TC303 Manual
TC303 Manual
Features
p Modern appearance
p Large, blue backlit, LCD screen
p Eco button for energy saving
p Sleeping mode for energy saving
p Energy savings mode-external energy savings
input from occupancy sensor or hotel cardkey
overrides comfort setpoint with setback heating
or cooling setpoint
p Energy saving input configurable, normally
open or normally closed
p Real time display
p Optional remote sensor
p Button lockout function avoids unauthorized
operation
p Non-volatile memory (EEPROM) retains user
setting during power loss
p Low temperature protection
p Standard 86x86mm box for installation
The TC300 series stand-alone digital fan coil
p Temperature sensors are provided with failure
thermostat is designed for temperature control
alarm function to facilitate maintenance
in industrial, commercial and residential environ-
ments. The thermostat improves comfort and
saves energy by comparing the room tempera-
Technical specifications
ture with the desired setting. This information is
p Sensing
��������������������
element: NTC
used to control the fan coil unit.
p Control ����������
accuracy: ���±1℃
TC300 features microprocessor-based control
p Setpoint
����������������
range: 5�� ~
�� 35℃
���
and a large LCD screen. The LCD display modes
p Display
���������������
range: 0�� ~
�� 50℃
���
include operation status (cooling, heating, ven-
p Operating
�����������������������
environment: 0 �� ~
�� 45℃
���
tilation), fan speed, room temperature, and tem-
p Environment humidity��: ������
5~95% ��� RH
perature setting. The following buttons are pro-
(non-condensing)
vided: power switch/fan speed adjustment button
p Button:
��������������������
Touch button
" ", mode switching button (M) , energy saving p Power
�������������������
requirement: < �� 1
�� W
�
button (Eco) and temperature setting button " p Power
��������������
supply: AC
��������
85 ~ 260
���� V,��� 50/60Hz
�������
". p �����������������������������������������
Terminals: can be connected to 2 x 1.5 mm2
or 1 x 2.5 mm2 conductors
p Load
������������������������������������
current: 2 A (resistive load),
1 A (inductive load)
p Enclosure:
������������������������������
Flame-retardant PC
engineering plastic
p Dimensions:
����������������������������������
88.5 x 86 x 16 mm (Wx H �� x����
D)
p Hole
����������������������������
pitch: 60 mm (standard)
p Protection
������������������
class: IP30
����
TC300 Series-Hotel Application Stand-alone Digital Fan Coil Thermostat 02
Model description ature setting, the low, medium and high air speed
TC303 -3 shift will be automatically selected respectively.
A2DLS: Designed for two-pipe systems and
used to control two-wire motorized valves and p Motorized valve control (A2DLS model): In
three-speed fans. Once the temperature setting cooling (heating) mode, the motorized valve will
is reached, the motorized valve will be shut off be switched on when the room temperature is
and the fan will continue to run (factory default) higher than (lower than) the temperature setting
or shut down (with configurable parameter). by 1℃ and switched off when the room tempera-
ture reaches the temperature setting.
A4DLS: Designed for four-pipe systems and used
to control two-wire cold/hot motorized valves and p Motorized valve control (A4DLS model):
three-speed fans. Once the temperature setting
In cooling mode, the cold water valve will be
is reached, the motorized valve will be shut off
opened when the room temperature is 1℃ high-
and the fan will continue to run (factory default)
or shut down (with configurable parameter). er than the temperature setting or closed when
It can also be adapted to two-pipe systems the room temperature drops to the setting, and
through parameter adjustment in order to control the hot water valve will remain closed. In heating
three-wire motorized valves. In this case, once mode, the hot water valve will be opened when
the temperature setting is reached, the motorized the room temperature is 1℃ lower than the tem-
valve will be shut off and the fan will continue to perature setting or closed when the room tem-
run (with configurable parameter) or shut down perature rises to the setting, and the cold water
(with configurable parameter). valve will remain closed.
p Temperature setting: With the power on, press Energy-saving mode of room key: It can be
switched into energy-saving mode by room card
" " to decrease the temperature setting and
and occupancy sensor. For example, after room
" " to increase in steps of 0.5℃.
key is taken out, if thermostat is in cooling
p Mode selection: With the power on, press M mode, the temperature will be automatically set
button to switch the operation mode. The LCD at 28℃ and fan is on low speed; if thermostat is
indicates cooling with " ", heating with " ", on heating mode, 16℃ will be set automatically
and ventilation with " ". with fan operating at low speed; the mode that
@2011 Schneider-electric, All rights reserved
Schneider Electric Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
Jun 2011
TC300 Series-Hotel Application Stand-alone Digital Fan Coil Thermostat 03
mode will not exceed 26℃; under heating mode, tomatically and the motorized valve will be opened
no less than 18℃ will be set on. Thermostat will (hot water valve will be opened for A4DLS model).
set temperature from 4am with 1 ℃ down or up When the room temperature rises to 7℃, the ther-
every one hour, until it comes back to the degree mostat will automatically switch off the output.
that guest has previously chosen at 7am.
Alarm
If a failure occurs in the sensor, the thermostat will
Timing setting function: During power on, press
shut off the fan and the motorized valve and dis-
and hold M button for 3 seconds to enter the dis-
play " " and E1 or E2.
play screen. Press M button again to select hour,
E1: Sensor short-circuit alarm. E2: Sensor open-
minute, week parameters. Press " " and circuit alarm.
" " to adjust this parameter. HI will be displayed if the temperature is higher
than 50℃. LO will be displayed if the temperature
Button lockout function is lower than 0℃.
Button lockout: Pressing and holding " " and
" " at the same time for five seconds will Parameter setting
activate keypad lockup function to prevent ther- During power off, press and hold M button for 5
mostat operation by others. Once this function is seconds to enter the display screen. Press M but-
activated, press and hold " " and " " at the ton again to select parameters as shown in the
same time for five seconds to unlock the buttons. table below. Press " " and " " to adjust this
parameter.
No. Parameter Factory default Function
description
Dimension
01 Low temperature OF OF: Low temperature
protection protection
88.5 deactivated;
On: Low temperature
protection activated
02 Fan operation status 01 00: Fan off
after temperature 01: Fan on
setting is reached
03 Selection between TC303-3A2DLS:00 00: Two-pipe system;
two-pipe and four- TC303-3A4DLS:01 01: Four-pipe system
pipe system
04 Not used
05 Sleeping mode On On:Sleeping mode
activated
86
Schneider Electric Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
Jun 2011
TC300 Series-Hotel Application Stand-alone Digital Fan Coil Thermostat 04
Wiring Diagram
Hi Hi
Hi
N Med N
N Med
Fan Med Fan
L Low
Fan L
L Low
Low
Two-pipe system with two-wire motorized valve Two-pipe system with three-wire Four-pipe system with two-wire motorized valve
motorized valve (parameters need resetting)
Installation diagram
1. Remove the main control 2. Completely remove the 3. Connect the wires in 4. Use the two screws 5. Put the two upper hooks
board and insert a 3.5 mm wires from the unit. accordance with the supplied in the package in place at 30 degrees.
wide flatheaded connection diagram box to secure the wired Press the two lower
screwdriver along the shown above. thermostat base plate to corners of the thermostat
bevel into the slot for 4 the wall. with a slight force to lock
mm. Pry it upward with a the uper cover. The
slight force to release the installation is now finished.
hook.
Warning: Please connect the wires in strict accordance with the connection diagram. Avoid the ingress of foreign matter such as water
or slurry into the thermostat, otherwise it can be damaged!
Schneider Electric Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
Jun 2011