Protection Coordination Study TNB PMU

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 9

PROTECTION COORDINATION STUDY

XXMWac SMALL HYDRO AT XX

For

XXX SDN BHD

Connected to

TNB 33kV PMU XXX


1.0 INTRODUCTION

XXXX Dua Sdn Bhd was given the license to generate electrical power by hydro
system and to export the power to TNB via the Interconnection Point at 33kV TNB
Pencawang Masuk Utama (PMU) XXX located at XXXXX

The objective of this report is to present the recommended protection coordination


settings for the overcurrent, earth fault and reverse power relays for the UiTM Solar
Power Dua On-Grid 25 MWac Solar Photovoltaic project.

2.0 ELECTRICAL SYSTEM

UiTM Solar Power Dua Sdn Bhd generates 25,000 kWac at 1500 V DC. The DC
power is then converted into 800 V AC through String Inverters. The low voltage AC
is then stepped up using a step-up transformer to 33kV and transmitted through an
underground 33kV XLPE cable where the point of common coupling is at TNB PPU
Seri Alam. Please refer to attachment for overall Single Line Diagram (SLD).

3.0 PROTECTION RELAY DETAILS

Below are the details of the protection relays that are used for the 33 kV system:-

i. Overcurrent and Earth Fault Protection

Make: Schweitzer SEL


Model: SEL 751A
CT Ratio: 600/300/5A (Class 5P20)

ii. Current Differential Protection

Make: ABB
Model: RED 615
CT Ratio: 600/300/1A (Class X)

iii. Reverse Power Protection

Make: Schweitzer SEL


Model: SEL 751A
CT Ratio: 600/300/5A (Class 5P20)

4.0 FULL LOAD CURRENT CALCULATION

Full load current of 25 MWac, Ifull load = (25,000kW) / (√3 x 33kV x p.f.)
= (25,000kW) / (√3 x 33kV x 1.0)
= 437.39 A
5.0 RELAY SETTINGS

Overcurrent & Earthfault Relay Type SEL 751A

The current setting (PMS) and time setting (TMS) of the OCEF relay is based on
grading with the existing relay settings at the TNB incomer at 33kV PPU Seri Alam.
This is to achieve discrimination between all the OCEF relays when a fault occurs in
any part of the system.

The proposed setting for OCEF relay is shows as below:-

No Item Details
1 CT Ratio 600/300/5A
2 Class 5P20
3 Max Power 25 MWac
4 Voltage 33 kV
5 Power Factor 1
6 OC setting (IDMT) PS 73% (437A), TMS 0.09
7 EF setting (IDMT) PS 15% (88A), TMS 0.08

Reverse Power Relay Type SEL 751A

Total Reverse Power calculated from the PV solar plant is 350 kW.

Assume voltage (primary) to be 33kV,

Primary Current, I = 350kW / (33kV x 1.732)


= 6.123 A

Ratio of the CT connected to the Reverse Power Relay (SEL 751A) is 600/300/5A,

Therefore, Secondary Current, I secondary = (6.123/600)*5


= 0.051A

Ratio of the VT connected to the Reverse Power Relay (SEL 751A) is 33/0.11kV,

Therefore, Secondary Power (in VA), Secondary = 0.051A x 110V x 1.732


= 9.72 VA

The proposed setting for OCEF relay is shows as below:-

No Item Details
1 CT Ratio 600/300/5A
2 Class 5P20
3 PT Ratio 33kV/110V
4 Losses 350 kW
5 Power Factor 1
6 Primary Current 6.123 A
7 Secondary Current 0.051 A
8 Secondary Pickup Power 9.72 VA
9 Time Delay 5 sec
Current Differential Relay Type ABB RED 615

The setting of low operating value should not be unnecessary low and in order to
ensure protection stability against transient in the event of external faults.

The recommended setting value for low operate value, = 0.2ln.

Differential protection emphasizes the protection in-zone. External fault occurred at


out of zone shall not trip the differential relay. High Operating value setting at
instantaneous stage operate value (Highest set value)

The recommended setting value for high operate value = 40In

The stabilisation slope is decisive for the stability of the protection during external
faults, i.e in the presence of high through-fault currents. The slope defines the ratio of
the differential current to restraint current. The setting should be like this, when
operating under load condition, weak faults causing only a low differential current still
can be detected, but at the same time there is no risk of false tripping during through
- faults. A typical slope is 0.5ln under fault current and 1.5ln under heavy fault current
is suitable in this protection application.

The recommended setting value, S2, = 50%


End section 1 is recommend at 1ln (100%)

The recommended setting value, S3 = 150%


End section 2 is recommend at 4ln (400%)

6.0 CONCLUSION

This report presents the protection coordination study and proposed relay settings for
UiTM Solar Power Dua plant interconnection to TNB 33kV PPU Seri Alam.
7.0 ATTACHMENT

Attachment I: Overall Single Line Diagram (SLD)


Attachment II: Reverse Power Calculation
·T ,. 0 iT M C &UAtrR POYRY
Rem.tb;

3311.V
INTERLOCKING SCHEME 'i' .\?.it, APPROVED - - -

r -2
lll<V PPU Seri Alam TENAGA
NASIONAL 8ElfHAD - . ,,,.,.,.........."'"""
'L
APPROVED1MTHCOMMENTS

'······ ········:Jl
AC
1 2 50A 25kA 3sec
VCB A TRI PPED - VCB B TRIPPED e v iewe d /Ver i f ie d .,,.,.,,..._.,""""'°"""''""'"• = ••
"'CIS P'.Iz n g m e or : "' D •e • RETURNED FOR CORRECTION I
<hconr!ectorswitch
R . I MPORT ANT

<C
....I
I-
VCB B CLOSED - VCB A CANNOT CLOSED
I ·-- ,,.,,.,.,..,°"
-
<C Ve mca1ion ,_. comformanc• 10 scM me end f\H"lctki c,iiilit y. Thi "" rtnca1ion
fo-,a Resubmit fOJ Approvlll 1 Ix
>-

c . m . . , . ,. ., ,,.,._.., I
RE J E C T E D
C l::
w P'.I ' S12lNSOCAL( VCB A OPEN - VCB B CANNOT CLOSED nc r o l lo .. fflo c:<1n tr1a or from >-"!eo"'<)ll• n l o conl r• clc1 i obh1jaUon & 1u nn!Qol
z g 600/300/lA BU2S58kAA,R/Js
RCO-e1,
!CURRENT DIFF. ... c l ffc11tk1n ACCEPTED F ORI NF ORI A TION
V)
□ CLX EARTH SVITCH B CLOSED- VCB A CANNOT CLOS- LI>• l)l)Uhan sl<im dan l""9si iAi tidal< '"" lepaska n konlrol:IV d, noa.i. P•••• Ma,i • """'.."""""""''""
:::) I- m (Rl'IO) 1ndat kontrak. I spes!ti k1;s ACCEPTED WITH COMMENTS
t H. n ik at
a.. <C
a.. '-' C
VCB A CLOSED - EARTH SVITCH B CANNOT CLOSHI f" alapp,ovolof UMldl lailed1c1>em, diav<• m• w.+be o.,t,j,,c"•'' !o ••.1•:c•1ttul _ .. ....,...,.,,...pon!lon1 , """"•"ic

I
C/EF
w CTS (RINC) t, L -
oruaetorof
- - - - - - - - - - - - - - - - - - - -; t- -i,te commi11ktn
nii l1 t al 1ilfl
w oondllr,y pri,nar, equi;HT""" '' nn6y
No•l: A pp,ov.11 0, commenst dou
.,,.,-
not iwlev• theC
t1onscov, r.-d Ul'!Mf comad R!VISIOH DESCRIPTION DATE
APPROVED
• App rtw JI ii
a..
>- □ •Subjei;ted to 8WA.'• ,fc
,00/YJO/>A
TARIFF TARIFF
LEGEND • lhert •haft ' te s t i n,pUc 1t lon .ttf\l li h • \'t i Eng in e-re: Tan Pi Hu Khemrnarat H. PROJECT TTTll!
Cl:: CL 0 .2, t5VA
PV Engin,/er E l ec t r i c a l
<C oil CIS I"") MffiR MAIN umR CHECK Db, t pl oe, 1 Dec 20j 19 12- Dec- 2019

i OC/EF PROPOSED INTERCONNECTIOHOF2SMW SOLAR PV AT


z
:::)
A a.. •If-/- OVERCURRENT RELAY & EARTH FAULT RELAY
UIIVERSITITEKNOLOGI MARA (IJITI) JAi.ANPURNA.IIA
□P :i:
Oat• : J
[AR!H SWITCH BANDAR SERI Al.All,11750 MASAI, JOHOR
PHAS( INDICATION LIGHT
CURRENT DIFF. CURRENT DIFFERENTIAL PROTECTION RELAY
0-36kV
'.I RPR & OC/EF REVERSE POWER RELAY WITH OVERCURRENT RELAY & EARTH FAULT RELAY
FlBRE OPTIC CABLE

P' ©r> VOLTAGE TRANSFORMER O!Vl!LOPt!:A:


z
.I
I- ¢ RING CURRENT TRANSFORMER · I :k & Did1p1ti Teratur Mea1ikut Spesifikasi SOLAR
,f-------33.V,>l/XLPE/AWA/F'IC, J IC 630 SO.UM (
7KU) ¢ WOUND CURRENT TRANSFORMER

Sa llf ungan
V'b.!. I POWER
DUA

. . . . .. .
Cl:: ws
w MAIN Teknik ,I B1p Tu j u 1 n :
a.. CABLE ENO TERMINATKJN SWITCHGEARI © AMMETER SELECTOR SWITCH
UiTM SOLAR POWER DUA SON. BHD.
□ Babat Boleh
Tenaga
( .
w
500/IA
CL 0.2, '""<D I I
STATION
{ VACUUM CIRCUIT BREAKER / GIS UiTM Solar Power Duo Sdn Bhd.
> ..
.........
[AR SWITCH
...I

> w Dwelling 3. INTEKMA Resort & Convention Centn


Cl::
<C A
O><O VT FUSE Pen11,·us Bts,ir (Asset Pl1nnia: &\
3&'1'11i»/'51
Persioron Rojo Mudo. Seksyen 7
@ Performance) Distri b B1haciara
A
z Cl IOVA SPRING CHARGING MOTOR 1ti11n Network. mbar- ci•n,
TNB 40000 Shoh Alam. Selongor
V)
..............................J . .,. ............
i
:::)

V) Urik
DPM

..
....I I DIGITAL POWER METER
b.......................
I
>
P'.I P'.I
CL.
0.5(20VA) .,._.,, I PHASE INDICATION LIGHT

, ss\ON
OY'tflEREIG NEER:
FuRRENT

-
600 /1A vrs
I © VOLTAGE SELECTOR SWITCH

POVRYI
Cl:: OIFF .
w
a..
I
@ X
CIS 11:BOA /4 (:v)_"' ?
>
D
....I
w

zC l llV, 125M. 25M, J,,ec --1 JEW 1250A
J5kV 1 251,A/Js

251,1
MINIATURE CIRCUIT BREAKER (in VCB Unit)
I- - '<' POYRY ENERGY SONBHO(551240-M)
w
1- I G1S

li-11
di9connedor switch ' C I -E3- FUSE 14--06, lML 14, MEN.IRA HIP S£HG 2, l'WA HIP SENC
w ::
+-"'.i-JEW 12501,251,1 .. - JE W NO. 1, JIU>I P.RAll£E, 502!0 K\IOIA UAf'LR
A a.. 1 Ir.

• QS
--,.;Id,
1250A
V)
J6kY 1250"- 25f<A/Js
9NCL£ 8US8AA r-;,XCIS
--{3-- LIGHTNING ARRESTER EU!CTNCAI. CONSU.TNff:

V) oil JkY 1250A 25kA/ J s

-
....I a.. SINGL£ BVSBAR

I
600/IA
Cl5P20 IOVA 7SR1102
600/1A (
Cl.5P20 lOYA 7SR\102 { LOAD SIJITCH
V)
C @- TRANSFORMER
w
k: a..600/IA
o2 \OVA I 11
l,htosurementl 600/1
CL0.2 I
ent ),_ DISC □NNECT□R
TRANSAFE CONSULT SON. BHD.
(MECHANICAL AND ELECTIRCAL CONSULTANTS)
z
:3
SIJITCH

--
□ PHASE IMOICATION UGHT :)'° E INOtCATION LIGHT No 9A, Jolan Snuker I3/'lB ,
Sekiyen 13, 40100 Shah Alam, Selongor.
Tel: 03-55233632 Fox: 03-5524 2632
VT PRIMARY SWITCH Emoit odmin.t,cilromole-consvll.com
J X I C X 630 SO.•M J X 1C X 630 so.
"-/XLPE/AWA/PVC :mv CABLE ;J./XIJ'f./AWA/PVC JJkV CABLE Cl S CONSU..TANT:
'-'"D UNOERCROUND LAID UNDERGROUND
PERUNDING ZE

--
JURIJTEJ« P8RUNDING
CONSl'l ff:\'G ENGINEERS

634. JolOft $$14/1.

::oo .,,,,... w..,.


ro•No: OJ- 7

t,WNCONT'IU,CTOfl:

rj, rl!t9:.!cb* i!!iS!Efit imi1'H {H nJ


SPIC ENERGY MALAYSIA BERHAD
(Company Numbfir 1216514-K)

No 23. Lo,ongSetiabucf.
Damonsaa Heights.50490Kuala Lump!.K, Moklysia.
J-,1: + 60320111002

MIH.t'ACT\JM:11:JV!NDOIII:
DRAWING
[OAA
...............
rm.,
PV Single Line Diagram

OltAWN, MFI SCALI:, NTS

CHECKED: ARH DAT,I! 8/11/2019

,,.._.,"°, UI TM/SPIC/TSC.PVSLD/001
A;IE\lfflON NO:
H
Reverse Power Calculation for UiTM Solar Plant

LV System

Smart Datalogger
Night Load per unit: 0W
No of SmartACU: 10 nos
Total Night Load: 0W

String Inverter
Night Load per unit: 3.3 W
No of Inverter: 140
Total Night Load: 462 W

Total Night Load 462 W


System Voltage: 240 V Single Phase
Current: 1.9 A

Power Supply Cable for LV system


Total Cable length: 10000 m
Cable resistance per unit: 0.0775 Ω/km
Total cable resistance: 0.775 Ω
Current flowing through: 1.9 A
Cable power loss: 2.8719 W (I^2R)

Total power for LVAC: 464.9 W

MVAC

33 kV transformer

Full load Loss per unit: 28600 W


No load loss per unit: 3000 W
No of Tx: 10 Nos
Total Load: 316000 W
System Voltage: 33000 V (Three Phase)
Current: 5.5 A (Per phase)

Cable for 33 kV Tx
Total Cable length: 10,245 m
Cable resistance per unit: 0.0469 Ω/km
Total cable resistance: 0.4804905 Ω
Current flowing through: 5.5 A
Cable power loss: 14.7 W (I^2R)

Total power for MVAC: 316,014.69 W


Interconnection Cable 33kV

Total Cable length: 6,500 m (6.5km, cable 2


Cable resistance per unit: 0.04785 Ω/km
Total cable resistance: 0.311025 Ω
Current flowing through: 5.5 A
Cable power loss: 9.5 W (I^2R)

Total power for Interconnection: 9.50705068 W

Grand total for reverse power: 316,489.07 W

Final Power Requirement: 350,000.00 W allowance 10%