Recloser Current transformer Accuracy testing

• U Series CT : 2000/1,1VA,0.2 class, FS15 For Metering and protection

• RL Series CT: 2000/1, 1VA, 0.1 class , FS15 For Metering

CPRI Bangalore
21-08-2017
1
Accuracy test requirement:
U Series CT : 2000/1,1VA,0.2 class, FS15 For Metering and protection

i. Accuracy Test for Metering class

ii. Accuracy test for Protection class

@ 800A @ 800A
@ 8000A & 16000A

RL Series CT: 2000/1, 1VA, 0.1 class , FS15 For Metering

i. Accuracy Test for Metering class

Confidential Property of Schneider Electric 2


Results:
1. U series : U01-180, Rev 0
i. Metering
Ipr=2000A 5% 20% 100% 120%
% Current error 0.183 0.12 0.091 0.089
Phase displacement
error 5.7 2.5 1.3 1.3

ii. Protection
Test for composite error of class P and PR protective current transformers : Indirect Method
For low-leakage reactance current transformers according to Annex 2C, the direct test may be replaced by the following indirect test. With the
primary winding open-circuited, the secondary winding is energized at rated frequency by a substantially sinusoidal voltage having an r.m.s.
value equal to the secondary limiting e.m.f. EALF.The resulting exciting current, expressed as a percentage of I × ALF shall not exceed the
composite error limit given in Table 205. The exciting voltage shall be measured with an instrument which has a response proportional to the
average of the rectified signal, but calibrated in r.m.s..

% Composite error
Ipr=2000A R in Ω @ 26°c R in Ω @ 75°c Zs in Ω ALS=ALFx1s Vn=ALSxZs
(Ie/ALS)x100
% Current error 7.737 9.189 10.19 10x1 101.9 Ie=4.03mA: 0.04%

The Composite error is 0.04% at ALF = 10 which is equal to 20kA Primary current for Ipr=800A , the equivalent ALF= 25

Confidential Property of Schneider Electric 3


2. RL series : RL2-193, Rev C

i. Metering
Ipr=2000A – PH-L3 5% 20% 100% 120%
% Current error 0.036 0.001 0.001 0
Phase displacement
error 3.3 2.3 1.6 1.5

Ipr=2000A – PH-L1 5% 20% 100% 120%


% Current error 0.117 0.088 0.076 0.077
Phase displacement
error 5.7 3.9 2.6 2.5

ii. Protection
% Composite error
Ipr=2000A R in Ω @ 26°c R in Ω @ 75°c Zs in Ω ALS=ALFx1s Vn=ALSxZs
(Ie/ALS)x100
% Current error 11.425 13.574 14.57 10x1 145.7 Ie=0.99mA : 9.9%

The Composite error is 9.9 % at ALF = 10 which is equal to 20kA Primary current
It was observed that the core saturation occurred at 8 times the primary current ( 16kA)
for Ipr=630A , the equivalent ALF= 25