Professional Documents
Culture Documents
AN0106 B SC200 Advanced Alarm Features
AN0106 B SC200 Advanced Alarm Features
Overview
The SC200 system controller (Version 3.00 or later) includes a new Smart Alarms feature (see details below) and
an enhancement to Analog Input Alarms (see details on page 12). These greatly increase the flexibility and
power of SC200 alarm and user-defined control functions.
Note: For standard alarm functions (System, Analog Input High, Analog Input Low and Digital Input alarms)
refer to the SC200 System Controller Handbook.
Smart Alarms
This application note provides details of Smart Alarms. It is intended for use by system designers with knowledge
of Boolean logic and digital electronics.
Glossary
Page 1 of 14
Eaton®, Powerware®, Intergy™, SiteSure™, CellSure™, DCTools™ and PowerManager™ are trade names, trademarks, and/or service
marks of Eaton Corporation or its subsidiaries and affiliates. Other marks are the property of their respective owners.
© Eaton Corporation 2008. All rights reserved.
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Introduction
Smart Alarms are a software simulation of logic gates to allow the logical combination of other alarms, time
schedules and/or system values.
A single Smart Alarm is the equivalent of a multi-input AND, OR or XOR logic gate. More complex logic
arrangements are created by using one Smart Alarm as an input into another. For example:
SAy = Sa OR Sb OR Sc Sa SAy
Sb
Sc
Note: One input is Smart Alarm SAx (output from another gate).
The other input is negated. This is available with Alarm
Sources only.
Where: SAx, etc. are Smart Alarms (entered in the Smart Alarms table).
Sa, Sb, etc. are the Sources (entered in the Alarm Sources, Schedule Sources or System Value
Sources tables.
Note: Up to 32 Smart Alarms can be configured.
Smart Alarms also have optional activation and deactivation delays. When activated they can cause alarm
indications (unless Severity is set to Control) and can activate one or two digital outputs (in the same way as
other alarms).
Sources
The inputs to Smart Alarms are called Sources, which can be any combination of:
Alarm Sources (up to 64):
System Alarms, Analog Input High alarms, Analog Input Low alarms, Digital Input alarms, Other Smart
Alarms
Note: Alarm Sources can either ignore an alarm’s recognition period and be triggered immediately the
alarm is triggered, or be triggered only after the alarm recognition period. Alarm Sources can also
be triggered either when the source alarm becomes active or becomes inactive.
Time Schedule Sources (up to 20)
Note: Time schedules can repeat for a fixed number of times, or indefinitely.
System Value Sources (up to 20):
Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load Power, System
Power, Ah Discharged.
Note: System Value Sources can active either when the system value is above or below a defined
threshold value.
Page 2 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Page 3 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
3. Configure the Sources that will be the inputs to the Smart Alarm. See details of sources on page 2.
Note: Every Smart Alarm must have at least one Source assigned to it.
i. Alarm Sources
In the Alarm Sources table make an entry for each source alarm (if any) to be combined into
the Smart Alarm:
SA Num: Enter the number (from the Smart Alarm States table) of the Smart Alarm for
which this source is an input.
Status: Set to Enabled.
Logic: Set to either:
EQUAL - the Alarm Source will become active when the source alarm is
Triggered or Active.
NOT - the Alarm Source will become active when the source alarm is
Inactive.
Trigger When Set to either:
Source is: Triggered - the Alarm Source will become active immediately when the
conditions for this alarm become true (or false when Logic is set to NOT).
The alarm does not have to be Enabled.
Note: 1. Do not use Triggered when Type is set to Smart Alarm, except
where stated in this application note. See the Appendix on page 13.
2. Recognition time and hysteresis do not apply.
Active - the Alarm Source will become active when the alarm becomes
active (or inactive when Logic is set to NOT), after the alarm recognition
time, and only if the alarm is Enabled.
Type: Set to the appropriate source type: System Alarm, Analog Input High, Analog
Input Low, DI, Smart Alarm.
Index: Enter to the number from the corresponding Alarm State table:
Type = System Alarm - enter the number of the alarm from the Alarm
States table.
Type = AI High/AI Low - enter the number of the alarm from the Analog
Input High Alarms or the Analog Input Low Alarms table.
Type = DI - enter the number of the alarm from the Digital Input Alarms
table.
Type = Smart Alarm - enter the number of the alarm from the Smart Alarm
States table.
Page 4 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
4. Configure and Enable the alarms and/or digital inputs entered in the Alarm Sources table.
Each System, Analog Input High, Analog Input Low and Digital Input alarm used as a source for a Smart
Alarm must be configured and Enabled (except if Alarm Source set to Trigger When Source is Triggered).
Note: Refer to the SC200 System Controller Handbook for details on alarm and DI configuration.
Page 5 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
AND
Smart Alarm Operator = AND
OR XOR
Smart Alarm Operator = OR Smart Alarm Operator = XOR
T T
Page 6 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
SA 1
Input Source
(DI 11) T Output
Configure a Smart Alarm with two source inputs. This example shows Smart Alarm 1 configured to latch.
SA 1
Input Source
(DI 11) Output
Page 7 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Smart Alarm Example 3: Hold a Smart Alarm active for a minimum time
The alarm will remain active for the configured time, and then remain active as long as the activation conditions
are still true.
Input Source
SA 2
(DI 11) Output
SA 1
In this example:
Smart Alarm 1 provides delay and logic “OR”. Severity is set to Control so it does not create an alarm.
Smart Alarm 2 is the required output. It is active if the input is active, or the delay timer (Smart Alarm 1) is
inactive.
Input Source SA 2
(DI 11) Output
SA 1
Page 8 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Input DI 11 SA 2 SA 3 Output
SA 1 T
Page 9 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Smart Alarm Example 6: Activate a Smart Alarm on one condition, and deactivate it on another
condition
SA 1
DI 11 Output
Inputs
SA 2
DI 12
Page 10 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Cautions
1. Time:
Times are stored in the SC200 using UTC (Universal Coordinated Time), similar to GMT.
When you connect to the SC200 using the web, DCTools or PowerManagerII, the times are converted to
local times, including any daylight saving times.
The schedules use UTC time and are not adjusted when daylight saving starts or ends.
Consider this situation:
A user connects to the SC200 during winter. He configures it to turn on a light at local time of 19:00 every
day.
This is converted to UTC and scheduled in the SC200 for the same UTC time every day.
When summer arrives, the local time changes by one hour.
But the SC200 does not change the time – the light will be turned on at the same UTC time, not local
time. So while daylight saving time applies, it will turn on the light one hour earlier every day (in local
time).
2. Interval / Duration
If Interval is set to less than Duration, then this Source will always be active.
Page 11 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Page 12 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Clock Alarm / DI
signal Enable
Logic
Alarm Source OR / AND
- Trigger when / XOR Optional
Latch Delay Source is Delay
Alarm / DI
Triggered
conditions
2. If an Alarm Source has Trigger When Source is set to Active, then the SC200 works from the alarm/DI itself.
The alarm/DI signal is latched by the “Clock signal”. This clock signal is an internal SC200 process, occurring
at least once per second.
So the Alarm Source will not become active until after the alarm/DI’s recognition time, and only if the alarm/DI
is enabled. It exactly matches the state of the alarm/DI itself.
Note: Digital input and some system alarms have individual alarm recognition times. The remaining System
alarms, Analog Input alarms and Smart Alarms use the global alarm recognition time.
Clock Alarm / DI
signal Enable
Logic
Alarm Source OR / AND
- Trigger when / XOR Optional
Latch Delay Source is Delay
Alarm / DI
Active
conditions
Page 13 of 14
AN0106: SC200 Advanced Alarm Features
Issue B, June 2011
Circular conditions
If a Smart Alarm is indirectly derived from itself (through another Smart Alarm), then this is called a “circular
condition”.
If all “edges” (source changes from inactive to inactive or active to inactive) are set to Trigger When Source is
Triggered, then the SC200 cannot correctly calculate the alarm operation.
In this case, the SC200 will leave the alarm as inactive.
Page 14 of 14