Instruction Manual
Plate Condenser
AlfaCond 400/600/800
Table of contents
UK
Description ....................................................................................... 1
Main components ..................................................................... 1
Function .................................................................................... 2
Installation ........................................................................................ 3
Requirements ........................................................................... 3
Lifting ........................................................................................ 4
Operation .......................................................................................... 5
Start-up ..................................................................................... 5
Unit in operation ........................................................................ 6
Shut-down ................................................................................. 6
Maintenance ..................................................................................... 7
Cleaning-In-Place (CIP) ............................................................ 7
Manual cleaning ........................................................................ 8
Regasketing ............................................................................ 15
Plate condenser UK
Description English
Description
UK
Main components
Carrying bar
Carries the cassettes and Support
Frame plate the pressure plate. column
Tightening bolts
Press the cassettes
together.
Bolt
protection
Connections
Holes through the frame
plate, permitting the
media to enter into the
plate condenser.
Pressure plate
Moveable steel plate.
Cassettes
Heat is transferred from one medium to
the other through the thin plates.
Protective sheets
Supplied on request.
Plate condenser UK 1
English Description
Function
UK
AlfaCond consists of a plate pack with plates The plate pattern is specifically designed for
welded together in pairs forming so-called optimal condensation, with an asymmetric config-
cassettes. uration that features a large gap on the vapour
side and a small gap on the cooling water side.
The cassette concept gives rise to two different This makes it possible to maintain a very low
type of channels - welded channels used for the pressure drop on the velocity and turbulence on
condensing vapour and gasketed channels used the water side. This maximizes the heat transfer
for the cooling water. efficiency and minimizes fouling.
UK 2 Plate condenser
Installation English
Installation
UK
Requirements
Vapour
Space
1500 mm minimum free
space is needed for lifting
plates in and out.
Vent gases
Foundation
Shut-off valves Install on a flat foundation
Shut-off valves should be giving enough support to
provided in the two cooling the frame.
water connections.
Condensate
Note! Safety valves should be installed according to
• Before connecting any piping, make sure current pressure vessel regulations.
all foreign objects have been rinsed out of
the system. If the plate condenser surface temperature is
• When connecting the pipe system make expected to be hot or cold, the condenser should
sure the pipes do not subject the plate con- be insulated.
denser to stress or strain.
• To avoid water hammer, do not use fast- It is recommended that protective sheets are
closing valves. used to cover the plate condenser.
Plate condenser UK 3
English Installation
Lifting
UK
Warning!
Never lift by the connections or the studs
around them. Straps should be used when
lifting. Place straps according to picture.
UK 4 Plate condenser
Operation English
Operation
UK
Start-up
Note! If there is a valve at the exit, make sure it
Adjustments of cooling water flow rate 3 is fully open.
should be made slowly in order to avoid the
Start the cooling water pump.
risk of water hammer.
4
Water hammer is a shortlasting pressure
peak that can appear during start-up or
Open the valve slowly.
shut-down of a system, causing liquids to
travel along a pipe as a wave at the speed 5
of sound. This can cause considerable
damage to the equipment.
Open slowly
2
Check that the valve is closed between the
pump and the cooling water inlet
6
If there is a valve in the condensate outlet,
.
7 make sure it is fully open.
Closed
Plate condenser UK 5
English Operation
Close
UK 6 Plate condenser
Maintenance English
Maintenance
UK
Cleaning-In-Place (CIP)
The Cleaning-In-Place (CIP) equipment permits The following Alfa Laval-CIP models can be used:
cleaning of the plate condenser without opening it. CIP75, CIP200, CIP400 and CIP800.
CIP performs
Cleaning liquids
AlfaCaus A strong alkaline liquid, for removing paint, fat, oil and biological deposits.
AlfaPhos An acid cleaning liquid for removing metallic oxides, rust, lime and other
inorganic scale.
AlfaPass An alkaline liquid for passivation (inhibition of corrosion).
AlfaNeutra A strong alkaline liquid for neutralization of AlfaPhos before drainage.
Alfa P-Scale An acidic cleaning powder with a corrosion inhibitor particularly effective
for removing of calcium carbonate and other inorganic scale.
Alfa P-Neutra An alkaline powder for neutralization of used Alfa P-Scale prior to dis-
posal.
AlfaAdd A neutral cleaning strengthener to be used with AlfaPhos, AlfaCaus and
Alfa P-Scale. Provides better cleaning results on oily, fatty surfaces and
where biological growth occurs. AlfaAdd also reduces any foaming.
Alpacon Descalant An acidic, water based, non-hazardous cleaning agent designed for
removal of scale, magnetite, algae, humus, mussels, shellfish, lime and
rust. Containing BIOGEN ACTIVE, a biological mixture made from renew-
able materials, as an active ingredient.
Alpacon Degreaser A neutral degreaser to be used with Alpacon Descalant. Effectively
removes oil, fat or grease layers, but also reduces foaming. Containing
BIOGEN ACTIVE, a biological mixture made from renewable materials,
as an active ingredient.
Plate condenser UK 7
English Maintenance
Manual cleaning
UK
Warning! Opening
To avoid hand injuries owing to sharp edges,
protective gloves should always be worn Warning!
when handling cassettes and protective If the plate condenser is
sheets. hot, wait until it has cooled
down to about 40 °C
(104 °F).
Mark
UK 8 Plate condenser
Maintenance English
Measure and note down the dimension A. The pairs of bolts that are fitted with bear-
4 6 ing boxes are opened alternately and diag-
UK
onally in two steps, see figures below.
Remove
the bolts
Remove
the bolts
Step 2: Loosen the two diagonal pairs of
bolts are loosened alternately, as shown in
the figure below.
Plate condenser UK 9
English Maintenance
Remove
the cassettes
UK 10 Plate condenser
Maintenance English
UK
Caution! Note!
Never use hydrochloric acid with Be careful not to damage the gasket dur-
stainless steel plates. Water of more ing manual cleaning.
than 330 ppm Cl may not be used for
the preparation of cleaning solutions.
Plates need not to be removed from the plate condenser during cleaning.
Remove deposits using a soft brush and Rinse with water using a high pressure
1 running water. 2 hose.
Plate condenser UK 11
English Maintenance
Concentration max 4%
Temperature max 60 °C (140 °F)
Caution!
The following solutions should not be used:
• Ketones (e.g. Acetone, Methyletylke-
tone, Methylisobutylketone
• Esters (e.g. Ethylacetate, Butylacetate)
• Halogenated hydrocarbons (e.g. Chlo-
rothene, Carbon tetrachloride, Freons)
• Aromatics (e.g. Benzene, Toluene).
UK 12 Plate condenser
Maintenance English
Closing
UK
Check that all the sealing surfaces are Press the plate assembly together. Tight-
1 clean. 5 ening is done in two steps, see figures be-
low. Be careful so that the frame plate and
the pressure plate are always in parallel.
Brush the threads of the bolts clean, using
2 a steel wire brush. Lubricate the threads
with a thin layer of grease, e.g. Gleitmo
Step Bolt No. To dimension
Note!
If the gasket is wrongly positioned, it will
show by the fact that it rises out of the gas-
ket groove or that it is positioned outside
the groove.
Plate condenser UK 13
English Maintenance
Note!
When a pneumatic tightening device is used,
see table below for maximum torque. Meas-
ure dimension A during tightening.
UK 14 Plate condenser
Maintenance English
Regasketing
UK
Open the plate condenser according to
1 page 8.
Glued gaskets
Separate gluing instructions will be deliv-
2 ered together with the glue. Glued
gaskets
Clip-on gaskets
Close the plate condenser according to
3 page 13.
Clip-on
gaskets
Note!
Make sure the two gasket prongs are in
correct position.
Plate condenser UK 15