Professional Documents
Culture Documents
700 Type 3
700 Type 3
Optional Features
• Marine environments • Fail Safe Open – energized to close main valve
• Seawater service
• Pressure-reducing add-on trim - for constant,
• Dual-redundant detection system regulated, lower outlet pressure
• Alarm pressure-switch
• Pneumatic release trim extension
• Fail-safe open – energized of close main valve
• Automatic Cycle Feature, shuts off and resets when
de-energized (requires on/off
detection system) ®
UL
LISTED EX5092
Fire Protection
700E Type 3 Electrically-Controlled, PORV-Activated, Deluge Valve
Operation
The BERMAD Model 700E Type 3 is suited for those cases, such as sea water installations, where it is
advantageous to keep the solenoid pilot valve ➊ dry. These systems include open nozzles and an electric fire
detection system.
The 700E Type 3 is held closed by pressure applied to the upper chamber of the main valve ➋. The closed valve
prevents the water or water-foam from entering the system until the pressure is released from the upper chamber.
In the SET condition, the water pressure, supplied through the priming line ➌, is trapped in the main valve's upper
chamber. The water pressure is held by a check valve ➍ and a normally closed PORV ➎ (Pressure-Operated
Relief Valve) pilot valve . The PORV is held closed by the maintained pneumatic pressure and normally closed
solenoid valve. The trapped pressure holds the seal-disk of the main valve to the valve seat ➏. Sealing is drip-
tight and keeps the system piping dry.
In a FIRE or TEST condition, an electric detection system, through a control panel, trips the 700E Type 3 deluge
valve. The deluge valve releases water from the upper chamber, either by the opened PORV or by the manual
release ➐. The PORV is opened by the electrically controlled solenoid pilot valve, releasing trapped pneumatic
pressure from the PORV. Water exits the accelerator ➑ faster than it can be supplied to the upper chamber,
allowing the main valve to open and water to flow into the system piping and to the alarm device.
For information on installation and maintenance, see BERMAD publication "700 Type 3 - IOM".
pneumatic ➊ ➎ pneumatic
➍ ➑
➌
➋ ➐
to drain
➏ to alarm
Te n d e r S p e c i f i c a t i o n s
The deluge valve shall be UL-listed as a unit, "Y" pattern (or angle), diaphragm-activated, with automatic reset.
Valve actuation shall be accomplished by one moving assembly, which shall include a flat seal-disk and a stainless
steel stem.
The valve seat shall be made of stainless steel and have an unobstructed flow path, with no stem guide or
supporting ribs.
The control trim shall be factory pre-assembled and integrated to the main valve, hydraulically-tested, UL-listed and
supplied as an assembly consisting of:
• PORV (Pressure-Operated Relief Valve), UL-listed
• "Y" strainer
• Venturi action accelerator
• Manual emergency release assembly with stainless steel bracket
• Spring-loaded check valve
• Non-corrosive trim of uniform metal, neither steel nor galvanized piping is permitted
The manufacturer shall be certified according to ISO 9001 standards.
Fire Protection
Electrically-Controlled, PORV-Activated, Deluge Valve 700E Type 3
System Components*
1 - Main Valve, BERMAD 700E Series
Basic Trim, includes "B" Items as listed(1)
2B - Accelerator & Priming Restriction
3B - Orifice Assembly
4B - Priming Strainer
6B - Pressure Operated Relief Valve
7B - Check Valve
14B - Solenoid Valve
15B - Manual Emergency Release
W
18B - Priming Valve
19B - Drip Check
Additional Trim Accessories - "A" Items(2)
1A - Alarm Test Valve
2A - Gauge Valve P
3A - Pressure Gauge
5A - Drain Valve
11A - Alarm Valve
11A
14A - Check Valve 3A
Optional 14A 1
W - Water Motor Alarm
1A 19B
P - Pressure Switch
3A
5A
2A
4B 6B
2A
3B
14B
18B 7B 2B
15B
Hydraulic
UL-Listed
The BERMAD Model 700 Type 3 Electric
is UL-listed as a unit when installed
Pneumatic
with specific components and accessories.
* Notes: Atmosphere
1. "B" items are standard trim components provided in the trim package.
2. "A" items are additional trim components required for the proper installation and use of the deluge system.
For ordering, add the suffix "A" to the model number.
Fire Protection
700E Type 3 Electrically-Controlled, PORV-Activated, Deluge Valve
Specifications
PROV
PROV
PROV
PROV
Tl Tl
Th Th
PROV
PROV PROV
Ly
Ly Dv
Hh
Inlet
Inlet Inlet Inlet
Th Tb Tb Tw La Tl
Tw Dv
Ly Tl
TI 200 77/8 200 77/8 170 63/4 165 61/2 160 65/16 140 51/2 130 51/8
Tw 317.5 121/2 329 1215/16 340 133/8 351.5 1313/16 400 153/4 435 171/8 480 187/8
h 82 34/16 102 4 102 4 127 5 152 6 203 8 219 85/8
Th 390 153/8 401 1513/16 464 181/4 517 203/8 645 253/8 736 29 841 331/8
Tb 258 103/16 269 109/16 280 11 292 111/2 320 125/8 350 1313/16 382 151/16
Dv 3/4” 11/2” 11/2” 2” 2” 2” 2”
Notes:
1. Provide adequate clearance around valve for maintenance. 4. Data is for envelope dimensions. Specific component positioning may vary.
2. Listed trim dimensions are maximum. 5. For complete dimensions of 700E main valve, see BERMAD
3. Tw = maximum trim width for both "Y" and angle patterns. publication "700E Basic Deluge Valve"
Materials
Manufacturers Standard Materials Optional Materials Solenoid Pilot Valve
Main valve body and cover Main valve body and accessories Standard model
• Ductile iron ASTM 536(1) • Stainless steel 316 • Enclosure: General purpose water-tight
• Carbon steel ASTM A216-WCB(1) • Marine bronze NEMA 4 and 4X / IP65
Main valve wetted parts (internals) • NiAl-bronze • Optional: Explosion-proof
• Stainless steel 304 and coated steel • Titanium Voltage
Control Trim System • Duplex and Super-duplex • 24, 110, 220, AC 50 Hz
• Accelerator: Brass ASTM B21 Main valve and accessories internals (or 24, 120, 240, AC 60 Hz)
• Forged brass fittings & copper tubing • Stainless steel 316 • 24, 120, DC
Elastomers • Bronze • Continuous duty-molded Class F
• NBR • Titanium • Wattage rating: 10.6 DC, 9.5 AC
• Copper-nickel Approvals
• Hastalloy • UL-listed
Notes:
1. Epoxy coated, fusion bonded - standard.
Tubing and Fittings • CSA Certified
Other coatings available on request. • Stainless steel 316 • Alternative: CENELEC certified for EEx
2. For seawater service see BERMAD • Copper-nickel
publication "Seawater and Corrosive Media".
© Copyright 1999 by BERMAD Control Valves www.bermad.com The information contained in this document is subject to
Cat # PC7PE13 ver 4/00 change without notice. BERMAD shall not be liable for any
English E-mail: info@bermad.com errors contained herein. All rights reserved.