R4850G5 (02312TCX)
R4850G5 (02312TCX)
R4850G5
Introduction
Features
96.50%
⚫ Maximum efficiency up to 96%, saving energy 96.00%
95.50%
⚫ Wide input voltage range: 85VAC - 300VAC
95.00%
⚫ Wide operating temperature range: -40℃ to +75℃ (full output up 94.50%
to 55℃) 94.00%
Efficiency
93.50%
⚫ Total harmonic distortion (THD) : ≤ 5% (load rate ≥ 50%) 93.00%
⚫ Hot-swappable 92.50%
92.00%
Vout = 53.5 V
⚫ Digital control 91.50%
91.00%
⚫ CAN communication
90.50% Vout = 57.0 V
⚫ Supporting voltage, current regulation and current balancing 90.00%
5 10 15 20 25 30 35 40 45 50 55 60
⚫ Certified by TUV, CE and UL, and got CB certification Output Current (A)
60 3300
3000
55 3000
50 2700
45 2400
40 2100
Output Voltage (V)
2100
Output Power (W)
35
1800
30
1500
25
1200
20
900
15
600
10
5 300
0
0 0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 -25 -15 -5 5 15 25 35 45 55 65 75
Output Current(A) Ta (℃)
96% Max
Efficiency
≥ 95% (230VAC, 30% - 80% load)
Output Voltage 42VDC - 58VDC, rated voltage: 53.5VDC / 57VDC
Output
Feature 3000W (176VAC - 300VAC) ,
Output Power
3000W - 1250W (176VAC - 85VAC linear derating)
Ripple and Noise ≤ 200mVp-p (bandwidth ≤ 20 MHz)
0 - 5000m (When the altitude ranges from 3000m to 5000m, the operating temperature
Altitude Range
decreases by 1°C for each additional 200m)
Input Overvoltage AC protection threshold: > 300VAC
Protection Recovery range: 290VAC - 300VAC
Input Under-voltage AC protection threshold: < 80VAC
Protection Recovery range: 80VAC - 90VAC
Output Over-voltage
Protection Protection range: 56VDC - 60VDC (can be set on the monitoring module)
Protection
Output Short Circuit A long term short circuit is allowed. After the fault disappears, the rectifier is restored to a
Protection healthy state automatically
Over-temperature
The rectifier protects against over-temperature
Protection
Reliability MTBF > 500,000 hours (25℃)
Audible
Specification ≤ 55dB (40℃, full load)
Noises
TUV, CE, and UL, CB certificate
Safety Certification
Complies with UL60950-1, IEC60950-1, CAN/CSA C22.2 No. 60950-1, and EN60950-1
Safety/EMC/
Lightening EN55032; EN55024; ETSI EN 300 386; IEC61000-3-2; IEC61000-3-3; IEC61000-6-1;
EMC
Protection IEC61000-6-2; IEC61000-6-3; IEC61000-6-4
Lightening protection 5kA
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Huawei Industrial Base
General Disclaimer Bantian Longgang
The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, Shenzhen 518129, P.R. China
future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those
expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an Tel: +86-755-28780808
acceptance. Huawei may change the information at any time without notice.
www.huawei.com