Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Electrical Notes & Articles

Sharing Abstracts,Notes on various Electrical Engineering Topics.

Abstract of IE Rules

Abstract of Indian Electricity Rules:

1) Cut-out on consumer’s premises:

The supplier shall provide a suitable cut-out in each conductor of every service-line other than an
earthed or earthed neutral conductor or the earthed external conductor of a concentric cable within a
consumer’s premises, in an accessible position. Such cut-out shall be contained within an adequately
enclosed fireproof receptacle.
Where more than one consumer is supplied through a common service-line, each such consumer
shall be provided with an independent cut-out at the point of junction to the common service
Every electric supply line other than the earth or earthed neutral conductor of any system or
the earthed external conductor of a concentric cable shall be protected by a suitable cut-out by its
owner
No cut-out, link or switch other than a linked switch arranged to operate simultaneously on the
earthed or earthed neutral conductor and live conductors shall be inserted or remain inserted in any
earthed or earthed neutral conductor of a two wire-system or in any earthed or earthed neutral
conductor of a multi-wire system or in any conductor connected thereto with the following
exceptions:(a) A link for testing purposes, or (b) A switch for use in controlling a generator or
transformer.

2) Danger Notices:

The owner of every medium, high and extra-high voltage installation shall affix permanently in a
conspicuous position a danger notice in Hindi or English and the local language of the district, with a
sign of skull and Bones on
(a) Every motor, generator, transformer and other electrical plant and equipment together with
apparatus used for controlling or regulating the same;
(b) All supports of high and extra-high voltage overhead lines which can be easily climb-upon
without the aid of ladder or special appliances.
3) Cables :

Flexible cables shall not be used for portable or transportable motors, generators, transformer
rectifiers, electric drills, electric sprayers, welding sets or any other portable or transportable
apparatus unless they are heavily insulated and adequately protected from mechanical injury.
Where the protection is by means of metallic covering, the covering shall be in metallic connection
with the frame of any such apparatus and earth.
The cables shall be three core type and four-core type for portable and transportable apparatus
working on single phase and three phases supply respectively and the wire meant to be used for
ground connection shall be easily Identifiable
Where A.C. and D.C. circuits are installed on the same support they shall be so arranged and
protected that they shall not come into contact with each other when live.

4) Safety:

Two or more gas masks shall be provided conspicuously and installed and maintained at accessible
places in every generating station with capacity of 5 MW and above and enclosed sub-station with
transformation capacity of 5 MVA and above for use in the event of fire or smoke.
Provide that where more than one generator with capacity of 5 MW and above is installed in a power
station, each generator would be provided with at least two separate gas masks in accessible and
conspicuous position.

5) High Voltage Equipments installations

High Voltage equipments shall have the IR value as stipulated in the relevant Indian Standard.
At a pressure of 1000 V applied between each live conductor and earth for a period of one minute the
insulation resistance of HV installations shall be at least 1 Mega ohm Medium and Low Voltage
Installations- At a pressure of 500 V applied between each live conductor and earth for a period of
one minute, the insulation resistance of medium and low voltage installations shall be at least 1 Mega
ohm

6) Every switchboard shall comply with the following


provisions, namely:

A clear space of not less than 1 meter in width shall be provided in front of the switchboard;
If there are any a achments or bare connections at the back of the switchboard, the space (if any)
behind the switchboard shall be either less than 20 centimeters or more than 75 centimeters in width,
measured from the farthest outstanding part of any a achment or conductor;
If the space behind the switchboard exceeds 75 centimeters in width, there shall be a passage-way
from either end of the switchboard clear to a height of 1.8 meters.

7) Declared voltage of supply to consumer:

In the case of low or medium voltage, by more than 6 per cent, or;
In the case of high voltage, by more than 6 per cent on the higher side or by more than 9 per cent on
the lower side, or;
In the case of extra-high voltage, by more than 10 per cent on the higher side or by more than 12.5 per
cent on the lower side.

8) Declared frequency of supply to consumer

Except with the wri en consent of the consumer or with the previous sanction of the State
Government a supplier shall not permit the frequency of an alternating current supply to vary from
the declared frequency by more than 3 per cent.

9) Meters, maximum demand indicators and other apparatus


on consumer’s premises

Any meter or maximum demand indicator or other apparatus placed upon a consumer’s premises in
accordance with section 26 shall be of appropriate capacity and shall be deemed to be correct if its
limits of error are within the limits specified in the relevant Indian Standard Specification and where
no such specification exists, the limits of error do not exceed 3 per cent above or below absolute
accuracy at all loads in excess of one tenth of full load and up to full load Connection with earth
Neutral conductor of a phase, 4 wire system and the middle conductor of a 2 phase, 3-wire system
shall be earthed by not less than two separate and distinct connections with a minimum of two
different earth electrodes of such large number as may be necessary to bring the earth resistance to
a satisfactory value both at the generating station and at the sub-station. The earth electrodes
so provided, may be interconnected to reduce earth resistance. It may also be earthed at one or more
points along the distribution system or service line in addition to any connection with earth which
may be at the consumer’s premises
In the case of a system comprising electric supply lines having concentric cables, the external
conductor of such cables shall be earthed by two separate and distinct connections with earth.
The connection with earth may include a link by means of which the connection may be temporarily
interrupted for the purpose of testing or for locating a fault.
All metal castings or metallic coverings containing or protecting any electric supply-line or apparatus
shall be connected with earth and shall be so joined and connected across all junction boxes and other
openings as to make good mechanical and electrical connection throughout their whole length.
10) Use of energy at high and extra-high voltage

Voltage Ground clearance Sectional clearance

11KV 2.75 Meter 2.6 Meter


33KV 3.7 Meter 2.8 Meter
66KV 4.0 Meter 3.0 Meter
132KV 4.6 Meter 3.5 Meter
220KV 5.5 Meter 4.3 Meter
400KV 8.0 Meter 6.5 Meter

11) Transformer:

Where transformer or transformers are used, suitable provision shall be made, either by connecting
with earth a point of the circuit at the lower voltage or otherwise, to guard against danger by reason
of the said circuit becoming Accidentally charged above its normal voltage by leakage from or
contact with the circuit at the higher voltage
A sub-station or a switch station with apparatus having more than 2000 litres of oil shall not be
located in the basement where proper oil draining arrangement cannot be provided.
Where a sub-station or a switch station with apparatus having more than 2000 litres of oil is installed,
whether indoor or out-doors, the following measures shall be taken, namely: –
The baffle walls 4[of 4 hour fire rating] shall be provided between the apparatus in the following
cases: –
(1) Single phase banks in the switch-yards of generating stations and substations;
(2) On the consumer premises;
(3) Where adequate clearance between the units is not available.
Provisions shall be made for suitable oil soakpit and where use of more than 9000 litres of oil in any
one oil tank, receptacle or chamber is involved, provision shall be made for the draining away or
removal of any oil which may leak or escape from the tanks receptacles or chambers containing the
same.
The transformer shall be protected by an automatic high velocity water spray system or by carbon
dioxide or BCF (Bromo chlorodi feuromethane) or BTM (Bromo tri fluromethane) fixed installation
system; and
Oil filled transformers installed indoors shall not be on any floor above the ground or below the first
basement.
Isolators and the corresponding earthing switches shall be interlocked so that no earthing switch can
be closed unless and until the corresponding isolator is in open position.
When two or more transformers are operated in parallel, the system shall be so arranged as to trip
the secondary breaker of a transformer in case the primary breaker of that transformer trips.
Where two or more generators operate in parallel and neutral switching is adopted, inter-lock shall
be provided to ensure that generator breaker cannot be closed unless one of the neutrals is connected
to the earthing system.
Gas pressure type protection to given alarm and tripping shall be provided on all transformers of
ratings 1000 KVA and above.
Transformers of capacity 10 MVA and above shall be protected against incipient faults by differential
protection; and All generators with rating of 100 KVA and above shall be protected against earth
fault/leakage. All generators of rating 1000KVA and above shall be protected against faults within the
generator winding using restricted earth fault protection or differential protection or by both.

1) Connection with earth:

In case of the delta connected system the neutral point shall be obtained by the insertion of a
grounding transformer and current limiting resistance or impedance wherever considered necessary
at the commencement of such a system.
Where the earthing lead and earth connection are used only in connection with earthing guards
erected under high or extra-high voltage overhead lines where they cross a telecommunication line
or a railway line, and where such lines are equipped with earth leakage relays of a type and se ing
approved by the Inspector, the resistance shall not exceed 25 ohms.

2) Clearance above ground of the lowest conductor

No conductor of an overhead line, including service lines, erected across a street shall at any part
thereof be at a height of less than:
For low and medium voltage lines 5.8 meters
For high voltage lines 6.1 metres
No conductor of an overhead line, including service lines, erected along any street shall at any part
thereof be at a height less than:
For low and medium voltage lines 5.5 metres
For high voltage lines 5.8 metres
No conductor of in overhead line including service lines, erected elsewhere than along or across any
street shall be at a height less than:
For low, medium and high voltages lines=4.6 meters.
For low, medium and high voltage=4.0 meters.
For high voltage lines above 11,000 volts=5.2 meters.
For extra-high voltage lines the clearance above ground shall not be less than 5.2 metres plus 0.3
meter for every 33,000 volts or part thereof by which the voltage of the line exceeds 33,000 volts.

89 Responses to Abstract of IE Rules


Pravinchandra Mehta says:
May 3, 2011 at 5:34 pm
Dear Sh Parmar,
I am Pravinchandra Mehta working as DGM Engineering at EMCO Ltd Thane Maharashtra.Nice to
meet u on this forum _every problem has solution.Congrats for the efforts for collection and sharing.I
am basically from vadodara and working in the power sector since 24 yrs..I would like to extend the
freindship with u.
Thanks and regards,
Pravin

Reply
Rajendra M tamhankar says:
October 12, 2015 at 10:06 am
In our Hsg society in Pune. We have Isolator installed between Elect meter and elect distribution
board installed in each flat. Is this system ok? or we should connect MCB in place of
Isolator.Kindly suggest.

Reply
srikanth says:
January 31, 2016 at 7:53 am
I am Srikanth from Chennai, can you clarify who will do the earth pit construction as per IS 3043
standards in chennai

Reply
Jerome Ryan Deleonio says:
May 10, 2011 at 7:26 am
Hi Jignesh Parmar,
I would like to thanks you for your post. I helps me a lot so far
I am currently working with standard/manual for distribution utility in the Phillipines.
Just wanting to say Good Job & More Power

Reply
dinesh narkhede says:
October 11, 2011 at 10:21 pm
Hi
Mr. Jignesh Parmar

I am Dinesh Narkhede working as Asistant Manager – Plant Engineering at Volkswagen India ,


Pune , Maharashtra. I would like to thank you for your post.
It’s a very collective information very useful to any Electrical Engineer.
Once again Thanks for your efforts and sharing the knowledge.

Thanks & Regards


Dinesh

Reply
vibhakar says:
June 6, 2013 at 8:19 am
hello sir
i did my b.tech in electrical engineering..and m.tech in electrical power systems..pls guide me
good course or any job in our core field

Reply
Deepak Chaudhari says:
December 11, 2011 at 5:37 am
Hi Jignesh Parmar,
I am Deepak Chaudhari working as Electrical Engg ,
Mumbai , Maharashtra. I would like to thank you for your post.
its really important information which required to have with every electrical engg.
I know that your many friends are working in power sector. so I suggest that you must kept one jobs
section on your site. so its will helps to many peoples.i hope u will consider my suggestion.

Thanks & Regards


Deepak

Reply
Rakesh Purohit says:
January 2, 2012 at 11:10 am
Hi Mr Jignesh,

You are doing a great job,not every one in today’s world share useful information and that too free.
It is a great platform for young electrical engineers to hone their professional skills.

Thank you

Reply
Naveen says:
February 25, 2012 at 2:33 am
Hi Jignesh Parmar,

I would like to thanks you for your post.I have 2 years exp in design field. i want study more and
more in power sector designing . please tell me any design books for substation or over all designing.

Thank u,

Reply
Ms.shaista khan says:
February 29, 2012 at 5:30 pm
Dear sir,
Thanks for giving information of electrical. I am working as a Sr. Engineer-Project (Execution) of
diesel generator. i have many query regarding to DG sets,

Reply
S M Mujumdar says:
March 8, 2012 at 5:01 pm
It is a good effort. However as per Electricity Act (EA) 2003, Central Electricity Authority has
formulated Regulations for Electrical safety 2010 & published in Gaze e of India. Hence as per
provision of EA 2003, IE Rules 1956 are repelled.
Reply
Anand says:
March 13, 2012 at 9:58 am
Dear Sir,

I am Anand from Delhi. Working for a private company a Asst. Manager (Electrical Projects).

I thank you very much for such a great job in the field of electrical engineering by compiling the
documents and sharing to everybody.

Wish you a great success ahead..

Reply
RAMESH says:
March 14, 2012 at 5:48 pm
Dear Sir..
Salute 2 u frm d depth of my heart ,4 such gr8 doings, helping all of us 2 learn and enjoy d real
learning ,,pls do this 4ever so we never 4get u nor ur teachings….mny more 2 say u r great…

thanks 2 u…

Reply
Parbat Singh says:
March 18, 2012 at 3:22 am
Dear sir,
Congratulations & Thanks for hard work and sharing your knowledge to everyone!!!
Sir, We have a request from electrical transmission company for crossing of underground EHV cable
( 33KV) across over existing underground LPG pipeline( crossing is perpendicular@ 90 deg angle).
What shall be mini. clearance between pipeline top and cable bo om. Pipeline is Cathodic protected (
-0.85 to -1.5 v). What precautionary measures we can take to avoid interference to our pipeline CP
system and avoid detrimental effect to our pipeline by high voltage in cable or any fault in cable.
We are planning to put RCC slabs in between pipeline and cable and enclose cable( 20 meter length)
in thick PVC pipe
with regards
Parbat Singh

Reply
Zulfeqar Ali says:
June 4, 2012 at 12:09 pm
Dear Sir,

Thanks a lot for sharing the Abstract of IE Rules.

One more thing I wanted to know that DG set Installion upto 10KVA permision is not required from
Electrical inspector, but above 10KVA is required,

I have tried to get the reference from where it has been taken, but could not get .

Can you tell me the reference clause of IE rule / Act or any other standards/documents in support of
it.
Regards

Zulfeqar Ali
JSPL Raigarh

Reply
BALARAMAN says:
June 23, 2012 at 1:58 pm
BALARAMAN
thank u sir.
sir I want totely thierical deatils of y d starter so please email me on address.

Reply
Mahi says:
July 11, 2012 at 6:43 am
Hello Mr Parmar,

I m a electrical engineer having 5 yrs of experience.Recently i changed my field into substation


design and finding it very interesting.But not due to proper design set up in my company i m not
clear about this design field..Ur posts really helped me a lot…Thnx …Mahi…

Reply
Er. Anil Prajapati says:
July 21, 2012 at 9:56 am
Dear Sir ,
Thanks for this wonderful positive power sharing. I am protection engineer at Jaipur in RVPN. Please
arrange to provide protection related experience to this blog and let the protection engineers
benefited.
Anil Prajapati

Reply
Sunil Kumar Pipada says:
August 1, 2012 at 6:06 am
Thanks for “Great Effort” Its really very useful for Project Designing & Project Management. I am
working as “Utilities Engineer_Electrical” with NATRiP (Under Ministry of Heavy
Industries_Central Govt. of India)

Reply
Kofi Appeagyei says:
September 18, 2012 at 1:17 pm
Hello Parmar,

I am a young Electrical Engr, just over 3 yrs experience in supervision and design, i find your site so
helpful, full of enlightening information. just wanna say thanks for sharing, God richly bless you.
Would appreciate stuff on lightening protection design, especially rolling sphere method, angle
method etc, particularly for high rise buildings

Reply
murali sir says:
March 9, 2013 at 3:44 pm
help full for all eee cptc engeineers thankq sir

Reply
SPS says:
May 29, 2013 at 6:17 am
Hi! Nice colation.

Can we locate Transformer next to building edge if the walls on two sides are fire rated and on two
sides it is open . Also open to sky.

Reply
Abhilash says:
June 4, 2013 at 3:57 am
You are doing a wonderful job. Thank you very much for your posts. keep on going

Reply
Praveenkumar says:
June 14, 2013 at 2:10 pm
The notes very useful engineering students .

Reply
Sivakumar says:
July 6, 2013 at 8:15 am
How much distance min or max we should keep between a transformer and a breaker panel…..

Reply
Prashant. Kudtarkar says:
July 22, 2013 at 4:53 pm
Sir,
We are installing 3 Nos of Indoor rectifier transformers ( covered by walls 3 sides and open 1 side ) ,
please suggest me the clearance to be maintained between transformer and walls.

Reply
Shriram V. Bhardwaj says:
September 6, 2013 at 10:52 am
Dear Parmar, I am really thankful to you for this valuable piece of Article, I am a law professional
from Himachal Pradesh. Although your article is based on technical knowledge and a person
belonging to engineering sector may well understand your article but still it has some good enough
material for layman like me. Actually I am searching for some info regarding the distance of a
electricity transformer(63 kv) from a residential home but I am not ge ing the proper information on
this point. So if you can write on this topic it would be more helpful for a layman to gain some bit
more knowledge from your scholarly article. If you can provide me this info as to how much distance
a electricity transformer should be having from a residential house? I shall be really thankful to you
for this solicited help. If anyone reading this reply may give me the answer please onto the following
emails:

Thanks

Shriram Vishwanath
Advocate,
Mandi, Himachal Pradesh

Reply
punith pm says:
September 13, 2013 at 9:58 am
sir am punith electrical engineer i need to know wether the DG can be installed in mezzanine flour
according to IE rule????

Reply
jahangir ahmad says:
September 18, 2013 at 6:57 pm
Dear Mr Jignesh. I am pleased to read your article,May you prosper always.
I may add that you also quote the no. of the relevant clause of the act against each note to make your
extracts more authentic.
Further to the above , for the flexible cables I wish to add in the relevant context,that sectional area of
the conductor of one of the wire should be larger as compared to others so that it may not burn off if
all other leads are burnt out due to short circuit & heavy fuse. This will keep the lead from breakage
which often results in the spread of elrctricity & fire.(This condition is essential for the unshielded
rubber insulated cables only, which are being used for domestic purpose in a large quantom now a
days.
Regards
Jahingir Ahmed
Karachi Pakistan

Reply
DK Sharma says:
October 20, 2013 at 6:46 am
Dear Shri Jignesh.Parmar,
I am D K Sharma, Retired Ass Electrical Engineer from Railways.
I feel very sorry, whenever I read about deaths due to overhead electrical wires snapping and falling
on the roads or in fields.
Para 87(1) of Indian Electricity Rules, 1956, stipulates ”Where an overhead line crosses or is in
proximity to any telecommunication line, either the owner of the overhead line or or the
telecommunication line, whoever lays his line later, shall arrange to provide for protective device or
guarding arrangement. This Guarding arrangement should be made for all LT and HT lines which do
not have any tripping arrangement in case the wire breaks.”

My question is, why Guarding is not made mandatory under Indian Electricity Rules 1956.
I have seen in UP, MP and Rajasthan, overhead lines in streets and on roads having no guarding
arrangement. Every year many deaths are reported due to falling of live electric wires on the ground
and causing deaths due to electrocution.

Reply
Alkesh Raval says:
October 25, 2013 at 12:48 pm
Hi,
I am Alkesh from Vadodara.
I want to know the rules of DG Set installation in India
We intend to install 25 KVA DG set at remote location away from village near Chanod.
Is is compulsory to install Silent DG Set?
What are other norms that we need to follow?

Reply
sandeep babariya says:
October 26, 2013 at 6:38 am
i would like to no what should be the height of meter from ground at consumer primisis

Reply
Jignesh.Parmar says:
October 26, 2013 at 6:06 pm
Already given in the blog..Request to search..

Reply
deepak prasad shrivastava says:
November 24, 2013 at 3:49 pm
Sir,I dont know IE rool no 50,so pl gide me fo this rool .I am working in pvt sector textile devision
last 15 years
Thanks ,
Deepak

Reply
B.Nagaraju says:
December 19, 2013 at 9:27 am
Dear Sir,
I came to know that, now everyone is following CEA Electricity Act 2003, no one is following IE rules
1956, is it correct.

Reply
B.Nagaraju says:
December 19, 2013 at 9:29 am
Could you please send me the NEC 1985 standard copy, if you have please..

Reply
ashok says:
January 22, 2014 at 6:52 am
NICE TO READ

Reply
Dipankar Sharma says:
March 20, 2014 at 8:31 am
Hello Mr. Jignesh,
Very Good afternoon , I am Dipankar Sharma working as an Executive Engineer (Engineering and
Operations solution for IT sector Facility Management) in Jones Lang Lasalle.

Thanks for sharing valuable information.

Reply
imran khan says:
August 5, 2014 at 1:09 pm
Electrical work job

Reply
ranjith says:
September 5, 2014 at 8:00 am
how to calculate transformer NCTratio

Reply
Electrical contractor brunswick says:
September 30, 2014 at 11:34 am
Hello there, you’ve done a great job. Keep posting such kind of information on your blog.
Regards: Electrical contractor brunswick

Reply
naval says:
November 19, 2014 at 5:22 pm
hi jignesh sir,
good one interesting for common man knowledge.

Reply
Lt Col S K Paul (Retd) says:
November 25, 2014 at 12:18 pm
Dear Sri Jignesh,
Thanks for sharing your knowledge. It saves a lot of time for quick reference to the rules and acts. I
am retired Electrical engineer and was in need to know the provision of guard wires /stirrups etc
under the high and very high tension lines passing over roads, canals, residents, rail lines etc. This in
case if a live tension wire snaps due to storm earth quake or snow. Thank you and keep up the good
work son.

Reply
arvind kumar says:
December 5, 2014 at 4:43 pm
sir,
i am arvind kumar site engineer in shalimar corp.ltd lucknow. it is most helpfull site for electrical
services installation work. thanking u sir.

Reply
Syed Faqruddin says:
January 5, 2015 at 11:45 am
Dear Sir,

I would like to know what is the safe distance from housing (Human in-habitation) a transformer can
be installed as IE Act / Rules. A neighboring apartment has installed a HV transformer very close to
the kitchen of my house.

Reply
carvalho says:
January 12, 2015 at 11:13 am
sir,
Location of diesel generators in on the roof ie 8 mtrs shall we get permission from electrical inspector

Reply
yogesh kulkarni says:
April 7, 2015 at 5:41 am
Dear Sir,
I am Yogesh Kulkarni,working in ThyssenKrupp pune.
For the moving machine (ship loader/stacker reclaimer) mounted dry type of transformer what are
the minimum mounting clearances required ? is there any IE/IS standard,rule for the same which
explain in detail.

Reply
S says:
July 5, 2015 at 5:15 am
Kindly inform me about new changes happend in CEA (Particularly about inspection) .s

Reply
B M SINGH says:
July 5, 2015 at 7:14 am
As said by you PWD Electrical inspector permission not required up to 10 kva mobile or stationary,
single or three phase DG set, please confirm the statutory rules/act for the same.

Reply
himanshu says:
July 27, 2015 at 1:54 pm
hello Mr. jignesh
I am himanshu pahwa from Delhi, I just wanted to know how much space should be their between a
transformer/ sub station and a residential house as per the electricity act
As their is a open space behind my house, electricity board want to install another transformer their
and leaving no open space. please suggest.

Reply
anshu baran maji says:
July 28, 2015 at 7:25 am
everything is risking in your life….

Reply
P Harikrishna says:
September 10, 2015 at 3:12 pm
thanks for the good interesting postings and its a passion for the existing and upcoming engineers

Reply
Channabasavaraju.M.D says:
September 16, 2015 at 8:28 am
safety distance for oil storage tank to Electrical high tension line & transformer

Reply
himanshu says:
September 17, 2015 at 7:55 am
hello Mr. Jignesh
can u please tell me what is the minimum clearance/ distance between a transformer and a residential
building
regards

Reply
Shakil Shaikh says:
November 1, 2015 at 1:27 pm
Dear Mr. Jignesh,

As per IE Rules, can you please inform what should be the minimum rating of Transformer for
providing Nitrogen based Fire Fighting System

Regards,

Shakil Shaikh

Reply
Suveer Kumar says:
November 4, 2015 at 10:50 am
Any Idea if the Installation certificate from Electrical Inspector is still a requirement for DG set in
NCR / Haryana/ UP / UK.

Reply
K.srao says:
February 21, 2016 at 11:38 pm
What is the meaning of link service disconnect ion, what is the elect act number?

Reply
electricalyadav1992 says:
February 29, 2016 at 9:51 am
can any one advice me are there any specific standards to be followed for multi gap (series gap)
Lightning arrester or any methods for calculations for designing the length of gap in between
two(Zinc) cylinders, for example let’s assume the lightning arrester is designed for 11 or 33 kV.

Reply
Aziz pathan says:
March 8, 2016 at 8:32 pm
Very importance massage ….
Dear sir,
I am pathan aziz working as operator in mahatransco Maharashtra. Best information electricity
&consumers safety rules .
Thanks and regards,
pathan

Reply
Samsher bahadur says:
March 23, 2016 at 12:15 pm
Dear sir
India mai voltage variations kitna hai
Reply
manoj malik says:
April 11, 2016 at 9:28 am
dear sir please provide the information in detail about the metering ie grid metering.KWH ,
KVARH,REVERSE CONNECTION OF CT/PT etc many more

in waiting
manoj malik

Reply
Mohammad firj says:
April 23, 2016 at 2:39 pm
Dear sir
Please tell me what does it mean ‘expiry date of LT PERMIT UNDER IE RULES FOR MINE.’

Reply
Suraj says:
August 24, 2018 at 3:52 am
How to get LT PERMIT UNDER IE RULES FOR MINE..

Reply
fazal rehman says:
June 7, 2016 at 11:42 am
faul current are given for 1second or how much time?plz add

Reply
T.sivarajkumar. says:
July 3, 2016 at 1:06 am
Dear sir.

Thank you very much. Please send all electrical safety procedure.

Reply
Vinoth says:
July 14, 2016 at 9:54 am
Sir ! data is very useful .

Reply
paresh says:
December 20, 2016 at 10:32 am
Dear sir,

mere gar ke piche 200kva ka 2 transfomer hai, vo Kafi aawaz kar raha hai, Aur me GEB Me gaya tha
to vo loge na bol rahe hai, vo 4-5 fit dur hoga to vo nomes ke hisab se ketna dur hona chahye kay me
RTI Karu, Karu to Kaha karni padegi

Paresh Patel

Reply
Malla Reddy AV says:
February 9, 2017 at 7:23 am
Dear Sir,

Thanks for good efforts and information provided.

AV Malla Reddy
Consultant – Management Systems
LA for QMS, EMS, OHSAS, EnMS & ISMS
IA for TS, AS & NABL; 6σ GB, Trainer-QCFI
e-mail: harshatech@gmail.com; Mobile: +91 9701455393

Reply
govardhan gaddam says:
February 17, 2017 at 2:45 pm
please clarify—we are installtion three numbers 10 MVA transformers for water pumping system in
its own switch yard. i would like to knoe whether 10 MVA tranformer (ONAN type) as per CBIP
recommendation. if no I would like to know references of that. in the tender document it is
mentioned. I wanted to know whether any mistake has taken place while mentioning or it is
required….regards, Govardhan gaddam, 9974735000

Reply
RAJESH JAIN says:
March 17, 2017 at 8:32 am
We want to know about horizontal distance between insulated AB cable of 415 volt system and
consumer premises. As per record there is 1.2 meter but this is in case of bare conductor but I want to
know about insulated AB cable.

Reply
S.Manikumar says:
March 17, 2017 at 10:44 am
Hi Sir,

I’m S.Manikumar working as Plant Maintenance Engineer- Power Sector in Apollo tyres Ltd, chennai

Thank you very much for your valuable Post in Electrical Field….

Reply
REJIN R G says:
April 11, 2017 at 12:07 pm
Sir, which rule states that electrical switch boards should not place in a window frame?

Reply
ramesh says:
May 24, 2017 at 6:41 am
very good information.

can you send me the new regulation on transformer losses

Reply
SATISH TIWARI says:
May 28, 2017 at 10:49 am
HI MYSELF SATISH TIWARI ,FROM RELIANCE MANUFACTRING DIVISION VADOPDARA, I
WANT TO KNOW UPTO HOW MUCH LITRE OF OIL THERE IS REQIREMENT OF OIL SOAK PIT
FOR TRANSFORMER ACCORDING TO CEA

Reply
shang tap shang says:
June 12, 2017 at 10:38 am
Dear sir,
Congratulations & Thanks for
hard work and sharing your
knowledge to everyone!!!
Sir, We have a request from
electrical traning course company for crossing of underground.

Reply
sanjeev singhal says:
June 29, 2017 at 6:56 pm
THANKS A LOT FOR VALUABL;E INPUT , PLEASE SHARE ALSO ON
sanjeevsinghal17@gmail.com

Reply
Jignesh.Parmar says:
July 2, 2017 at 7:07 am
Press “FOLLOW THIS MAIL BY BLOG”

Reply
Papoo Sankaran says:
August 17, 2017 at 9:35 pm
You are providing an excellent service to the Electrical Engineering fraternity; keep it up, there
are very rare persons like you

sashank pradhan says:


August 3, 2017 at 7:48 pm
sir I want to know is there any rule or permission should be needed from electric dept to instal 35kv
dg…

Reply
Papoo Sankaran says:
August 17, 2017 at 9:39 pm
What are the most authentic publications to refer to in India for Earthing and Bonding of Electrical
Installations at Substations ?

Reply
Amit Lunia says:
January 27, 2018 at 3:42 am
Hi Jignesh

Can provide further insight into electrical safety audit criterion and also CEA regulation 2010 which
has superseded IER
Reply
BEN says:
February 25, 2018 at 4:39 pm
Hello
I would like to ask about the rules you are adapting there in electricity domain..
Thank you

Reply
sanjeev says:
May 10, 2018 at 10:18 am
very usefull i formaation

Reply
Arabinda says:
June 14, 2018 at 7:14 am
Hello,
I m Arabinda Seth, working in OPTCL, thank you for the valuable information shared. I’m going to
takeover the charge of Newly constructed o132/33KV Grid S/S. Pleasesend me a check list with values
for inspection before taking operation.
With Regards,
AKSeth. Manager(Elect)

Reply
Raju.N says:
July 23, 2018 at 11:05 am
Let me know the minimum vertical clearance and horizontal clearance required from Tree to Low
and medium voltage overhead lines.

Reply
NIKUNJ KUMAR says:
July 30, 2018 at 12:02 pm
hello,
is there any Indian Standard which mentions the minimum number of persons required to be present
while doing HT operation/maintenance?

Reply
Nawal Kumar mahto says:
August 30, 2018 at 8:55 am
11KV to440Volt

Reply
Sankar says:
September 7, 2018 at 3:14 am
Very useful thank you

Reply
Somnath Gupta says:
December 9, 2019 at 5:29 am
What does the rule says for the isolation of Transformer input source in case of fire/ smoke or any
other abnormality.
Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.

You might also like