SCOPE OF WORK:

1. INSTALL 1 X 750kVA GROUND MOUNT TRANSFORMER WITH CFC SWITCHGEAR AND DISTRIBUTION BOARD WITHIN THE KIOSK BUILDING (KIOSK TO BE CONSTRUCTED BY
THE DEVELOPER, REFER TO 'DETAIL A' AND 'DETAIL B' FOR TRENCH LAYOUT).
2. CUT EXISTING HV CABLE TO MAKE JOINT AT LOCATION MARKED J1.
3. LAY AND TERMINATE 300MM² 3C AL HV XLPE U/G CABLE BETWEEN JOINT J1 TO PROPOSED CFC SWITCHGEAR, PROPOSED CFC SWITCHGEAR TO CFC SWITCHGEAR
INSTALLED WITHIN KIOSK SUBSTATION T3017 AND PROPOSED 750KVA TRANSFORMER AND CFC SWITCHGEAR.
4. LAY AND TERMINATE 240MM² 4 X 1C PER PHASE ALU XLPE LV UNDERGROUND CABLE FROM PROPOSED 750KVA TRANSFORMER TO DISTRIBUTION BOARD.
5. INSTALL HV AND LV EARTHING WITHIN THE PROPOSED EARTHING TRENCH.
Name: TIVAM
Client: Project Title: ELECTRICITY SUPPLY TO CHARAN KATONIVERE Scheme No: G19-22
MR. CHARAN JEET SINGH HOLDINGS PTE LTD'S COMMERCIAL DEVELOPMENT
0 Original Issue TTK
No Revision Date By energising our nation AT LOT 3, YASAWA STREET IN LAUTOKA Scale:
Name: TIVAM
Client: Project Title: ELECTRICITY SUPPLY TO CHARAN KATONIVERE Scheme No: G19-22
MR. CHARAN JEET SINGH HOLDINGS PTE LTDS COMMERCIAL DEVELOPMENT
0 Original Issue TTK
No Revision Date By energising our nation AT LOT 3, YASAWA STREET IN LAUTOKA Scale:
Energy Fiji Limited

Project Cost Estimate

Scheme No: G19-22 Quotation Date: 31/05/2022

Customer Name: Charan Jeet Singh Scheme Name: Electricity Supply to Charan Jeet Singh Group at L

Remarks:

Code Description Quantity Unit Cost Line Total


I04260 300MM 3C AL 11KV XLPE Cable 45 78.74 3,543.51

I04597 11kV Safelink2 CFC (ID) 1 15,571.71 15,571.71

I04407 750kVA GM Transformer 1 38,860.93 38,860.93

I04672N 11kV 3C Stra Joint 185-300sqmm 1 1,136.96 1,136.96

B-PA-HV-EARTHING Hv Earthing 1 271.16 271.16

B-PA-LV-EARTHING LV-EARTHING 2 364.59 729.19

I07130 Hep Tape (300m x 300mm) 1 57.68 57.68

I05487 150mm x 5mm HD Cable Cover 15 4.88 73.24

I04267 0. 6/1kv Al. XLPE 1core 240mm 100 9.24 923.98

I04677 11kV 3C Trifur Kit 185-300sqmm 4 1,390.73 5,562.92

I05494 DANGER SIGN (3 LANGUAGES) 4 8.26 33.03

I04678A END CAPS TO SUIT 240 MM TO 300 4 12.61 50.45

I03028A 1 1/4 X3/8 BRASS BOLTS & NU 25 3.17 79.28

I03089 M10 BRASS WASHERS 50 .42 20.98

I04611 80A Stricker Pin Fuses 3 224.91 674.74

I02066 500A NH3 DIN FUSE 6 30.28 181.69

I03206 Elect. Insulating Tape Black 6 1.7 10.21

I03207 Elect. Insulating Tape Red 6 1.7 10.18

I03208 Elect. Insulating Tape Green 6 1.7 10.2

I03209 Elect. Insulating Tape Yellow 6 1.7 10.18

I03230 SCOTCH 22 HEAVY DUTY ELECTRICA 8 70.92 567.34

I03266 SCOTCH 23 RUBBER SPLICING TAPE 8 67.89 543.12

I03685 HACKSAW BLADES 8 1.87 14.95

I03402A EFL Stickers 4 4.59 18.35

I03597 Master Padlock Code1 5 182.23 911.13

I00858A 1250A DIST. BOARD VC122 1 9,741.51 9,741.51

I05420 2M X 100 X 75 HARDWOOD X-ARMS 2 74.86 149.73

I03102 12MMX50X50X3 GALV. SQUARE WASH 8 .27 2.18

I02764 M350XM12 (14 X1/2 ) GALV BOL 4 1.74 6.97

I04557 Safelink Termination Kit-300mm 4 1,004.43 4,017.72

I04672M 11kV 3C Tem Kit ID 120-300sqmm 1 571.53 571.53

I02880 50MM X 12MM DYNA BOLTS 4 .52 2.09

I03417 WASTE COTTON RAGS 3 1.79 5.36


I04567 Mounting Plate - Safelink S/G 2 348.5 697

I02326 35 sqmm Copper Crimp Lug 12 .9 10.8

I05725 3 X 1/4 COPPER BUS BAR 2 346.93 693.87

I04896 MV INSULATOR FOR BUSBAR 2 47.54 95.08

R0026 Ground-mount Equipment Labelling 2 15.6 31.2

I04675 11kV Rht Ang Boot 120-300sqmm 3 301.44 904.31

I02489 240 sqmm Bi-metal Crimp Lug 32 15.36 491.43

I03210 Elect. Insulating Tape Blue 6 1.7 10.18

B-PG-INS Electrical Inspection Team 1 249.29 249.29

B-PG CJC Cable Jointer Team 9 766.7 6,900.34

CART Internal Cartage 6 100 600

R0001 Engirng dsgn DrawgsGIS 9.6 100 959.89

R0002 Pwrline Rte SVY/WL ACQ 3.53 100 352.99

R0003 Financial administration 1.62 100 161.47

R0006 Construction Mangmt/Suprvsn 25.12 100 2,511.6

R0008 Civil/Structl Engin Studies 2.01 100 200.82

R0010 Inventory Management 2.06 100 205.72

I03595 303SC deadlock 61073 11kv 2 293.96 587.92

___________

Total Price: $100,028.10

Markup Amount of 0.00% : $0.00

Vat Amount (9.0% :) $9,002.53

Total Value Incl VAT : $109,030.63

Customer Contribution (100%): $109,030.63

End of Quote
1 2 3 4 5 6 7 8

42700

6185 6050 6050 6060 6030 6050 6275

Refer Enlarge drawings


U V W
(sheet A3a) refer enlarge
A13 A14 A15
e detail (A20)

A
10 10 10
Managers 1
Cosmetic X
Office Lift Stairs
10 1 A10

Railings
16

Canopy Roof
5655

17
10
EFL

Planter
2
transformer Trolley
Location
RL=0.380
B

1900
1 d Y
a Supermarket A11
Cargo Lift 751 sqm 1

Entry
Ramp UP.
5545

Railings
3000 2060
Counter (6)
Ratio 1:8 1 RL=0.000

C
1 c
refer enlarge 8 8
detail (A21)
22400

d
Storage 1 Butcher
5465

Exit
7 1
RL=0.380
2 1
1
9 7

D 4

Canopy Roof
6 5 5 5 6
RL=0.380
15
e 12
5735

Cool Room Butcher Cool Z


1
Room 1
2 Liqour 2 A12
18 1
2 Milk Bar Liqour c
14 13 11 11 11
cooler 3
Display
E

d
PROPOSED GROUND FLOOR PLAN
SCALE 1: 150

NOTE: KEY FOR WALL REFERENCE KEY FOR FLOOR FINISHES REFERENCE LEGEND
1. confirm all dimensions on site existing conc. blockwall to remain, Selected 600 x 600 Ceramic a new lift to be installed as per manufactures 1 Check-out counter (double)- 2400 x 7 Butcher Display Freezer- 1875 x 13 Mixed Veges (3 door) - 3750 x 940 x
prior to construction allow to protect from damages specification 2000mm (6 units) 1181x 1151mm (2 - units) 2030mm (1 unit)
floor tiles to be supplied by
during construction 1 2 Counter with bulkhead above- 600mm 8 Butcher Display Freezer- 1250 x 14 Mixed Veges (2 door) - 2500 x 940 x
2. Whole of interior (fitout area) to client, Contractor to b new cooler room to be installed as per
be painted as per Designers new gib board wall painted as install including adhesive 3 Liqour Freezer - 2600 x 745 x 1181 x 1151mm (2 - units) 2030mm (1 unit)
manufactures specification
instruction per Building Designers instruction, refer (Ardex - X56) & grout. 1900mm (1 unit) 9 Butcher meat slicer 15 Juice Freezer - 2500 x 745 x 1900mm
wall sections for details c selected ceramic wall tiles to be supplied by (1 unit)
3. All floor tiles/ carpet to be laid 4 Ice Cream Freezer - 2580 x 1042 x 10 Potatoe, Garlic, Onion Shelves- 1300
client, contractor to install including adhesive.
as per Designers instruction new 200mm conc. wall painted as per 1024mm (1 unit) x 1000mm (4) 16 Dairy choclate Freezer - 1975 x 754 x
Existing concrete floor with (ardex - x56) & grout.
building consultants instruction, refer 5 Crest Freezer - 3750 x 1830 x 1900mm (1 unit)
4. Existing walls, allow to make 2 Steel trowel & soft broom d 40mm dia ss pipe, refer detail 11 Fruits, Veges, Dairy & Frozen - 3750 x
wall sections for details 1016mm (3 units) 17 Flour, small shelf - 1300 x 1000mm (2)
good & paint as per Designers finish 940 x 2030mm (3 units)
new 150mm conc. wall painted as per e replaster any damage columns & paint apply 6 Small wings Freezer - 1830 x 1100 x
instruction 12 Roast chicken Oven - 1300 x 1200mm 18 Liqour cool room- 2300 x 2400mm (1)
building consultants instruction, refer wall putty and sand before painting. remove 1000mm (2 units)
wall sections for details any electrical fixtures and wires, refer enlarge
NOTES: THE CONTRACTOR MUST VERIFY ALL DIMENSIONS ON THE PROJECT: DRAWING TITLE: SCALE: DATE : SHEET NO:
Architectural Studio

A3
DRAWING BEFORE THE EXECUTION OF WORK OR SHOP DRAWINGS. THE
CONTRACTOR SHALL NOTIFY THE PROJECT CONSULTANT OF ANY Building Designer | Building Consultant
CHARAN KATONIVERE HOLDINGS LIMITED PROPOSED GROUND As Shown 30. 05. 2022

DISCREPANCIES. FIGURED DIMENSIONS SHALL TAKE PREFERENCE OVER 9027 451 | 3411 329 PROPOSED COMMERCIAL BUILDING FLOOR LAYOUT REVISION #: DESIGNED BY:
SCALED DIMENSIONS .THIS DRAWING IS COPYRIGHT AND THE PROPERTY
M. Ahmed
P.O.Box 8444, Nakasi LOT 3, YASAWA STREET,
OF THE AUTHOR AND MUST NOT BE RETAINED, COPIED OR USED arcstudio@outlook.com.au R3 DRAWN BY: PROJECT:
WITHOUT THE AUTHORITY OF ARCHITECTURAL STUDIO. LAUTOKA M. Ahmed 2021 - arcstd26
1 2

6185

wc
UP.

2240
Stairs

whb

Contractor to relocate
600 x 600mm
duct shown dotted to
Duct over
5655

Grid line D

3510
4800 1380

Lockers

2920
Exact

4700
Transformer
Location

1000

B
700

600 x 600mm
Duct over
3990
3100

Cargo Lift

Contractor to relocate
duct shown dotted to
Grid line D
ENLARGE GROUND FLOOR PLAN
SCALE 1: 50

NOTES: THE CONTRACTOR MUST VERIFY ALL DIMENSIONS ON THE PROJECT: DRAWING TITLE: SCALE: DATE : SHEET NO:
Architectural Studio

A3a
DRAWING BEFORE THE EXECUTION OF WORK OR SHOP DRAWINGS. THE
CONTRACTOR SHALL NOTIFY THE PROJECT CONSULTANT OF ANY Building Designer | Building Consultant
CHARAN KATONIVERE HOLDINGS LIMITED PROPOSED GROUND As Shown 30. 05. 2022

DISCREPANCIES. FIGURED DIMENSIONS SHALL TAKE PREFERENCE OVER 9027 451 | 3411 329 PROPOSED COMMERCIAL BUILDING FLOOR LAYOUT REVISION #: DESIGNED BY:
SCALED DIMENSIONS .THIS DRAWING IS COPYRIGHT AND THE PROPERTY
M. Ahmed
P.O.Box 8444, Nakasi LOT 3, YASAWA STREET,
OF THE AUTHOR AND MUST NOT BE RETAINED, COPIED OR USED arcstudio@outlook.com.au R3 DRAWN BY: PROJECT:
WITHOUT THE AUTHORITY OF ARCHITECTURAL STUDIO. LAUTOKA M. Ahmed 2021 - arcstd26
TYPICAL TRENCH DETAILS ACROSS ROADWAYS, DRIVEWAYS & FOOTPATHS
33kV + 11kV + FIBRE TRENCH 33kV + 11kV + LV/MV + FIBRE TRENCH 33kV + 11kV + LV/MV TRENCH 33kV + 11kV TRENCH

PAVED SURFACE PAVED SURFACE PAVED SURFACE PAVED SURFACE


BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS
150 (REFER TO NOTE # 5) 150 150 150
MARKER/ HEP MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE TAPE
90
BACKFILL MATERIALS TO BE IN MECHANICAL PROTECTION/
ACCORDANCE TO EFL REQUIREMENTS 240 HARD-COVER
BACKFILL MATERIALS TO BE IN
(REFER TO NOTE # 5) 100
ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5) 360 BACKFILL MATERIALS TO BE IN
MECHANICAL PROTECTION/ U/G OPTICAL FIBRE CABLE
100 ACCORDANCE TO EFL REQUIREMENTS 510
HARD-COVER (100mm CONDUIT)
100
(REFER TO NOTE # 5)

MECHANICAL PROTECTION/ 70 MECHANICAL PROTECTION/


U/G OPTICAL FIBRE CABLE HARD-COVER (INSTALL BY 2) HARD-COVER (INSTALL BY 2)
100 1130
(100mm CONDUIT) 100 100
1130
1200 1200
70
MECHANICAL PROTECTION/ MECHANICAL PROTECTION/
HARD-COVER (INSTALL BY 2) LV/MV CABLE 150 LV/MV CABLE 150 HARD-COVER (INSTALL BY 2)
100 (150mm CONDUIT) (150mm CONDUIT) 100

70 70
11kV(OR 6.6kV) CABLE 150 11kV(OR 6.6kV) CABLE 150
(150mm CONDUIT) (150mm CONDUIT)
11kV(OR 6.6kV) CABLE 150 11kV(OR 6.6kV) CABLE 150
(150mm CONDUIT) (150mm CONDUIT)
70 70

33kV CABLE 70 70 33kV CABLE


100 100
(100mm CONDUIT)
(100mm CONDUIT)
33kV CABLE
SAND 50 33kV CABLE 100 100 50
(100mm CONDUIT) SAND
(100mm CONDUIT)
SAND 50 SAND 50
500 500

500 500

33kV + FIBRE TRENCH 33kV + LV/MV TRENCH 33kV + LV/MV + FIBRE TRENCH 11kV+FIBRE TRENCH

PAVED SURFACE PAVED SURFACE PAVED SURFACE PAVED SURFACE


BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS
150 150 (REFER TO NOTE # 5) 150 150
MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE MARKER/ HEP
90 TAPE
BACKFILL MATERIALS TO BE IN MECHANICAL PROTECTION/
BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 230 HARD-COVER 240
BACKFILL MATERIALS TO BE IN ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5) 100
ACCORDANCE TO EFL REQUIREMENTS (REFER TO NOTE # 5)
(REFER TO NOTE # 5) 360
MECHANICAL PROTECTION/ U/G OPTICAL FIBRE CABLE MECHANICAL PROTECTION/
HARD-COVER (100mm CONDUIT) 100
HARD-COVER
100 900 100
70
MECHANICAL PROTECTION/ 980 MECHANICAL PROTECTION/ 980 980
U/G OPTICAL FIBRE CABLE 100 HARD-COVER (INSTALL BY 2) HARD-COVER (INSTALL BY 2) U/G OPTICAL FIBRE CABLE
100
(100mm CONDUIT) 100 100 (100mm CONDUIT)

70 70
MECHANICAL PROTECTION/ MECHANICAL PROTECTION/
HARD-COVER (INSTALL BY 2) LV/MV CABLE LV/MV CABLE HARD-COVER
150 150
100 (150mm CONDUIT) (150mm CONDUIT) 100

33kV CABLE 100 70 70


(100mm CONDUIT) 11kV(OR 6.6kV) CABLE 150
33kV CABLE 33kV CABLE (150mm CONDUIT)
SAND 50 100 100
(100mm CONDUIT) (100mm CONDUIT)
SAND SAND 70
SAND 50 50
500

500 500 500

LV/MV + FIBRE TRENCH 11kV + LV/MV TRENCH 33kV TRENCH


11kV + LV/MV + FIBRE TRENCH

PAVED SURFACE PAVED SURFACE PAVED SURFACE PAVED SURFACE


BACKFILL MATERIALS TO BE IN BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5) 150 (REFER TO NOTE # 5) 150 150 150
MARKER/ HEP MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE TAPE
90 90
MECHANICAL PROTECTION/ MECHANICAL PROTECTION/
HARD-COVER HARD-COVER
100 100 BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 360
U/G OPTICAL FIBRE CABLE (REFER TO NOTE # 5)
100
U/G OPTICAL FIBRE CABLE 100
(100mm CONDUIT) BACKFILL MATERIALS TO BE IN
830 (100mm CONDUIT) 500
ACCORDANCE TO EFL REQUIREMENTS 900
70 70 (REFER TO NOTE # 5)
MECHANICAL PROTECTION/ MECHANICAL PROTECTION/ MECHANICAL PROTECTION/
HARD-COVER HARD-COVER 1050 HARD-COVER 1050
100 100 100

MECHANICAL PROTECTION/
LV/MV CABLE LV/MV CABLE LV/MV CABLE HARD-COVER (INSTALL BY 2)
150 150 150
(150mm CONDUIT) (150mm CONDUIT) (150mm CONDUIT) 100

SAND 70 70 70 LV/MV CABLE


100
(100mm CONDUIT)

11kV(OR 6.6kV) CABLE SAND 50


150 11kV(OR 6.6kV) CABLE 150
500 (150mm CONDUIT) (150mm CONDUIT)

SAND SAND 500


70 70

500 500 SHEET 1 OF 3


TYPICAL TRENCH DETAILS ACROSS ROADWAYS, DRIVEWAYS & FOOTPATH
11kV TRENCH LV/MV TRENCH

PAVED SURFACE PAVED SURFACE

150 150
MARKER/ HEP MARKER/ HEP
TAPE TAPE

BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS
BACKFILL MATERIALS TO BE IN 360
510 (REFER TO NOTE # 5)
ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5) 830

980 MECHANICAL PROTECTION/


HARD-COVER
100

MECHANICAL PROTECTION/
HARD-COVER LV/MV CABLE 150
100 (150mm CONDUIT)

SAND 70
11kV(OR 6.6kV) CABLE 150
(150mm CONDUIT)

SAND 500
70

500

TYPICAL TRENCH DETAILS FOR DIRECT BURIED CABLES

33kV + 11kV + FIBRE TRENCH 33kV + 11kV + LV/MV + FIBRE TRENCH 33kV + 11kV + LV/MV TRENCH 33kV + 11kV TRENCH

GRASS SURFACE GRASS SURFACE GRASS SURFACE GRASS SURFACE

150 150 150 150


MARKER/ HEP MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE TAPE

BACKFILL MATERIALS TO BE IN
BACKFILL MATERIALS TO BE IN 240
ACCORDANCE TO EFL REQUIREMENTS
ACCORDANCE TO EFL REQUIREMENTS 330 (REFER TO NOTE # 5)
(REFER TO NOTE # 5) 420
BACKFILL MATERIALS TO BE IN
MECHANICAL PROTECTION/ BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 510
HARD-COVER ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5)
100 (REFER TO NOTE # 5)
MECHANICAL PROTECTION/
HARD-COVER
100 U/G OPTICAL FIBRE CABLE D
1020 1060 MECHANICAL PROTECTION/ 1060 1020
70
D MECHANICAL PROTECTION/ HARD-COVER (INSTALL BY 2)
U/G OPTICAL FIBRE CABLE 100
HARD-COVER (INSTALL BY 2) MECHANICAL PROTECTION/
70 100
MECHANICAL PROTECTION/ HARD-COVER (INSTALL BY 2)
HARD-COVER (INSTALL BY 2) LV/MV CABLE D 100
100 LV/MV CABLE D
70 11kV(OR 6.6kV) CABLE
D
70
11kV(OR 6.6kV) CABLE D
11kV(OR 6.6kV) CABLE D
70
D
70 11kV(OR 6.6kV) CABLE
70 33kV CABLE D
D 70
33kV CABLE 50
33kV CABLE D SAND
SAND 50 33kV CABLE D
SAND 50
SAND 50
500
500
500
500

33kV + FIBRE TRENCH 33kV + LV/MV TRENCH 33kV + LV/MV + FIBRE TRENCH 11kV+FIBRE TRENCH

GRASS SURFACE GRASS SURFACE GRASS SURFACE GRASS SURFACE

150 150 150 150


MARKER/ HEP MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE TAPE

BACKFILL MATERIALS TO BE IN BACKFILL MATERIALS TO BE IN


BACKFILL MATERIALS TO BE IN ACCORDANCE TO EFL REQUIREMENTS 270 ACCORDANCE TO EFL REQUIREMENTS
ACCORDANCE TO EFL REQUIREMENTS BACKFILL MATERIALS TO BE IN (REFER TO NOTE # 5) (REFER TO NOTE # 5) 330
360 ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5) 450
(REFER TO NOTE # 5)
MECHANICAL PROTECTION/
HARD-COVER
100 MECHANICAL PROTECTION/
MECHANICAL PROTECTION/ 950 HARD-COVER 950
900
HARD-COVER 100
U/G OPTICAL FIBRE CABLE D 950
100
MECHANICAL PROTECTION/ U/G OPTICAL FIBRE CABLE
70 D
HARD-COVER (INSTALL BY 2) MECHANICAL PROTECTION/
U/G OPTICAL FIBRE CABLE D
100 HARD-COVER (INSTALL BY 2) 70
70 100 MECHANICAL PROTECTION/
MECHANICAL PROTECTION/ HARD-COVER
HARD-COVER (INSTALL BY 2) LV/MV CABLE D 100
100 LV/MV CABLE D
70
70 11kV(OR 6.6kV) CABLE D
33kV CABLE D
33kV CABLE D
SAND 50 33kV CABLE D SAND 70
50
SAND
SAND 50

500
500 500
500
SHEET 2 OF 3
TYPICAL TRENCH DETAILS FOR DIRECT BURIED CABLES
11kV TRENCH 11kV + LV/MV + FIBRE TRENCH 11kV + LV/MV TRENCH 33kV TRENCH

GRASS SURFACE GRASS SURFACE GRASS SURFACE GRASS SURFACE

150 150 150 150


MARKER/ HEP MARKER/ HEP MARKER/ HEP MARKER/ HEP
TAPE TAPE TAPE TAPE

BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 240
(REFER TO NOTE # 5) BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 420
BACKFILL MATERIALS TO BE IN (REFER TO NOTE # 5)
510 MECHANICAL PROTECTION/
ACCORDANCE TO EFL REQUIREMENTS BACKFILL MATERIALS TO BE IN
(REFER TO NOTE # 5) HARD-COVER ACCORDANCE TO EFL REQUIREMENTS 540
950 100
900
U/G OPTICAL FIBRE CABLE D 950
950
MECHANICAL PROTECTION/
MECHANICAL PROTECTION/ 70 HARD-COVER
MECHANICAL PROTECTION/ HARD-COVER 100
HARD-COVER 100
MECHANICAL PROTECTION/
100 LV/MV CABLE D HARD-COVER (INSTALL BY 2)
LV/MV CABLE D 100
11kV(OR 6.6kV) CABLE D 70
70 33kV CABLE D
SAND 70 11kV(OR 6.6kV) CABLE D
11kV(OR 6.6kV) CABLE SAND 50
D
SAND 70
SAND 70
500 500

500
500

LV/MV + FIBRE TRENCH LV/MV TRENCH NOTE:


1. THE STANDARD TRENCH DETAILS ARE IN ACCORDANCE WITH THE ELECTRICITY REGULATION 2019 AND RELEVANT AS/NZS
GRASS SURFACE STANDARD.
GRASS SURFACE
2. CABLES LAID IN THE TRENCH ACROSS ROADWAYS, DRIVEWAYS AND FOOTPATH SHALL BE IN ELECTRICAL CONDUITS. THE
BACKFILL MATERIALS TO BE IN
ACCORDANCE TO EFL REQUIREMENTS 150 CONDUITS SHALL MEET THE REQUIREMENTS OF AS/NZS 2053.
(REFER TO NOTE # 5) 150
MARKER/ HEP 3. WHERE MORE THAN ONE CONDUIT IS LAID, THE TRENCH WIDTH WILL CHANGE ACCORDINGLY HAVING THE CONDUITS/
MARKER/ HEP TAPE TAPE
MECHANICAL PROTECTION/
30
BACKFILL MATERIALS TO BE IN
CABLES 70mm APART.
HARD-COVER 100 ACCORDANCE TO EFL REQUIREMENTS
(REFER TO NOTE # 5)
210 4. THE DESIGNER SHALL INCLUDE SPARE CONDUITS AT ROADWAYS, DRIVEWAYS AND FOOTPATH AS DEEMED NECESSARY.
600
U/G OPTICAL FIBRE CABLE D MECHANICAL PROTECTION/
600 5. THE BACKFILL MATERIAL AT ROADWAYS, DRIVEWAYS AND FOOTPATHS SHALL BE AP40 AGGREGATE AND MECHANICALLY
MECHANICAL PROTECTION/ 70
HARD-COVER COMPACTED DURING INSTALLATION. FOR DIRECT BURIED CABLES, FRIABLE SOIL SHALL BE USED WITHOUT ANY SHARP
100
HARD-COVER STONES.
100
LV/MV CABLE D 6. THE FINE SAND USED SHALL MEET THE REQUIREMENTS STATED IN DOCUMENT "SPECIFICATION FOR BEDDING SAND USED
LV/MV CABLE D
SAND 70 FOR UNDERGROUND CABLING WORKS".
SAND 70 7. THE CABLE DEPTH FROM GROUND LEVEL HAS BEEN OBTAINED TO ACHIEVE MAXIMUM CURRENT CARRYING CAPACITY.
500 8. THE HARD COVER/ MECHANICAL PROTECTION USED SHALL MEET THE REQUIREMENTS OF AS 4702.
500 9. THE HEP TAPE (MARKER) USED SHALL MEET THE REQUIREMENTS OF AS/NZS 2648.1.
10. THE AP40 BASECOURSE, AP65 SUB-BASE AGGREGRATE AND ENGINEERED FILLING DEPTHS WILL DEPEND ON THE MAXIMUM
ALLOWABLE BURYING DEPTH OF EFL UNDERGROUND POWER CABLES. THE POWER CABLE DEPTHS CAN BE OBTAINED FROM
SHEETS 1 & 2 OF THIS DRAWING. IT IS NECESSARY THAT THE CABLE BURYING DEPTH BE FOLLOWED TO OBTAIN THE
FIJI ROADS AUTHORITY (FRA) - SERVICE TRENCH REQUIREMENTS ACROSS ROADS MAXIMUM CURRENT CARRYING CAPACITIES.
11. THE TRENCH STEP/BENCH LAYOUT SHALL BE MAINTAINED FOR ALL ROAD CROSSINGS.
SURFACING DEPTH TO BE CONFIRMED BY FRA DEPENDING ON
12. THE BEDDING MATERIAL FOR ALL ROAD CROSSING TRENCH SHALL BE FINE SAND COMPLYING TO EFL REQUIREMENTS AS
SITE LOCATIONS MENTIONED ON NOTE # 6.
13. WHERE INCONSISTENCIES ARE IDENTIFIED, EFL SHALL BE CONTACTED FOR RESOLUTION.
AP40 AGGREGATE COMPACTED TO 98% MMDD TO
AS 1289 (REFER TO NOTE # 10)

AP65 AGGREGATE COMPACTED TO 95% MMDD TO


AS 1289 (REFER TO NOTE # 10)

ENGINEERED FILL FREE OF SOIL AND DELETORIOUS


SUBSTANCE, COMPACTED TO 95% MMDD TO AS 1289
(REFER TO NOTE # 10)

EFL UNDERGROUND POWER CABLES (33kV, 11kV


240/45V). BEDDING TO BE FINE SAND COMPLYING TO
EFL REQUIREMENTS (REFER TO NOTE # 12 )

200 200 200 200


MIN. MIN. MIN. MIN. 500

TRENCH STEP/BENCH LAYOUT


(REFER TO NOTE # 11) SHEET 3 OF 3