requirements applied to
movable, stationary and fixed electronic that
D C u n i n t e rru p t i b l e p o w e r s y s t e m s ( D C U P S )
– incorporate an , and
e n e rg y s t o ra g e d e v i c e
in I EC publications referred to in the bibliograph y that appl y so far that they are not in
contradiction with this docum ent.
DC s have been developed over a wide range of power, from less than a hundred watts
U PS
to m egawatts, to m eet requirements for availability and quality of power to a variety of loads.
Refer to Annexes A and B for information on typical configurations and topologies.
DC U PS
This docum ent also includes perform ance and test requirem ents related to
DC U PS
of l oad .
p o we r
NOTE 1 This docum ent recognises that power availability to inform ation tech nol og y (I T) equi pm ent represents a
m ajor UPS appl ication. The DC output characteristics specified in this docum ent are therefore also aim ed at
UPS
ensuring com patibil ity with the requi rem ents of I T equipm ent. This, subject to any l im itation stated in the
m anufacturer’s decl aration, i n cludes requ irem ents for stead y state and voltag e variati on as well as for
t ra n s i e n t
NOTE 2 Test loads specified in this docum ent sim ulate both resistive an d characteristics.
co n s ta n t p o wer l oad
Thei r use is prescribed with the objective of verifyi ng d esig n an d perform ance, as declared by the m anufacturer,
and al so of m inim ising any com plexity and energ y consum pti on d uri ng th e tests.
–8– I EC 62040-5-3: 201 6 © I EC 201 6
The following docum ents are referred to in the text in such a way that som e or all of their
content constitutes requirements of this docum ent. For dated references, onl y the edition
cited applies. For undated references, the latest edition of the referenced docum ent (including
an y am endm ents) applies.
sta te
I EC 601 46-1 -1 : 2009, Se m ico n ductor con ve rte rs – Ge n e ra l re quire m e n ts a n d lin e com m uta te d
I EC 601 46-2: 1 999, Se m ico n ductor co n ve rte rs – Pa rt 2: Se lf-co m m uta te d se m ico n ductor
I EC 60364-1 : 2005, L o w- vo lta ge e le ctrica l in sta lla tion s – Pa rt 1: Fun da m e n ta l p rin cip le s ,
corre la tio n and tra n sform a tio n of e n viro n m e n ta l con ditio n cla ss e s of IEC 60721 - 3 to th e
IEC 61 000-2-2: 2002, Ele ctro m a gn e tic com p a tib ility (EMC) – Pa rt 2- 2: En viro n m e n t –
Co m p a tib ility le ve ls for lo w- fre que n cy co n ducte d disturb a n ce s a n d sign a llin g in p ub lic lo w-
for UPS
IEC 62040-2, Un in te rrup tib le p o we r syste m s (UPS) – Pa rt 2: Ele ctro m a gn e tic co m p a tib ility
(EMC) re quire m e n ts
ISO 7779, A co ustics – Me a s ure m e n t o f a irb orn e n o is e e m itte d b y in form a tio n te ch n o logy a n d
3. 1 G en eral
For the purposes of this document, the followi ng terms and definitions apply.
ISO and I EC m aintain terminological databases for use in standardization at the following
addresses:
I EC 62040-5-3: 201 6 © I EC 201 6 –9–
3.2.2
electronic power converter
power converter
converter
operative unit for electronic power conversion, comprising one or more electronic valve
devices, transform ers and filters if necessary and auxiliaries if an y
Note 1 to entry: I n Eng lish, th e two spellin gs "con vertor" an d " con verter " are in use, an d both are correct. I n this
docum ent, the spell ing " converter" is used in order to avoi d dupl ications.
Note 2 to entry: Fi gu re 1 sh ows exam ples of basic electron ic power converters .
rectifier inverter
[SOU RCE: I EC 60050-551 : 1 998, 551 -1 2-01 , modified — N ote 2 to entry and the figure have
been added. ]
3.2.3
functional unit
< DC U PS > com plete subassem bl y that perform s a given function in a DC U PS
EXAMPLE Converter, rectifier.
– 10 – I EC 62040-5-3: 201 6 © I EC 201 6
3.2.4
energy storage device
system consisting of single or multiple devices and designed to provide power to the DC UPS
for the required stored energy time
Note 1 to entry: Notwithstanding chal lenges with respect to recharg e, exam ples of an energ y storage device
includ e but are n ot lim ited to battery, dou ble-l ayer capacitor (“su per” or “ultra” capacitor), flywh eel and fu el-cell
system s.
3.2.5
internal DC bus
integral DC power interface of the com ponents of the DC UPS ( battery , DC circuits, rectifiers,
converters , etc) including points of connection for the DC output but excluding the ph ysical
DC output
3.2.6
battery
one or m ore electrochem ical cells fitted with devices necessary for use, for exam ple case,
term inals, m arking and protective devices
Note 1 to entry: A typical battery consists of
– one stri ng of a quantity of seri es connected cell s, or
– two or m ore paral lel ed strin gs, each strin g containi ng the sam e qu antity of seri es connected cells
[SOU RCE: I EC 60050: 2004, 482-01 -04], modified — The word "electrochem ical" has been
added to the definition, as well as the note to entry. ]
3.2.7
secondary battery
<electrochem ical cells> battery intended to be discharged and recharged
Note 1 to entry: A val ve reg u lated secondary battery consists of cells which are closed but h ave a valve which
allows th e escape of g as if the internal pressu re exceeds a predeterm ined valu e. Valve regul ated l ead -aci d cells
are abbrevi ated "VRLA cells" (see I EC 60050-482: 2004, 482-05-1 5).
Note 2 to entry: A vented secondary battery consists of cells havin g a cover provided with an openin g throu gh
which prod ucts of electrol ysis and evaporati on are all owed to escape freely, or throug h a venting system , from the
cell to the atm osphere (see I EC 60050-482: 2004, 482-05-1 4).
3.2.8
flywheel storage system
mechanical energy storage device wherein stored kinetic energy can be converted to DC
power during stored energ y m ode of operation
3.2.9
battery charger
device for battery charging and maintaining the charged state of the battery
3.2.1 0
DC UPS switch
controllable switch used in accordance with applicable requirements for load power continuity
to interconnect or isolate power ports of DC UPS units , or load
3.2.1 1
DC UPS rectifier
electronic converter for rectification
I EC 62040-5-3: 201 6 © I EC 201 6 – 11 –
3.2.1 2
interrupter
DC UPS switch which is capable of m aking, carrying and breaking currents under norm al
circuit conditions, m aking and carrying currents for a specified tim e and breaking currents
under specified unusual circuit conditions
3.2.1 3
DC distribution network
DC system that connects sources and storage system s to distributed loads
3.2.1 4
AC input power
grid input power
product of instantaneous com ponents of the alternating grid input current and voltage
averaged over a complete cycle
3.2.1 5
DC UPS unit
complete DC UPS consisting of at least one of each of the following functional units : DC
UPS, DC output power module, and battery or other energy storage device(s)
3.2.1 6
single DC UPS
DC UPS com prising onl y one DC UPS unit
3.2.1 7
parallel DC UPS
DC UPS com prising two or m ore DC UPS units operating in parallel
3.2.1 8
redundant system
system in which one or m ore functional units can fail without affecting continuity of load
power
3.2.1 9
parallel redundant DC UPS
DC UPS with a number of paralleled load sharing DC UPS units , which, upon failure of one
or m ore DC UPS units , can take over full load with the remaining units
3.3.2
stand-by power
external electrical power source intended to replace primary power in the event of primary
power failure
3.3.3
power failure
an y variation in power supply which can cause unacceptable performance of the load
equipm ent
– 12 – I EC 62040-5-3: 201 6 © I EC 201 6
3.3.4
continuity of load power
maintenance of power delivery within the limits specified for the DC UPS output under
abnormal utility suppl y conditions
3.3.5
battery ripple current
superimposed effective (RMS) alternating component of the battery current
3.3.6
normal mode
stable m ode of operation that the DC UPS attains under the following conditions:
a) AC input suppl y is within required tolerances and supplies the DC UPS ;
b) the energy storage device remains charged or is under recharge;
c) the load is within the specified rating of the DC UPS
3.3.7
stored energy mode of DC UPS operation
stable m ode of operation that the DC UPS attains under the following conditions:
a) AC input power is disconnected or is out of required tolerance;
b) all power is derived from the energy storage device ;
c) the load is within the specified rating of the DC UPS
3.3.8
movable DC UPS
equipm ent which is either 1 8 kg or less in mass and not fixed, or equipment with wheels,
castors or other m eans to facilitate m ovement as required to perform its intended use
Note 1 to entry: Derived from I EC 60950-1 .
3.3.9
stationary DC UPS
equipm ent that is not movable equipment
3.3.1 0
fixed DC UPS
stationary equipm ent which is fastened or otherwise secured at a specific location
Note 1 to entry: Derived from I EC 60950-1 .
3.3.1 1
skilled person
person with relevant education and experience to enable him or her to perceive risks and to
avoid hazards which the equipment can create
[SOU RCE: I EC 60050-826: 2004, 826-1 8-01 , m odified — The reference to "electricity" has
been replaced by a reference to "the equipment". ]
3.3.1 2
type test
conform ity test made on one or m ore items representative of the production
3.3.1 3
routine test
conform ity test made on each individual item during or after m anufacture
[SOU RCE: I EC 60050-1 51 : 2001 , 1 51 -1 6-1 1 , modified — The words "of a m achine, device or
equipm ent" have been added. ]
3.4.2
rated value
value of a quantity used for specification purposes, generall y established by a m anufacturer
for a specified set of operating conditions of a component, device, equipm ent, or system
[SOU RCE: I EC 60050-1 51 : 2001 , 1 51 -1 6-08, modified — The words "generall y" and "by a
manufacturer" have been added. ]
3.4.3
reference test load
rated DC load
load or condition in which the output of the DC UPS delivers the power (W) for which the DC
UPS is rated
Note 1 to entry: Rated l oad is a value of load used for specification pu rposes, gen erall y establ ished by a
m anufacturer for a specified set of operatin g con ditions of a com ponent, d evice, eq uipm ent, or system .
3.4.4
resistive load
load that when supplied from a source with a variable voltage presents a resistive impedance
that for practical purposes is constant
3.4.5
constant power load
load that when supplied from a source with a variable voltage V presents a resistive
im pedance R that for practical purposes varies so that the active power P consumed by the
circuit is constant, i. e. P = V2 /R = constant
3.4.6
step load
instantaneous addition or removal of electrical loads
3.4.7
light load
condition at which the DC UPS supplies approximatel y 1 0 % of rated output power
3.4.8
nominal value
value of a quantity used to designate and identify a component, device, equipment, or system
Note 1 to entry: The nominal value is generall y a round ed value.
3.4.9
tolerance band
range of values of a quantity within specified lim its
3.4.1 0
deviation
difference between the actual value and the desired value of a variable quantity at a given
instant
[SOU RCE: I EC 60050-351 : 201 3, 351 -41 -04, modified – The note to entry has been deleted. ]
3.4.1 1
current limit
current lim it control
function that limits a current to its prescribed m axim um value
3.4.1 2
rated voltage
Vrated
rated value of the voltage assigned by the m anufacturer to a component, device or
equipment and to which operation and perform an ce characteristics are referred
Note 1 to entry: A DC UPS may h ave m ore than one rated voltage for its input an d for its output.
Note 2 to entry: For DC UPS with th ree-phase i nput, th e lin e-to-l ine voltage applies.
3.4.1 3
rated voltage range
input or output voltage range as declared by the m anufacturer expressed by its lower and
upper rated voltages
Note 1 to entry: A DC UPS may h ave m ore than one rated voltage range for its input an d for its output.
Note 2 to entry: For DC UPS with th ree-phase i nput, th e lin e-to-l ine voltage applies.
3.4.1 4
RMS voltage variation
difference between the RMS voltage and the corresponding previousl y undisturbed RMS
voltage
Note 1 to entry: For the pu rposes of this docum ent, th e term “vari ation” has the followin g m eaning: the difference
of the valu es of a qu antity before and after a ch ang e of an infl uenced qu antity.
3.4.1 5
rated current
input or output current of the equipm ent assigned by the manufacturer for a specified
operating condition
[SOU RCE: I EC 60050-442: 1 998, 442-01 -02 modified — The word "current" has been replaced
by "input or output current" and the words "of an accessory" have been deleted. ]
3.4.1 6
active power
under periodic conditions, m ean value, taken over one period T, of the instantaneous power p :
T
P= 1 ⋅
∫ p ⋅ dt
T
0
Note 1 to entry: Under sin usoidal con ditions, the active power is the real part of the com pl ex power.
I EC 62040-5-3: 201 6 © I EC 201 6 – 15 –
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -42, m odified — The note 3 to entry has been added. ]
3.4.1 7
apparent power
product of the RMS values of voltage and current at a port:
S = UI
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -41 , m odified — Onl y RMS values are considered. ]
3.4.1 8
power factor
ratio of the absolute valu e of the active power P to the apparent power S :
P
λ=
S
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -46, modified — The words "under periodic
conditions" have been deleted". ]
3.4.1 9
DC UPS efficiency
ratio of output active power to input active power under specified testing conditions
Note 1 to entry: Test conditions for DC UPS efficiency are foun d in An nex F.
3.4.20
rated frequency
input frequency of the equipment assigned by the manufacturer for a specified operating
condition
3.4.21
frequency variation
variation of the input frequency
3.4.22
total harmonic distortion
THD
ratio of the RMS value of the harmonic content of an alternating quantity to the RMS value of
the fundam ental component quantity
Note 1 to entry: The En glish abbreviati on THD is also used in French.
[SOU RCE: I EC 60050-551 : 1 998, 551 -1 7-06, modified — The note to entry has been added. ]
3.4.23
harmonic components
com ponents of the harmonic content as expressed in terms of the order and RM S values of
the Fourier series terms describing the periodic function
– 16 – I EC 62040-5-3: 201 6 © I EC 201 6
3. 4. 2 4
h a rm o n i c c o n t e n t
3 . 4. 2 5
t ra n s i e n t
3 . 4. 2 6
s t o re d e n e rg y t i m e
minim um time during which the DC U PS , under specified service conditions, will ensure
, when the
con ti n u i ty of l o ad p o we r fails
p ri m a ry p o w e r
3 . 4. 2 7
c u t - o ff v o l t a g e
3. 4. 2 8
re s t o re d e n e rg y t i m e
maxim um tim e required to, under n o rm a l mod e of operation and with the charging capacity
installed, recharge the e n e rg y s t o ra g e d evi ce of the DC so that
U PS s t o re d e n e rg y ti m e
3 . 4. 2 9
a m b i e n t t e m p e ra t u re
tem perature of the air or other medium where the equipment is to be used
Note 1 to entry: Duri ng th e measurem ent of the am bi en t t e m p e ra t u re the m easuring i nstrum ent/probe shoul d be
shield ed from drau ghts an d rad iant h eatin g.
[SOU RCE: I EC 60050-826: 2004, 826-1 0-03, m odified — The adj ective "average" has been
deleted, and the definition has been rephrased. ]
3. 5 I n p u t va l u es
3. 5. 1
i n p u t v o l t a g e t o l e ra n c e
maxim um variation of stead y-state input voltage specified by the manufacturer for n o rm a l
mod e operation
3. 5. 2
i n p u t fre q u e n c y t o l e ra n c e
maxim um variation of stead y-state input frequency specified by the m anufacturer for n o rm a l
m od eoperation
3. 5. 3
i n p u t p o w e r fa c t o r
d evi ce
I EC 62040-5-3: 201 6 © I EC 201 6 – 17 –
3.5.4
DC UPS rated input current
input current with DC UPS operating in normal mode , at rated input voltage, rated load and
with a full y charged energy storage device
3.5.5
DC UPS maximum input current
input current with DC UPS operating in normal mode , at worst-case input voltage, rated load
and with a full y depleted energy storage device
3.5.6
DC UPS inrush current
maximum instantaneous value of the input current when the DC UPS is switched on for
normal mode
3.5.7
input current distortion
maximum input current harmonic distortion, in normal mode
3.5.8
supply impedance
im pedance at the input term inals to the DC UPS with the DC UPS disconnected
3.5.9
high impedance failure
failure where the supply impedance is regarded as infinite
3.5.1 0
low impedance failure
failure where the supply impedance is negligible
3.5.1 1
prospective short-circuit current
Icp
RMS value of the current which would flow if the suppl y conductors to the circuit are short
circuited by a conductor of negligible impedance
3.6.2
output voltage tolerance
m axim um variation of stead y-state output voltage with the DC UPS operating in normal
mode or in stored energ y m ode
3.6.3
output current
DC value of the current (unless otherwise specified for a particular load) from the output
terminals
3.6.4
overload capability
ratio of output current to rated current over a given tim e
– 18 – I EC 62040-5-3: 201 6 © I EC 201 6
3.6.5
output power
power available at the DC UPS output terminals
3.6.6
load sharing
sim ultaneous suppl y of power to a load from two or m ore power sources
EXAMPLE One load bus bei n g suppli ed from two or m ore parall eled DC UPS units .
Note 1 to entry: The share all ocated to each power source is not necessaril y the sam e .
3.6.7
rated output power
continuous output power as declared by the m anufacturer
3.6.8
ripple voltage
alternating voltage component of the voltage on the DC side of a functional unit
[SOU RCE: I EC 60050-551 : 1 998, 551 -1 7-27, m odified — The word "convertor" has been
replaced by "functional unit". ]
4 Environmental conditions
4.1 Test environment
The test environm ent applicable to this document shall, unless otherwise agreed between
manufacturer/supplier and purchaser, comply with pollution degree 2 of I EC 60664-1 and the
conditions defined in Clause 4.
NOTE Polluti on d eg ree is a characteristic of an envi ron m ent and is detail ed i n I EC 60664-1 from wh ere the
following is d eri ved.
– Pollution degree 1 applies where there is n o polluti on or on ly dry, non-conducti ve poll ution.
– Pollution d eg ree 2 applies where th ere is onl y n on-cond uctive pol lution th at m ight tem poraril y becom e
conducti ve d ue to occasional condensati on.
– Pollution degree 3 applies where a l ocal envi ronm ent withi n the equipm ent is subj ect to con ductive pol lution, or
to dry non-cond uctive poll ution that coul d becom e cond uctive due to expected cond ensati on.
NOTE A requi rem ent for th e DC UPS to perform when operati ng beyond the m inim um am bient rang es is
considered an u nusu al con dition. See 4. 3.
4.2.1 .2 Altitude
A DC U PS conform ing to this docum ent shall be designed to operate as rated at an altitude
up to and including 1 000 m above sea level.
If agreed between the manufacturer/supplier and the purchaser that the DC U PS shall operate
at a specific altitude in excess of 1 000 m , the manufacturer shall state, for that altitude:
– new rated output power, if different from the rated output power specified for normal
conditions.
NOTE The fol lowing Tabl e 1 i s provid ed for gui dance. I t is an exam ple of the power deratin g requi red by altitu de.
Table 1 – Example of power derating factors for use at altitudes above 1 000 m
Al titude Derating factor
m feet Convection cooling Forced air cooling
1 000 3 300 1 , 000 1 , 000
1 200 4 000 0, 994 0, 990
1 500 5 000 0, 985 0, 975
2 000 6 600 0, 970 0, 950
2 500 8 300 0, 955 0, 925
3 000 1 0 000 0, 940 0, 900
3 500 1 1 600 0, 925 0, 875
3 600 1 2 000 0, 922 0, 870
4 000 1 3 200 0, 91 0 0, 850
4 200 1 4 000 0, 904 0, 840
4 500 1 5 000 0, 895 0, 825
5 000 1 6 500 0, 880 0, 800
This table is d eri ved from ANSI C57. 96-1 999 for loadin g of d ry-type distributi on and power transform ers.
Values are generally calculated by i nterpolation for altitu des not listed.
Containers not designed for wet (condensing) ambient conditions shall be m arked by
adequate warning labels.
The stored energy device m ay require other storage and transportation conditions, for
example for a battery the duration of high or low ambient temperature can affect the battery
– 20 – I EC 62040-5-3: 201 6 © I EC 201 6
life. The battery m anufacturer typicall y provides instructions for battery transportation,
storage and recharging.
4.3.2 Operation
Unusual operating conditions to be identified include the following:
– pollution degree in excess of 2 (see Note in 4. 1 ) ;
– temperature and relative humidity conditions exceeding the ranges listed in 4. 2;
– altitude conditions exceeding those listed in 4.2;
– exposure to abnormal vibration, shocks, tilting;
NOTE 1 This is a concern for DC UPS instal led i n a veh icle or m arin e vessel.
– exposure to earthquake acceleration forces;
NOTE 2 M ore details are gi ven in I EC 60068-3-3.
– electromagnetic immunity exceeding the applicable requirem ents in I EC 62040-2;
– radioactive im munity to radiation levels exceeding those of the natural background;
– an y of the following: moisture, steam, fungus, insects, verm in dust, abrasive dust,
corrosive gases, salt laden air or contam inated cooling refrigerant, damaging fum es,
explosive m ixtures of dust or gases, restriction of ventilation (for DC U PS and/or battery ),
radiated or conducted heat from other sources.
4.3.3 Storage and transportation
Unusual storage and transportation conditions to be identified include the following:
– tem perature and relative hum idity conditions exceeding the ranges listed in 4.2;
– altitude conditions exceeding those listed in 4.2;
– exposure to abnorm al vibration, shocks, tilting and to earthquake acceleration forces;
– special transportation and equipment handling requirem ents.
5. 1 . 2 M a rki n g s a n d i n s t ru c t i o n s
DC com pl ying with this document shall be marked and supplied with adequate
U PS
instructions for the installation and operation of the for its controls and indications. DC U PS
5. 2 D C U P S i n p u t s p e c i fi c a t i o n
5. 2 . 1 C o n d i t i o n s fo r n o rm a l m o d e o p e ra t i o n
A DC conforming to this docum ent shall be compatible with public low-voltage supplies
U PS
b) ± 1 0 % of
R M S v o l t a g e v a ri a t i o n ; ra t e d v o l t a g e
c) ra t e d ; fre q u e n c y
d) ± 2 % of
fre q u e n c y v a ri a t i o n ; ra t e d fre q u e n c y
harmonic voltages according to the compatibility levels for individual harm onic voltages in
low-voltage networks given in Table 2. See N ote 3 below;
g) voltages, superimposed high -frequency voltages and other electrical noise such
t ra n s i e n t
separatel y gen erated supplies are generall y requi red to m eet m ore severe con ditions. The purchaser then specifies
such cond itions as appl icabl e. I n the absence of such i nform ation, the m anufacturer/suppli er appli es thei r
experience as to the com patibil ity of the desig n for th e intend ed install ati on.
NOTE 3 Com pati bility levels for in dividu al h arm onic voltages in public l ow-vol tage n etworks are specifi ed i n
I EC 61 000-2-2. The Table 2 below is an extract from I EC 61 000-2-2: 2002 presentin g such com patibility levels
(RMS valu es as percent of RM S valu e of the fu nd am ental com ponent).
T a b l e 2 – C o m p a t i b i l i t y l e v e l s fo r i n d i v i d u a l h a rm o n i c v o l t a g e s i n l o w v o l t a g e n e t w o rk s
Od d h a rm o n i c s Odd h a rm o n i c s E ve n
a
n o n -m u l ti p l e o f 3 m u l ti p l e o f 3 h a rm o n i c s
H a rm o n i c H a rm o n i c H a rm o n i c H a rm o n i c H a rm o n i c H a rm o n i c
o rd e r vo l ta g e o rd e r vo l ta g e o rd e r vo l ta g e
n % n % n %
5 6 3 5 2 2
7 5 9 1 ,5 4 1
11 3, 5 15 0, 4 6 0, 5
13 3 21 0, 3 8 0, 5
17 ≤ n ≤ 49 2, 27 × (1 7/ n ) – 0, 27 21 ≤ n ≤ 45 0, 2 10 ≤ n ≤ 50 0, 25 × (1 0/ n ) + 0, 25
a The l evels g iven for od d h arm onics that are m ultipl es of th ree appl y to zero sequence harm onics. Also, on a
three-phase n etwork without a neutral conductor or with out load con nected between lin e and g rou nd, the
val ues of th e 3 rd an d 9 th harm onics m ay be m uch lower than the com patibil ity l evels, d ependi ng on the
unbalance of the system .
5. 2 . 2 I n p u t c h a ra c t e ri s t i c s t o b e d e c l a re d b y t h e m a n u fa c t u re r
The m anufacturer shall declare the actual and applicable input characteristics. I n addition to
those covered in 5. 2. 1 , the following characteristics shall be declared:
– 22 – I EC 62040-5-3: 201 6 © I EC 201 6
a) number of phases;
b) neutral requirements;
c) rated current ;
d) power factor at rated current ;
e) inrush current characteristics;
f) m axim um stead y state current at the worst-case condition, including the effect of battery
charging, mains tolerance (for example ± 1 0 % voltage tolerance) and an y continuousl y
permitted overload; and, where applicable, curve of current against time;
g) total harmonic distortion (THD) of current and m inimum prospective short-circuit
current ( Icp ) required from the AC input suppl y for compliance with the THD of current
declared;
NOTE 1 For THD current com pliance purposes th e m inimum prospective short-circuit current requ irem ent is
generall y gi ven as a m ultipl e of the rated in put cu rrent of the DC UPS . Th e valu e is typi cally 33 tim es for rated
input current ≤ 300 A an d 20 tim es for rated in put current > 300 A. For exam ple for a DC UPS with 1 6 A of rated
input cu rrent, the m inim um prospective short-circui t current from the AC input su ppl y is 33 × 1 6 A = 528 A.
h) earth leakage current characteristics (where in excess of 3, 5 m A);
i) AC power distribution system compatibility (TN, TT or I T as defined in I EC 60364-1 ).
NOTE 2 The d eclaration wh en in th e form of a technical data sheet is typicall y inclu d ed in th e user m anu al .
Annex C presents a technical d ata sheet for g uid ance.
Further, the purchaser shall identify an y particular conditions that may be required by national
wiring regulation and an y adverse or special service conditions including
a) pre-existing harmonic voltage distortion when in excess of 75 % of the I EC 61 000-2-2
com patibility levels at the intended point of coupling of the DC UPS . Refer to N ote 3 in
5. 2. 1 ,
b) requirements for compatibility with characteristics of protective d evices of the DC UPS
input suppl y,
c) requirements for all-pole isolation of the DC UPS from the AC input suppl y, and
d) stand-by power generator characteristics, if an y.
NOTE I EC 60034-22 presents characteristics for intern al com bustion engi ne-d ri ven gen erating sets.
Such service conditions and deviations may require special design and/or protection
features.
Further, the purchaser shall identify an y particular condition that may be required by national
wiring regulation and an y adverse or special load condition, including
a) inrush and start-up characteristics,
b) time varying characteristics including period and duty cycle,
c) independent earthing of an y output polarity required ,
d) load distribution facilities,
e) requirements for all polarities of the DC UPS to be isolated from the load via a disconnect
device,
f) coordination requirem ents with downstream protective devices,
g) future extension/expansion requirem ents,
h) functional safety (see I EC 61 508 (all parts)),
i) degree of redundancy (see Annex A), and
j) automatic load shedding.
5.3.4 Performance classification
The manufacturer shall classify the DC UPS com pl ying with this document in accordance with
the coding
– 24 – I EC 62040-5-3: 201 6 © I EC 201 6
XX
where X is an alpha character.
The first X character denotes the output voltage variation from stead y-state when operating
in normal mode and a step load is applied as defined in 6.4. 2. 9. 3.
The second X character denotes the output voltage variation from stead y-state when
operating in stored energy mode and a step load is applied as defined in 6.4. 2. 9. 4.
+5 %
Nominal
+11 %
value 0
N limits
-5 %
-2 0
W limits -22%
-32 %
-4 0
-6 0
-8 0
-1 0 0
0 ,0 0 1 0 ,0 1 0 ,1 1 10 1 00 1 0 00 1 0 00 0 1 00 000
NOTE 1 Th e lim its m entioned in Fig ure 2 are representati ve of req uirem ents for switch-m ode power su ppl ies
com patible with I TU-T L. 1 200 requi rem ents.
NOTE 2 The obj ective of classifying DC UPS by perform ance is to provi de a com m on base on which al l DC UPS
m anufacturers/suppl ier’s data are eval uated. This enables purch asers, for sim ilar DC UPS power ratings , to
com pare products from different m anufacturers un der the sam e m easurem ent conditi ons.
NOTE 3 Purch asers are rem inded that due to the di versity of load types, DC UPS m anufacturers' data are based
on in dustry stand ard test loads that sim ul ate typical l oad appli cations expected.
NOTE 4 The actual perform ance i n a gi ven application is subject to variation un der transient conditions since
actual l oad ratings , i ndi vid u al sequencing, and start cu rrents are likel y to differ from the stand ardized test
situations.
NOTE 5 A DC UPS with perform ance classification NW represents an exam ple of a DC UPS with a narrow-band
output voltage in normal mode and with a wide-ban d output voltage in stored energ y m ode (for exam ple a direct
energ y storag e conn ect singl e con versi on topol og y DC UPS ). The DC UPS h as a d ynam ic voltag e response
I EC 62040-5-3: 201 6 © I EC 201 6 – 25 –
conform ing to cu rve N of Fig ure 2 upon a step load in normal mode . The DC UPS h as a dynam ic voltag e
response conform ing to cu rve W of Fig ure 2 upon chan ge into stored energ y m ode and upon a step load in stored
energ y m ode.
NOTE 6 Refer to An nex E for guid ance on m easurem ent techniq ues.
NOTE 7 The perform ance is gen erall y determ ined by th e DC UPS topolog y – refer to Ann ex B.
I t is recognized that other technologies, for exam ple flywheel systems, may replace the need
for a battery system. Such technologies m ay be full y com patible with DC UPS characteristics
prim aril y intended for batteries. With this in m ind, subj ect to an agreem ent between the
manufacturer/supplier and the purchaser and where applicable, the specification m ay be used
for other stored energ y technologies.
5.4.2 Battery
5.4.2.1 Requirements for all batteries
A battery intended to serve as an energy storage device for a DC UPS compl ying with this
document shall compl y with the applicable clauses of I EC 62040-1 regarding safety
requirements for location, ventilation, markin g and protection of a battery .
o) charging regime, for example constant voltage, constant current, boost or equalization
capability, two-state charging;
p) charging voltage and tolerance band ;
q) end of discharge voltage;
r) charging current limit or range.
5.4.2.3 Characteristics and conditions to be identified by the purchaser
The purchaser shall identify an y requirements, characteristics and conditions that deviate or
are m ore severe than those listed in 5.4.2. 1 and 5. 4. 2.2. This includes an y particular
conditions required by national regulation and an y adverse or special service conditions
including when a battery is supplied by third parties.
NOTE Nati onal regul ations may specify a m inim um back-up autonom y tim e and defin e th e type of energ y storage
device to be used.
5.5 DC UPS switch specification
DC UPS switches supplied as an integral part of a DC UPS are covered by the prescribed
electrical service conditions and performance requirements in this Clause 5 and need not to
be specified separatel y .
Switches that are supplied separately, intended to operate in conjunction with the DC UPS
shall be com patible with the applicable electrical service conditions and performance
requirem ents of the DC UPS , and shall specified in com pliance with their own product
standard.
6 DC UPS tests
6.1 Summary
6.1 .1 Venue, instrumentation and load
6.1 .1 .1 Test venue
A DC UPS shall generally be tested at the manufacturer’s premises and in accordance with
Table 3.
Tests m ay be performed on the DC UPS in its com plete form or, alternativel y, on a functional
unit .
Testing of DC UPS may require facilities that are not available at the manufacturer’s premises
and/or facilities that are not econom icall y justified within the scope of a particular suppl y. The
manufacturer m ay then elect to
I EC 62040-5-3: 201 6 © I EC 201 6 – 27 –
a) use a third party com petent bod y to carry out com pliance testing on the m anufacturer’s
behalf. Evidence of third party certification shall be deem ed sufficient to prove com pliance
with the relevant clauses;
b) demonstrate by calculation or by experience and/or testing of sim ilar designs or sub-
assemblies in sim ilar conditions and through com pilation of a technical construction file
that the design is compliant. Evidence through a technical construction file shall be
deem ed sufficient to prove compliance with the relevant clauses;
c) defer, subj ect to an agreement with the purchaser, applicable tests to be performed on
site (see 6.3).
Separate tests on diverse functional units may be necessary for large and/or complex DC
UPS configurations that cannot be completel y tested prior to delivery on site. When such
necessity arises, the functional unit test of 6. 6 applies and the m anufacturer/supplier and the
purchaser should agree on conditions for final site testing. The manufacturer’s
recom mendation should be followed in this respect.
Routine and type tests shall be performed as prescribed in the relevant test clause, for
exam ple no-load, light load , resistive load , constant power load or reference test load.
Where not otherwise prescribed in the relevant test clause, load tests shall be performed with
reference test load .
Large DC UPS that operate in parallel connection m ay be load-tested by testing individual DC
UPS units separatel y.
NOTE I n particul ar cases, a special l oad, inclu ding th e actual site load, m ay be used if agreed u pon between
m anufacturer/supplier an d purchaser.
Test of characteristics other than those covered by routine tests is subject to an agreement
between the m anufacturer and the purchaser.
6. 1 . 4 Wi tn e s s t e s t
In addition to the perform ed by the m anufacturer, the purchaser may wish their
ro u t i n e te s ts
representative to witness testing of selected item s of Table 3 and/or of other specific item s.
Witness tests are subject to an agreem ent between the manufacturer and the purchaser.
NOTE The pu rchaser m ay eval uate the need for witness testing taki ng i nto account th e m anufacturer’s q uality
assurance status.
6. 1 . 5 T yp e t e s t
shall be performed on a
T yp e t e s t s that represents a series of substantially identical
DC U PS
products. T yp e are intended to assure that such identical products become compliant
te s t s
with their full specification when produced under relevant quality standards and after having
passed the detailed in 6. 2. The
ro u t i n e te s t s used for type-testing is not necessaril y
DC UPS
6. 1 . 6 S ch ed u l e o f te s ts
T ab l e 3 – D C U P S te s t s ch e d u l e
T e s t d e s c ri p t i o n Ro u ti n e te s t T yp e t e s t S u bcl au se
T e s t d e s c ri p t i o n Ro u ti n e te s t T yp e t e s t S u bcl au se
6. 2 R o u t i n e t e s t p ro c e d u re
6. 2. 1 E n v i ro n m e n t a l
No ro u t i n e t e s t s are required.
NOTE Refer to 6. 5 for en vironm ental t yp e t e s t s .
6. 2. 2 E l e c t ri c a l
6. 2. 2 . 1 I n s u l ati o n a n d d i e l e c t ri c
Insulation and dielectric is a safety requirement not within the scope of this docum ent.
NOTE I nsulati on and di electri c com pliance is verifi ed d uring the applicable DC UPS safety test.
6. 2. 2 . 2 C ab l e an d i n t e rc o n n e c t i o n ch eck
The DC shall be inspected in accordance with the manufacturer’s installation and wiring
U PS
Further, all temporary test connections introduced or removed during an y insulation and
dielectric tests shall be confirm ed as having been restored to their normal condition.
pro te ct, sup e rvise , m e a s ure a n d sign a l DC UPS a ctivitie s p e rform a s e xp e cte d a n d th a t th e
loa d vo lta ge re m a in s with in sp e cifie d va lue s durin g th e m a n ua l a n d a uto m a tic tra n sfe rs .
6.2.2.4 No load
The DC UPS output voltage shall remain within the specified values when the DC UPS
operates at nominal input voltage and frequency and with no load connected at the output.
The DC UPS shall not be damaged during operation with the loss of one input phase ( type
test onl y).
Co m p lia n ce is ve rifie d b y te s t wh e n , fo llo win g th e in p ut A C fa ilure , th e DC UPS o p e ra te s in
6. 2 . 2 . 7 AC i n p u t re t u rn
energizing all input feeders at the sam e tim e. This test shall be performed with an
DC U PS
connected.
e n e rg y s t o ra g e d e v i c e
normal mode with in ste a dy sta te output voltage lim its sp e cifie d in 5. 3. 4.
NOTE 1 Walk-in is a function that controls the input AC current so that it increases gradu al ly within a specifi ed
tim e when the starts or restarts. Walk-in is also called soft-start.
DC UPS
NOTE 2 This test is gen erally perform ed in con juncti on with the l i g h t l oad test of 6. 2. 2. 3 e).
6. 3 S i t e t e s t p ro c e d u re
and wiring require their final performance tests to be com pleted on site. The site test
procedure generall y consists of the manufacturer’s comm issioning procedure and of
com pletion of an y of Table 3 that were not completed prior to delivery.
ro u t i n e t e s t s
Site tests shall preferably occur under conditions representing those of actual service and
shall use the load available on site. The load shall not exceed the rated continuous load of the
com plete as configured on site.
DC U PS
Where not otherwise prescribed in the relevant test clause, tests shall be perform ed with
re fe re n c e t e s t l o a d
NOTE 1 When subject to an agreem ent with the m anufacturer, the pu rchaser form ulates a specific site
DC U PS
6. 4 T yp e t e s t p ro c e d u re ( e l e c t ri c a l )
6. 4. 1 I n p u t – AC s u p p l y c o m p a t i b i l i t y
6. 4. 1 . 1 G e n e ra l
The AC input suppl y shall present the applicable characteristics declared for the DC U PS (see
5. 2. 2 i)) and be capable of
– m aintaining the voltage waveform within the limits of 5. 2. 1 when the operates in DC U PS
n o rm a l at rated DC
m od e (see Note 3 in 5. 2. 1 ), and
o u tp u t p o we r
– providing a variable frequency and voltage within the characteristics declared for the DC
input (see 5. 2. 1 ).
UPS
6. 4. 1 . 2 S t e a d y - s t a t e i n p u t v o l t a g e t o l e ra n c e
With the DC in U PS of operation and input set at nom inal, the input voltage
n o rm a l m od e
shall be adj usted to the m inim um and maxim um values of the tolerance range declared by the
manufacturer. The shall rem ain in
DC UPS of operation over the specified
n o rm a l m od e
suppl y voltage by a change of m ode to stored energy mode, the value recorded shall be the
voltage prior to change of mode. The input voltage shall be the m axim um rated input voltage
to ensure operation without circuit damage.
6. 4. 1 . 3 I n p u t fre q u e n c y t o l e ra n c e
The stead y-state i n pu t test (see 6. 4. 1 . 2) shall be repeated with the input
vo l ta g e t o l e ra n c e
frequency adj usted to the lim its specified by the manufacturer in conjunction with the input
voltage variations. The shall rem ain operating in
DC U PS . n o rm a l mod e
NOTE A decrease in freq uen cy is assum ed not to coincid e with an increase i n line voltag e, and vice versa.
6. 4. 1 . 4 I n ru s h c u rre n t
Two inrush current tests shall be perform ed sequentiall y. The first test shall be perform ed
after an absence of input voltage for more than 5 m in.
The subsequent test shall be perform ed after an absence of input voltage for 1 s. I f the DC
UPS topolog y requires a time delay greater than 1 s, the test shall be performed with the
manufacturer specified delay, which shall be stated in the installation instructions .
For the purpose of this test, initial current surges attributable to energization of RFI capacitors
in input filters with a time duration of less than 1 ms shall be disregarded.
The p ro s p e c t i v e of the
s h o rt - c i rc u i t c u rre n t suppl y shall be at least
( I cp ) AC i n pu t p o we r
33 tim es the rated input current of a with rated input current less than 300 A or at
DC U PS
least 20 tim es for with rated input current over 300 A. Testing at an ( Icp ) lower than
DC U PS
specified is perm itted when the test result is corrected by an appropriate calculation.
The input suppl y shall be switched on to the input coincident with various angular
DC U PS
points on the input voltage waveform in order to determine the worst-case inrush current
condition.
NOTE The worst-case in rush current wi ll n orm al ly be foun d for transform er cou pled un its, wh en switched on at
the zero voltage point and for di rect rectifi er/capacitor loads at or near th e peak of th e input supply voltag e
waveform .
b y th e m a n ufa cture r.
6. 4. 1 . 5 H a rm o n i c d i s t o rt i o n o f i n p u t c u rre n t
The harmonic distortion of the input current is tested at nominal power up to the 50 th
harm onic using the .
re fe re n c e t e s t l o a d
6. 4. 1 . 6 P o w e r fa c t o r
The is tested at
i n p u t p o w e r fa c t o r re fe re n c e t e s t l o a d in n o rm a l mode of operation and at
rated AC input suppl y conditions as defined in 5. 2. 1 .
6.4.1 .7 Efficiency
The no-load losses and the DC U PS efficiency at 1 00 %, 75 %, 50 % and 25 % reference
test load shall be m easured as prescribed in Annex F.
NOTE 1 This test is generall y perform ed in conj unction with the input voltage tolerance tests (see 6. 4. 1 . 2 an d
6. 4. 1 . 3).
NOTE 2 Su bject to an ag reem ent between the m anufacturer/suppl ier and the pu rchaser, this test is perform ed on
site.
NOTE 3 I EC 60034-22 presents characteristics for intern al com bustion eng ine-d ri ven gen erati ng sets.
to le ra n ce of Figure 2.
Co m p lia n ce is ve rifie d wh e n [( V
0
− V Ra te d
) / V Ra te d
] * 1 00 (% ) is with in th e lim its o f th e
Co m p lia n ce is ve rifie d wh e n V
[(
1 00
− VRa te d
) / VRa te d
] * 1 00 (% ) is with in th e lim its o f th e
ripple voltage
0 Ra te d Ra te d
Co m p lia n ce is ve rifie d wh e n V
[( - V ) / V ] * 1 00 (% ) is with in th e lim its of th e
ripple voltage
1 00 Ra te d Ra te d
p e rform a n ce cla ss ifica tio n de cla re d in 5. 3. 2 a ) a n d wh e n th e A C co m p o n e n t ( )
This test is required for XN output type onl y (see 5.3. 4).
NOTE The tim e duration of th e test is lim ited by the stored energy source.
I f the DC UPS is rated for operation over a range of input and output voltages , the short
circuit test shall be performed at the highest nom inal rated input and output voltages .
NOTE Faul t cleari ng capabil i ty test verifies the DC UPS output perform ance wh en appl ying a con ditional sh ort-
circuit.
The DC UPS input and output waveform s shall be observed on suitable storage
instrumentation to permit the calculation of any transient perform ance deviation of the
output voltage waveform during the transition from normal to stored energy mode of
operation.
The test is generall y perform ed in conjunction with 6. 2. 2.6 AC input failure (see Figure D. 1 ).
Reduce the load to 20 % of rated output power by switching off the 80 % load.
Assum ing that the energy storage device is a battery , subject to an y particular agreem ent
between the purchaser and the DC UPS m anufacturer, the reference tem perature of the
battery shall be 25 °C. The tem perature of the battery bank shall be measured im m ediatel y
prior to the test for the purpose of calculation of an y adjustm ent to the expected stored
energy time .
NOTE 1 Sim ilar consid erati on appli es for other stored en erg y techn ologies.
The battery voltage shall not fall below the cut-off voltage specified before the stored
energy time has elapsed.
Before carrying out this test, operate the DC UPS in normal mode of operation with nominal
input suppl y and no output load applied for a period in excess of the m anufacturer's stated
restored energy time .
Appl y a 1 00 % resistive reference load and interrupt the input suppl y to force stored energy
mode of operation. Record the DC UPS output voltage . Wait for the declared duration of the
stored energy time . Record the DC UPS output voltage .
Co m p lia n ce is ve rifie d wh e n b oth output voltage m e a s ure m e n ts a re with in th e de cla re d
ra n ge in 5. 3. 2 a ) .
NOTE 2 Since new batteries often do not provid e full capacity du rin g a start - u p period, the discharg e test is
gen erall y repeated after a reasonabl e restored energ y time , if the tim e achieved i nitiall y is less than specified
lim it. A num ber of charge/disch arg e cycles m ay be necessary before full battery capacity is achieved.
After the manufacturer's stated restored energy time has elapsed, the test of 6. 4. 4.1 shall
then be repeated.
NOTE Stored energ y an d restored en erg y times are i nfluenced by ambien t temperature an d th e values stated
by th e m anufactu rer for restored en erg y time is the tim e to restore 90 % of rated capacity unl ess otherwise
stated.
NOTE As an exam ple the l i m it for AC com ponent (RMS val ue) of th e battery cu rrent is typical ly 5 % of th e
num erical val ue of th e rated Ah battery capacity (l ead-acid) and 1 0% (N iCd ).
6. 5. 1 . 3) .
6.5.2 Storage
The following storage test steps shall be perform ed in the chronological order below:
a) as initial measurem ents, perform the electrical routine tests described in 6. 2. 2 on the DC
UPS . Before carrying out these tests, charge internal battery for the period defined in the
m anufacturer's instructions;
– 40 – I EC 62040-5-3: 201 6 © I EC 201 6
b) ensure the DC UPS is not operational, but packed in its norm al shipping state for
transportation and storage with controls in shipping state;
c) conduct tests as follows:
1 ) dry heat as per the norm al environm ental conditions: + 55 °C ± 2 °C for a duration of
1 6 h using the test method Bb of I EC 60068-2-2;
2) dam p heat as per the norm al environm ental conditions: + 40 °C ± 2 °C at a humidity of
90 % to 95 % for a duration of 96 h using I EC 60068-2-78;
3) cold as per the normal environm ental conditions: –25 °C ± 3 °C for a duration of 1 6 h
where practicable using test m ethod Ab of I EC 60068-2-1 .
NOTE No electrical m easu rem ent are requ ired d uri ng th e tests.
d) as final measurements after the tests, unpack the DC UPS , inspect for signs of ph ysical
dam age or distortion to components and for corrosion of metallic parts. ;
e) as final m easurem ents, allow the DC UPS to return to normal ambient temperature and
pressure and perform the light load and functional tests (see 6.2. 2. 3) as routine tests .
Co m p lia n ce is ve rifie d wh e n th e re quire m e n ts o f d) a n d e ) a re s a tisfie d.
6.5.3 Operation
The following operation test steps shall be perform ed in the chronological order below:
a) perform the electrical routine tests described in 6. 2. 2 on the DC UPS ;
b) ensure the DC UPS works in normal mode of operation at rated input voltage and rated
output power;
c) conduct tests in the following sequence:
1 ) dry heat as per the normal environm ental conditions or as per the manufacturer's
stated maximum value for a duration of 1 6 h using test m ethod Bb/Bd of
I EC 60068-2-2;
2) dam p heat as per the norm al environm ental conditions: + 30 °C ± 2 °C at a humidity of
72 % to 78 % for a duration of 96 h using test m ethod Cb of I EC 60068-2-78;
3) cold as per the norm al environmental conditions or as per the m anufacturer's stated
m inim um tem perature for a duration of 2 h using test m ethod Ab/Ad of I EC 60068-2-1 ;
4) dam p heat repeated.
I n the case where the DC UPS incorporates energy storage device (s) in the form of
batteries, conduct the test with tem perature between + 1 5 °C m inimum and + 30 °C
maximum .
d) take m easurements during testing as applicable to check that the DC UPS continues to
function according to this docum ent in normal and stored energy modes of operation;
e) repeat step a) after the DC UPS has returned to am bient conditions to confirm normal
operation;
f) as final requirements after the tests, perform the light load and functional tests (see
6. 2. 2.3) as routine tests and check the DC UPS for signs of ph ysical dam age or
distortion and that it continues to perform in accordance with the initial characteristics.
Values shall be measured when the DC UPS operates at rated stead y-state resistive load
under the following conditions;
– normal mode of DC UPS operation, at rated input voltage;
– stored energy mode of DC UPS operation .
The acoustic noise level shall be measured at the 1 m distance and stated in dBA (dB
referenced to acoustic weighing scale A obtained from a sound level m eter com pl ying with
IEC 61 672-1 ).
The acoustic noise from audible alarm s shall not be included in the values stated.
The acoustic noise from fans required to operate under an y rated condition shall be included
in the values stated.
6.6 DC UPS functional unit tests (where not tested as a complete DC UPS)
6.6.1 DC UPS rectifier tests
Line-comm utated rectifiers shall be tested in accordance with the applicable tests in Clause 7
of I EC 601 46-1 -1 :2009.
Routine tests will cover insulation test and light load test and a checking of auxiliary
protection devices and control systems.
Type tests will include additional load tests, determination of losses, temperature rise, etc.
6.6.2 DC UPS converter tests
Where applicable, converter tests shall be perform ed in accordance with the applicable tests
in Clause 7 of I EC 601 46-2: 1 999 that presents a schedule of routine tests , type tests and
optional tests.
DC UPS switches that are not regarded as integrated parts of a complete DC UPS shall be
tested in accordance with their own product standard.
The DC UPS type test program shall include tests to prove the rated values given in
Clause 5 of this docum ent as far as those values are not proved by adequate calculation. I f
previous type tests have been perform ed, the original manufacturer’s specifications shall be
acceptable and no further tests will be required.
Stored and restored energy time s and an y additional on -site testing, shall be a m atter of
agreement between the DC UPS manufacturer or supplier, and the purchaser.
An n e x A
(informative)
D C U P S c o n fi g u ra ti o n s
A. 1 G e n e ra l
DC UPSare used to suppl y power to equipm ent which requires continuous operation, also
referred to as critical or essential loads. Examples of critical loads include but are not lim ited
to telecom munication facilities, data centers, process control, em ergency lighting, etc. DC
UPS function is to supply continuous power to critical loads, and specificall y for a specified
time when utility outage occurs. A also provides a highl y regulated
DC U PS ou tpu t p o we r
quality due to its independent output from the AC input. A general systems consist DC U PS
configurations are used to achieve different degrees of availability of load power an d/or to
increase output capacity and redundancy
ra t i n g
A. 2 Si n gl e DC U PS
A. 2 . 1 I n t ro d u c t i o n
. A
c o n v e rt e r single generally presents availability consistent with equipm ent
DC U PS
requiring reliability integrity level 1 (RI L-1 – I EC 62040-3: 201 1 , Annex K).
A. 2 . 2 Basi c si n g l e DC U PS
B as i c s i n g l e D C U P S
will suppl y the power at a decreasing DC voltage until it is too low for satisfactory DC output.
The type and capacity of the will determine the length of time the system can operate
b a t t e ry
NOTE The foll owing DC UPS topologies represent exam ples of a basic single DC UPS : direct en ergy storag e
connect, seri es c o n v e rt e r con nect and sh unt con n ect. Refer to Annex B.
c o n v e rt e r
A. 2 . 3 S ca l a b l e s i n g l e D C U P S
– M od u l ar si n g l e DC U PS
in parallel.
– M o n o l i th i c s i n g l e D C U P S
Servicing and field replacem ent requires isolation and/or system shut-down. Scalability is
achieved by connecting like cabinets in parallel. si n gl e DC U PS
A. 3 P a ra l l e l D C U P S
A. 3 . 1 G e n e ra l
DC U PS u n i ts is sufficient to support the load and where " r" stands for the quantity of
redundant D C U P S u n i ts .
A. 3 . 2 P a ra l l e l n o n - re d u n d a n t D C U P S
B as i c s i n g l e D C U P S
B as i c s i n g l e D C U PS
IEC
F i g u re A. 2 – S y s t e m s i z e d fo r l o a d ( N D C U P S u n i t s ) – N o re d u n d a n c y
I EC 62040-5-3: 201 6 © I EC 201 6 – 45 –
A. 3 . 3 P a ra l l e l re d u n d a n t D C U P S
B as i c s i n g l e D C U P S
B as i c s i n g l e D C U PS
B as i c s i n g l e D C U P S
IEC
F i g u re A. 3 – S y s t e m s i z e d fo r l o a d ( N D C U P S u n i ts) – N + 1 re d u n d a n c y
A. 3 . 4 En h an ced p a ra l l e l re d u n d a n t D C U P S
Further availability enhancem ent can be achieved by increasing the number of redundant DC
from 1 to r.
U P S u n i ts
B as i c s i n g l e D C U P S
B as i c s i n g l e D C U PS
Ou tpu t d i s tri bu ti on
B as i c s i n g l e D C U P S
B as i c s i n g l e D C U P S
A. 4 Du al bu s
A. 4 . 1 G e n e ra l
Dual bus configuration is primaril y intended to supply loads equipped with redundant power
supplies and with dual input cords.
sufficient to support the load and where “ r” stands for the quantity of redundant DC U PS
.
u n i ts
A. 4 . 2 D u a l b u s s ys tem 2( N r
+ )
IEC
F i g u re A. 5 – D u a l bu s DC U PS
The 2( N + r) requires however duplication of the equipm ent and the infrastructure.
I EC 62040-5-3: 201 6 © I EC 201 6 – 47 –
DC output – BUS B
IEC
Figure A.6 – Dual bus DC UPS variant
– 48 – I EC 62040-5-3: 201 6 © I EC 201 6
Annex B
(informative)
Topologies – DC UPS
B.1 General
Annex B describes the m ost commonl y used DC UPS topologies in the form of simple block
diagrams including the m ost comm on form of stored energy source, a battery . This is
notwithstanding that other forms of stored energ y sources are equall y possible. See 5. 4. 1 .
For each topolog y, depending on the load and the power distribution system requirem ents,
additional circuits and components such as filters ( transient /EMC) and input isolation
transform ers may be required. These details are om itted for sim plicity. The technical merits
are not discussed and the purchaser should verify with the vendor the suitability of an y
system for the intended load requirem ents. Refer to Annex C.
Direct energ y storage connect topolog y contains an AC-DC converter that when operating in
normal mode provides a tightl y regulated output voltage to the load and maintain the
energy storage device charged. I n stored energ y m ode, for exam ple during an AC input
power failure the AC-DC converter is not active and the power to the load is provided
directl y from the energy storage device . The output voltage will decrease as the energy
storage device discharges or until it reaches a predetermined level at which the load can no
longer operate properl y.
Series converter connect and shunt converter connect contain an additional DC-DC
converter that regulate output voltage under normal and stored energ y modes of operation
until the end of energy storage device discharge level.
I n case of AC input power failure , the energy storage device (for example a battery or
bank of batteries) will suppl y power at decreasing DC voltage to the load, until the voltage
reaches a level, which is too low for satisfactory operation of the powered equipment. The
type and capacity of the battery will determine the length of tim e the system can operate
without an AC input suppl y.
NOTE Direct energ y storag e connect topology DC UPS gen erally perform s with NW characteristics (see 5. 3. 4)
I EC 62040-5-3: 201 6 © I EC 201 6 – 49 –
AC input
Wideband
AC-DC DC output
Energy
storage
device
IEC
Figure B.1 – Direct energy storage connect
B.2.3 Series converter connect
The series converter connect topology DC UPS consists of a direct energ y storage connect
topolog y DC UPS to which a series connected DC-DC converter is inserted in series with the
output to the DC load. The purpose of the DC-DC converter is to assure that the output to the
DC load rem ains constant during energy storage device discharge.
NOTE Seri es converter conn ect topolog y DC UPS gen erall y perform s with NN characteristics (see 5. 3. 4)
Energy
storage
device
IEC
Figure B.2 – Series converter connect
B.2.4 Shunt converter connect
The shunt converter connect topology DC UPS consists of a direct energy storage connect
topology DC UPS to which a series connected DC-DC converter is inserted between the
AC-DC converter and the energy storage device . The purpose of the DC-DC converter is to
assure that the output to the DC load rem ains constant irrespective of the discharge and
recharge characteristics of the energy storage device .
NOTE Shunt converter con n ect topolog y DC UPS gen erall y perform s with NN characteristi cs (see 5. 3. 4)
– 50 – I EC 62040-5-3: 201 6 © I EC 201 6
Narrowband
AC input AC-DC DC output
DC-DC
Energy
storage
device
IEC
Fi g u re B. 3 – Sh u n t con verter con n ect
I EC 62040-5-3: 201 6 © I EC 201 6 – 51 –
An n e x C
(informative)
P u rc h a s e r s p e c i fi c a ti o n g u i d e l i n e s
C. 1 G e n e ra l
A variety of s have been developed to meet the requirem ents for continuity and
DC U PS
quality of power. There are different types of loads over a wide range of power from less than
one hundred watts to several megawatts.
Annex C has been compiled to assist purchasers to formalize criteria important to their
application and/or to confirm agreem ent with conditions declared by the
manufacturer/supplier.
The DC technical data sheet contained in Annex C presents a sum m ary of the normal
U PS
and unusual environmental and electrical conditions to be considered. This data sheet also
references the specific subclause of concern. The reader’s attention is drawn to Clauses 4
(Environmental conditions) and 5 (Electrical conditions, perform ance and declared values).
Tabl e C . 1 – D C U P S te c h n i ca l d a t a – M a n u fa c t u re r’ s d e c l a ra t i o n (1 of 4)
I E C 6 2 0 40 -5 -
3: 201 6
P u rc h a s e r’ s
s u bcl au s e D e c l a re d c h a ra c t e ri s t i c s M a n u fa c t u re r’ s
i d e n t i fi e d
(excep t i f G e n e ra l d e c l a re d val u es
va l u e s
o t h e rw i s e
n o te d )
5. 6 C o m m u n i ca ti o n c i rc u i t s
Tabl e C . 1 (2 of 4)
I E C 6 2 0 40 -5 -
3: 201 6
P u rc h a s e r’ s
s u b cl au s e D e c l a re d c h a r a c t e ri s t i c s M a n u fa c t u re r’ s
i d e n t i fi e d
(excep t i f O u t p u t ( e l e c t ri c a l ) d e c l a re d val u es
va l u e s
o t h e rw i s e
n o te d )
Vo l ta g e (stead y state)
5. 3. 2 b) V
– rated
6. 4. 2 . 1
6. 4. 2 . 2
and
– n o rm a l m o d e v a ri a t i o n at n o l oad an d fu l l l oad %
6. 4. 2 . 3 a n d – s to re d e n e rg y m o d e v a ri a t i o n at n o l oad an d fu l l
%
6. 4. 2 . 4 l oad
5. 3. 2 g ) A
– rated
(contin ued)
I EC 62040-5-3: 201 6 © I EC 201 6 – 53 –
Tabl e C . 1 (3 of 4)
I E C 6 2 0 40 -5 -
3: 201 6
M a n u fa c t u re r’ s P u rc h a s e r’ s
s u bcl au s e D e c l a re d c h a r a c t e ri s t i c s
d e c l a re d i d e n t i fi e d
(excep t i f I n p u t ( e l e c t ri c a l )
va l u e s val u e s
o t h e rw i s e
n o te d )
5. 2. 1 c) Hz
– rated
5. 2. 1 d ) – tolerance %
5. 2. 2 a) phases req uired (1 , 2 or 3)
5. 2. 2 b) neutral req uired (yes/no)
C u rre n t RMS
5. 2. 2 c) A
– rated (with the en erg y storag e device charged)
5. 2. 2 d ) – power factor
5. 2. 2 e) – inrush characteristics %
– m axim um (with low i nput voltage and energ y storage A
5. 2. 2 f) device chargi ng )
– current against tim e %, s
(continued)
– 54 – I EC 62040-5-3: 201 6 © I EC 201 6
Tabl e C . 1 (4 of 4)
I E C 6 2 0 40 -5 -
3: 201 6
M a n u fa c t u re r’ s P u rc h a s e r’ s
s u bcl au s e D e c l a re d c h a r a c t e ri s t i c s
d e c l a re d i d e n t i fi e d
(excep t i f B a t t e r y/ s t o r e d e n e rg y d e v i c e
va l u e s val u e s
o t h e rw i s e
n o te d )
5. 4. 2. 2 d ) Technolog y
Desig n life or years
5. 4. 2. 2 a) Expected life
float service life
5. 4. 2. 2 b) Quantity of bl ocks or cells of parallel ed stri ngs
5. 4. 2. 2 c) Nom inal voltage (total ) V DC
5. 4. 2. 2 e) Nom inal capacity Ah
5. 4. 2. 2 f) Stored en erg y tim e (back-up ti m e at 1 00 % rated l oad)
5. 4. 2. 2 g ) Restored energy tim e (rech arg e tim e to 90 % capacity)
5. 4. 2. 2 h ) Am bient reference tem perature °C
5. 4. 2. 2 i ) Earth con dition/I solati on
%of rated
5. 4. 2. 2 j ) RMS ripple cu rrent battery Ah
capacity
5. 4. 2. 2 k) Maxim um discharge cu rrent A
5. 4. 2. 2 l ) Fault current rati ng A DC
(en d)
I EC 62040-5-3: 201 6 © I EC 201 6 – 55 –
An n e x D
(normative)
I n p u t m a i n s fa i l u re – T e s t m e th o d
The characteristics of the DC U PS when the mains fail shall be tested using the circuit of
Figure D.1 .
Fuse S1
L
DC
S2 UPS Load
N
IEC
Ke y
L m ains phase(s)
N m ains neutral (or phase where no n eutral is used )
S1 switch or contactor capabl e of carryin g an d of opening the DC UPS ra t e d i n p u t c u rre n t
S2 switch or contactor capabl e of carryin g the m ains fault cu rrent while the fuse opens
Fuse rated to support the DC UPS at l i g h t l oad .
F i g u re D . 1 – C on n e cti o n o f t e s t c i rc u i t
Test D. 1 – High i m p e d a n c e m a i n s fa i l u re
N o rm a l mode of operation, l i g h t l o ad :
– S1 = closed;
– S2 = open;
– Close S2 to sim ulate the mains failure (fuse blown).
The fuse ra t i n g shall com ply with the DC U PS input current. The S2 ra t i n g shall be according
to the fuse ra t i n g .
– 56 – I EC 62040-5-3: 201 6 © I EC 201 6
Annex E
(informative)
Dynamic output performance – Measurement techniques
E.1 General
Annex E provides guidance for validation of the dynam ic output performance of a DC U PS as
specified in 5. 3.4.
Validation is achieved when the voltage variation fits within the applicable lim its in Figure
E. 1 . The voltage variation between 0 and 0, 001 s is ignored. Refer to 6. 4. 2. 9. 1 for further
tim ing details. Figures E. 1 and E. 2 below provide examples of the graphical validating
method
Voltage (%)
20
+5 %
+1 1 %
Nominal
value 0
N l im its
–5 %
–20
–22 %
W lim its
–32 %
–40
–60
–80
–1 00
0, 001 0, 01 0, 1 1 10 1 00 1 000 1 0 000 1 00 000
Transi ent d uration (s)
IEC
Voltage (%)
20
+5 %
Nominal
+1 1 %
value 0
N l im its
–5 %
–20
–22 %
W lim its
–32 %
–40
–60
–80
–1 00
0, 001 0, 01 0, 1 1 10 1 00 1 000 1 0 000 1 00 000
Transi ent duration (s)
IEC
An n e x F
(normative)
D C U P S e ffi c i e n c y – M e t h o d s o f m e a s u re m e n t
F. 1 G e n e ra l
during
e ffi c i e n c y specified in 6. 4.1 . 7.
t yp e t e s t s
F. 2 M e a s u re m e n t c o n d i t i o n s
F.2. 1 E n v i ro n m e n t a l c o n d i ti o n s
F.2. 2 O p e ra t i o n a l an d e l e c t ri c a l co n d i ti on s
For the purpose of Annex F, the efficiency measurem ents shall be perform ed with a re s i s t i v e
the power (W) for which it is rated. The input loss shall be m easured at no-load. The following
requirements appl y for each m easurem ent.
a) The shall operate in
DC U PS . n o rm a l m od e
transfer of energy.
c) The DC and the load shall have been operated for a sufficient length of time to reach
U PS
stead y state conditions. The length of tim e determined d uring tem perature rise typ e tests
and load condition shall be within the range of 95 % to 1 05 % of the intended load.
e) The AC input to the shall be at 97 % to 1 03 % of the
DC U PS and 99 % to ra t e d vo l ta g e
I EC 61 000-2-2.
NOTE 1 Th e test with is considered to be th e m ost reli abl e i n term s of repeatability and constitutes
re s i s t i v e l o a d
a solid base for the evaluati on of efficiency im provem ents at al l load levels.
NOTE 2 For tolerances, refer to 7. 8 of I EC 601 46-1 -1 : 2009.
F.2. 3 I n s t ru m e n t a t i o n
The combination of instruments and transducers used for the measurem ent of DC UPS
shall
e ffi c i e n c y
– provide true RMS measurements of the active input power and of the , with o u tp u t p o we r
an uncertainty at full rated load of less than or equal to 0, 5 % at the 95 % confidence level
notwithstanding that voltage and current waveforms can include , h a rm o n i c co m p on en ts
and
– m easure input and output values sim ultaneousl y.
NOTE 1 Th e confi dence level of an instrum ent’s uncertainty is u nderstood as th e probability of m easurem ents
presented by such instrum ent being accurate withi n the u ncertai nty lim its. A norm al distribution of data with
coverage factor 1 , 960 represents a 95 % confid ence level which is a generall y accepted level. For
further inform ation, refer to I SO/I EC Guid e 98-3.
I EC 62040-5-3: 201 6 © I EC 201 6 – 59 –
NOTE 2 Sim ultaneous input and output m easurem ents are gen erall y provided throu gh separate in put and output
instrum ents. Neverthel ess, one singl e m ulti-chan nel i nstrum ent providi ng fast seri al sam pling (“m ultipl exed
sam pling”) is also deem ed to provid e sim ultaneous m easurem ents.
An n e x G
(informative)
C l i m a ti c te s t
G.1 G e n e ra l
The obj ective of Annex G is to clarify the relationship between the clim atic environm ental
requirements in 4. 2. 1 . 1 and 4. 2. 2 and the procedures in 6. 5. 2 and 6. 5.3. t yp e te s t
G.2 T e s t i n g o f c o m p l i a n c e t o c l i m a t i c re q u i re m e n t s
Tabl e G . 1 – Re co m m e n d ed t e s t s fo r I E C 6 0 7 2 1 - 3 - 3 – C l a s s 3 K 2 ( c o n t i n u o u s l y
t e m p e ra t u re - c o n t ro l l e d en cl o s ed l o c a ti o n s ; h u m i d i t y n o t c o n t ro l l e d )
I E C 6 0 7 2 1 -3 -3 – C l i m a ti c c o n d i ti o n s I E C 6 0 0 6 8 -2 – C l i m a ti c c o n d i t i o n s
E n v i ro n m e n t a l p a ra m e t e r Cl as s N e a re s t I E C 6 0 0 6 8 - 2 Re c o m m e n d e d te s t N ote
N o.
3 K2
Te st m e th o d S e veri ty Te st m e th od s S e veri ty
50
Dry h ea t x) Dry heat +30° C, 1 ), 2)
Absolute humidity g/m 3
40
60068-2-2: 16 h
Bb/Bd
Temperature °C
30
20 22
10
0 y) Col d Non e 3)
–1 0 2
Col d 60068-2-1 :
–20
0 20 40 60 80 1 00 Ab/Ad
Relative humidity % RH
1 °C/min t1 =
3h
h) Low air pressu re 70 kPa 60068-2-1 3: 70 kPa, Test norm ally not req uired 5)
M 30 m in – See n ote 5)
i) High air pressure 1 06 kPa No I EC 60068-2 test Test norm ally not req uired 6)
– See n ote 6)
– 62 – I EC 62040-5-3: 201 6 © I EC 201 6
I E C 6 0 7 2 1 -3 -3 – C l i m a ti c c o n d i ti o n s I E C 6 0 0 6 8 -2 – C l i m a ti c c o n d i t i o n s
E n v i ro n m e n t a l p a ra m e t e r Cl as s N e a re s t I E C 6 0 0 6 8 - 2 Re c o m m e n d e d te s t N ote
N o.
3 K2
Te st m e th o d S e veri ty Te st m e th od s S e veri ty
Bibliography
I EC 60034-22, Rota tin g e le ctrica l m a ch in e s ‒ Pa rt 22: A C ge n e ra tors for re cip roca tin g in te rn a l
I EC 60050 (all parts), In te rn a tio n a l Ele ctrote ch n ica l Voca b ula ry (available at
www. electropedia.org)
IEC 60068-2-5, En viron m e n ta l te stin g – Pa rt 2-5: Te sts – Te s t Sa : Sim ula te d so la r ra dia tio n a t
pre ss ure
equip m e n t
IEC 601 46-1 -3: 1 991 , Se m ico n ductor con ve rte rs – Ge n e ra l re quire m e n ts a n d lin e com m uta te d
I EC 60664-1 , In s ula tio n co ordin a tio n for e quip m e n t with in lo w-vo lta ge syste m s – Pa rt 1:
I EC 60721 -3-3, Cla ss ifica tion o f e n viro n m e n ta l co n ditio n s – Pa rt 3: Cla ssifica tion o f group s of
lo ca tio n s
IEC TR 60721 -4-0, Cla s sifica tio n of e n viro n m e n ta l con ditio n s – Pa rt 4- 0: G uida n ce fo r th e
corre la tio n a n d tra n s form a tio n o f th e e n viro n m e n ta l con ditio n cla sse s o f IEC 60721 - 3 to th e
IEC 60947-3, L o w-volta ge switch ge a r and co n tro lge a r – Pa rt 3: Switch e s, disco n n e cto rs ,
IEC 60947-6-1 , L o w-vo lta ge switch ge a r and con trolge a r – Pa rt 6-1 : Multip le fun ction
IEC 61 000-4-30, Ele ctro m a gn e tic com p a tib ility (EMC) – Pa rt 4- 30: Te s tin g a n d m e a s ure m e n t
I EC 61 508 (all parts), Fun ctio n a l s a fe ty of e le ctrica l/e le ctro n ic/p ro gra m m a b le e le ctro n ic
sa fe ty-re la te d sys te m s
AN SI C57.96-1 999, G uide for L o a din g Dry Typ e D istrib utio n a n d Powe r Tra n sform e rs
_____________
– 66 – I EC 62040-5-3: 201 6 © I EC 201 6
SOMMAIRE
AVANT-PROPOS . ... ... ... ... ... ... ... ... ... ... ... ... . . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... . 69
1 Domaine d'application ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... .. 71
2 Références normatives .. ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . .. ... .. 72
3 Termes et définitions .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... .. 73
3. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . ... . 73
3. 2 Définitions relatives aux systèm es et composants .. ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... 73
3. 3 Perform ance des systèm es et com posants . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... .. 76
3. 4 Valeurs spécifiées ‒ .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... .. 77
G é n é ra l i t é s
3. 5 Valeurs d'entrée . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... . .. ... .. 81
3. 6 Valeurs de sortie ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. .. 82
4 Conditions d'environnement ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... 83
4. 1 Environnement d'essai . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 83
4. 2 Conditions normales .. .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 83
4. 2. 1 Fonctionnem ent ... ... ... ... .. ... ... ... ... ... ... ... . .. ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. . ... .. 83
4. 2. 2 Entreposage et transport . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 84
4. 3 Conditions inhabituelles .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . 85
4. 3. 1 General .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . .. . 85
4. 3. 2 Fonctionnem ent ... ... ... ... .. ... ... ... ... ... ... ... . .. ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. . ... .. 85
4. 3. 3 Entreposage et transport . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 85
5 Conditions électriques, perform ances et valeurs déclarées .. ... ... ... ... ... ... ... ... .. ... ... ... ... . .. . 86
5. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . ... . 86
5. 1 . 1 Configuration de l'ASI à tension continue . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. 86
5. 1 . 2 Marquages et instructions ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... . 86
5. 2 Spécification d'entrée de l'ASI à tension continue .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... 86
5. 2. 1 Conditions relatives au mode norm al de fonctionnem ent. ... ... ... ... .. ... ... ... ... ... .. 86
5. 2. 2 Caractéristiques d'entrée que le fabricant doit déclarer ... ... ... ... ... ... ... ... ... ... ... . 87
5. 2. 3 Caractéristiques et conditions que l'acheteur doit identifier .. ... ... ... ... ... ... ... ... .. 87
5. 3 Spécification de sortie de l'ASI à tension continue . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... 88
5. 3. 1 Conditions nécessaires pour que l'ASI à tension continue alimente une
charge . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. . ... . 88
5. 3. 2 Caractéristiques que le fabricant doit déclarer ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... 88
5. 3. 3 Caractéristiques et conditions que l'acheteur doit identifier .. ... ... ... ... ... ... ... ... .. 89
5. 3. 4 Classification des performances ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... 89
5. 4 Spécification d'autonom ie . ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. 90
5. 4. 1 Généralités .. ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . 90
5. 4. 2 Batteries ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... . .. ... ... ... . 91
5. 5 Spécification des interrupteurs d'ASI à tension continue .. ... ... ... ... ... ... ... ... ... ... ... ... . 92
5. 6 Circuits de com munication ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . .. ... ... ... ... ... ... ... ... ... .. .. 92
6 Essais d'ASI à tension continue .. ... ... ... ... ... .. ... ... ... ... ... ... ... .. . ... ... ... ... ... ... ... .. ... ... ... ... ... ... . 92
6. 1 Résumé ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... . .. .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... . 92
6. 1 . 1 Lieu, instrum entation et charge ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 92
6. 1 . 2 Essais individuels de série .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... ... .. ... ... ... ... ... ... .. 93
6. 1 . 3 Essais sur site .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 93
6. 1 . 4 Essais clients ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 94
6. 1 . 5 Essais de type .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. 94
6. 1 . 6 Calendrier des essais . ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 94
I EC 62040-5-3: 201 6 © I EC 201 6 – 67 –
6. 2 Procédure d'essais individuels de série .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... . 96
6. 2. 1 Essais d'environnem ent . ... ... ... ... ... .. ... ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 96
6. 2. 2 Essais électriques . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... 96
6. 3 Procédure d'essais sur site .. ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. .. 98
6. 4 Procédure d'essai de type (électrique) ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... . .. ... ... ... ... . 98
6. 4. 1 Entrée – Com patibilité de l'alimentation en courant alternatif .. ... ... ... ... ... ... ... .. 98
6. 4. 2 Caractéristiques de sortie – Charge résistive ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... 1 01
6. 4. 3 Caractéristiques de sortie – Charge à puissance constante . ... ... ... ... ... ... ... ... 1 05
6. 4. 4 Durées d'autonomie et de recharge . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1 05
6. 5 Procédure d'essai de type (environnemental) . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... 1 06
6. 5. 1 Méthodes d'essai d'environnem ent et de transport .. ... ... ... ... ... ... ... ... .. ... ... ... .. 1 06
6. 5. 2 Entreposage .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... 1 07
6. 5. 3 Fonctionnem ent ... ... ... ... .. ... ... ... ... ... ... ... . .. ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. . ... 1 08
6. 5. 4 Bruit acoustique ... ... ... ... .. ... ... ... ... ... ... ... ... .. . ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... 1 09
6. 6 Essais d'unités fonctionnelles d'ASI à tension continue (lorsqu'elles ne sont
pas soumises à l'essai en tant qu'ASI à tension continue com plète) . ... ... ... ... ... .. .. 1 09
6. 6. 1 Essais de redresseurs d'ASI à tension continue . ... ... ... ... ... ... ... ... ... ... ... .. ... ... . 1 09
6. 6. 2 Essais de convertisseurs d'ASI à tension continue.. ... ... ... ... ... ... ... ... .. ... ... ... .. 1 09
6. 6. 3 Essais d'interrupteurs d'ASI à tension continue .. ... ... ... ... ... ... ... ... ... ... ... .. ... .. . . 1 09
6. 6. 4 Essais d'autonom ie/de batterie .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... ... ... ... ... . 1 1 0
Annexe A (inform ative) Configurations d'ASI à tension continue .. .. ... ... ... ... ... ... ... ... ... ... ... ... 1 1 1
A. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 1 1
A. 2 ASI à tension continue unitaire . ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . 1 1 1
A. 2.1 I ntroduction ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . .. ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... 1 1 1
A. 2.2 ASI à tension continue unitaire de base ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... .. . ... .. ... 1 1 1
A. 2.3 ASI à tension continue unitaire évolutive . .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. 1 1 2
A. 3 ASI à tension continue parallèle ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . 1 1 2
A. 3.1 Généralités .. ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. 1 1 2
A. 3.2 ASI à tension continue parallèle sans redondance active ... ... ... ... .. ... ... ... ... ... 1 1 2
A. 3.3 ASI à tension continue parallèle en redondance active ... ... ... ... ... ... ... ... ... ... .. 1 1 3
A. 3.4 ASI à tension continue parallèle en redondance active am éliorée ... ... ... ... ... . 1 1 4
A. 4 Double voie de distribution ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1 1 5
A. 4.1 Généralités .. ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. 1 1 5
A. 4.2 Systèm e à double voie de distribution 2( N + r) ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... . 1 1 5
A. 4.3 ASI à tension continue à double voie de distribution ( N + r) . ... ... ... ... ... ... ... ... 1 1 5
Annexe B (inform ative) Topologies – ASI à tension continue ... ... ... .. ... ... ... ... ... ... ... ... ... ... . .. .. 1 1 6
B. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 1 6
B. 2 Topologies de base . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... . 1 1 6
B. 2.1 Généralités .. ... ... ... ... ... ... ... .. ... ... ... ... .. . ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... .. 1 1 6
B. 2.2 Topologie à dispositif de stockage d'énergie en connexion directe . ... ... ... ... .. 1 1 6
B. 2.3 Topologie à convertisseur série . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . 1 1 7
B. 2.4 Topologie à convertisseur parallèle . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1 1 7
Annexe C (inform ative) Directives relatives aux spécifications de l'acheteur .. ... ... ... ... ... ... .. 1 1 9
C. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 1 9
Annexe D (norm ative) Défaillance du réseau d'entrée – Méthodes d'essai ... .. ... ... ... ... ... ... .. 1 23
Annexe E (inform ative) Perform ances d ynam iques de sortie – Techniques de mesure ... ... . 1 24
E. 1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 24
E. 2 Méthode de validation graphique . ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... . 1 24
– 68 – I EC 62040-5-3: 201 6 © I EC 201 6
Annexe F (norm ative) Rendement de l'ASI à tension continue – Méthodes de mesure . ... .. . 1 26
F.1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 26
F.2 Conditions de mesure .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... ... ... ... ... ... ... ... ... ... ... ... . 1 26
F. 2. 1 Conditions d'environnement ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... 1 26
F. 2. 2 Conditions de fonctionnement et conditions électriques .. ... ... ... ... .. ... ... ... ... ... 1 26
F. 2. 3 I nstrumentation . ... ... ... ... .. ... ... ... ... ... ... .. . ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... 1 26
F.3 Méthode de m esure ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . .. ... ... ... ... ... ... ... .. ... ... ... ... ... . 1 27
F.4 Rapport d'essais ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... 1 27
Annexe G (informative) Essai climatique .. ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... . 1 29
G.1 Généralités ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . .. ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... .. . .. 1 29
G.2 Essai de conform ité aux exigences clim atiques ... ... ... ... ... ... ... ... ... ... ... ... .. . .. ... ... ... . 1 29
Bibliographie . .. ... ... ... ... ... ... ... ... ... ... ... . .. ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... . 1 32
Figure 1 – Exem ples de convertisseurs électroniques de puissance de base .. ... ... ... ... ... ... ... . 74
Figure 2 – Performances d ynam iques de sortie ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... . 90
Figure A. 1 – ASI à tension continue unitaire de base .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. . ... ... 1 1 1
Figure A. 2 – Système dimensionné pour la charge ( N unités d'ASI à tension continue)
– Sans redondance .. ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... . .. ... ... ... ... .. .. 1 1 3
Figure A. 3 – Système dimensionné pour la charge ( N unités d'ASI à tension continue)
– Redondance N + 1 ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... . .. ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. . .. .. 1 1 4
Figure A. 4 – Systèm e dim ensionné pour la charge ( N unités d'ASI à tension continue)
– Redondance N + r . ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... .. . ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. 1 1 4
Figure A. 5 – ASI à tension continue à double voie de distribution ... ... ... ... ... ... ... ... .. ... ... ... ... 1 1 5
Figure A. 6 – Variante d'ASI à tension continue à double voie de distribution . .. ... ... ... ... ... ... .. 1 1 5
Figure B. 1 – Topologie à dispositif de stockage d'énergie en connexion directe . ... ... ... ... ... .. 1 1 7
Figure B. 2 – Topologie à convertisseur série . ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1 1 7
Figure B. 3 – Topologie à convertisseur parallèle . ... ... ... ... ... ... ... ... ... ... ... ... ... . . ... ... ... ... ... ... ... .. 1 1 8
Figure D.1 – Raccordem ent du circuit d'essai .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... .. . ... ... ... ... ... .. 1 23
Figure E. 1 – Exemple: Validation de la réponse en tension d ynam ique avec la lim ite
bande étroite .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. .. . ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... . 1 24
Figure E. 2 – Exemple: Validation de la réponse en tension d ynam ique avec la lim ite
large bande .. ... ... ... ... ... ... ... ... ... .. ... ... ... ... ... ... .. . ... ... ... ... ... ... ... .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1 25
AL I M E N T AT I O N S S AN S I N T E R RU P T I O N ( AS I ) –
P a rti e 5 -3 : AS I à te n s i o n d e s o rti e c o n t i n u e –
P e rfo rm a n c e s e t e x i g e n c e s d ' e s s a i
AVANT-PROPOS
1 ) La Com m ission Electrotech n ique I ntern ational e (I EC) est une organisation m ondiale de norm alisation
com posée de l'ensem ble des com ités électrotechni ques n ati onaux (Com ités nationau x de l 'I EC). L'I EC a pou r
objet de favoriser la coopérati on i nternati onale pou r toutes l es qu estions d e n orm alisation dans l es d om aines
de l'él ectricité et de l'électroniq ue. A cet effet, l'I EC – entre autres activités – publi e des N orm es
internati onales, d es Spécifications tech niq ues, d es Rapports techniq ues, d es Spécificati ons accessibles au
publ ic (PAS) et des Guid es (ci -après d én omm és "Publication (s) de l 'I EC"). Leu r él aborati on est confiée à des
com ités d'études, au x travau x desquels tout Com ité national intéressé par l e sujet traité peut participer. Les
org anisati ons international es, gou vern em ental es et n on g ou vernem entales, en li aison avec l'I EC, participent
égal em ent au x travau x. L'I EC collabore étroitem ent avec l'Organisation I nternational e d e Norm alisation (I SO),
selon d es conditi ons fi xées par accord entre l es deu x organisations.
2) Les décisions ou accords officiels de l 'I EC concernant les questions techni qu es représentent, dans la m esure
du possibl e, un accord intern ation al sur les sujets étudi és, étant don né q ue les Com ités nationau x de l 'I EC
intéressés sont représentés d ans chaqu e com ité d'étud es.
3) Les Publicati ons de l'I EC se présentent sous la form e de recom m andations intern ational es et sont agréées
comm e telles par l es Com ités nationau x d e l'I EC. Tous les efforts raison nabl es sont entrepris afin q ue l'I EC
s'assure de l'exactitude du con tenu tech niqu e de ses pu blications; l'I EC ne peut pas être tenue responsabl e de
l'éventu elle m au vaise util isation ou i nterprétation qui en est faite par u n qu elconqu e utilisateur fi nal.
4) Dans l e but d'encourag er l'u ni form ité intern ation ale, les Com ités nationau x d e l'I EC s'eng agent, d ans toute l a
m esure possible, à appl iqu er d e façon transparente les Publi cations d e l'I EC d ans l eu rs pu blications nati on ales
et régional es. Toutes di verg ences entre toutes Publicati on s de l'I EC et toutes publicati ons n ation ales ou
rég ion ales correspon dantes doivent être ind iqu ées en term es clairs dans ces dernières.
5) L'I EC elle-m êm e ne fournit aucune attestati on d e conform ité. Des org anism es de certification ind épendants
fournissent d es services d'évaluati on de conform ité et, d ans certai ns secteu rs, accèdent au x m arques de
conform ité de l'I EC. L'I EC n'est responsable d'aucun d es services effectu és par les organ ism es de certificati on
indépendants.
6) Tous les utilisateurs d oi vent s'assurer qu'ils sont en possession d e la d ernière édition de cette publication.
7) Aucune responsabilité n e d oit être im putée à l'I EC, à ses adm inistrateurs, em ployés, au xiliai res ou
m andataires, y com pris ses experts particuli ers et l es m em bres de ses com ités d'étud es et des Com ités
nationau x d e l'I EC, pou r tout préjudice causé en cas de domm ages corporels et m atéri el s, ou de tout autre
dom m age de quel que natu re q ue ce soit, directe ou indi recte, ou pou r supporter les coûts (y com pris les frais
de j ustice) et les d épenses découlant d e la pu blicati on ou de l'utilisation d e cette Publication de l'I EC ou d e
toute autre Publicati on d e l'I EC, ou au crédit q ui lui est accord é.
8) L'attenti on est attirée sur les références norm atives citées d ans cette publication. L'utilisation de publ ications
référencées est obl igatoire pou r un e applicati on correcte de la présente publicati on.
9) L'attenti on est attirée sur l e fait que certains d es élém ents de la présente Pu blicati on de l'I EC peu vent fai re
l'obj et de droits de brevet. L'I EC ne saurait être ten ue pou r responsable de n e pas avoir i d entifié de tels d roits
de brevets et de ne pas avoi r signalé leur existence.
La N orme internationale I EC 62040-5-3 a été établie par le sous-com ité 22H : Alim entations
sans interruption (ASI ), du com ité d'études 22 de l'I EC: Systèm es et équipem ents
électroniques de puissance.
Le rapport de vote indiqué dans le tableau ci-dessus donne toute inform ation sur le vote ayant
abouti à l'approbation de cette norm e.
– 70 – I EC 62040-5-3: 201 6 © I EC 201 6
Cette publication a été rédigée selon les Directives I SO/I EC, Partie 2.
Dans le présent document, les caractères d'im primerie suivants sont em ployés:
– exigences proprement dites et annexes normatives: caractères romains;
– déclarations de conformité et m odalités d'essai: ca ra ctè re s ita lique s ;
– notes et commentaires: petits caractères rom ains;
– conditions norm atives au sein des tableaux: petits caractères rom ains;
– term es définis à l'Article 3: . g ra s
Une liste de toutes les parties de la série I EC 62040, publiées sous le titre général
peut être consultée sur le site web de l'I EC.
A lim e n ta tio n s s a n s in te rrup tio n (A SI) ,
Le com ité a décidé que le contenu de cette publication ne sera pas m odifié avant la date de
stabilité indiquée sur le site web de l'I EC sous "http://webstore. iec.ch" dans les données
relatives à la publication recherchée. A cette date, la publication sera
• reconduite,
• supprim ée,
• rem placée par une édition révisée, ou
• am endée.
c o n s é q u e n t , i m p ri m e r c e t t e p u b l i c a t i o n e n u t i l i s a n t u n e i m p ri m a n t e c o u l e u r.
I EC 62040-5-3: 201 6 © I EC 201 6 – 71 –
AL I M E N T AT I O N S S AN S I N T E R RU P T I O N ( AS I ) –
P a rti e 5 -3 : AS I à te n s i o n d e s o rti e c o n t i n u e –
P e rfo rm a n c e s e t e x i g e n c e s d ' e s s a i
1 D o m a i n e d ' a p p l i ca ti o n
La présente partie de l'I EC 62040 établit les exigences de perform ance et d'essai appliquées
aux al i m e n ta ti o n s san s i n t e rru p t i o n à ten si on con ti n u e ( AS I à ten si o n co n ti n u e )
– intègrent un , et
d i s p o s i t i f d e s t o c ka g e d ' é n e rg i e
dans les publications I EC citées dans la ibliographie, qui s'appliquent tant qu'elles ne
contredisent pas le présent docum ent.
Les AS I à ten si on ont été développées pour une plage étendue de puissances,
co n ti n u e
allant de moins d'une centaine de watts à plusieurs m égawatts, pour satisfaire aux exigences
de disponibilité et de qualité de l'énergie de charges diverses. Pour plus d'inform ations sur les
configurations et les topologies types d' , voir Annexes A et B.
AS I à ten s i on co n ti n u e
Le présent document couvre également les exigences de perform ances et d'essais des AS I à
te n s i o n relatives aux
con ti n u e , aux interrupteurs d'isolem ent ainsi qu'aux
i n t e rru p t e u rs
interrupteurs de liaison (s'il y a lieu) qui font partie intégrante des . AS I à te n s i o n con ti n u e
NOTE 1 Le présent docum en t reconn aît que l a disponi bilité de l'alim entati on pour l es appareils de traitem ent de
l'inform ation (ATI ) constitue u ne applicati on m ajeure des ASI . Les caractéristiqu es de sortie des AS I à ten s i on
spécifiées dans le présent d ocum ent ont donc égalem ent pour but de g aranti r la com patibilité avec les
co n ti n u e
exi gences des ATI . Sous réserve d'éventu elles l im itations in diqu ées d ans l a décl aration d u fabricant, l e présent
docum ent spécifi e l es exig ences relati ves au x variati ons de l a tension en régim e établ i et d e la tension , t ra n s i t o i re
NOTE 2 Les charges d'essai spécifiées dans le présent docum ent sim ulent les caractéristiqu es de ch arg e
résistive et de c h a rg e à . Leur usag e est prescrit avec pour obj ectif d e vérifi er la concepti on
pu i ss an ce co n s ta n te
– 72 – I EC 62040-5-3: 201 6 © I EC 201 6
et la perform ance déclarées par l e fabricant, m ais égalem ent de lim iter le plus possible toute com plexité et
consomm ation d'énergi e pend ant l es essais.
Les documents suivants cités dans le texte constituent, pour tout ou partie de leur contenu,
des exigences du présent docum ent. Pour les références datées, seule l’édition citée
s’applique. Pour les références non datées, la dernière édition du docum ent de référence
s'applique (y com pris les éventuels am endements).
I EC 60068-2-27, Essa is d'e n viro n n e m e n t – Pa rtie 2- 27: Essa is – Essa i Ea e t guide : Ch ocs
IEC 60068-2-31 , Essa is d'e n viro n n e m e n t – Pa rtie 2-31 : Essa is – Essa i Ec: Ch o c lié à de s
IEC 60068-2-78, Essa is d'e n viro n n e m e n t – Pa rtie 2-78: Essa is – Essa i Ca b : Ch a le ur h um ide ,
e ssa i co n tin u
I EC 601 46-2: 1 999, Co n ve rtisse urs à s e m ico n ducte urs – Pa rtie 2: Co n ve rtisse urs
a utoco m m uté s à s e m ico n ducte urs y co m p ris le s con ve rtisse urs à co ura n t co n tin u dire cts
IEC 60364-1 : 2005, In s ta lla tio n s é le ctrique s à b a ss e te n s ion – Pa rtie 1 : Prin cip e s
IEC TR 60721 -4-3, Cla ss ifica tio n de s co n ditio n s d’e n viro n n e m e n t – Pa rtie 4-3: G uide p o ur la
co rré la tio n e t la tra n s form a tio n de s cla ss e s de con ditio n s d’e n viro n n e m e n t de la CEI 60721 -3
en e ssa is d’e n viron n e m e n t de la CEI 60068 – Utilisa tio n à p oste fixe , p ro té gé co n tre le s
in te m p é rie s I EC 61 000-2-2: 2002 , Co m p a tib ilité é le ctro m a gn é tique (CEM) – Pa rtie 2-2:
En viro n n e m e n t – Nive a ux de co m p a tib ilité p o ur le s p e rturb a tion s co n duite s à b a sse fré que n ce
IEC 62040-1 , A lim e n ta tio n s sa n s in te rrup tio n (A SI) – Pa rtie 1 : Exige n ce s gé n é ra le s e t rè gle s
de s é curité p o ur le s A SI
I EC 62040-2, A lim e n ta tio n s sa n s in te rrup tio n (A SI) – Pa rtie 2: Exige n ce s p o ur la co m p a tib ilité
3 T e rm e s e t d é fi n i t i o n s
3. 1 G é n é ra l i t é s
Pour les besoins du présent docum ent, les termes et définitions suivants s'appliquent.
L’I SO et l’I EC tiennent à j our des bases de données terminologiques destinées à être utilisées
en normalisation, consultables aux adresses suivantes:
• I EC Electropedia: disponible à l'adresse http: //www. electropedia. org
• I SO Online browsing platform: disponible à l'adresse http://www. iso. org/obp
NOTE Dans le présent d ocu m ent, les définitions de l'I EC 60050 sont citées d ès que cela est possibl e, en
particu lier celles d e l'I EC 60050-551 .
Lorsq u'u ne d éfiniti on d e l'I EC 60050 n écessite d'être dével oppée ou com plétée, le term e "m odifiée" est ajouté
après l a référence à l'I EC 60050.
3. 2 D é fi n i t i o n s re l a t i v e s a u x s y s t è m e s e t c o m p o s a n t s
3. 2. 1
AS I à te n s i o n c o n ti n u e
ensemble de , d'interrupteurs et de
c o n v e rt i s s e u rs d i s p o s i t i fs de s to cka g e d ' é n e rg i e (tels
que des batteries) constituant un systèm e d'alimentation capable d'assurer la co n t i n u i té de
l ' a l i m e n ta ti o n de la c h a rg e en cas de
en c o u ra n t c o n ti n u d é fa i l l a n c e de la s o u rc e
la distorsi on ou l es interrupti on s se trouvent en dehors des li m ites spécifiées pour l' . AS I à ten si on c o n ti n u e
3. 2. 2
c o n v e rt i s s e u r é l e c t ro n i q u e d e p u i s s a n c e
c o n v e rt i s s e u r d e p u i s s a n c e
c o n v e rt i s s e u r
correctes. Dans le présent d ocum ent, l'orth ographe " " est utilisée pour éviter les dupl ications.
c o n v e rt e r
redresseur onduleur
IEC
F i g u re 1 – E x e m p l e s d e c o n v e rt i s s e u rs é l e c t ro n i q u e s d e p u i s s a n c e d e b a s e
[SOU RCE: I EC 60050-551 : 1 998, 551 -1 2-01 , m odifiée — La note 2 à l'article et la figure ont
été aj outées. ]
3. 2. 3
u n i t é fo n c t i o n n e l l e
< AS I à ten si on c o n ti n u e > sous-ensemble complet qui accomplit une fonction donnée dans
une AS I à ten si on co n ti n u e
EXEMPLE U n c o n v e rt i s s e u r ou u n redresseur.
3. 2. 4
d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
système com portant un ou plusieurs dispositifs, conçu pour fournir l'énergie nécessaire à
l'onduleur d' AS I pour la
à te n s i o n c o n ti n u e requise d u ré e d ' a u t o n o m i e
Note 1 à l'articl e: Exception faite des difficultés liées à la recharg e, les exem ples de d i s p o s i t i fs de s to c ka g e
condensateu r), les systèm es à vol ant d'i nertie et à pil e com bustible.
3. 2. 5
al i m e n ta ti o n à c o u ra n t c o n t i n u i n t e rn e
3. 2. 6
b a t t e ri e
– une ch aîne constituée d'u ne certain e qu antité d'él ém ents connectés en série; ou
– deu x ou plusi eu rs chaînes en parallèle, chaque ch aîn e contenant la m êm e quantité d 'él ém ents connectés en
série.
[SOU RCE: I EC 60050: 2004, 482-01 -04, m odifiée — Le m ot "électrochim iques" a été ajouté à
la définition, ainsi que la note à l'article. ]
I EC 62040-5-3: 201 6 © I EC 201 6 – 75 –
3. 2. 7
b a t t e ri e d ' a c c u m u l a t e u rs
Note 1 à l'article: Une à soupapes est constitu ée d'élém ents qui sont ferm és, m ais
b a t t e ri e d ' a c c u m u l a t e u rs
m unis d'une soupape perm ettant l'échappem ent des g az lorsq ue l a pression intern e excède une valeu r
prédéterm inée. Les batteries au plom b étanches à soupapes sont abrégées "VRLA" (voi r l'I EC 60050-482: 2004,
482-05-1 5).
Note 2 à l'article: Une b a t t e ri e ouverte est constitu ée d'élém ents ayant un cou vercle m uni
d ' a c c u m u l a t e u rs
d'un e ouverture au travers d e laqu elle les prod uits de l'électrolyse et de l'évaporati on peu vent s'échapper
librem ent, ou par u n systèm e de ventil ation, de l'él ém ent vers l 'atm osphère (voi r l'I EC 60050-482: 2004,
482-05-1 4).
3. 2. 8
s y s t è m e d e s t o c k a g e à v o l a n t d ' i n e rt i e
3. 2. 9
c h a rg e u r d e b a t t e ri e
3. 2. 1 0
te n s i o n ou d'une charge
con ti n u e
3. 2. 1 1
re d re s s e u r d ' AS I à te n s i o n co n ti n u e
3. 2. 1 2
i n t e rru p t e u r
d'interrom pre des courants dans des conditions normales du circuit, d'établir et de supporter
des courants pendant une durée spécifiée et d'interrompre des courants du circuit dans des
conditions inhabituelles spécifiées
3. 2. 1 3
ré s e a u d e d i s t ri b u t i o n d e c o u ra n t c o n t i n u
réseau à courant continu qui connecte des sources et des systèm es de stockage aux charges
réparties
3. 2. 1 4
p u i s s an c e d ' a l i m e n tat i o n a l t e rn a t i v e
p u i s s an c e d ' a l i m e n tati o n d u ré s e a u
valeur moyenne, prise sur un cycle com plet, des produits de la valeur instantanée de la
com posante alternative du courant par la valeur, au m êm e instant, de la tension
d'alimentation du réseau
3. 2. 1 5
u n i t é d ' AS I à ten si on co n ti n u e
3. 2. 1 6
AS I à te n s i o n c o n t i n u e u n i t a i re
3. 2. 1 7
AS I à te n s i o n c o n t i n u e p a ra l l è l e
fonctionnant en parallèle
3. 2. 1 8
s y s t è m e re d o n d a n t
systèm e dans lequel une ou plusieurs u n i tés fo n c t i o n n e l l e s peuvent tomber en défaut sans
affecter la co n ti n u i té d e l ' a l i m e n ta ti o n d e l a c h a rg e
3. 2. 1 9
AS I à te n s i o n c o n t i n u e p a ra l l è l e e n re d o n d a n c e a c t i v e
parallèle se partageant l'alim entation de la charge de telle sorte qu'en cas de défaillance
d'une ou plusieurs d'entre elles, les unités restantes fournissent la totalité de la puissance à
la charge
3. 3 P e rfo rm a n c e d e s s y s t è m e s e t c o m p o s a n t s
3. 3. 1
ré s e a u p ri n c i p a l
3. 3. 2
ré s e a u d e s e c o u rs
3. 3. 3
d é fa i l l a n c e d u ré s e a u
toute variation de la source d'alimentation qui peut provoquer des perform ances
inacceptables de l'équipement à alimenter
3. 3. 4
co n t i n u i té d e l ' al i m e n ta ti o n d e l a c h a rg e
maintien de l'énergie fournie dans les limites spécifiées pour la sortie de l' AS I à ten si on
3. 3. 5
c o u ra n t d ' o n d u l a t i o n d e l a b a t t e ri e
3. 3. 6
m o d e n o rm a l
mode stable de fonctionnem ent que l' AS I à te n s i o n co n ti n u e atteint dans les conditions
suivantes:
a) l'alim entation alternative d'entrée respecte les tolérances requises et alim ente l' AS I à
te n s i o n ;
con ti n u e
con ti n u e
3. 3. 7
m o d e d e fo n c t i o n n e m e n t e n a u t o n o m i e d e l ' AS I à ten si on co n ti n u e
requises;
b) l'intégralité de l'alimentation provient du ;d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
.
con ti n u e
3. 3. 8
AS I à te n s i o n co n ti n u e m o b i l e
matériel qui est de m asse inférieure ou égale à 1 8 kg et non installé à poste fixe, ou équipé
de roues, roulettes ou autres m oyens qui en facilitent le déplacement lorsque cela est
nécessaire pour garantir son utilisation prévue
Note 1 à l'article: D'après l'I EC 60950-1 .
3. 3. 9
AS I à te n s i o n c o n t i n u e s e m i - fi xe
3. 3. 1 0
AS I à te n s i o n c o n t i n u e i n s t a l l é e à p o s t e fi x e
3. 3. 1 1
p e rs o n n e q u a l i fi é e
personne ayant la formation et l'expérience appropriées pour lui permettre de percevoir les
risques et d'éviter les dangers que peut présenter le matériel
[SOU RCE: I EC 60050-826: 2004, 826-1 8-01 , m odifiée — La référence à "l'électricité" a été
remplacée par une référence au "m atériel". ]
3. 3. 1 2
es s ai d e t yp e
essai de conform ité effectué sur une ou plusieurs entités représentatives de la production
3. 3. 1 3
es s ai i n d i vi d u e l d e s é ri e
essai de conform ité effectué sur chaque entité en cours ou en fin de fabrication
3. 4 V a l e u rs s p é c i fi é e s ‒ G én éralités
3. 4. 1
c a ra c t é ri s t i q u e s a s s i g n é e s
ensem ble des v a l e u rs ass i g n ées et des conditions de fonctionnem ent d'une machine, d'un
dispositif ou d'un matériel
[SOU RCE: I EC 60050-1 51 : 2001 , 1 51 -1 6-1 1 , modifiée — Les m ots "d'une machine, d'un
dispositif ou d'un matériel" ont été ajoutés. ]
– 78 – I EC 62040-5-3: 201 6 © I EC 201 6
3. 4. 2
val eu r as s i g n ée
valeur d'une grandeur, utilisée à des fins de spécification, généralement établie par un
fabricant et correspondant à un ensem ble spécifié de conditions de fonctionnem ent d'un
composant, dispositif, m atériel ou systèm e
[SOU RCE: I EC 60050-1 51 : 2001 , 1 51 -1 6-08, modifiée — Les m ots "généralem ent établie par
un fabricant et" ont été aj outés. ]
3. 4. 3
c h a rg e d ' e s s a i d e ré fé re n c e
c h a rg e à c o u ra n t c o n t i n u assi g n ée
charge ou condition dans laquelle la sortie de l' AS I à ten si on con ti n u e fournit l'énergie
active (W) pour laquelle l' AS Iest assignée
à te n s i o n c o n ti n u e
Note 1 à l'article: La charge assignée est la valeur de la ch arg e utilisée à d es fins de spécification, général em ent
établi e par le fabricant pour un ensem ble spécifié de con ditions d e fonctionnem ent d'u n com posant, dispositif,
m atériel ou systèm e.
3 . 4. 4
c h a rg e ré s i s t i v e
charge qui, lorsqu'elle est fournie par une source à tension variable, présente une impédance
résistive qui dem eure constante pour des usages pratiques
3 . 4. 5
c h a rg e à p u i s s a n c e c o n s t a n t e
charge qui, lorsqu'elle est fournie par une source à tension variable V, présente une
im pédance résistive R qui varie pour des usages pratiques de sorte que la pu i s s an ce
acti veP consomm ée par le circuit dem eure constante, ce qui revient à P = V2 /R = constante
3 . 4. 6
c h a rg e p a r p a l i e rs
3 . 4. 7
c h a rg e ré d u i t e
s o rt i e a s s i g n é e
3 . 4. 8
val eu r n o m i n a l e
val e u r d e d é n o m i n ati o n
valeur d'une grandeur, utilisée pour dénomm er et identifier un com posant, un appareil, un
m atériel ou un systèm e
Note 1 à l'article: La va l e u r n o m i n a l e est gén éralem ent un e valeur arrondi e.
3 . 4. 9
p l a g e d e t o l é ra n c e
3 . 4. 1 0
é c a rt
[SOU RCE: I EC 60050-351 : 201 3, 351 -41 -04, m odifiée – La note à l'article a été supprim ée. ]
I EC 62040-5-3: 201 6 © I EC 201 6 – 79 –
3. 4. 1 1
l i m i t a t i o n d e c o u ra n t
3. 4. 1 2
te n s i o n assig n ée
V ra t e d
matériel et à laquelle il est fait référence pour le fonctionnement et pour les caractéristiques
fonctionnelles
Note 1 à l 'articl e: Un e AS I à ten si on co n ti n u e peut posséd er plus d 'un e te n s i o n as si g n ée pour son entrée et sa
sortie.
Note 2 à l'article: Dans le cas d'une AS I à ten si on c o n ti n u e à entrée tri ph asée, la tension entre ph ases
s'appli que.
3 . 4. 1 3
pl ag e as si g n ée d e ten si on s
plage de tensions d'alimentation d'entrée ou de sortie déclarée par le fabricant, exprimée par
ses inférieure et supérieure
ten si on s as s i g n ées
3 . 4. 1 4
v a ri a t i o n d e l a ten si on e ffi c a c e
différence entre la tension efficace et la tension efficace correspondante précédemm ent non
perturbée
Note 1 à l'article: Pour les besoins de ce docum ent, le term e "variation" a la significati on suivante: la différence
des valeu rs d'u ne grandeu r avant et après u ne m odification d 'une grand eu r d'i nfluence.
3 . 4. 1 5
c o u ra n t a s s i g n é
[SOU RCE: I EC 60050-442: 1 998, 442-01 -02 modifiée – Le mot "courant" a été remplacé par
"courant d'entrée ou courant de sortie" et les m ots "d'un appareil" a été supprimé.]
3 . 4. 1 6
p u i s s an c e ac ti ve
T
P= 1 ⋅
∫ p ⋅ dt
T
0
Note 1 à l'article: En régim e sinusoïd al, la p u i s s a n ce a cti ve est la parti e réell e de l a puissance com plexe.
Note 2 à l'article: L'unité SI de p u i s s a n ce a c ti ve est le watt.
Note 3 à l 'articl e: Les tensi on s à courant conti nu, fondam entales et harm oniqu es contri buent directem ent à défini r
la valeur de l a pu i s san ce . Les instrum ents adéq uats utilisés pour m esurer la
a c ti ve présentent p u i s s an ce a c ti ve
une l argeu r de ban de suffisante pour m esurer les com posants de puissance non sym étriq ue et h arm oni que
significatifs.
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -42, modifiée — La note 3 à l'article a été aj outée. ]
– 80 – I EC 62040-5-3: 201 6 © I EC 201 6
3. 4. 1 7
p u i s s a n c e a p p a re n t e
produit des valeurs efficaces de la tension électrique et du courant électrique au niveau d'un
accès:
S = UI
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -41 , modifiée — Couvre uniquem ent les valeurs
efficaces. ]
3. 4. 1 8
fa c t e u r d e p u i s s a n c e
P
λ=
S
[SOU RCE: I EC 60050-1 31 : 2002, 1 31 -1 1 -46, m odifiée — Les mots "en régim e périodique" ont
été supprim és. ]
3 . 4. 1 9
re n d e m e n t d e l ' AS I à ten si on co n ti n u e
Note 1 à l'article: Les condi tions d'essai pour le re n d e m e n t de l ' AS I à te n s i o n c o n ti n u e se trou vent à
l'Annexe F.
3 . 4. 2 0
fré q u e n c e a s s i g n é e
3 . 4. 2 1
v a ri a t i o n d e fré q u e n c e
3 . 4. 2 2
t a u x d e d i s t o rs i o n h a rm o n i q u e t o t a l e
TH D
[SOU RCE: I EC 60050-551 : 1 998, 551 -1 7-06, modifiée — La note à l'article a été ajoutée. ]
3 . 4. 2 3
c o m p o s a n t e s h a rm o n i q u e s
3 . 4. 2 4
ré s i d u h a rm o n i q u e
Note 2 à l'article: Pour l'an alyse prati que, il peut être nécessaire de procéder à u ne approxim ation d e la
périodicité.
Note 3 à l'articl e: Le ré s i d u dépend d u choi x de la com posante fon dam entale. En cas d'am bigu ïté
h a rm o n i q u e
3 . 4. 2 5
t ra n s i t o i re
com portem ent d'une grandeur au cours du passage d'un régim e établi à un autre
3 . 4. 2 6
d u ré e d ' a u t o n o m i e
assure la
con ti n u e co n ti n u i té de l ' al i m en tati on de la c h a rg e , dans les conditions de
service spécifiées
3 . 4. 2 7
t e n s i o n d ' a rrê t
3. 4. 2 8
d u ré e d e re c h a rg e
de l'
d ' é n e rg i e AS I à de façon à ce que la
te n s i o n con ti n u e puisse de d u ré e d 'au ton om i e
3 . 4. 2 9
t e m p é ra t u re a m b i a n t e
Note 1 à l'article: Pendant l a m esure de la t e m p é ra t u re am bi an te , il con vient q ue l'i nstrum ent/la sonde d e
m esure soit protég é des cou rants d'air et de l a chaleur rayon nante.
[SOU RCE: I EC 60050-826: 2004, 826-1 0-03, m odifiée — L'adjectif "moyenne" a été supprimé,
et la définition a été reform ulée. ]
3. 5 V a l e u rs d ' e n t ré e
3. 5. 1
t o l é ra n c e d e l a t e n s i o n d ' e n t ré e
variation maximale de la tension d'entrée en régime établi spécifiée par le fabricant en mode
de fonctionnement
n o rm a l
3. 5. 2
t o l é ra n c e d e l a fré q u e n c e d ' e n t ré e
3. 5. 3
fa c t e u r d e p u i s s a n c e d ' e n t ré e
en
co n ti n u e m o d e n o rm a l de fonctionnement à une tension assignée d'entrée et une charge
assignée, et le étant totalement chargé
d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
– 82 – I EC 62040-5-3: 201 6 © I EC 201 6
3. 5. 4
c o u ra n t a s s i g n é d ' e n t ré e d e l ' AS I à t e n s i o n co n ti n u e
3. 5. 5
3. 5. 6
valeur instantanée m axim ale du courant d'entrée lorsque l' AS I à ten s i o n con ti n u e est mise
en fonctionnem ent en m o d e n o rm a l
3. 5. 7
d i s t o rs i o n du c o u ra n t d ' e n t ré e
3. 5. 8
i m p é d a n c e d e s o u rc e
3. 5. 9
d é fa u t h a u t e i m p é d a n c e
3. 5. 1 0
d é fa u t b a s s e i m p é d a n c e
3. 5. 1 1
c o u ra n t d e c o u rt - c i rc u i t p ré s u m é
Icp
valeur efficace du courant qui circule lorsque les conducteurs d'alim entation du circuit sont
court-circuités par un conducteur d'im pédance négligeable
3. 6 V a l e u rs d e s o rt i e
3. 6. 1
t e n s i o n d e s o rt i e
valeur continue de la tension (sauf spécification contraire pour une charge particulière) aux
bornes de sortie de l' AS I à ten s i on co n ti n u e
3. 6. 2
t o l é ra n c e d e l a t e n s i o n d e s o rt i e
3. 6. 3
c o u ra n t d e s o rt i e
valeur continue du courant (sauf spécification contraire pour une charge particulière) aux
bornes de sortie
I EC 62040-5-3: 201 6 © I EC 201 6 – 83 –
3. 6. 4
c a p a c i t é d e s u rc h a rg e
3. 6. 5
p u i s s a n c e d e s o rt i e
3. 6. 6
p a rt a g e d e c h a rg e
3. 6. 7
p u i s s a n c e d e s o rt i e a s s i g n é e
te n s i o n d ' o n d u l ati o n
[SOU RCE: 551 -06-28, m odifiée - "convertisseur" remplacé par "unité fonctionnelle"]
4 C o n d i t i o n s d ' e n vi ro n n e m e n t
4. 1 E n v i ro n n e m e n t d ' e s s a i
NOTE Le deg ré de pol lution est une caractéristique d'u n envi ronnem ent. I l est décrit de m anière détaillée d ans
l'I EC 60664-1 , d'où sont tirées les inform ations suivantes.
– Le degré de pol lution 1 s'appli que lorsqu'il n'existe pas de polluti on ou u niq uem ent une polluti on sèche non
conductrice.
– Le degré de polluti on 2 s'appliqu e lorsq u'il existe un iqu em ent un e poll ution non cond uctrice, qui pourrait
tem porai rem ent devenir cond u ctrice par suite d'une cond ensation occasionnelle.
– Le degré de polluti on 3 s'appl ique lorsqu'un en vi ron nem ent local à l'i ntéri eur du m atéri el est soum is à un e
poll ution con ductrice ou à une poll ution sèche non con ductrice, qui pou rrait d eveni r con ductrice par suite d'u ne
condensation atten du e.
4. 2 C o n d i t i o n s n o rm a l e s
4. 2 . 1 F o n cti on n e m e n t
4. 2 . 1 . 1 H u m i d i t é re l a t i v e e t t e m p é ra t u re a m b i a n t e
NOTE Un e exig ence concern ant le fonctionn em ent de l' AS I à au-del à des plag es am biantes
ten s i on c o n ti n u e
m inim ales est considérée com m e faisant parti e des con dition s inhabituell es. Voir 4. 3.
– 84 – I EC 62040-5-3: 201 6 © I EC 201 6
vé rifié e co n form é m e n t à l'IEC TR 60721 -4-3, la vé rifica tion é ta n t ré a lis é e se lo n la p rocé dure
4. 2 . 1 . 2 Al t i t u d e
fonctionner conform ément aux caractéristiques assignées à une altitude inférieure ou égale à
1 000 m au-dessus du niveau de la m er.
fonctionner à une altitude particulière au-delà de 1 000 m , le fabricant doit indiquer, pour
cette altitude:
– la nouvelle p u i ss an ce , si elle diffère de la
de s o rt i e assi g n ée p u i s s an ce de s o rt i e
NOTE Le Tableau 1 ci-dessous fournit des li gnes di rectrices. I l s'agit d'un exem pl e de dég rad ation des
caractéristiqu es assignées de puissance, exi gée par l'altitu de.
Tabl eau 1 – F a c t e u rs d e d é g ra d a t i o n
d e p u i s s a n c e à u t i l i s e r à d e s a l t i t u d e s s u p é ri e u re s à 1 000 m
Al t i t u d e F a c t e u r d e d é g ra d a ti o n
m pieds R e fro i d i s s e m e n t p a r
c o n ve c ti o n
R e fro i d i s s e m e n t p a r
ve n ti l a ti o n fo rc é e
4. 2 . 2 E n t re p o s a g e e t t ra n s p o rt
entreposage sem i-fixe dans un bâtim ent et être transportable dans son conteneur d'expédition
normal par avion comm ercial pressurisé, par cargo ou par cam ion, dans les plages ambiantes
minimales suivantes:
– tem pérature de –25 °C à +55 °C;
– hum idité relative de 1 0 % à 95 % sans condensation.
L a co n fo rm ité e s t vé rifié e lors que l' ASI à tension continue ré uss it l'e ssa i sp é cifié e n 6. 5. 2.
I EC 62040-5-3: 201 6 © I EC 201 6 – 85 –
Les conteneurs non conçus pour des conditions ambiantes humides (avec condensation)
doivent être marqués au moyen d'étiquettes d'avertissement adéquates.
te n s i o n conforme à le présent docum ent doit pouvoir être entreposé à une altitude
co n ti n u e
pour laquelle la pression atm osphérique équivalente est supérieure ou égale à 70 kPa.
NOTE La pression atm osphériq ue à u ne altitude d e 3 000 m au-dessus du ni veau de la m er se situe autou r d e
70 kPa.
4. 3 C o n d i ti o n s i n h a b i t u e l l e s
4. 3 . 1 G e n e ra l
4. 3 répertorie les conditions qui, selon un accord entre le fabricant et l'acheteur, nécessitent
une conception spéciale et/ou des fonctions de protection spéciales. L'acheteur doit identifier
les exigences qui s'écartent des conditions normales indiquées en 4. 2.
4. 3 . 2 F on cti on n e m e n t
Les conditions de stockage et de transport inhabituelles à identifier incluent les élém ents
suivants:
– des conditions de température et d'hum idité relative supérieures aux plages indiquées
en 4. 2;
– des conditions d'altitude supérieures à celles indiquées en 4. 2;
– une exposition à des vibrations, chocs et basculem ents anorm aux et à des forces
d'accélération sism ique;
– des exigences spéciales pour le transport et la manutention du matériel.
– 86 – I EC 62040-5-3: 201 6 © I EC 201 6
5 C o n d i t i o n s é l e c t ri q u e s , p e rfo rm a n c e s e t va l e u rs d é c l a ré e s
5. 1 G é n é ra l i t é s
5. 1 . 1 C o n fi g u ra t i o n d e l ' AS I à te n s i o n c o n ti n u e
5. 1 . 2 M a rq u a g e s e t i n s t ru c t i o n s
accom pagnée des instructions d'installation et d'exploitation adéquates pour l' AS I à ten si on
5. 2 . 1 C o n d i t i o n s re l a t i v e s a u m o d e n o rm a l d e fo n c t i o n n e m e n t
fonctionnem ent lorsqu'elle est raccordée à une alim entation alternative d'entrée présentant
les caractéristiques suivantes:
a) te n s i o n ; assi g n ée
b) v a ri a t i o n égale à ± 1 0 % de la
d e l a ten si o n e ffi c a c e ; ten si on as s i g n ée
c) ;
fré q u e n c e a s s i g n é e
d) v a ri a t i o n égale à ± 2 % de la
d e fré q u e n c e ; fré q u e n c e a s s i g n é e
tels que ceux causés par la foudre ou une commutation inductive ou capacitive,
respectant les niveaux d'im munité électrom agnétique applicables prescrits dans
l'I EC 62040-2.
NOTE 1 U ne dim inution d e l a fréq uence n 'est pas censée coïncider avec un e augm entati on de la tension de l ign e
à courant al ternatif et vice-versa.
NOTE 2 Les lim ites ci-dessus s'appliqu ent au x réseau x pu blics d'alim entation à courant alternatif basse tensi on.
Les AS I à ten s i o n à usag e in dustri el ou l es ali m entations électriqu es générées séparém ent peuvent
co n ti n u e
devoi r satisfai re à des conditi ons plus sévères. Le cas échéant, l'ach eteu r spécifie ces cond itions. En l'absence de
telles inform ations, le fabricant/fournisseu r s'appuie sur son expérience pour assu rer que la concepti on est
com patibl e avec l'instal lation prévue.
NOTE 3 Les ni veau x d e com patibilité pour l es tensions harm oniq ues indi vid uell es applicabl es au x réseau x publics
basse tensi on sont spécifiés d ans l'I EC 61 000-2-2. Le Tabl eau 2 ci-d essous est un extrait d e l'I EC 61 000-2-2: 2002;
I EC 62040-5-3: 201 6 © I EC 201 6 – 87 –
il répertorie ces ni veau x d e com patibilité (valeu rs efficaces exprim ées sous la form e d'un pourcentage d e la valeu r
efficace de l a com posante fon d am entale).
h a rm o n i q u e s i n d i v i d u e l l e s a p p l i c a b l e s a u x ré s e a u x b a s s e t e n s i o n
H a rm o n i q u e s i m p a i re s H a rm o n i q u e s i m p a i re s H a rm o n i q u e s p a i r e s
a
n on m u l ti p l e s d e 3 m u l ti p l e s d e 3
Ra n g Te n s i o n Ra n g Te n s i o n Ra n g Te n s i o n
h a rm o n i q u e h a rm o n i q u e h a rm o n i q u e h a rm o n i q u e h a rm o n i q u e h a rm o n i q u e
n % n % n %
5 6 3 5 2 2
7 5 9 1 ,5 4 1
11 3, 5 15 0, 4 6 0, 5
13 3 21 0, 3 8 0, 5
17 ≤ n ≤ 49 2, 27 × (1 7/ n ) – 0, 27 21 ≤ n ≤ 45 0, 2 10 ≤ n ≤ 50 0, 25 × (1 0/ n ) + 0, 25
a Les ni veau x donnés pour les harm oni qu es im paires qu i sont d es m ultiples de trois s'appl i quent au x
harm oni ques hom opolai res. En outre, sur u n réseau triph asé sans cond ucteu r n eutre ou sans charg e
connectée entre l a lig ne et l a terre, les val eurs d es troisièm e et neu vièm e harm oniq u es peuvent être
significati vem ent inférieures au x ni veau x de com patibilité, sel on le déséq uili bre du réseau.
5. 2 . 2 C a ra c t é ri s t i q u e s d ' e n t ré e q u e l e fa b ri c a n t d o i t d é c l a re r
Le fabricant doit déclarer les caractéristiques d'entrée réelles et applicables. Outre les
caractéristiques abordées en 5. 2.1 , les caractéristiques suivantes doivent également être
déclarées:
a) nom bre de phases;
b) exigences relatives au neutre;
c) ;
c o u ra n t a s s i g n é
d) au
fa c t e u r d e p u i s s a n c e ; c o u ra n t a s s i g n é
tension ± 1 0 %), de toute surcharge admise continue et, le cas échéant, de la courbe du
courant en fonction du tem ps;
g) tau x de d i s t o rs i o n du courant et
h a rm o n i q u e to ta l e (TH D) c o u ra n t de c o u rt - c i rc u i t
NOTE 1 Pour l es besoins d e conform ité du courant par rapport au TH D, l'exi gence de c o u ra n t de c o u rt - c i rc u i t
p ré s u m ém inim al est général em ent donn ée sous la form e d'un m ultiple d u courant assig né d'entrée de l' AS I à
te n s i o n . La valeur est habituell em ent égale à 33 fois pou r un cou rant assign é d'entrée ≤ 300 A et à
co n ti n u e
20 fois pou r un courant assign é d'entrée > 300 A. Par exem ple, pou r un e présentant un AS I à te n s i o n c o n ti n u e
5. 2 . 3 C a ra c t é ri s t i q u e s e t c o n d i t i o n s q u e l ' a c h e t e u r d o i t i d e n t i fi e r
L'acheteur doit identifier les caractéristiques et conditions qui sont plus sévères que celles
déclarées par le fabricant.
– 88 – I EC 62040-5-3: 201 6 © I EC 201 6
Par ailleurs, l'acheteur doit identifier les conditions particulières pouvant être exigées au titre
de la réglementation nationale en m atière de câblage ainsi que les éventuelles conditions de
service défavorables ou spéciales, notamment
a) la distorsion de la tension harmonique préexistante lorsque la valeur dépasse 75 % des
niveaux de compatibilité de l'I EC 61 000-2-2 au point de couplage prévu avec l' AS I à
b) les exigences de com patibilité par rapport aux caractéristiques des dispositifs de
protection de l'alimentation d'entrée de l' , AS I à ten si on co n ti n u e
Ces conditions de service et ces é c a rt s peuvent exiger une conception et/ou des fonctions de
protection spéciales.
5. 3 S p é c i fi c a t i o n d e s o rt i e d e l ' AS I à te n s i o n con ti n u e
5. 3. 1 C o n d i t i o n s n é c e s s a i re s p o u r q u e l ' AS I à t e n s i o n c o n t i n u e a l i m e n t e u n e c h a rg e
une AS I à ten si on conforme à le présent docum ent doit être capable d'alim enter
con ti n u e
5. 3 . 2 C a ra c t é ri s t i q u e s q u e l e fa b ri c a n t d o i t d é c l a re r
Le fabricant doit déclarer les caractéristiques de sortie réelles et applicables, notamm ent les
élém ents suivants:
a) classification des perform ances XX conform ément à 5. 3. 4;
b) ten s i o n , par exem ple 380 V en courant continu;
assi g n ée
c) identification des polarités disponibles pour la connexion des charges, conformém ent à la
définition donnée en 31 2. 2. 4 de l'I EC 60364-1 : 2005, par exemple L+, L-. Le point
médian M doit être identifié uniquement s'il est censé transporter le courant de charge,
par exemple L+, M , L-;
d) com patibilité de la m ise à la terre (TN, TT ou I T, com me défini en 31 2. 2. 4 de
l'I EC 60364-1 : 2005), y compris les informations relatives aux polarités, s'il y a lieu,
pouvant être mises à la terre par l'installateur;
e) schéma de mise à la terre des polarités;
f) com posante alternative ( );
te n s i o n d ' o n d u l a ti o n
g) (W) et
p u i s s a n c e d e s o rt i e a s s i g n é e ; c o u ra n t a s s i g n é
h) ;
c a p a c i t é d e s u rc h a rg e
un tem ps spécifié;
j) capacité d'élim ination de défaut: la capacité assignée d'élim ination de défaut doit être
donnée com me étant la maximale du dispositif de protection de
c a ra c t é ri s t i q u e a s s i g n é e
I EC 62040-5-3: 201 6 © I EC 201 6 – 89 –
défaut;
k) pertes à vide et de l' re n d e m e n t à une
AS I à ten s i o n con ti n u e c h a rg e d ' essai de
NOTE 1 Les val eu rs de ren dem ent au x valeurs d e charge i nterm édiai res sont g én éralem ent calculées.
NOTE 2 La déclarati on, lorsqu'el le est sous l a form e d'u n e fiche techni que, est h abituel lem ent incluse dans le
m anuel de l'utilisateu r. A titre d'aide, l'An nexe C propose u ne fiche techni que q ui inclut l es caractéristiq ues de
perform ances particuli ères dan s des conditions an orm ales, par exem ple à u ne tension d'entrée altern ati ve él evée.
5. 3. 3 C a ra c t é ri s t i q u e s e t c o n d i t i o n s q u e l ' a c h e t e u r d o i t i d e n t i fi e r
L'acheteur doit identifier les caractéristiques et conditions qui sont plus sévères que celles
déclarées par le fabricant, m ais sans s'y limiter.
Par ailleurs, l'acheteur doit identifier les conditions particulières pouvant être exigées au titre
de la réglem entation nationale en matière de câblage ainsi que les éventuelles conditions de
charge défavorables ou spéciales, notamm ent
a) les caractéristiques d'appel et de démarrage,
b) les caractéristiques variables (y compris la période et le cycle de service),
c) la m ise à la terre indépendante des polarités de sortie exigées,
d) les installations de distribution de la charge,
e) les exigences relatives à l'ensemble des polarités de l' AS I à te n s i o n c o n ti n u e devant
être isolées de la charge par l'intermédiaire d'un dispositif de déconnexion,
f) les exigences de coordination par rapport aux dispositifs de protection en aval ,
g) les exigences futures en termes d'extension/expansion,
h) la sécurité fonctionnelle (voir I EC 61 508 (toutes les parties)),
i) le degré de redondance (voir Annexe A), et
j) le délestage automatique.
5. 3 . 4 C l a s s i fi c a t i o n d e s p e rfo rm a n c e s
XX
où X est un caractère alphabétique.
Le premier X représente la variation de la te n s i o n d e s o rt i e par rapport au régim e établi, lors
d'un fonctionnement en et lorsqu'une
m od e n o rm a l c h a rg e par est appliquée,
p a l i e rs
comme défini en 6. 4. 2. 9. 3.
Tension (%)
20
+5 %
Valeur
+11 %
N
0
nominale
Limites
-5 %
-2 0
-22 %
-40
-32 % Limites W
-60
-80
-1 00
IEC
F i g u re 2 – P e rfo rm a n c e s d y n a m i q u e s d e s o rt i e
NOTE 1 Les lim ites indiq uées à l a Fig ure 2 sont représentati ves des exig ences q ui s'appliq uent à des
alim entations à découpage com patibles avec les exigences d e l'I TU -T L. 1 200.
fournir une base com m une pour l'évalu ation des d on nées de l'ensem ble des fabricants/fournisseurs d' AS I à
à te n s i o n , d e com parer l es prod uits de différents fabricants dans les m êm es conditions de m esure.
co n ti n u e
NOTE 3 I l est rappel é au x acheteu rs qu e, com pte tenu de la di versité d es types de ch arges, les données des
fabricants d' AS I à sont basées su r d es charges d'essai norm alisées de l'ind ustrie q ui sim ulent
te n s i o n co n ti n u e
courants de d ém arrage sont susceptibles de différer par rapport au x situ ations d'essai norm alisées.
NOTE 5 U ne AS I à classifiée NW constitue u n exem ple d'
ten si on co n ti n u e présentant AS I à te n s i o n c o n ti n u e
fonctionnem ent en autonom ie (par exem ple: un e à topologie de con version sim ple, à
AS I à te n s i o n co n ti n u e
continu e possède un e réponse en tensi on dynam ique conform e à la courbe W de la Figu re 2 après passage en
m ode de fonctionn em ent en autonom ie et après une en m ode de foncti onn em ent en
c h a rg e par p a l i e rs
autonom ie.
NOTE 6 Pour des l i gnes di rectrices sur les techn iqu es de m esure, voi r Annexe E.
NOTE 7 Les perform ances sont général em ent déterm inées par la topol ogi e des AS I à te n s i o n c o n ti n u e – voir
Annexe B.
5. 4 S p é c i fi c a t i o n d ' au to n o m i e
5. 4. 1 G é n é ra l i t é s
technologie la plus fréquemment utilisée pour le stockage d'énergie, destinée à être utilisée
lorsque l'alimentation alternative d'entrée n'est pas disponible.
I EC 62040-5-3: 201 6 © I EC 201 6 – 91 –
Il est reconnu que d'autres technologies, par exem ple les systèmes à volant d'inertie, peuvent
se substituer à l'utilisation d'une . Ces technologies peuvent être entièrem ent
b a t t e ri e
aux batteries. Dans cette optique, selon un accord entre le fabricant/fournisseur et l'acheteur,
et s'il y a lieu, la spécification peut être utilisée pour d'autres technologies de stockage
d'énergie.
5. 4. 2 B a t t e ri e s
5. 4. 2 . 1 E xi g e n c e s re l a t i v e s à t o u t e s l e s b a t t e ri e s
l'I EC 62040-1 en ce qui concerne les exigences de sécurité relatives à l'emplacem ent, à la
ventilation, au marquage et à la protection d'une . b a t t e ri e
5. 4. 2 . 2 C a ra c t é ri s t i q u e s q u e l e fa b ri c a n t d o i t d é c l a re r
f) (voir 6. 4. 4. 1 );
d u ré e d ' a u t o n o m i e
g) ;
d u ré e d e re c h a rg e
seulement);
j) courant d'ondulation efficace en de fonctionnement de l'
mod e n o rm a l AS I à ten si on
;
con ti n u e
5. 4. 2 . 3 C a ra c t é ri s t i q u e s e t c o n d i t i o n s q u e l ' a c h e t e u r d o i t i d e n t i fi e r
L'acheteur doit identifier les exigences, caractéristiques et conditions qui s'écartent de celles
répertoriées en 5.4. 2. 1 et en 5. 4. 2.2, ou sont plus sévères. Cela inclut les conditions
particulières exigées par la réglementation nationale, ainsi que les éventuelles conditions de
service défavorables ou spéciales lorsqu'une est fournie par des parties tierces.
b a t t e ri e
NOTE Les réglem entati ons n ationales peuvent spécifi er u ne durée d'autonom ie de secou rs m inim ale et défini r le
type de à utiliser.
d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
perform ances électriques prescrites au présent Article 5 et ne nécessitent pas d'être spécifiés
séparément.
Les interrupteurs fournis séparém ent et destinés à fonctionner conjointement avec l' AS I à
La liste suivante donne des exemples de norm es de produits qui s'appliquent à des
interrupteurs particuliers:
– systèmes de transfert autom atique (ATS, a utom a tic tra n s fe r sys te m ): I EC 60947-6-1 ;
– isolem ent manuel, interrupteurs de liaison et de transfert: I EC 60947-3.
5. 6 C i rc u i t s d e c o m m u n i c a t i o n
Le fabricant doit fournir les instructions adéquates pour l'utilisation et l'installation des circuits
de communication et de signalisation fournis comme faisant partie intégrante de l' AS I à
par exem ple des autom ates programm ables, des réseaux locaux (LAN, loca l a re a n e twork) ou
des réseaux de télécommunications.
6 E s s a i s d ' AS I à t e n s i o n c o n t i n u e
6. 1 Ré s u m é
6. 1 . 1 Li eu , i n s t ru m e n t a t i o n e t c h a rg e
6. 1 . 1 . 1 Li eu d e te n u e d e s e s s a i s
Une AS I à doit généralement être soum ise aux essais dans les locaux du
te n s i o n con ti n u e
Les essais peuvent être réalisés sur l' AS I à ten si on con ti n u e dans sa forme com plète ou, à
défaut, sur une .
u n i t é fo n c t i o n n e l l e
Les essais de l' AS I peuvent nécessiter des installations qui ne sont pas
à te n s i o n co n ti n u e
disponibles dans les locaux du fabricant et/ou des installations qui n e sont pas justifiables
d'un point de vue économ ique eu égard à un réseau d'alimentation particulier. Le fabricant
peut ensuite décider de:
a) recourir à un organism e tiers com pétent afin de procéder aux essais de conformité pour le
com pte du fabricant. La j ustification de la certification par l'organism e tiers doit être jugée
suffisante pour dém ontrer la conformité aux articles applicables;
b) démontrer, par calcul ou par expérience et/ou en procédant à l'essai de conceptions ou de
sous-assem blages analogues dans des conditions sim ilaires et en com pilant un fichier de
I EC 62040-5-3: 201 6 © I EC 201 6 – 93 –
ne peuvent pas être entièrem ent soumises à l'essai avant livraison sur le site. Lorsque le
besoin s'en fait sentir, l'essai de l' en 6.6 s'applique. I l convient que le
u n i té fo n c t i o n n e l l e
fabricant/fournisseur et que l'acheteur se m ettent d'accord sur les conditions pour l'essai de
site final. I l convient de suivre la recomm andation du fabricant à ce suj et.
6. 1 . 1 . 2 I n s t ru m e n t a t i o n d 'essai
Les instruments utilisés pour la m esure des param ètres électriques doivent présenter une
largeur de bande suffisante pour m esurer avec précision une valeur efficace vraie sur des
formes d'ondes pouvant être différentes d'une sinusoïdale fondam entale, autrem ent dit qui
peuvent présenter un considérable. Quel que soit le type
ré s i d u h a rm o n i q u e
6. 1 . 1 . 3 E ss ai s e n c h a rg e
Pour effectuer des essais en charge, les charges sont connectées à la sortie de l' AS I à
Les essai s et les essais individuels de série doivent être effectués de la manière
de t yp e
prescrite dans les articles relatifs aux essais adéquats (p. ex. : à vide, à , avec c h a rg e ré d u i t e
une c h a rg e , une
ré s i s t i v e c h a rg e ou une
à p u i s s a n ce co n s ta n te c h a rg e d ' es s ai de
).
ré fé re n c e
Sauf prescription contraire dans l'article d'essai applicable, les essais de charge doivent être
effectués avec une .
c h a rg e d ' e s s a i d e ré fé re n c e
peuvent être soumises à l'essai en charge en effectuant un essai distinct sur chacune des
différentes u n i t é s d ' AS I . à ten si on co n ti n u e
NOTE Dans certains cas, u ne charge spécial e, notam m ent la charg e réelle du site, peut être utilisée sous réserve
d'avoi r été convenu e entre l e fabricant/fou rnisseur et l'acheteur.
6. 1 . 2 E s s a i s i n d i v i d u e l s d e s é ri e
pour vérifier que les exigences de le présent docum ent sont respectées. Les essais
L'essai des caractéristiques autres que celles couvertes dans les essais individuels de série
fait l'obj et d'un accord entre le fabricant et l'acheteur.
6. 1 . 3 E ss ai s s u r s i te
Les alimentations sans interruption couvertes par le présent docum ent vont des AS I à
te n s i o n de grande taille m ultim odules qui peuvent être livrées sous la form e
co n ti n u e
– 94 – I EC 62040-5-3: 201 6 © I EC 201 6
d' u n i tés distinctes destinées à être assemblées et câblées sur site. Ces
fo n c t i o n n e l l e s AS I
6. 1 . 4 E ss ai s cl i en ts
souhaiter que son représentant soit présent à des essais clients de certains éléments du
Tableau 3 et/ou d'autres élém ents spécifiques.
Les essais clients font l'objet d'un accord entre le fabricant et l'acheteur.
NOTE L'ach eteu r peut éval u er la nécessité de réaliser ou non u n essai client en fonction du statut d'assurance
qual ité du fabricant.
6. 1 . 5 E s s a i s d e t yp e
que ces produits identiques sont conform es à la spécification complète lorsqu'ils sont produits
selon les norm es de qualité adéquates et après avoir réussi les essai s i n d i vi d u e l s de s é ri e
décrits en 6.2. L' AS I à utilisée pour les essais de type n'est pas
te n s i o n co n ti n u e
décrits en 6. 4 et en 6. 5.
6. 1 . 6 C a l e n d ri e r d e s e s s a i s
i n d i vi d u e l
d e s é ri e
Mode n orm al – A vi de X 6. 4. 2. 1
Mode n orm al – Plei ne ch arge X 6. 4. 2. 2
Mode d e fonctionn em ent en au tonom ie – A vi de X 6. 4. 2. 3
Mode d e fonctionn em ent en au tonom ie – Pl ei ne charg e X 6. 4. 2. 4
Essai de partag e de ch arge X 6. 4. 2. 5
Essai de surtension d e sorti e X 6. 4. 2. 6
Essai de variati on périod iqu e d e la tensi on d e sorti e X 6. 4. 2. 7
(m odulati on )
Surcharg e – Mode n orm al X 6. 4. 2. 8. 1
Surcharg e – Mode d e fonction nem ent en auton om ie X 6. 4. 2. 8. 2
Capacité d'élim ination de d éfaut – M od e norm al X 6. 4. 2. 8. 3
Capacité d'élim ination de d éfaut – M od e de X 6. 4. 2. 8. 4
fonction nem ent en autonom ie
Perform ances dynam iques – Passage d u m ode norm al X 6. 4. 2. 9. 1
au m ode de fonctionnem ent en auton om ie
Perform ances dynam iques – Passage d u m ode de X 6. 4. 2. 9. 2
fonction nem ent en autonom ie au m ode norm al
Perform ances dynam iques – Charge par pali ers – Mode X 6. 4. 2. 9. 3
norm al
Perform ances dynam iques – Charge par pali ers – Mode X 6. 4. 2. 9. 4
de fonctionnem ent en auton om ie
– 96 – I EC 62040-5-3: 201 6 © I EC 201 6
i n d i vi d u e l
d e s é ri e
con s tan te
Durée d'auton om ie X 6. 4. 4. 1
Durée de recharge X 6. 4. 4. 2
Cou rant d'ond ulation d e la batteri e X 6. 4. 4. 3
Essai de redém arrag e X 6. 4. 4. 4
E s s a i s d ' e n v i ro n n e m e n t
6. 2 P ro c é d u re d ' e s s a i s i n d i v i d u e l s d e s é ri e
6. 2. 1 E s s a i s d ' e n v i ro n n e m e n t
6. 2. 2 E s s a i s é l e c t ri q u e s
6. 2. 2 . 1 E s s a i s d ' i s o l e m e n t e t e s s a i s d i é l e c t ri q u e s
Les caractéristiques d'isolem ent et diélectriques constituent une exigence de sécurité qui ne
relève pas du dom aine d'application de le présent document.
NOTE La conform ité au niveau des caractéristiq ues d'isol em ent et diélectri ques est vérifiée pend ant l'essai de
sécurité d e l' AS I applicable.
à te n s i o n co n ti n u e
6. 2. 2 . 2 V é ri fi c a t i o n d e s c â b l e s e t d e s i n t e rc o n n e x i o n s
L'AS I à ten si on doit être inspectée conformém ent aux schémas d'installation et de
con ti n u e
6. 2 . 2 . 3 E ssai fo n c t i o n n e l à c h a rg e ré d u i t e
est correctem ent connectée et que toutes les fonctions sont réalisées correctem ent.
co n ti n u e
Pour des raisons pratiques et économiques, la charge appliquée est limitée à un pourcentage
de la , par exemple 1 0 %. Le bon fonctionnem ent des éléments suivants doit
val eu r a s s i g n é e
être vérifié:
a) tous les interrupteurs de commande et les autres dispositifs permettant de mettre l' AS I à
courant alternatif;
NOTE Cet essai est général em ent réalisé conjoi ntem ent avec les essais de défaut/retour du courant al tern atif
en 6. 2. 2. 6 et en 6. 2. 2. 7.
f) la déconnexion m anuelle d'une u n i té d ' AS I à ten s i o n faisant partie d'une
con ti n u e
La co n form ité est vé rifié e par o b se rva tio n , en con trô la n t que le s dis p os itifs et fo n ctio n s
de stin é s à co n trô le r, p roté ge r, s up e rvise r, m e sure r et s ign a lis e r le s a ctivité s de l' ASI à
tension continue se co m p o rte n t de la m a n iè re a tte n due e t que la te n s io n e n ch a rge re sp e cte
6. 2 . 2 . 4 A vi d e
La ten si on de l'
de s o rt i e doit rester dans les lim ites spécifiées
AS I à ten si on con ti n u e
6. 2 . 2 . 5 P l e i n e c h a rg e
doit être comprise dans les valeurs spécifiées pour un fonctionnement à la fréquence
s o rt i e
peuvent être soum ises à l'essai en charge en effectuant des essais distincts sur chacune des
différentes u n i t é s d ' AS I , ou bien un effectuant un essai sur l'ensemble.
à ten si on co n ti n u e
6. 2 . 2 . 6 D é fa i l l a n c e d u c o u ra n t d ' e n t ré e a l t e rn a t i f
L'essai doit être réalisé avec une ou toute autre source de courant continu
b a t t e ri e
appropriée. La défaillance du courant d'entrée est sim ulée en interrom pant l'entrée en courant
alternatif aussi loin que possible en amont et selon la façon décrite à l'Annexe D.
La co n form ité est vé rifié e par e ssa i, qua n d, a p rè s la dé fa illa n ce à l'e n tré e en co ura n t
6. 2 . 2 . 7 Re t o u r d u c o u ra n t d ' e n t ré e a l t e rn a t i f
Cet essai doit être réalisé soit en rétablissant l' al i m e n t ati o n a l t e rn a t i v e d ' e n t ré e , soit être
simulé en m ettant sous tension toutes les lignes d'alim entation en entrée de l' AS I à ten s i on
connecté.
d ' é n e rg i e
Un fonctionnem ent correct de tous les re d re s s e u rs d ' AS I à ten si o n con ti n u e , y com pris le
dém arrage progressif, s'il y a lieu, doit être observé. Les variations de la te n s i o n de s o rt i e
L a con form ité e st vé rifié e p a r un e ss a i qua n d, a p rè s le re to ur du coura n t d'e n tré e a lte rn a tif,
NOTE 1 Le dém arrage progressif est une fonction qui contrôle le cou rant d'entrée alternatif de m anière à ce qu'i l
augm ente progressivem ent d ans un délai spécifi é l orsqu e l' dém arre ou red ém arre.
AS I à te n s i o n c o n ti n u e
NOTE 2 Cet essai est gén éralem ent réal isé avec l'essai à c h a rg e r é d u i t e en 6. 2. 2. 3. e).
6. 3 P ro c é d u re d ' e s s a i s s u r s i t e
destinées à être assemblées et câblées sur site nécessitent que leurs essais de
performances finaux soient réalisés sur site. La procédure d'essais sur site inclut
habituellem ent la procédure de m ise en service du fabricant, ainsi que l'exécution des es s ai s
Les essais sur site doivent préférentiellem ent être réalisés dans d es conditions
représentatives des conditions de service réelles et doivent utiliser la charge disponible sur le
site. La charge ne doit pas dépasser la charge perm anente assignée de l' AS I à te n s i o n
Sauf prescription contraire dans l'article d'essai adéquat, les essais doivent être effectués
avec une .
c h a rg e d ' e s s a i d e ré fé re n c e
NOTE 1 Après accord avec le fabricant de l' AS I à , l 'ach eteur form ule un prog ram m e d'essais
te n s i o n co n ti n u e
de récepti on sur site (SAT, s ite a cce p ta n ce te s t) dans l e cadre d'u n contrat d'ach at.
NOTE 2 Pour des raisons économ iques et pour éviter toute contrainte inutil e sur l' , AS I à te n s i o n co n ti n u e
l'acheteur l im ite de m anière gén érale l e prog ram m e d'essais sur site à l a vérificati on d es caractéristiqu es
essentiell es par aill eurs non vérifiées.
6. 4 P ro c é d u re d ' e s s a i d e t y p e ( é l e c t ri q u e )
6. 4. 1 E n t ré e – C o m p a t i b i l i t é d e l ' a l i m e n t a t i o n en c o u ra n t a l t e rn a t i f
6. 4. 1 . 1 G é n é ra l i t é s
L'alim entation alternative d'entrée doit présenter les caractéristiques applicables déclarées
pour l' AS I à ten si on (voir 5.2.2 i)) et être capable de
co n ti n u e
– maintenir la forme d'onde de tension dans les lim ites du 5. 2. 1 , lorsque l' AS I à te n s i o n
fonctionne en
con ti n u e à la m od e continue assignée (voir
n o rm a l pu i s san ce de s o rt i e
Note 3 du 5. 2. 1 ), et
– fournir une fréquence et une tension variables respectant les caractéristiques déclarées
pour l'entrée de l' (voir 5. 2. 1 ).
AS I à ten si o n con ti n u e
I EC 62040-5-3: 201 6 © I EC 201 6 – 99 –
6. 4. 1 . 2 T o l é ra n c e d e l a t e n s i o n d ' e n t ré e e n ré g i m e é t a b l i
Avec l' AS I à en
te n s i o n de fonctionnem ent et avec l'entrée réglée à
co n ti n u e mod e n o rm a l
sa valeur nominale, la tension d'entrée doit être m odifiée j usqu'aux valeurs minimale et
maxim ale de la plage de tolérance déclarée par le fabricant. L' doit AS I à te n s i o n c o n ti n u e
La ten si on de l'
de s o rt i e doit être mesurée, et sa tolérance
AS I à ten si o n co n ti n u e
6. 4. 1 . 3 T o l é ra n c e d e l a fré q u e n c e d ' e n t ré e
fréquence d'entrée étant adaptée aux lim ites spécifiées par le fabricant conj ointement aux
variations de la tension d'entrée. L' doit rester en
AS I à ten s i on de
con ti n u e m od e n o rm a l
fonctionnement.
NOTE Un e dim inution de l a fréq uence n'est pas censée coïncider avec un e au gm entation de la tension de li gne,
et vice-versa.
6. 4. 1 . 4 C o u ra n t d ' a p p e l
Deux essais de courant d'appel doivent être effectués l'un après l'autre. Le premier essai doit
être effectué après une absence de tension d'entrée d'au m oins 5 min.
L'essai suivant doit être réalisé après une absence de 1 s de la tension d'entrée. Si la
topologie de l' AS I à nécessite un délai supérieur à 1 s, l'essai doit être
ten si on c o n ti n u e
réalisé avec le délai spécifié par le fabricant. Celui-ci doit être indiqué dans les instructions
d'installation .
Pour les besoins de cet essai, les pointes de courant initiales im putables à l'alimentation des
condensateurs de filtrage RFI ( ra dio- fre que n cy in te rfe re n ce , brouillage radioélectrique) des
filtres d'entrée, d'une durée inférieure à 1 ms, ne doivent pas être prises en com pte.
Le c o u ra n t de de la source de
c o u rt - c i rc u i t p ré s u m é (I cp ) p u i s s an ce d ' a l i m e n tat i o n
doit être égal à au moins 33 fois le courant assigné d'entrée pour une
a l t e rn a t i v e AS I à
assigné d'entrée supérieur à 300 A. I l est adm is de réaliser un essai à u ne valeur ( Icp )
inférieure à la valeur spécifiée lorsque le résultat d'essai est corrigé au m oyen d'un calcul
approprié.
L'alim entation d'entrée doit être appliquée à l'entrée de l' à divers AS I à ten s i on con ti n u e
NOTE Le courant d 'appel l e plus d éfavorable sera norm alem ent constaté avec les unités couplées à
transform ateur, lors d'u ne m ise sous tension au zéro de tension et dans le cas de red resseur/cond ensateu r en
direct à la crête ou près d e la crête d e la form e d'on de de la tension d'alim entati on d'entrée.
– 1 00 – I EC 62040-5-3: 201 6 © I EC 201 6
L a co n fo rm ité e s t vé rifié e qua n d le coura n t d'a p p e l à l'e n tré e de l' ASI à tension continue se
6. 4. 1 . 5 D i s t o rs i o n h a rm o n i q u e d u c o u ra n t d ' e n t ré e
La distorsion harm onique du courant d'entrée fait l'obj et d'un essai à la puissance nominale
jusqu'au 50 e harmonique avec la .
c h a rg e d ' e s s a i d e ré fé re n c e
d'e n tré e de l' ASI à tension continue s e situe da n s le s lim ite s dé cla ré e s p a r le fa b rica n t.
6 . 4. 1 . 6 F a cte u r d e p u i s s a n c e
La co n form ité e st vé rifié e qua n d le facteur de puissance du co ura n t d'e n tré e de l'ASI à
tension continue e s t sup é rie ur o u é ga l à ce lui dé cla ré p a r le fa b rica n t.
6. 4. 1 . 7 Re n d e m e n t
l'Annexe F.
6. 4. 1 . 8 E ss ai d e c o m p a t i b i l i t é a v e c u n g é n é ra t e u r d e s e c o u rs
sortie d'un générateur de secours étant utilisée comm e source d'alim entation d'entrée. Les
caractéristiques du générateur de secours doivent être spécifiées par le fabricant.
NOTE 1 Cet essai est généralem ent réalisé conj ointem ent avec l es essais d e t o l é ra n c e de la te n s i o n d ' e n t ré e
(voir 6. 4. 1 . 2 et 6. 4. 1 . 3).
NOTE 2 Après accord entre l e fabricant/fourn isseur et l'ach eteu r, cet essai est réalisé sur site.
NOTE 3 L'I EC 60034-22 présente les caractéristiqu es des groupes électrogènes entraîn és par u n m oteur à
com bustion interne.
6. 4. 1 . 9 E ss ai d e ro t a t i o n d e ph ase
Avec l' AS I à en
ten s i on de fonctionnem ent avec des batteries
c o n ti n u e m od e n o rm a l
6. 4. 2 C a ra c t é ri s t i q u e s d e s o rt i e – C h a rg e ré s i s t i v e
6. 4. 2 . 1 M o d e n o rm a l – A vi d e
Les fréquences retenues pour les mesures de la tension d'ondulation sont situées entre 1 H z
et 1 50 kH z.
6. 4. 2 . 2 M o d e n o rm a l – P l e i n e c h a rg e
Avec l' AS I à en
te n s i o n de fonctionnement, avec une
co n ti n u e m od e n o rm a l c h a rg e
).
d ' o n d u l ati o n
Les fréquences retenues pour les mesures de la tension d'ondulation sont situées entre 1 H z
et 1 50 kH z.
6 . 4. 2 . 3 M o d e d e fo n c t i o n n e m e n t e n au to n o m i e – A vi d e
( ).
te n s i o n d ' o n d u l a ti o n
Cet essai est exigé pour le type de sortie XN uniquem ent (voir 5. 3. 4).
Les fréquences retenues pour les mesures de la ten si on d ' on d u l a ti o n sont situées entre
1 H z et 1 50 kH z.
6. 4. 2 . 4 M o d e d e fo n c t i o n n e m e n t e n a u t o n o m i e – P l e i n e c h a rg e
une instrum entation avec un temps d'anal yse suffisant pour observer l es variations résultant
de la chute de tension dans le tem ps du dispositif de stockage d'énergie. Pour une AS I à
de connecter une supplém entaire ou toute autre source d'alim entation en courant
b a t t e ri e
Cet essai est exigé pour le type de sortie XN uniquement (voir 5. 3. 4).
Les fréquences retenues pour les mesures de la ten si on d ' o n d u l a ti o n sont situées entre
1 H z et 1 50 kH z.
– 1 02 – I EC 62040-5-3: 201 6 © I EC 201 6
6. 4. 2 . 5 E ss ai d e p a rt a g e d e c h a rg e
6. 4. 2 . 6 E ss ai d e s u rt e n s i o n d e s o rt i e
variation supérieure en régime établi et de 5 % supplém entaires, ou selon tout autre accord
convenu entre le fabricant et l'acheteur.
6. 4. 2 . 7 E s s ai d e v a ri a t i o n p é ri o d i q u e d e l a t e n s i o n d e s o rt i e ( m o d u l a t i o n )
Seulement lorsque, après accord spécifique entre l'acheteur et le fabricant, cet essai est
spécifié, il doit être vérifié par enregistrem ent de la tension à différentes charges et dans
différentes conditions d'exploitation.
6. 4. 2 . 8 C a p a c i t é d e s u rc h a rg e e t d ' é l i m i n a t i o n d e d é fa u t
6 . 4. 2 . 8 . 1 S u rc h a rg e – M o d e n o rm a l
Avec l' AS I à en
te n s i o n c o n ti n u e mod e n o rm a l à c h a rg e ré d u i t e , appliquer une c h a rg e
L a co n fo rm ité e s t vé rifié e qua n d l' ASI à tension continue co n tin ue de fon ctio n n e r da n s le s
6 . 4. 2 . 8 . 2 S u rc h a rg e – M o d e d e fo n c t i o n n e m e n t e n au to n o m i e
L'essai décrit en 6. 4. 2. 8.1 doit être répété en m ode de fonctionnement en autonom ie, le
dispositif de stockage d'énergie étant entièrem ent chargé.
Cet essai est exigé pour le type de sortie XN uniquement (voir 5. 3. 4).
NOTE La d urée d e l'essai est l im itée par la source d'énergi e stockée.
6. 4. 2 . 8 . 3 C ap a ci té d ' é l i m i n a ti o n d e d é fa u t – M o d e n o rm a l
court-circuit doit ensuite être appliqué en utilisant un fusible ou un disjoncteur dont les
I EC 62040-5-3: 201 6 © I EC 201 6 – 1 03 –
c o u rt - c i rc u i t supérieur à 20 kA et de 3 ms pour un
p ré s u m é c o u ra n t de c o u rt - c i rc u i t
inférieur à 20 kA.
p ré s u m é
L a co n form ité e s t vé rifié e lors que le s p e rfo rm a n ce s dyn a m ique s de sortie de m e ure n t da n s le s
NOTE Un essai portant sur la capacité d'élim inati on de d éfaut vérifi e les perform ances de sorti e d e l' AS I à
6. 4. 2 . 8 . 4 C ap a ci té d ' é l i m i n a ti o n d e d é fa u t – M o d e d e fo n c t i o n n e m e n t e n a u to n o m i e
6. 4. 2 . 9 P e rfo rm a n c e s d y n a m i q u e s
6. 4. 2 . 9 . 1 P as s ag e d u m o d e n o rm a l au m o d e d e fo n c t i o n n e m e n t e n au ton om i e
Avec l' AS I à en
te n s i o n de fonctionnem ent, avec une
c o n ti n u e m od e n o rm a l c h a rg e
avec des instruments d'enregistrement adaptés pour perm ettre le calcul de tout é c a rt
des performances de la
t ra n s i t o i re pendant le passage du m ode normal au
ten s i on d e s o rt i e
L'essai est généralem ent effectué conj ointement avec la défaillance du courant d'entrée
alternatif du 6. 2.2. 6 (voir Figure D.1 ).
– qui suit la ferm eture de l'interrupteur S2, lorsque le courant augmente à travers S2 (pour
le défaut basse impédance du réseau).
– 1 04 – I EC 62040-5-3: 201 6 © I EC 201 6
6. 4. 2 . 9 . 2 P as s ag e d u m o d e d e fo n c t i o n n e m e n t e n au to n o m i e au m o d e n o rm a l
autonomie au . Cet essai est généralem ent effectué conjointement avec l'essai
mode n o rm a l
6. 4. 2 . 9 . 3 C h a rg e p a r p a l i e r – M o d e n o rm a l
6. 4. 2 . 9 . 4 C h a rg e p a r p a l i e r – M o d e d e fo n c t i o n n e m e n t e n a u t o n o m i e
acti ve
Cet essai est exigé pour une parallèle intégrant une redondance.
AS I à ten si on co n ti n u e
L'essai doit être réalisé en appliquant la charge assignée à l' . Par AS I à ten si on co n ti n u e
cas échéant, doivent être m ises en défaut (par exemple: défaillance du semiconducteur). La
te n s i o n doit être mesurée et doit satisfaire aux lim ites déclarées par le
t ra n s i t o i re de s o rt i e
redondante.
co n ti n u e
L a co n form ité e st vé rifié e lors que le s p e rfo rm a n ce s dyn a m ique s de sortie de m e ure n t da n s le s
6. 4. 3 C a ra c t é ri s t i q u e s d e s o rt i e – C h a rg e à p u i s s a n c e c o n s t a n t e
6. 4. 4 D u ré e s d ' a u t o n o m i e e t d e re c h a rg e
6. 4. 4. 1 D u ré e d ' a u t o n o m i e
La d u ré e d ' au to n o m i e doit être déterm inée en coupant l'entrée en courant alternatif de l' AS I
l'obj et d'un accord particulier entre l'acheteur et le fabricant de l' , la AS I à ten si on con ti n u e
doit être mesurée imm édiatement avant l'essai afin de calculer un éventuel
b a t t e ri e s
NOTE 1 Des considérati ons sim ilaires s'appl iqu ent au x autres technologies de stockage d'énergie.
ne soit écoulée.
d 'au ton om i e
de fonctionnem ent avec une alimentation d'entrée nominale, en n'appliquant aucune charge
de sortie pendant une période supérieure à la déclarée par le fabricant.
d u ré e d e re c h a rg e
de l'
t e n s i o n d e s o rt i e AS I .à ten si on con ti n u e
NOTE 2 Les batteries neuves n'offrant pas toujours leur plei ne capacité pend ant l a période de dém arrage, l'essai
de déch arge est gén éralem en t répété après une raisonnabl e, si la durée est initialem ent
d u ré e de re c h a rg e
inférieu re à la l im ite spécifiée. Un certai n nom bre d e cycles de charge/d écharg e peut être nécessai re avant
d'attei nd re la plei ne capacité d e la . b a t t e ri e
6. 4. 4. 2 D u ré e d e re c h a rg e ( j u s q u ' à 9 0 % d e l a c a p a c i t é )
L a co n fo rm ité e st vé rifié e lors que la n o uve lle va le ur de la durée d'autonomie e s t sup é rie ure
ou é ga le à 90 % de la d u ré e d ' a u t o n o m i e dé cla ré e .
établi es par le fabricant pour la d u ré e de re c h a rg e étant égal es à la durée d e rétabl i ssem ent de 90 % de la
capacité assig née, sauf indication contrai re.
6. 4. 4. 3 M e s u re d u c o u ra n t d ' o n d u l a t i o n d e l a b a t t e ri e
doit fonctionner en
co n ti n u e et la doit être totalement chargée. Le
m od e n o rm a l b a t t e ri e
– 1 06 – I EC 62040-5-3: 201 6 © I EC 201 6
courant d'ondulation le plus défavorable doit faire l'objet d'un rapport si cette mesure est
affectée par le chargement de l' .AS I à ten si on co n ti n u e
La co n form ité e st vé rifié e lors que le co ura n t d'o n dula tion m e suré e st in fé rie ur ou é ga l à la
NOTE La lim ite q ui s'appli q ue à la com posante alternati ve (valeur efficace) du cou rant de la est b a t t e ri e
habituell em ent égale à 5 % d e la val eu r num ériqu e de l a capacité assign ée de la Ah (plom b-acide) et à b a t t e ri e
6. 4. 4. 4 E ss ai d e re d é m a rra g e
Les moyens de redémarrage automatique ou autre doivent être soum is à l'essai après l'arrêt
com plet de l' AS I à . L'essai de redémarrage de l'
ten s i on co n ti n u e AS I à te n s i o n co n ti n u e
doit perm ettre de s'assurer de la présence des tensions réseau correctes ou de la décharge
et du redém arrage autom atique en du m o d e n o rm a l . d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
6. 5 P ro c é d u re d ' e s s a i d e t y p e ( e n v i ro n n e m e n t a l )
6. 5. 1 M é t h o d e s d ' e s s a i d ' e n v i ro n n e m e n t e t d e t ra n s p o rt
6. 5. 1 . 1 G é n é ra l i t é s
Les essais suivants sont destinés à sim uler les exigences d'environnement et de transport
que l' AS I à est conçue pour satisfaire. Les essais de transport évaluent la
te n s i o n co n ti n u e
d'expédition, aux dommages liés aux opérations norm ales de m anu tention pendant le
transport.
6. 5. 1 . 2 E ss ai d e ch ocs
La procédure suivante doit être réalisée sur une com plète de m oins
AS I à ten si on c o n ti n u e
électriques décrits en 6. 2. 2;
d e s é ri e
b) vérifier que l' AS I à ne fonctionne pas et qu'elle est emballée dans son
ten si on co n ti n u e
lib re (vo ir 6. 5. 1 . 3) .
Il co n vie n t de te n ir co m p te de to ute con s é que n ce de s ré s ulta ts d'e ssa is qui p e ut e xige r que
6. 5. 1 . 3 E ssai en c h u t e l i b re
La procédure d'essai en chute libre suivante doit être réalisée dans l'ordre chronologique ci-
dessous:
a) à titre de mesures initiales, soumettre l' aux AS I à te n s i o n con ti n u e es s ai s i n d i vi d u el s
électriques décrits en 6. 2. 2;
d e s é ri e
b) vérifier que l' AS I à ne fonctionne pas et qu'elle est em ballée dans son
ten si on co n ti n u e
suspension sur une surface solide. La surface de l'emballage qui touche la surface solide
à la suite de la chute est la surface sur laquelle l'em ballage repose norm alement. La
méthode d'essai est conforme à l'I EC 60068-2-31 . Vérifier que les conditions d'essai
ci-dessous sont respectées:
1 ) l'essai est effectué deux fois;
2) l'essai est réalisé avec l' AS Idans sa m allette de transport ou dans
à ten si o n con ti n u e
P o i d s d e l ' é p ro u v e t t e d é b a l l é e H au teu r d e ch u te
kg mm
M≤ 10 250
1 0 < M ≤ 50 1 00
50 < M ≤ 1 00 50
1 00 < M 25
6. 5. 2 E n t re p o s a g e
La procédure d'essai d'entreposage suivante doit être réalisée dans l'ordre chronologique ci -
dessous:
a) pour les m esures initiales, soum ettre l' aux AS I à ten s i on con ti n u e es s ai s i n d i vi d u e l s d e
6. 5. 3 F on cti on n e m e n t
La procédure d'essai de fonctionnem ent suivante doit être réalisée dans l'ordre chronologique
ci-dessous:
a) soumettre l' AS I à aux
te n s i o n co n ti n u e électriques décrits
essais i n d i vi d u e l s de s é ri e
en 6. 2. 2;
b) vérifier que l' AS I à fonctionne en
ten s i on co n ti n u e à la tension d'entrée
m od e n o rm a l
assignée et à la ;
p u i s s a n c e d e s o rt i e a s s i g n é e
sous la forme de batteries, procéder aux essais avec une tem pérature
d ' é n e rg i e
6. 5. 4 B ru i t a c o u s t i q u e
Le fabricant doit indiquer dans la documentation technique le niveau de bruit acoustique qui
doit être m esuré conformém ent à la méthode de mesure spécifiée dans l'I SO 7779 et en
fonction du positionnem ent normal prévu dans le cadre de l'utilisation (posé sur table, à
montage m ural ou sur pied).
Le bruit acoustique provenant d'alarmes sonores ne doit pas être inclus dans les valeurs
indiquées.
Le bruit acoustique provenant des ventilateurs devant fonctionner dans les conditions
assignées doit être inclus dans les valeurs indiquées.
6. 6. 1 E s s a i s d e re d re s s e u rs d ' AS I à ten si o n co n ti n u e
Les redresseurs comm utés par le réseau doivent être soum is à l'essai conform ément aux
essais applicables de l'Article 7 de l'I EC 601 46-1 -1 :2009.
commande.
Les essai s comprennent les essais de charge supplém entaires, la déterm ination des
d e typ e
Le cas échéant, les essais de doivent être réalisés conform ément aux essais
c o n v e rt i s s e u rs
applicables de l'Article 7 de l'I EC 601 46-2: 1 999, qui présente un plan d' e s s ai s i n d i vi d u el s d e
, d'
s é ri e et d'essais facultatifs.
e s s a i s d e typ e
intégrantes d'une AS I à ten si o n com plète et qui satisfont aux exigences de l'
co n ti n u e AS I à
Les i n t e rru p t e u rs d ' AS I qui ne sont pas considérés comme des parties
à te n s i o n co n ti n u e
valeurs ne sont pas démontrées par des calculs appropriés. Si des préalables es s ai s d e typ e
ont été réalisés, les spécifications d'origine du fabricant doivent être acceptables, et des
essais com plémentaires seront exigés.
6. 6. 4 E s s a i s d ' a u t o n o m i e /d e b a t t e ri e
Sauf spécification contraire dans le contrat d'achat, les essais en usine réalisés sur un
d i s po s i ti f de à l'intérieur d'une
s t o c ka g e d ' é n e rg i e ou dans des AS I à ten si on con ti n u e
aux essais individuels de série en production jugés nécessaires, par le fabricant de l'ASI ,
pour vérifier les perform ances du .
d i s p o s i t i f d e s t o c ka g e d ' é n e rg i e
et l'acheteur.
co n ti n u e
Les régim es de charge spéciaux (p. ex. : exigences de charge rapide/d'égalisation) exigés par
le fabricant du doivent être dém ontrés.
d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
I EC 62040-5-3: 201 6 © I EC 201 6 – 111 –
An n e xe A
(informative)
C o n fi g u ra ti o n s d ' AS I à te n s i o n c o n ti n u e
A. 1 G é n é ra l i t é s
Les AS I à te n s i o nsont utilisées pour alim enter les équipem ents qui doivent
co n ti n u e
fonctionner en continu, égalem ent appelés charges critiques ou charges essentielles. Les
matériels de télécomm unication, les centres de données, les comm andes de processus ou les
éclairages de secours sont des exemples de charges critiques (liste non exhaustive).
L'obj ectif de l' AS I à est d'assurer l'alim entation perm anente des charges
ten si on con ti n u e
l'alim entation de la charge et/ou pour augmenter les de capacité c a ra c t é ri s t i q u e s assi g n ées
de sortie et la redondance.
A. 2 AS I à t e n s i o n c o n t i n u e u n i t a i re
A. 2 . 1 I n t ro d u c t i o n
continu/continu. U ne ASI à tension continue unitaire présente généralem ent une disponibilité
com patible avec des équipem ents présentant un niveau d'intégrité de fiabilité 1 (RI L-1 –
IEC 62040-3, 2 e édition, 201 1 , Annexe K).
A. 2 . 2 AS I à te n s i o n c o n t i n u e u n i t a i re d e b a s e
Entrée en Sortie en
courant AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
courant
alternatif Convertisseur(s) continu
Dispositif
de puissance de stockage
statique(s) d'énergie
IEC
F i g u re A. 1 – AS I à ten si on c o n t i n u e u n i t a i re d e b a s e
En cas de de la
d é fa i l l a n c e s o u rc e , le
d ' a l i m e n ta ti o n d ' e n t ré e en c o u ra n t a l t e rn a t i f
dispositif de stockage d'énergie (par exem ple: une ) fournira la puissance à tension b a t t e ri e
continue décroissante j usqu'à ce qu'elle soit trop faible pour une alim entation en sortie
continue satisfaisante. Le type et la capacité de la détermineront la durée pendant b a t t e ri e
NOTE Les topologies d' AS I sui vantes représentent d es exem ples d'
à te n s i o n co n ti n u e AS I à te n s i o n co n ti n u e
A. 2 . 3 AS I à te n s i o n c o n t i n u e u n i t a i re é v o l u t i v e
et/ou
u n i t a i re s d'
u n i tés identiques en parallèle. Les
fo n c t i o n n e l l e s AS I à ten si on con ti n u e
– AS I à te n s i o n c o n t i n u e u n i t a i re s m o d u l a i re s
Une assure l'entretien et le remplacem ent sur site. Dans certains cas,
p e rs o n n e q u a l i fi é e
le rem placement à chaud est adm is. L'évolutivité est assurée soit en connectant des
u n i tés en parallèle dans l'armoire de l'
fo n c t i o n n e l l e s , AS I à ten s i on co n ti n u e u n i t a i re
parallèle.
– AS I à te n s i o n c o n t i n u e u n i t a i re s m o n o l i t h i q u e s
L'entretien et le remplacem ent sur site nécessitent l'isolation et/ou l'arrêt du système.
L'évolutivité est assurée en connectant des arm oires d' AS I à ten si o n co n ti n u e u n i t a i re s
identiques en parallèle.
A. 3 AS I à t e n s i o n c o n t i n u e p a ra l l è l e
A. 3 . 1 G é n é ra l i t é s
redondantes.
A. 3 . 2 AS I à t e n s i o n c o n t i n u e p a ra l l è l e s a n s re d o n d a n c e a c t i v e
parallèle sans redondance active est inférieure à celle de chacune des u n i t é s d ' AS I à
Entrée en AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
Sortie en
courant courant
alternatif
Convertisseur(s) Dispositif continu
de puissance de stockage
statique(s) d'énergie
N
Sortie en
Entrée en
courant
AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
courant
alternatif continu
Ve rs l a c h a rg e c ri t i q u e
Convertisseur(s) Dispositif
D i s t ri b u t i o n e n e n t ré e
D i s t ri b u t i o n e n s o rt i e
de puissance de stockage
statique(s) d'énergie
IEC
F i g u re A. 2 – S y s t è m e d i m e n s i o n n é p o u r l a c h a rg e
( N u n i t é s d ' AS I à t e n s i o n c o n t i n u e ) – S a n s re d o n d a n c e
A. 3 . 3 AS I à te n s i o n c o n t i n u e p a ra l l è l e e n re d o n d a n c e a c t i v e
l'alimentation de la charge.
Entrée en AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e Sortie en
courant courant
alternatif continu
Convertisseur(s) Dispositif
de puissance de stockage
statique(s) d'énergie
N
Entrée en AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
Sortie en
courant courant
D i s t ri b u t i o n e n s o rt i e
de puissance de stockage
statique(s) d'énergie
Entrée en Sortie en
courant
AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
courant
alternatif continu
1 Convertisseur(s) Dispositif
de puissance de stockage
statique(s) d'énergie
IEC
F i g u re A. 3 – S y s t è m e d i m e n s i o n n é p o u r l a c h a rg e
( N u n i t é s d ' AS I à te n s i o n c o n ti n u e ) – Re d o n d an ce N + 1
A. 3 . 4 AS I à te n s i o n c o n t i n u e p a ra l l è l e e n re d o n d a n c e a c t i v e a m é l i o ré e
Une plus grande disponibilité peut être obtenue en augm entant le nom bre d' u n i t é s d ' AS I à
te n s i o n redondantes de 1 à r. con ti n u e
AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
courant courant
alternatif continu
Ve rs l a c h a rg e c ri t i q u e
Convertisseur(s) Dispositif
D i s t ri b u t i o n e n e n t ré e
D i s t ri b u t i o n e n s o rt i e
de puissance de stockage
statique(s) d'énergie
Entrée en AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
Sortie en
courant courant
alternatif continu
Convertisseur(s) Dispositif
de puissance de stockage
statique(s) d'énergie
r
Entrée en Sortie en
courant
AS I à te n s i o n c o n ti n u e u n i ta i re d e b a s e
courant
alternatif continu
Convertisseur(s) Dispositif
de puissance de stockage
statique(s) d'énergie
IEC
F i g u re A. 4 – S y s t è m e d i m e n s i o n n é p o u r l a c h a rg e
( N u n i t é s d ' AS I à te n s i o n c o n ti n u e ) – Re d o n d an ce N r +
I EC 62040-5-3: 201 6 © I EC 201 6 – 115 –
A. 4 D o u b l e vo i e d e d i s t ri b u t i o n
A. 4 . 1 G é n é ra l i t é s
La configuration à double voie est en premier lieu destinée à alimenter les charges équipées
d'alimentations redondantes et de deux cordons d'entrée.
A. 4 . 2 S y s t è m e à d o u b l e v o i e d e d i s t ri b u t i o n 2( N r + )
com posé de deux configurations d' décrites dans l'Annexe A, dont les
AS I à ten si on con ti n u e
sorties continues sont connectées à des j eux de barres distincts. Voir Figure A.5.
Entrée en
courant Sortie en courant
alternatif continu – BARRE A
AS I à t e n s i o n c o n t i n u e A
Entrée en
courant Sortie en courant
alternatif continu – BARRE B
AS I à te n s i o n c o n t i n u e B
IEC
F i g u re A. 5 – AS I à ten si on con ti n u e à d ou b l e voi e
d e d i s t ri b u t i o n
A. 4 . 3 AS I à te n s i o n c o n t i n u e à d o u b l e v o i e d e d i s t ri b u t i o n ( N r
+ )
Sortie en courant
continu – BARRE B
IEC
F i g u re A. 6 – V a ri a n t e d ' AS I à te n s i o n c o n t i n u e à d o u b l e v o i e d e d i s t ri b u t i o n
– 116 – I EC 62040-5-3: 201 6 © I EC 201 6
An n e xe B
(informative)
T o p o l o g i e s – AS I à t e n s i o n c o n ti n u e
B. 1 G é n é ra l i t é s
L'Annexe B décrit les topologies d' les plus fréquem ment utilisées
AS I à ten s i o n c o n ti n u e
sous la forme de simples schém as fonctionnels, incluant la forme la plus commune de source
d'énergie stockée, à savoir une . D'autres formes de sources d'énergie stockée sont
b a t t e ri e
des transform ateurs d'isolement d'entrée peuvent être exigés. Ces détails sont om is pour des
raisons de simplicité. Les avantages techniques ne sont pas présentés et il convient que
l'acheteur vérifie auprès du fournisseur la com patibilité d'un systèm e aux exigences de
charge prévue. Voir Annexe C.
B. 2 Top ol o g i e s d e b as e
B. 2. 1 G é n é ra l i t é s
Trois topologies de base sont représentées par les Figures B. 1 , B. 2 et B. 3. Elles diffèrent en
term es de comportement de la en mode de fonctionnem ent en autonomie.
te n s i o n de s o rt i e
un niveau préalablem ent déterm iné auquel la charge ne peut plus fonctionner correctement.
norm al de fonctionnement ainsi qu 'en m ode de fonctionnem ent en autonom ie jusqu'à la fin de
décharge du .
d i s p o s i t i f d e s t o c ka g e d ' é n e rg i e
B. 2. 2 T o p o l o g i e à d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e e n co n n exi on d i re c t e
d'une distribution associée qui peut être interne ou externe à l' . Cette AS I à ten s i on co n ti n u e
architecture fournit une voie d'alimentation unique vers la charge desservie. Pour plus de
détails sur l'évolutivité des u n i té s m odulaires et monolithiques,
d ' AS I à ten si on co n ti n u e
voir A.2.3.
En cas de défaillance de la s o u rc e , le
d ' al i m en tati o n d ' e n t ré e en c o u ra n t a l t e rn a t i f
d'én ergie en con nexion di recte possède des caractéristiq ues de type NW (voi r 5. 3. 4).
IEC
F i g u re B . 1 – T o p o l o g i e à d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e e n c o n n e xi o n d i re c t e
B.2.3 T o p o l o g i e à c o n v e rt i s s e u r s é ri e
sortie vers la charge. L'obj ectif du continu/continu est d'assurer une sortie
c o n v e rt i s s e u r
.
d ' é n e rg i e
Dispositif de
stockage
d'énergie
IEC
F i g u re B . 2 – T o p o l o g i e à c o n v e rt i s s e u r s é ri e
B. 2. 4 T o p o l o g i e à c o n v e rt i s s e u r p a ra l l è l e
sortie) vers la charge, quelles que soient les caractéristiques de décharge et de recharge du
.
d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e
Courant continu-
courant continu
Dispositif de
stockage
d'énergie
IEC
Fig u re B. 3 – Topolog i e à con verti sseu r paral l èl e
I EC 62040-5-3: 201 6 © I EC 201 6 – 119 –
An n e xe C
(informative)
D i re c t i ve s re l a t i ve s a u x s p é c i fi c a ti o n s d e l ' a c h e te u r
C. 1 G é n é ra l i t é s
continuité et de qualité de l'alimentation. I l existe différents types de charges sur une large
plage de puissances, de m oins d'une centaine de watts à plusieurs m égawatts.
L'Annexe C a été rédigée pour aid er les acheteurs à identifier les critères importants pour leur
application et/ou confirm er leur accord aux conditions déclarées par le fabricant/fournisseur.
D é c l a ra t i o n du fa b ri c a n t (1 de 4)
P a ra g ra p h e d e
V a l e u rs
l ' I E C 6 2 0 4 0 -5 - V a l e u rs
i d e n t i fi é e s
3: 2 01 6 (s au f C a r a c t é ri s t i q u e s d é c l a r é e s g é n é ra l e s d é c l a ré e s p a r l e
par
i n d i c a ti o n fa b ri c a n t
l ' a ch e te u r
c o n t r a i re )
M od èl e (référence du fabricant)
5. 3. 2 g ) P u i s s a n c e d e s o rt i e , assignée W
5. 1 . 1 Confi gu ration d e l' AS I à ten s i o n co n ti n u e
5. 6 C i rc u i t s d e c o m m u n i c a t i o n
P a ra g ra p h e d e
V a l e u rs
l ' I E C 6 2 0 4 0 -5 - V a l e u rs
C a r a c t é ri s t i q u e s d é c l a r é e s i d e n t i fi é e s
3: 2 01 6 (s au f d é c l a ré e s p a r
S o rt i e ( é l e c t ri q u e ) par
i n d i c a ti o n l e fa b ri c a n t
l ' a ch e te u r
c o n t r a i re )
ré s e a u d e d i s t ri b u t i o n d e c o u ra n t c o n t i n u (TN, TT, I T)
Te n s i o n (régim e établi )
5. 3. 2 b) V
– assignée
6. 4. 2 . 1 et – v a ri a t i o n en m o d e n o rm a l à vi d e et en pl ei n e
%
6. 4. 2 . 2 c h a rg e
6. 4. 2 . 3 e t – v a ri a t i o n en m o d e d e fo n c t i o n n e m e n t e n
%
6. 4. 2 . 4 a u to n o m i e à vi d e e t e n p l e i n e c h a rg e
6. 4. 2. 9. 4 – v a ri a t i o n en m o d e d e fo n c t i o n n e m e n t e n
%
a u to n o m i e e n c h a rg e p a r p a l i e r
C o u ra n t
5. 3. 2 g ) A
– assigné
5. 3. 2 h ) – capacité d e surch arge (% d u courant assig né/d urée) %/s
5. 3. 2 i) – lim itation (% du cou rant assign é/du rée) %/s
(suite)
I EC 62040-5-3: 201 6 © I EC 201 6 – 1 21 –
P a ra g r a p h e
de V a l e u rs
V a l e u rs
l ' I E C 6 2 0 4 0 -5 - C a r a c t é ri s t i q u e s d é c l a r é e s i d e n t i fi é e s
d é c l a ré e s p a r
3: 201 6 (s au f E n t ré e ( é l e c t ri q u e ) par
l e fa b ri c a n t
i n d i ca ti o n l ' a ch e te u r
c o n t ra i re )
5. 2. 1 c) Hz
– assignée
5. 2. 1 d ) – tolérance %
5. 2. 2 a) phases exig ées (1 , 2 ou 3)
5. 2. 2 b) neutre exi gé (oui/non )
C o u ra n t efficace
5. 2. 2 c) – assigné (le dispositif de stockage d'énergi e étant A
chargé)
5. 2. 2 d ) – facteur d e puissance
5. 2. 2 e) – caractéristiques du cou rant d'appel %
– courant m axim al (avec un e fai ble tension d'entrée et le A
5. 2. 2 f) dispositif de stockag e d'énergi e en charg e)
– courant en fonction du tem ps %, s
(suite)
– 1 22 – I EC 62040-5-3: 201 6 © I EC 201 6
P a ra g r a p h e
de V a l e u rs
V a l e u rs
l ' I E C 6 2 0 4 0 -5 - C a r a c t é ri s t i q u e s d é c l a r é e s i d e n t i fi é e s
d é c l a ré e s p a r
3: 201 6 (s au f B a t t e ri e / d i s p o s i t i f d e s t o c k a g e d ' é n e rg i e par
l e fa b ri c a n t
i n d i ca ti o n l ' a ch e te u r
c o n t ra i re )
5. 4. 2. 2 d ) Technologi e
Vie de conception ou ann ées
5. 4. 2. 2 a) Durée de vie prévu e
Durée en service
(fin)
I EC 62040-5-3: 201 6 © I EC 201 6 – 1 23 –
An n e xe D
(normative)
D é fa i l l a n c e d u ré s e a u d ' e n tré e – M é th o d e s d ' e s s a i
Lég en d e
L Phase(s) du réseau
N Neutre d u réseau (ou ph ase en l 'absence de n eutre)
S1 I nterrupteu r ou contacteur capable d'alim enter et d'ou vri r le c o u ra n t as si g n é d ' e n t ré e de l ' AS I à te n s i o n
co n ti n u e
S2 I nterrupteur ou contacteu r capable d'alim enter le courant d e défaut du réseau à l 'ou verture du fusibl e
Fusible cali bré pour alim enter l ' AS I à te n s i o n co n ti n u e à c h a rg e ré d u i t e .
F i g u re D . 1 – R a c c o rd e m e n t d u c i rc u i t d ' e s s a i
E ssai D.1 – D é fa u t h a u t e i m p é d a n c e d u ré s e a u
M o d e n o rm a l de fonctionnement, à c h a rg e ré d u i t e :
– S1 = fermé;
– S2 = ouvert;
– Ouvrir S1 pour simuler le défaut côté réseau.
E s s ai D . 2 – D é fa u t b a s s e i m p é d a n c e d u ré s e a u
M o d e n o rm a l de fonctionnement, à c h a rg e ré d u i t e :
– S1 = ferm é;
– S2 = ouvert;
– Ferm er S2 pour simuler le défaut côté réseau (le fusible a fusionné).
Le calibre du fusible doit correspondre au courant d'entrée de l' AS I à ten si o n co n ti n u e . Les
de S2 doivent correspondre au
c a ra c t é ri s t i q u e s a s s i g n é e s c a l i b re du fusible.
– 1 24 – I EC 62040-5-3: 201 6 © I EC 201 6
An n e xe E
(informative)
P e rfo rm a n c e s d yn a m i q u e s d e s o rti e – T e c h n i q u e s d e m e s u re
E. 1 G é n é ra l i t é s
L'Annexe E donne les lignes directrices relatives à la validation des perform ances
d ynamiques de sortie d'une (voir 5.3. 4).
AS I à ten s i o n c o n ti n u e
E. 2 M é t h o d e d e va l i d a t i o n g ra p h i q u e
de de l'
s o rt i e AS I à , par exemple à l'aide d'un oscilloscope, puis à la
te n si on con ti n u e
Tension (%)
20
+5 %
+1 1 %
Valeur
nominale 0
Lim ites N
–5 %
–20
–22 %
Lim ites W
–32 %
–40
–60
–80
–1 00
0, 001 0, 01 0, 1 1 10 1 00 1 000 1 0 000 1 00 000
Durée transitoire (s)
IEC
F i g u re E . 1 – E xe m p l e : V a l i d a t i o n d e l a ré p o n s e e n t e n s i o n d yn a m i q u e
a v e c l a l i m i t e b a n d e é t ro i t e
I EC 62040-5-3: 201 6 © I EC 201 6 – 1 25 –
Tension (%)
20
+5 %
Valeur
+1 1 %
nominale 0
Lim ites N
–5 %
–20
–22 %
Lim ites W
–32 %
–40
–60
–80
–1 00
0, 001 0, 01 0, 1 1 10 1 00 1 000 1 0 000 1 00 000
Durée transitoire (s)
IEC
An n e x e F
(normative)
Re n d e m e n t d e l ' AS I à te n s i o n c o n ti n u e – M é t h o d e s d e m e s u re
F. 1 G é n é ra l i t é s
6. 4. 1 . 7.
F. 2 C o n d i t i o n s d e m e s u re
F.2. 1 C o n d i t i o n s d ' e n v i ro n n e m e n t
F.2. 2 C o n d i t i o n s d e fo n c t i o n n e m e n t e t c o n d i t i o n s é l e c t ri q u e s
Pour les besoins de l'Annexe F, le rendem ent doit être mesuré avec une c h a rg e ré s i s t i v e
et 1 00 % de la puissance (W) pour laquelle elle est assignée. Les pertes à l'entrée doivent
être mesurées à vide. Les exigences suivantes s'appliquent pour chaque m esure.
a) L' AS I à te n s i o ndoit initialement fonctionner en
c o n ti n u e . m o d e n o rm a l
suffisamm ent longue pour leur permettre d'atteindre les conditions de régim e établi. La
durée d'échauffem ent déterm inée lors des , augm entée de 25 %, est
es s ai s de t yp e
considérée com me suffisante. Sinon, une tendance de vari ation de température inférieure
à 2 °C sur au moins 3 m esures consécutives effectuées à au moins 1 0 min d'intervalle
peut être considérée comme un régim e établi pour les besoins de l'Annexe F.
d) Tous les sous-systèm es d' AS I destinés à fonctionner en
à ten si on c o n ti n u e m od e
doivent être activés, et la condition de charge doit être comprise dans la plage de
n o rm a l
95 % à 1 05 % de la charge prévue.
e) La tension alternative d'entrée de l'ASI à tension continue doit être com prise entre 97 %
et 1 03 % de la , sa fréquence comprise entre 99 % et 1 01 % de la
ten si on ass i g n ée
l'I EC 61 000-2-2.
NOTE 1 L'essai avec la est considéré comm e le plus fiable en term es de répétabilité et
c h a rg e ré s i s ti v e
représente u ne base soli de d'éval uation d es am éliorati ons d u ren dem ent à tous les niveau x de charg e.
NOTE 2 Pour les tolérances, voi r 7. 8 de l'I EC 601 46-1 -1 : 2009.
F.2. 3 I n s t ru m e n t a t i o n
NOTE 1 Le niveau de confiance de l'i ncertitude d'u n instrum ent est enten du com m e la probabil ité d'obteni r, à
l'aid e de cet i nstrum ent, des m esures com prises dans les lim ites d'incertitud e. Un e d istributi on d e d onn ées
norm ale avec un facteu r d'élargissem ent de 1 , 960 représente u n n iveau d e confiance d e 95 %, qui est u n niveau
généralem ent accepté. Pour pl us d'inform ations, voi r le Guid e 98-3 I SO/I EC.
NOTE 2 Les m esures sim ultanées d e l'entrée et d e la sorti e sont en général assu rées par d es équ ipem ents d e
m esure d'entrée et d e sorti e distincts. Néanm oins, un seul instrum ent m ulticanal offrant un échantill onn age en
série rapide ("éch antill on nag e m ultiplexé") est ég alem ent réputé procéd er à des m esures sim ultanées.
F. 3 M é t h o d e d e m e s u re
relevé.
Si une AS I à est raccordée à plusieurs sources d'alim entation, la
ten si on con ti n u e
doit alors être obtenue. Le résultat est considéré com me étant la valeur de la mesure de
rendem ent.
d) Les étapes a), b) et c) doivent être répétées aux conditions de charge de référence de
75 %, 50 % et 25 %.
e) Les étapes b) et c) doivent être répétées pour les conditions à vide, m ais seules les
pertes de doivent être enregistrées.
pu i s s an ce acti ve
F. 4 Ra p p o rt d ' e s s a i s
Un form at recom mandé de rapport d'essai est donné à l'Annexe C. Si la fiche technique de
l'
AS I à ten s i o n (voir Tableau C. 1 ) est utilisée, elle doit être renseignée pour chaque
con ti n u e
– ;
p u i s s a n c e d e s o rt i e a s s i g n é e
– (°C);
t e m p é ra t u re a m b i a n t e
An n e xe G
(informative)
E s s a i c l i m a ti q u e
G.1 G é n é ra l i t é s
L'obj ectif de l'Annexe G est de préciser les relations entre les exigences d'environnement
clim atiques de 4. 2. 1 . 1 et de 4. 2. 2 et les procédures d' de 6.5. 2 et de 6. 5. 3.
e s s a i d e t yp e
G.2 E s s a i d e c o n fo rm i t é a u x e xi g e n c e s c l i m a t i q u e s
fe rm é s à t e m p é ra t u re ré g u l é e e n p e rm a n e n c e , h u m i d i té n on c o n t rô l é e )
I E C 6 0 7 2 1 -3 -3 – C o n d i ti o n s c l i m a ti q u e s I E C 6 0 0 6 8 -2 – C o n d i ti o n s c l i m a ti q u e s
P a ra m è t re d ' e n v i ro n n e m e n t C a t é g o ri e I E C 6 0 0 6 8 -2 l a p l u s E ssai re c o m m a n d é N o te
3 K2 p ro c h e N°
30
22
60068-2-2:
20 Bb/Bd
10
0 y) Froi d Aucune 3)
–1 0 2
–20
Froi d 60068-2-1 :
0 20 40 60 80 1 00 Ab/Ad
Humidité relative % RH
z) Chaleu r Aucune 3)
hum ide
60068-2-56:
Cb
I E C 6 0 7 2 1 -3 -3 – C o n d i ti o n s c l i m a ti q u e s I E C 6 0 0 6 8 -2 – C o n d i ti o n s c l i m a ti q u e s
P a ra m è t re d ' e n v i ro n n e m e n t C a t é g o ri e I E C 6 0 0 6 8 -2 l a p l u s E ssai re c o m m a n d é N o te
3 K2 p ro c h e N°
Bibliographie
I EC 60034-22, Ma ch in e s é le ctrique s to urn a n te s – Pa rtie 22: G é n é ra trice s à co ura n t a lte rn a tif
I EC 60050 (toutes les parties), Voca b ula ire Ele ctrote ch n ique In te rn a tion a l (disponibles à
l'adresse www. electropedia.org)
IEC 60068-2-1 3, Essa is fon da m e n ta ux clim a tique s e t de ro b uste sse m é ca n ique – Pa rtie 2-1 3:
IEC 60068-3-3, Ess a is d'e n viro n n e m e n t – Pa rtie 3: G uide – Mé th ode s d'e ssa is s is m ique s
a p p lica b le s a ux m a té rie ls
IEC 601 46-1 -3: 1 991 , Co n ve rtisse urs à s e m ico n ducte urs – Sp é cifica tio n s co m m un e s et
con ve rtiss e urs co m m uté s p a r le ré s e a u – Pa rtie 1 -3: Tra n s form a te urs e t b o b in e s d'in ducta n ce
IEC 60721 -3-3, Cla ssifica tion de s co n dition s d'e n viro n n e m e n t – Pa rtie 3: Cla ssifica tio n de s
I EC TR 60721 -4-0, Cla ssifica tio n de s con ditio n s d'e n viro n n e m e n t – Pa rtie 4-0: Guide p o ur la
corré la tio n e t la tra n sform a tio n de s cla ss e s de con ditio n s d'e n viron n e m e n t de la CEI 60721 - 3
IEC 60950-1 , Ma té rie ls de tra ite m e n t de l'in fo rm a tio n – Sé curité – Pa rtie 1 : Exige n ce s
gé n é ra le s
pro te ction
IEC 61 000-4-30, Co m p a tib ilité é le ctro m a gn é tique (CEM) – Pa rtie 4-30: Te ch n ique s d'e ssa i e t
ISO/I EC Guide 98-3, In ce rtitude de m e sure – Pa rtie 3: G uide p o ur l'e xp re s sion de l'in ce rtitude
AN SI C57.96-1 999, G uide fo r L o a din g Dry Typ e D istrib utio n and Po we r Tra n sform e rs
______________
INTERNATIONAL
ELECTROTECHNICAL
COMMISSI ON
3, rue de Varembé
PO Box 1 31
CH-1 21 1 Geneva 20
Switzerland
Tel: + 41 22 91 9 02 1 1
Fax: + 41 22 91 9 03 00
info@iec.ch
www.iec.ch