Professional Documents
Culture Documents
Schonknecht 2003
Schonknecht 2003
2, MARCH/APRIL 2003
(1)
(2)
where
This equation can be simplified if all resonant inductances This means that the distribution of the total power among
have the same value the single inverters is primarily determined by the design of the
resonant inductors .
if (9) The measurements shown in Fig. 5 validate (10). It shows
output voltages and currents of two parallel-connected
inverters switching simultaneously at resonant frequency
B. Hybrid Simulator kHz. The operation point is specified in Table II (see also
To validate analytical and simulation results, as well as to Table I for LCL parameters). According to (10), the output cur-
prove the practicality of the proposed topology, a hybrid sim- rent (inverter 2) is twice (inverter 1), because the reso-
ulator, shown in Fig. 4, with a scaled working point was con- nant inductance (inverter 1) is twice (inverter 2). Fur-
structed. At the top of the rack, a model inductor is installed. In- thermore it is interesting that both output currents are in phase.
side this inductor, a water-cooled metal pot is mounted for heat Thus, the output current, respectively, the power throughput of
sinking. The control units are mounted in the front of the rack, the inverters can be adjusted individually.
with the power electronic components at the backside. Eupec
IGBT modules, type BSM50GB60 DLC, dc-current of 50 A (at D. Nonsynchronous Switching
80 C), were installed.
Up to now, the behavior of the system has been investigated
The parallel connection of five high-frequency inverters was
for ideal, i.e., simultaneous, switching of the inverters. De-
successfully tested with this hybrid simulator. The parameters
pending on the applied control scheme, simultaneous switching
of the hybrid simulator, used in all measurements presented in
cannot be guaranteed for all working points. Consequently, the
this paper, are listed in Table I.
system behavior during nonsynchronous switching has to be
C. Partitioning of the Power Throughput investigated.
The plots in Figs. 6 and 7 show measurement results of the
With a suitable design of the resonant circuit parameters, the hybrid simulator confirming (10), at the operating point speci-
voltage at the resonant capacitor is substantially higher fied in Table III. The crucial result of this investigation is that
than the voltage at the dc link , if the system is operated at the output currents of both inverters are nearly in phase and
(see Fig. 2). As a result, the output current of each inverter have nearly the same amplitudes despite the nonsynchronous
and, thus, its power, is not determined by the switching behavior switching. Only if there exists a large phase lag between the
of the inverters, but by the ratio . The following formulas output voltages of different inverters (see Fig. 7), the output
illustrate this behavior: currents differ visibly from each other. Obviously, there is no
if shunt current between different inverters due to nonsynchronous
switching.
TABLE II
OPERATING POINT SHOWN IN FIG. 5
TABLE I
PARAMETERS OF HYBRID SIMULATOR
Fig. 7. Measured switching behavior of two parallel-connected inverters Fig. 8. Currents and voltages of two inverters with different dc-link voltage.
during nonsynchronous switching with a phase lag of 90 .
TABLE IV
OPERATING POINT SHOWN IN FIG. 8
TABLE III
OPERATING POINT SHOWN IN FIGS. 6 and 7
F. Redundancy
At industrial assemblies with a power demand in the
megawatt range, the system availability is of particular interest.
To achieve high reliability, it is desirable that operation with
possibly reduced power is ensured, even if one or more inverters
of the system are out of order.
The straightforward way to continue operation is to discon-
nect the defective inverter from the dc link and the resonant ca-
pacitor. In this case, one has to take the detuning of the LCL
circuit into consideration, especially if only a small number of
Fig. 9. One of two inverters is turned off.
inverters is connected in parallel.
Furthermore, it is interesting to investigate what happens if an
inverter, which is turned off, remains connected at the ac and dc TABLE V
OPERATING POINT SHOWN IN FIG. 9
sides. Fig. 9 shows a plot of this situation. The operation point
is specified in Table V. The inverter turned off transmits energy
from the LCL circuit back to the dc link via the freewheeling
diodes of its power semiconductors. Thus, an inverter turned off
operates “against” the running inverters. In Fig. 9, the running
inverter 1 represents three inverters feeding into the LCL circuit,
as its resonant inductor has an inductance , which is three
times smaller than inductance of the turned-off inverter 2.
Hence, as long as and if all resonant inductors have
the same inductance for all inverters), an inverter verter operating in forward mode back from the LCL circuit into
which is turned off feeds the same amount of power of an in- the dc link.
SCHÖNKNECHT AND DE DONCKER: PARALLEL CONNECTION OF SOFT-SWITCHING HIGH-POWER HIGH-FREQUENCY INVERTERS 555
The total power fed into the LCL circuit is determined by the power at frequencies, from about 10 kHz up to the megawatt
following formulas: range. Depending on the frequency and the dc-link voltage, ei-
ther MOSFETs or IGBTs have to be applied.
if (12)
REFERENCES
[1] S. Dieckerhoff, M. J. Ryan, and R. W. De Doncker, “Design of an IGBT-
where based LCL-resonant inverter for high-frequency induction heating,” in
Conf. Rec. IEEE-IAS Annu. Meeting, 1999, pp. 2039–2045.
equivalent inductance of resonant inductor; [2] H. Rüedi and H. G. Matthes, “1.6 MW/150 kHz inverter for welding
number of inverters turned on; applications,” presented at the Power Conversion Conf. (PCIM2000),
number of inverters turned off. Nürnberg, Germany, June 2000.
[3] H.-C. Doht, G. Birk, and G. L. Fischer, “Control mode for inverters with
The total power fed into the LCL circuit is calculated with (6) resonance transformation in induction heating applications,” in Proc.
Power Conversion Conf., June 1994, pp. 57–67.
[4] J. Nuns, S. Legac, and M. Gillot, “High frequency transformers for in-
(13) duction heating,” in Proc. Int. Induction Heating Seminar (IHS), 1998,
pp. 35–45.