GENERAL NOTES:

1.0 WIRING SHALL BE COLOR CODED


4 LINE 01 - RED 1. SERVICE VOLTAGE SHALL BE 220 VOLTS 1-PH, 3 WIRE
LINE 02 - BLACK 2. WIRING METHOD SHALL BE POLYVINYL CHLORIDE (PVC) FLEXIBLE
400 920 920 920 400
GROUND - GREEN CONDUIT UNLESS OTHERWISE SPECIFIED.
CONTROL WIRE - WHITE, YELLOW & BLUE 3.

720
500 500
1
2.0

370
INSULATED FOR 600V.

720
2 SHALL BE USED, INSULATED WITH RUBBER AND PLASTIC TAPES.

350
4. NO BRANCH CKT SHALL HAVE LOAD OF MORE THAN 80% OF ITS

680
750
DL

400
920 920 920 390
650
3.0 CIRCUIT BREAKERS TO BE PROVIDED SHALL BE COMMON TRIP TYPE RATING.

1370
700 700 700

1050
1050 1050 1050
780
4.0 ALL CONDUITS EXPOSED ABOVE CEILING SHALL BE FIRMLY 5. CIRCUIT BREAKERS SHALL BE "GE" OR WESTINGHOUSE OR "FUJI" BRAND

1000

880
OR APPROVED EQUAL. ALL CIRCUIT BREAKERS SHALL BE BOLT ON

1020

1020
500 500 500 SUPPORTED

1200
670
420 a
TYPE.
@ 50cm O.C. WITH CLAMPS AND HANGERS / CABLE TIES.

450

1450
6. MOUNTING HEIGHT SHALL BE AS FOLLOWS:

880
670
780
5.0 ALL ROUGH-INS SHALL BE DONE PARALLEL TO THE

1020

1020
500
700 700 700
820 820 a. LIGHT CONTROL SWITCH-1.40M ABOVE FLOOR @ CENTER
WALLS/BEAMS

500
820 b. CONVIENIENCE OUTLET-0.30M ABOVE FLOOR @ CENTER, EXCEPT FOR

820
AND NOT IN CRISS-CROSS MANNER. CO'S INSIDE BATHROOM @ 1.40M ABOVE FLOOR, AND FOR KITCHEN

0
500

99
1020
940

60

1240

1240
CO'S @ 0.15M FROM COUNTER TOP.

11
6.0 UPON COMPLETION OF ELECTRICAL WORK, THE FOLLOWING

820

570
1630

a. PANEL BOARD - 1.50M ABOVE FLOOR @ CENTER

1070

0
SHALL BE

99
1020

80
450
PERFORMED BY THE ELECTRICAL CONTRACTOR. b. SPECIAL PURPOSE- AS REQUIRED BY EQUIPT. SERVED OUTLET

820
630

11

1240

1240

0
A. INSULATION RESISTANCE (MEGGER) TEST

99
1000 1000

400
1720
B. GROUNDING SYSTEM CHECK. ALL WORKS HEREIN SHALL COMPLY WITH THE PROVISIONS OF LATEST
1630

400
820 820 400 500 1180
C. OPERATIONAL TEST APPROVED EDITION OF THE PHILIPPINES ELECTRICAL CODE, AND THE
D. LOAD TEST RULES AND REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITY
920 920 7.0 UPON TURN OVER OF THE PROJECT, THE CONTRACTOR SHALL CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND
5 SUBMIT ORDINANCES AND WITH THE REGULATIONS OF THE UTILITY COMPANY
THREE(3) COPIES OF AS-BUILT PLANS AND ONE(1) CONCERNED.
ELECTRONIC FILE
TO THE PROJECT MANAGER DULY SIGNED AND SEALED BY A ALL MOUNTING HEIGHTS ARE SUBJECT TO THE ARCHITECT'S APPROVAL PRIOR TO THE
PROFESSIONAL ELECTRICAL ENGINEER. INSTALLATION.

LOWER GROUND SECOND FLOOR

1 3
A-1 SCALE 1:100 MTS. A-1 SCALE 1:100 MTS.

1360 2-22SQ.MM THHN

400
1-8SQ.MM. TW WIRE
IN 25 MM DIA. RSC PIPE

1200

1200
830 830 400
820

400
3
840

840

1120
630 MECO A
820

710
KWHR Meter
840

840

500
450
570

1120
820

6
400

830 830
400

400

780 920 920


Circuit Breaker
1P-100AT-100AF Grounding Rod
Copperweld 3/4 x 10'
OUTDOOR DISCONNECT
NEMA 3R

UPPER GROUND ROOF DECK

2 4 5
A-1 SCALE 1:100 MTS. A-1 SCALE 1:100 MTS. E-1 NOT TO SCALE

ELECTRICAL ENGINEER / MASTER ELECTRICIAN: PROJECT NAME & LOCATION: SHEET CONTENT: REVISIONS: APPROVED BY: SHEET NO.:
LIGHTING LAYOUT
METER DETAIL
GENERAL NOTES

E-1
Block 4 Lot 49, Sierra Vista Subd. Brgy. Nagkaisang Nayon,
PRC NO.: PTR NO.:
Novaliches Quezon City 7 11
T I N: ISSUED: