Calculating Fire Resistance Ratings of Wood
Assemblies Using the IBC
Home » Articles » Calculating Fire Resistance Ratings of Wood Assemblies Using the IBC
Architects and Contractors can spend a lot of time hunting for miscellaneous fire rated
assemblies in wood construction. What you'll eventually learn is that the easiest place to
design your own I-hour assembly is Section 721.6 of the International Building Code. The
section details the procedures for calculating fire resistance of walls, floor/ceiling and
rooffccling assemblies.
The total fire rating is determined by adding each component to reach a minimum total
of 60 minutes. Fire protection rating is calculated from the flame side of the assembly
pclae contallsnykesktnce ge caoodneméten stig hee haace 12200
3/8" gypsum wallboard - 10 minutes
/2" gypsum wallboard ~ 1S minutes
5/8" gypsum wallboard - 30 minut
Type X gypsum wallboard -25 minu
aang Fie Rosas Range food fase Ung he WC =v
'be not more than 16! on center. When they are
you get 20 minutes in a wall and 10 minutes
with fleor and root joists,
Wall Finishes and their ratings:
3/8" wood structural panel with exterior glue~S
minutes
5/32" we
Jod structural panel with exterior glue—
0 minutes
19/32" wood structural panel with exterior glue =
1S minutes
5/8" Type X gypsum wallboard - 40 minutes
3/8" + 3/8" gypsum wallboard - 25 minutes
/2" + 318° ayosum wallboard ~35 minutes
pclae contallsnykesktnce ge caoodneméten stig heeace 12200 aang Fie Rosas Range food fase Ung he WC =v
minutes, The spaces between studs must be completely filed with glass fiber mineral
batts a minimum of 2 Ibicf or rockwool or slag material batts a minimum of 33 Ib/ef or
cellulose a minimum of 26 lo/et.
Floors must have 2 subfloor of at least 15/32" wood structural panels or I/16" T&G. Roofs
must have a deck of at least 15/32" wood structural panels or TI/16" T&G and finished
roofing.
There are quite a few additional rules for fire resistance so please ask questions,
@ Sean OHara_ i November 16,2018 @Building Technology, Commercial
Author
Sean O'Hara
Select Cateaory .
slovaca combs rovsstanceingealanedarerblonstbeite anaace 12200 atuning Fie Rosas Range food fase Ung he WC - vate
Assemblies Using the IBC”
‘TOM PAUL.
AUGUST9,2017 AT 827 AM
HL
lam a single business owner, architect, in Cleveland, Ohio. Ihave been to your website
2 few times and the blog listings | have read have been very helpful. Thanks so much.
CYPRESS COLLEGE
MAY 14, 2017 AT 615 PM
Hey great post! I hope it’s alright that I shared this
on my Facebook, if not, no worries just tell
me and Ill remove it Either way keep up the great work
CHRISTIAN NIELSEN-PALACIOS.
MAY 3,2017 AT 800. A
pclae contallsnykesktnce ge caoodneméten stig hee aneace 12200
atuning Fie Rosas Range food fase Ung he WC - vate
Leraing @boul, my question iS. Uoes instaIIng & Gwe CelIny on fal crannets auacrea
to the bottom of wood trusses increase or decrease the assembly's fire rating
(compared to no hat channels}? This is similar to UL HW-S-0089,
BILL FOSTER
MARCH 16,2016 AT 206 PM
Joe,
‘Try using the prescriptive additive method in the IBC Ch. 7 for older assemblies,
Bill Foster
Director of Architecture
30E
MARCH 7, 2016 1208 PM
‘Trying to find the fire rating/UL assembly of a 3 1/2" TnG roof decking that is on a 1950's
school. | keep strikuing out on the web and in the UL book any help would be
annreciated
pclae conten revsktne ope od nemesis siaace 12200
atuning Fie Rosas Range food fase Ung he WC - vate
BPA reeuaavas 2aresrranaew
Stephen, you might look at the Type IV construction requirements in the IBC,
otherwise its discussion with the building official. - Sean
STEPHEN CHARAMELLA
FEBRUARY 2, 2016 AT 104 PM
Hi, we are presently working on a 1885 firehouse to residential conversion. the existing
main level garage area shall remain as a garage under with living area above on second
level, The existing garage ceiling 's pristine t&g southern yellow pine bead board with
crown molding details anc dental work, Any ideas how we can achieve the required $0
min resistance between spaces without removing the trim to install 5/8 type x. WE will
be removing all sub floor from above to expose norn..2+12 floor joists 16"
ED LATTHITHAM
ABRIL 50,2014 AT 506 OM
[have neen lnokina for a fire ratina for the 7/8! stucco +924 studs @ 16" ac +19" aves
ipclotdo contain ewan tinge ceed netted aneace 12200
Caknng Fie Rasta Range food fase Ung he WC =v
SEAN OHARA
[EMBER 1, 2011 AT 946 PM
Hideff, know exactly the dilemma that you're asking about. Certainly a big part of why
so many rated stair enclosures are not wood. Personally would tend to say that you
Use the spacer and have the structural engineer choose appropriate fasteners to
support it,
JEFF
NOVEMBER 30, 2011 AT 5:45 PM
Sean,
What are your thoughts regarding combustible wood trusses, or dimensional lumber
framing perpendicular into a “fire barrier” wall, such as a stair enclosure? In the best
case, Ihave wood trusses parallel to the long dimension of the stair, but would have to
frame at least the stair landings through the ayp board shaft enclosure membrane to
anchor them to the wall studs. Structural engineers do not want the drywall "spacer"
between the ledger and the wall studs. Code officials do not want the ayp board
plot contain aan lrg dnocb entero oaace 12200 Catunng Fie Rosas Range food fates Ung he WC =e
we are sunt igniuing We Geta
SEAN OHARA
NOVEMBER 29,2011 AT 9:05 PM
Josh, if the columns are big enough they can be Type IV, heavy timber.
30sH
NOVEMBER 14 20017140 PM
Jay,
Any suggestions as to finding a rated assembly for wood columns in a type VA building,
We are using PSL columns & beams and | am looking for a way to protect those with
gy.
cHP
NOVEMBER I) 2011 741 AM
pclae contallsnykesktnce ge caoodneméten stig hee aneace 12200
aang Fie Rosas Range food fase Ung he WC =v
as cenmy aia roo1 panels. We are using a ermenuous materiel on une interior ana
exterior walls, ceiling, and roof, so flame spread should not be an issue. However, we are
looking at the thermal barrier issue regarding delaminating of the foam from OSB
andlor an extreme heat transfer from fire causing structural issues. Do you have any
suggestions on how we can achieve a thermal transfer rating of 15 minutes without,
Using drywall Without going into the many reasons, lets assume that there are strong
reasons to avoid the use of drywall on this project.
Thank you.
SEAN OHARA
SEPTEMBER 15,2011 AT 10.87 PM
HiJay, I would generally look to the manufacturer of @ product Ike mag board to find
out the ratings. The IBC doesn't address that
aay
SEPTEMBER 2,201" AT 3O1 AM
“Trina tn vice Mannacit im Ove Roar aunr ASR sheathed 61D tn achioue ana havi fen.
tpl contallany heater sage conocb anesthe oneace 12200
Catan re Aimee ars fod Aunts Unig 18 Et
Kyle, the answers are in the IBC, section 721.6 (2006 version}.
You need at least 15 minutes of fire resistance fram the top, which means a 5/8"
structural panel over the T&G. The 16" OC. framing will give you 10 minutes. That leaves
you needing 35 minutes from the bottom, a layer of §/8" type X will give you 40,
minutes, So, your suggested assembly would actually add up to 60 minutes, but you
need the 5/8" sheathing for the IS minutes from the top.
hope that helps.
kn
AUGUST 6, 2011 AT 909 PM
Hi,
Ineed some help on a] hr fire rated floor system. this is @ retrofit job, exisitng floor
framing is 05" T&G on top of 246 at 76" oc{ can't find anything for the 2x6 everything
said use 2*10}, with the new retrofit, framing become double 2*6 at 16'oc. 5/8" type x
mum hnard attached halo vicitner TRO ta remain and 8! etn ictiral nanal attachad
pclae contain heii ingens ante eigthehe toeace 12200
akunng Fie Rasta Range food fares Ung ne WC =v
unannks tor your newp
SEAN OHARA
MAY 16,2011 AT 185.AM
The code (IBC) will look for minimum S/8" ayp board to get 30 minutes. | would also say
that on a 24" spacing, you'll want 5/8” gyo on a ceiling. /2" is really too thin fer that span
and will ead to a rippled appearance.
RAY BEAUDY
MAY, 2097 AT 108 PM
Hello,
need help to determine the fire rating of a ceiling (unfinished attic space above) with
1/2" Gyp Board with attached to wood trusses 24” OCC, and 12" of R-38 fiberglass batt
insulation. By code I need a minimum 1/2 hour rating
Thanks.
pclae contain reste ngs c-ecodneméleesting hee neace 12200
atuning Fie Rosas Range food fase Ung he WC - vate
Read the 721.6.2.4 carefully and you shauld also be getting some fire protection from
your subfloor. If the code official interprets it differently, then you're looking at 2 leyers
of 2" type X.
CRAIG SUTTON
‘ABRIL, 2011 AT 417 PM
‘Trying to use section 721611 of the IC to acheive a | hour rating of existing floor
assemblies in 20 buildings, by using only 1 layer of 5/8" drywall, Floor joists vary in depth
but maintain 16° of¢ or less,
Using 5/8" type
norninal thickness & subyfinish floor requirements but come up 10 minutes short
{0 minutes, +16" ofe spacing = 10 minutes, meet all other criteria for
Any other ideas skim coat plaster any minutes, insulation in lfoor any minutes?
UL L501 covers me for 2X10 but no other UL for less than a 2X10,
pclae contallsny kesitnce ope cod-eemétee sting hee saneace 12200
atuning Fie Rosas Range food fase Ung he WC - vate
With the cypress are you looking for structural members or panels, The building codes
don't spend a lot of time on species except when it comes to strength
LABRINE VOUTSINAS.
NOVEMBER 23,2010 AT 6.48 PM
Can you tell what the fire rating for row cypress wood is?
COLE APPELMAN
AUGUST 26,2010 AT 136M
What is the fire rating of @ 1116 T&G subfloor with V4 layment floor with insulation on a
210 floor joist?
SEAN OHARA
JANUARY 21,2010 ATTIO6 PM
pclae contallsnykesktnce ge caoodneméten stig hee saeace 12200
atuning Fie Rosas Range food fase Ung he WC - vate
ana 0) COUTSe SIFS Lyp ically Nave # wouu StrUCwUTe InsiGe {NeM, IneTe are Ways Ww rae
SIPs.
You have a lot of options for walls that don't use drywall like concrete, block and brick,
Plaster is still an option. | would not advise SIPs though without finish.
‘What's the opposition to drywall and paint where necessary?
KRISTIN EPLEY
JANUARY 21,2010 ATTISO AM
lam considering what other finishes could be used in place of drywall to achieve 15
minute fire rating (Iwould like to use SIPS walle-not great as a wall finish, but more
importantly don't believe they produce a properly rated wall on their own) that would
be cost effective. I'm trying to figure out if [could build @ house without drywall or
paint.
Leave a Comment
Your email address will not be ublished Reuired fields are marked *
pclae contain revesktne ings -eoodanttenigthee aieinane 1282 Pw akg Fie Rosas Range food fares Ung he WC - Eves
Namet
Email
Website
Related Articles
pclae contain reste ge ceoodneméten sting hee 18ace 12200
aang Fie Rosas Range food fase Ung he WC =v
In Approximately 30 Secones)
smvyncen
A Brief Behind-the-Scenes on Modular Construction
Trending Articles
Filing Cost Per Sauare Foot of Commercial Construction ay Region
Construction Types V-A and V-8 in the International Building Code
‘Type vs. Type '3'in Residential Design
Popular Articles
Fiiiiisag Cost Per Sauare Foot of Commercial Construction ay Region
Construction Types V-A and V-B in the International Building Code
Er Electrical Panel Locations. 4 guide for placement
pclae contain erste ngs dono memantineace 12200 aang Fie Rosas Range food fase Ung he WC =v
About EVstudio
EVstudio is a full-service in-house design firm specializing in architecture, engineering,
planning, and other design services for commercial and residential projects.
Contact EVstudio
nfow
pclae contallsnykesktnce ge caoodneméten stig hee amieace 12200
PLANNING
ARTICLES
CAREERS
contact
pclae contallsng ke sitnc ings cod neméten sigh seace 12200
pclae contallsnykesktnce ge caoodneméten stig hee oo