Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Important work deserves the best tools

Three things are required for advanced balancing: plant. Thirdly, a smart balancing procedure that
Firstly, balancing valves that can adjust the flow enables you to quickly and efficiently work towards a
with high accuracy. They shall be easy to set and to good result.
read. Secondly, reliable measuring instruments that We can offer you all these, plus sound knowledge
will provide you with clear and unambiguous infor- about balancing that you can share through manuals,
mation concerning the flows and pressure drops in the seminars and courses.

STAD TA-CBI
With TA balancing valves TA-CBI measures differential pres-
STAD/STAF you obtain the sure, water flow and temperature.
correct distribution of water flows One person using a TA-CBI loaded
in heating and cooling installa- with the TA Balance program can
tions. They include test points for balance even large installations.
measuring differential pressure You can use TA-CBI to balance and
and flow, and permit easy shut- document the flows during com-
off and draining. missioning, check the flows dur-
ing inspection,as a diagnostic aid
to solve operating problems and
for logging.

STAP Total Hydronic Balancing


STAP differential pressure con- Total Hydronic Balancing is our
troller maintains a constant differ- comprehensive manual about
ential pressure across the circuit, hydronic heating and cooling
regardless of the variations on installations. Here you will find
the primary side. It offers the advice on planning systems for
same shut-off and draining facil- precise control and the best
ities as the STAD/STAF units. operating conditions.

BPV TA Select
BPV is an automatic proportional Our TA Select, TA Calc
relief valve which stabilises the TA Monoplus and TA Shunt com-
differential pressure for better puter programs help you to cal-
control. culate the parameter values that
ensure the most economical
design on the basis of defined
system requirements.

www.tourandersson.com

www.tourandersson.com

Australia Great Britain Singapore Sweden (Parent Company)


Tour & Andersson Tour & Andersson LTD Tour & Andersson PTE LTD Tour & Andersson AB
PO Box 154 42 Coldharbour Lane 171 Chin Swee Road SE-524 80 LJUNG
HIGHETT Vic 3190 HARPENDEN, Herts AL5 4UN #05-01 an Centre Tel Int +46 513 540 00
Tel 9553 3366 Tel 01582 76 79 91 SINGAPORE 169877 Telefax Int +46 513 508 44
Telefax 9553 3733 Telefax 01582 76 92 30 Tel+65 65 32 06 26
Telefax+ 65 65 32 29 19

M-020 GB
1997.12
The three hydronic conditions for accurate control
Why you must fulfil them and the easiest way to do it
TA brings you total system knowledge based on experience
from more than 100,000 hydronic heating and cooling plants around the
world. Some of our knowledge is available to you through this brochure.
You can access more knowledge by contacting us to order more infor-
mation. Or visit our web site, www.tourandersson.com
There are three hydronic conditions for accurate control
And just one way to fulfil them

Two fundamental requirements are demanded of incorrectly implemented balancing calculations to


every heating and cooling installation. pure assembly mistakes such as check valves
The first is that the installation shall provide the installed the wrong way round, or blocked filters.
best possible indoor climate. The second is that it During the balancing procedure you can immedi-
shall do this at the lowest possible energy cost. ately see the effect of disturbances, find the reasons
Today’s advanced control technology means that for them and take corrective measures. You are
it is possible to achieve both goals. At least in theory. ensuring that the installation has the best possible
In practice however, the most sophisticated con- chance of providing optimum comfort at the lowest
trollers don’t always keep their promises. The result energy cost.
is a lower comfort level and higher operational costs This brochure summarises our expertise concern-
than expected. ing the three hydronic conditions. What symptoms
The reason this happens is that these controllers indicate that the conditions are not being fulfilled?
are not being allowed to do their job. And they can What are the underlying reasons for this? And what
only work properly if all three hydronic conditions is the best way of solving the problem?
for accurate control are fulfilled: Feel free to use this information when you are
1. The design flow must be available at all fault tracing, or the next time you carry out an
terminals. installation.
2. The differential pressure across control valves
must not vary too much.
3. Flows must be compatible at system interfaces.
Performing a balancing procedure is the very best
way to fulfil these three hydronic conditions.
First and foremost balancing ensures that the plant
does actually perform in accordance with its specifi-
cations, operating in the way the designer intended.
Balancing reveals and removes a number of threats
to the installation’s functions. These may range from
CONDITION 1

The design flow must be available at all terminals

The first condition for stable and accurate control is in certain circuits from causing underflows in others,
that the design flow is available at all terminals. detects possible oversizing of pumps and verifies that
Hydronic balancing is necessary for this condition to the plant actually does provide the functions and per-
be fulfilled. Hydronic balancing prevents overflows formance intended by the designer.

Symptoms indicating Common, and


Typical, and usually
that the condition is not incorrect, Correct solutions Advantages
neglected, root causes
fulfilled counter measures

Too hot in some parts of Increase pump head Overflow in some cir- Balance distribution The power installed is
the building, too cold in (main or secondary cuits create underflow system using deliverable
other parts pump head) in others STAD/STAF balancing
valves Correct room tempera-
tures at optimized
No balancing of circuits energy cost
downstream of ∆p con-
troller Shortest possible start
up time after night
setback

Balancing identifies
Long time before all Increase supply tem- Overflow in some Balance circuits down- hydronic problems
rooms reach correct perature (heating). circuits create under- stream of ∆p controller which can be solved at
temperature after night Reduce supply temper- flow in others an early stage
setback ature (cooling) Balance distribution
No balancing of circuits system using Flows are verified
downstream of ∆p STAD/STAF balancing anddocumented
Cancel the night set- controller valves
back function Possibility to minimize
pump energy
consumption

Possibility to measure
and logg the flow and
Abnormal pump energy Oversizing of pump Balance the plant with detect problems
consumption STAD/STAF to reveal
actual pump oversizing

Change pump
Example: Restart after night setback is a critical
situation in a system with variable flow.

In a distribution system with variable flow, underflow after a night setback. Then, most of the control valves
mainly occurs under heavy loading. begin by opening fully. This creates overflows that in
At first glance it may appear that there is no reason turn give rise to unpredictable pressure drops the pip-
to balance a system with two-way control valves at ing system, and underflows in unfavoured areas in the
the terminals, since the job of the valves is to adjust system.
the flow to the requirement. Balancing should there- The less fortunate circuits do not receive sufficient
fore be done automatically. flow until the favoured areas have reached their
However, one finds that, despite careful calcula- respective thermostat’s set point, causing their control
tion, control valves with exactly the required Kv- valves to start controlling.
value are not commercially available, with the result The restart becomes difficult, and takes longer
that most control valves will be oversized. than expected, which result in higer energy costs. An
There are many situations where fully open control uneven restart makes centralised control and all
valves cannot be avoided, such as when restarting forms of optimisation virtually impossible.

An unbalanced plant must start ear-


lier, which results in higher energy
costs.
CONDITION 2

The differential pressure across control valves


must not vary too much
The second condition for stable and accurate control filled. Hydronic balancing is in addition the only way
is that the differential pressure across the control to find and resolve the real reasons behind operational
valves in the plant must not vary too much. Hydronic problems in the plant.
balancing is necessary for this condition to be ful-

Symptoms indicating Common, and


Typical, and usually
that the condition is not incorrect, Correct solutions Advantages
neglected, root causes
fulfilled counter measures

Supply air temperature Modify control software Plant not balanced Balance the plant using Stable and accurate
or room temperature although it is a hydronic STAD/STAF balancing temperature control
fluctuate problem Control valve authority valves or STAP ∆p con-
is too low trollers Low energy cost
Replace correctly sized No noise problems
but hunting control Wrong control parame-
valves by smaller ones ters Balancing identifies
hydronic problems
Control valve oversized which can be solved at
an early stage
Flows are verified and
documented
Noise from control Replace control valves Differential pressure Limit ∆p variations using
valves varies too much STAP ∆p controllers Possibility to measure
and log the flow and
detect problems
Example: Stabilization of the differential pressure across
individual control valves with STAP.

The relationship between the highest and the low- exceed four. The control valve, therefore, has a dif-
est differential pressure across a control valve ficult time doing its job. Then it is suitable to let a
should not be greater than four. In other words, the local differential pressure controller stabilize the
valve authority (the lowest differential pressure differential pressure across the control valve.The
divided by the highest differential pressure) should principle is simple. The membrane in the STAP dif-
be at least 0.25. ferential pressure controller is connected to the
In a plant with two-way control valves and vari- inlet and outlet of the control valve. When the dif-
able flow, you can improve the valve authority with a ferential pressure increases, the force acting on the
variable speed pump. When a control valve closes, membrane also increases, closing the STAP propor-
the flow in the circuit decreases. Therefore, the tionally. STAP maintains the differential pressure
pressure drop in terminals, pipes and accessories across the valve constant. The control valve will
decreases, resulting in an increase in differential never be overdimensioned, and the valve authority
pressure across the control valve. But at the same becomes 1.
time, the pump reduces the speed (the pressure) to
compensate for the reduced flow requirement in
the plant. That limits the difference between the
highest and the lowest differential pressure across Limiting ∆p and
flow through a con-
the control valve. STAM STAP trol valve.
But in some circuits, the difference between the
highest and the lowestdifferential pressure can still a

Example: Stabilisation of the differential pressure across


a group of control valves with STAP.

STAP can also be used in heating plants to control STAP maintains the differential pressure constant
groups of radiators so that the total flow in the com- in each branch or minor riser. The flow in the branch
plete branch system will be correct. This confirms (qs) is measured using a STAM measuring valve.
the pre-setting of the radiator valves and the differ-
ential pressure of 10 kPa can be expected to apply at
the centre of the branch.
STAM
qS
In radiator systems with available differential
pressures exceeding 30 kPa, there is a great risk of
∆Hmax ∆Ho =10 kPa ∆Hmin
noise in the plant, especially if there is air in the ∆Hp
qR

water.
In this case you can use STAP to reduce the dif- STAP
STAP maintains a constant differential
ferential pressure and to keep it constant. pressure at the circuit inlet.
CONDITION 3

Flows must be compatible at system interfaces

The third condition is that the flows must be com- balancing procedure helps to localise and resolve
patible at system interfaces. Hydronic balancing is hydronic problems. It also reveals any possible over-
necessary for this condition to be fulfilled, so that the sizing of pumps and helps to reduce pumping costs.
installed power in the plant can be delivered. The

Symptoms indicating Common, and


Typical, and usually
that the condition is not incorrect, Correct solutions Advantages
neglected, root causes
fulfilled counter measures

Maximum installed Increase secondary Secondary maximum Balance the plant and SInstalled power is
power is not deliverable pump head flow not compatible with ensure flow compatibility deliverable
when required primary maximum flow throughout the plant
Install more production using STAD/STAF Correct room tempera-
units balancing valves tures at optimized energy
cost
Increase supply temper- Balancing identifies
ature (heating). Reduce hydronic problems
supply temperature which can be solved at
(cooling) an early stage
Flows are verified and
Long time before all Increase secondary Secondary maximum Balance the plant and documented
rooms reach correct pumphead flow not compatible with ensure flow compatibility
Possibility to measure
temperature after night primary maximum flow throughout the plant
and logg the flow and
setback Install more production using STAD/STAF bal-
detect problems
units ancing valves
Short start up time
Increase supply temper-
ature (heating). Reduce
supply temperature
(cooling)

Cancel the night set-


back function
Example:
Heating plant based on a boiler.

The plant in our example consists of a boiler that is The situation is however made worse if the plant
fed by a pump and a distribution circuit that oper- has not been balanced, as there will be excessive
ates with a constant flow. overflow in the radiators closest to the pump. Since
If the flow through the distribution circuit is the pressure drop in the piping will be much greater
greater than the flow through the boiler, the surplus than nominal, the most distant radiators will operate
will pass into the by-pass AB in the direction B to A. least efficiently, as they will neither receive sufficient
Water from the boiler will then be mixed with the water nor a sufficiently high water temperature – the
distribution circuit return water in A and the tem- room temperature will inevitably fall.
perature in the circuit’s supply water will be lower
than the boiler water temperature (tgs).
Under partial load this does not matter, since the
water temperatures are lower. However, under full
load, such as when starting up the plant in the morn-
ing, full power cannot be achieved since water tem-
perature cannot reach its nominal value. Thus the
power output from the boiler will not be fully trans-
ferred to the distribution circuit.
If the radiators are balanced to have equal over-
flows the result may be acceptable even if the The flows are compatible between the boiler
desired temperature cannot be attained. and the distribution circuit.

Example: Cooling plant with constant flow distribution system.

The terminals are controlled by means of three-way water temperature and the installed power will not be
valves. The water flow that does not pass through the transferred. With 50 percent overflow in the distribu-
terminals goes instead through the shunt loop and so tion at maximum load it will only be possible to pro-
the total water flow is held constant. vide 90 percent of the installed power.
If the circuit contains several parallel-connected
refrigeration units the design cooling temperature
STAM
qS
can only be maintained if all the refrigeration units
are kept in operation.
If the distribution circuit is not balanced and has an ∆Hmax ∆Ho=10 kPa ∆Hmin
∆Hp
overflow, this will give rise to a flow through the by- qR

pass from B to A, despite all refrigeration units being


in operation, which generates a mixing point at M. In STAP
The production flow can vary, while
this case it is impossible to maintain the nominal cold the distribution flow is kept constant.
Simple, effective and
accurate balancing with TA Balance.

Balancing is absolutely necessary in order to fulfil Preparations save time and unnecessary work
the three hydronic conditions for good control. Careful preparation, both in the office and at the
Unfortunately many people mistakenly believe plant, is the key to a simple, efficient and rapid
that balancing is difficult and time-consuming, balancing process. Hence you begin at the drawing
especially in larger installations. board:
With our TA-CBI balancing instrument and TA – Study the drawings.
Balance computer program it is easy to balance a – Identify the main, riser and branch piping and
complete installation. equipment.
Here is a general description of a typical balanc- – Divide the plant into modules. You can read how
ing sequence. to do this in our manual “Balancing distribution
systems”.
It all starts with careful calculation – Check that the flow for each balancing valve is
Designers should provide accurate information to stated on the drawings, and that the design flow
allow simple and precise balancing. The desired for each riser is equivalent to the sum of the
flow for each balancing valve always has to be design flows for the branches, etc.
noted on the drawings. In addition, kv-values
and/or preset values can be included. This facili- The preparations continue into installation:
tates presetting of the balancing valves during – Locate all the balancing valves and ensure that
installation. they are accessible.
However careful the calculations may have been – Clean all filters and deaerate the plant.
at the design stage, some adjustments will always – Open all the shut-off valves that should be
be required when the installation has been complet- open and open all the control valves.
ed. Equipment is not always installed precisely in – Ensure that the pumps operate properly and
accordance with the drawings. Changes affect the rotate in the correct direction.
flows. The actual flow values and any alterations
that have been made should be noted in the final
commissioning report.
TA Balance is a computer program in the TA-CBI. The program permits just
one person with a TA-CBI to balance even very large plants.

One person, one TA-CBI and TA Balance get When you have entered the desired flows for all
the job done the valves in the module, the CBI calculates the
At the plant you then follow these simple steps: correct settings for the balancing valves. Instantly.
1. Select a module, it does not matter which. All you have to do then is to set each balancing
Choose any balancing valve in the module. valve in accordance with the CBI data.
2. Measure the differential pressure with the CBI at When you have finished balancing the first
the currently set valve position. module, go on to the next. If you want to keep a
3. Close the valve completely. Measure the differen- complete record of the measurements, go all round
tial pressure again. Then re-open the valve to the the plant and measure the flow in each valve. Then
same position as before. you just have to transfer the measured data from
4. Enter the required flow for the valve into the CBI. the CBI to your PC back in the office, and print
5. Repeat steps 2 to 4 inclusive for the other out a neat record page.
balancing valves in the module.

You might also like