Main features :-
• Wide Input Op range: 90 to 300Vac
• Energy saving – Leading power efficiency, ≥95%
• Wide operating temperature range.
• Max capacity 1KW.
• Adjustable Battery parameters through RS-485 and CAN
• Advance battery management- Settable charging rate, voltage and current.
• Periodic Battery checking.
• Modular architecture
• User-friendly LED’s for customer interface.
• PFC alarms.
Applications :-
• GPON / OLT/ ONT/ WI-FI.
• Telecom
• Smart City
Specification
INPUT
Voltage range 90 VAC ~ 176 VAC (power derating)
176 VAC ~ 300VAC ( Full power)
Voltage nominal 230 VAC
Frequency 50 Hz
Current Max. 6 A
OUTPUT
Voltage range 42 ~ 58 VDC (Adjustable)
Voltage nominal 54 VDC
Capacity Max. 1KW
O/P Current 18.5 A ( Max. 20.8 A)
Battery charge modes Float, Boost & Equalize
Battery current default 0.3 C (C = Input capacity in GUI)
Battery current range 0 ~20.8 A (settable as per battery capacity)
No. of Outputs Battery x 1 nos
Load x 1 nos
GENERAL
Efficiency ≥95% @ 50 % load
≥94% @ 100% load
Power density 12 W/in3
Controller Internal controller
Comunication CAN , RS485
User Interface GUI , 3 LED indications
PFC 4 PFC terminals
Protections Over voltage, Battery Under Voltage, Battery Over current, Short circuit, Thermal
protection, Battery terminal (Short circuit protection fuse need to change)
Operating Temp. -10˚ C to +55˚ C (above 55 ˚C power derating till 70 ˚C )
Cooling Fan cooling
Humidity 5% ~ 95%, Non condensing
Acaustics < 55 dB
Applicable Standards
• Safety IEC 60950, UL60950, CSA-C22.2
• EMC EN300386
• Environment RoHS
Dimensions (WxDxH) 125x273x40 all in mm