Professional Documents
Culture Documents
ASTM D8169 - Bi-Directional Test
ASTM D8169 - Bi-Directional Test
for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: D8169/D8169M − 18
1. Scope dures. The text of this standard references notes and footnotes
1.1 The test methods described in this standard measure the which provide explanatory material. These notes and footnotes
axial displacement of a single, deep foundation element when (excluding those in tables and figures) shall not be considered
loaded in bi-directional static axial compression using an as requirements of the standard. This standard also includes
embedded bi-directional jack assembly. These methods apply illustrations and appendixes intended only for explanatory or
to all deep foundations, referred to herein as “piles,” which advisory use.
function in a manner similar to driven piles, cast in place piles, 1.7 Units—The values stated in either SI units or inch-
or barrettes, regardless of their method of installation. The test pound units (presented in brackets) are to be regarded sepa-
results may not represent the long-term performance of a deep rately as standard. The values stated in each system may not be
foundation. exact equivalents; therefore, each system shall be used inde-
1.2 This standard provides minimum requirements for test- pendently of the other. Combining values from the two systems
ing deep foundations under bi-directional static axial compres- may result in non-conformance with the standard. Reporting of
sive load. Plans, specifications, and/or provisions prepared by test results in units other than SI shall not be regarded as
a qualified engineer may provide additional requirements and nonconformance with this test method.
procedures as needed to satisfy the objectives of a particular 1.8 The gravitational system of inch-pound units is used
test program. The engineer in charge of the foundation design, when dealing with inch-pound units. In this system, the pound
referred to herein as the engineer, shall approve any deviations, (lbf) represents a unit of force (weight), while the unit for mass
deletions, or additions to the requirements of this standard. is slugs. The rationalized slug unit is not given, unless dynamic
1.3 This standard provides the following test procedures: (F=ma) calculations are involved.
Procedure A Quick Test 9.2.1 1.9 All observed and calculated values shall conform to the
Procedure B Extended Test 9.2.2
(optional)
guidelines for significant digits and rounding established in
Practice D6026.
1.4 Apparatus and procedures herein designated “optional”
may produce different test results and may be used only when 1.9.1 The procedures used to specify how data are collected,
approved by the engineer. The word “shall” indicates a recorded and calculated in this standard are regarded as the
mandatory provision, and the word “should” indicates a industry standard. In addition, they are representative of the
recommended or advisory provision. Imperative sentences significant digits that should generally be retained. The proce-
indicate mandatory provisions. dures used do not consider material variation, purpose for
obtaining the data, special purpose studies, or any consider-
1.5 The engineer may use the results obtained from the test ations for the user’s objectives; and it is common practice to
procedures in this standard to predict the actual performance increase or reduce significant digits of reported data to be
and adequacy of piles used in the constructed foundation. See commensurate with these considerations. It is beyond the scope
Appendix X1 for comments regarding some of the factors of this standard to consider significant digits used in analysis
influencing the interpretation of test results. methods for engineering design.
1.6 A qualified engineer (specialty engineer, not to be 1.10 This standard offers an organized collection of infor-
confused with the foundation engineer as defined above) shall mation or a series of options and does not recommend a
design and approve the load test configuration and test proce- specific course of action. This document cannot replace edu-
cation or experience and should be used in conjunction with
1
professional judgment. Not all aspects of this guide may be
This test method is under the jurisdiction of ASTM Committee D18 on Soil and
applicable in all circumstances. This ASTM standard is not
Rock and is the direct responsibility of Subcommittee D18.11 on Deep Foundations.
Current edition approved Jan. 1, 2018. Published February 2018. DOI: 10.1520/ intended to represent or replace the standard of care by which
D8169_D8169M-18. the adequacy of a given professional service must be judged,
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
4. Significance and Use
3.1.1 For definitions of common technical terms used in this
standard, refer to Terminology D653. 4.1 The bi-directional axial compressive load test provides
separate, direct measurements of the pile side shear mobilized
3.2 Definitions of Terms Specific to This Standard: above an embedded jack assembly and the pile end bearing
3.2.1 axial compressive capacity, n—the maximum axial plus any side shear mobilized below the jack assembly. The
compressive load that a deep foundation can transfer to the soil maximum mobilized pile resistance equals two times the
and rock around it at an acceptable axial movement. maximum load applied by the jack assembly. Test results may
3.2.2 bi-directional jack, n—a specialized hydraulic jack also provide information used to assess the distribution of side
that has a repeatable, linear load-pressure calibration over its shear resistance along the pile, the amount of end bearing
expansion range. mobilized at the pile bottom, and the long-term load-
displacement behavior.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or 4.2 The specified maximum test load should be consistent
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM with the engineer’s desired test outcome. For permanent
Standards volume information, refer to the standard’s Document Summary page on (working) piles, the engineer may require that the magnitude of
the ASTM website.
3
applied test load be limited in order to measure the pile
Available from American Society of Mechanical Engineers (ASME), ASME
International Headquarters, Two Park Ave., New York, NY 10016-5990, http:// movement at a predetermined proof load as part of a quality
www.asme.org. control or quality assurance program. Tests that attempt to fully
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
testing will generally not test the structural suitability of a pile to support NOTE 6—The engineer should assure that the capacity of the jack
a load as typically placed at the pile top. Structural defects near the pile assembly can mobilize the desired pile capacity found above and below
top may go undetected unless separate integrity tests are performed prior the jack. Tests performed for design optimization should fully mobilize the
to or after bi-directional testing (see Note 8). The analysis of bi-directional axial compressive capacity when possible.
load test results to estimate the pile-top movement that would be measured
by applying a compressive load at the top of the pile should consider strain 5.2 For cast-in-place piles constructed by excavating an
compatibility and load-displacement behavior. ASTM D1143/D1143M open hole in the ground, such as drilled shafts or bored piles,
provides a standard test method for the direct measurement of pile top position the jack assembly at the desired location within the
movement during an axial static compressive load applied at the pile top. pile prior to placing the pile concrete. Use a steel reinforcement
NOTE 3—The analysis of bi-directional load test results to estimate pile
displacements that would be measured by applying a tensile (uplift) load
cage, or a similar support frame, with centralizer devices to
at the top of the pile should consider strain and movement compatibility. maintain the location and orientation of the assembly during
Users of this standard are cautioned to interpret conservatively the tensile concrete placement. Obtain sound concrete around the assem-
capacity estimated from the analysis of a compressive load. ASTM bly by using a fluid concrete mixture, placing concrete at a
D3689/D3689M provides a standard test method for the direct measure- slow and steady rate, and providing adequate clearance around
ment of axial static tensile capacity.
the jack assembly to avoid restricting concrete flow and
4.4 For the purpose of fully mobilizing the axial compres- trapping any sediments, drill fluid, or laitance. If the allowable
sive capacity, the engineer will usually locate the jack assem- jack expansion is inadequate to compress sediments and
bly at a location within pile where the capacity above the mobilize the planned end bearing Sediments and cuttings
assembly equals the capacity below it. A poorly chosen should be removed from the pile bottom before concreting.
assembly location may result in excessive movement above or This unremoved material may reduce the maximum possible
below the jack assembly, limiting the applied load and reduc- test load since some or all the end bearing may not be
ing the usefulness of the test result. Determination of the mobilized. The jack assembly should be placed a minimum
assembly’s location requires suitable site characterization, distance of one-half pile diameter above the pile bottom, as
consideration of construction methods, and the proper applica- needed to place sound concrete or grout below it. A jack
tion of engineering principles and judgement (see Note 4). assembly placed along the pile length shall provide access to
More complex test configurations, using multiple levels of jack place concrete beneath the assembly. The engineer shall
assemblies, may provide a higher probability that the full determine or at a minimum document what if any effect
resistance of the pile along its entire length may be determined. construction procedures may have on the bi-directional test
Details regarding such complex arrangements are beyond the results or the design assumptions.
scope of this standard.
NOTE 7—When testing a cast-in-place pile, the size, shape, material
NOTE 4—The bi-directional load test may not fully mobilize the axial composition and properties of the pile can influence the pile capacity and
compressive pile resistance in all sections of the pile. Practical, the interpretation of strain measurements described in Section 7.
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
FIG. 1 Schematic of Bi-Directional Load Test Instrumentation
Therefore, direct or indirect measurements of the pile size, shape, material 5.5 Use a jack assembly containing a single jack when
composition and properties versus depth are recommended. possible. Multi-jack assemblies shall be designed to load the
5.3 For cast-in-place piles constructed by placing grout or pile symmetrically about its axis, typically using jacks of the
concrete during withdrawal of an auger, the jack assembly shall same make, model, and capacity with each jack having
be attached to a steel reinforcement, or a similar support frame, independent pressure supply hoses or pipes.
and then placed into the fluid grout or concrete to the desired 5.6 Unless approved otherwise by a qualified test engineer,
location. Use centralizing devices to avoid damaging the jack install a minimum of two hydraulic hoses or pipes (input and
or altering the size and shape of the pile. Provide a minimum return) extending from the pile top to the jack assembly. To
clearance between the jack and the sidewalls of the excavation confirm the hydraulic flow to each jack and to isolate potential
of the lesser of 75 mm [3 in.] or 8 times the diameter of largest pressure leaks during the test, two hoses or pipes extending
coarse aggregate unless otherwise specified by the engineer. from the pile top are recommended for each individual jack.
NOTE 8—Deep foundations sometimes include hidden defects that may Jacks directly connected together within an assembly in series
go unnoticed prior to static testing. Low strain integrity tests (D5882), shall be tested together to verify flow continuity and check for
ultrasonic crosshole integrity tests (D6760), thermal integrity (D7949) or pressure leaks. Alternatively, jacks may be connected in
similar integrity tests may provide useful pre-test information about the
test pile. However, the embedded jack assembly typically, but may not parallel using a manifold. Flow and pressure to each jack can
always, appear as an anomaly itself. The engineer should use caution be directly verified. To limit potential leaks, the hoses or pipes
when using such tests and the results to conclude that an anomaly exists should not include unnecessary fittings or connections within
near the assembly as opposed to being the anomaly. In most cases the the pile. Each hose or pipe shall be clearly marked at each jack,
initial part of the load test itself is the best indicator of whether such an at both sides of any connections, and at the pile top to identify
anomaly is significant or likely to affect the test.
the jack connected to it.
5.4 For driven, pushed, or screwed piles, the jack assembly
is usually installed during the manufacture of the pile. The pile 5.7 Install a minimum of two pipes or tubes to vent the
is then installed as per normal procedures. Alternatively, if location at which the jack assembly will cause the pile to break
these piles have a full-length central void (for example, pipe, during the test.
cylinder, etc.), any material inside the pile may be excavated 5.8 Permanent (working) piles may use the vent pipes or
after installation and the jack assembly may be installed as tubes for post-test grouting of the fracture plane created in the
described in 5.2. pile by the expanded jack assembly. The hydraulic hoses or
supports firmly embedded in the ground at a clear distance months prior to each test. Furnish calibration reports prior to
from the test pile of at least five times the diameter of the test performing a test, including the ambient air temperature during
pile but not less than 2.5 m [8 ft]. Depending on the size and calibration. Targets used with these levels shall have a length
height of the pile top, orient a single reference beam across the no less than 150 mm [6 in.] and provide for a reading precision
pile top or two parallel reference beams, one on each side of of 0.25 mm [0.01 in.] or less, with similar accuracy or better.
the test pile. Reference beams shall have adequate strength, The movement from digital survey levels shall be displayed in
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
FIG. 3 Schematic of Instrumentation for Measuring Axial Pile Movements (Single survey device and target shown for clarity.)
object with a fixed elevation (for example, driven pile) outside 8.2.3 Optical or Laser Survey Level—A single survey level
of the immediate test area and shall reference a stable bench- or laser may be used only as a secondary system to measure the
mark located outside of the immediate test area. The level may axial movement of a scale, target, detector, staff, or survey rod
also be mounted directly on top of the test pile with a stable mounted on the top of the test pile and parallel with its axis (see
measurement point and a benchmark located outside of the Fig. 3). A single pile top measurement point shall be located on
immediate test area. the axis of the pile, or two measurement points shall be located
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
across, and remain clear of, a scale mounted on the test pile anticipated pile bottom movement, and shall measure the axial
parallel to the axis of the pile or pile group. Mount the scale on movement of the pile bottom to the nearest 0.1 mm [0.01 in.]
a mirror affixed to the test pile and use the wireline as a or less. Reference the telltale rods to the top of the pile or to a
reference line to read the scale. Use the mirror to eliminate reference beam system. Alternatively, measure the pile com-
parallax error in the scale reading by lining up the wire its pression below the jack assembly directly as described in 8.5
image in the mirror. Align the wire not more than 13 mm [0.5 and then calculate the pile bottom movement.
in.] from the face of the scale.
8.5 Pile Compression Measurements (optional):
8.2.6 Other Types of Measurement Systems (optional)—The
engineer may specify another type of measurement system 8.5.1 Measure the compression of the test pile between the
satisfying the basic requirements of 8.2. locations specified by the engineer to help define pile move-
ments or evaluate the distribution of load transfer from the pile
8.3 Jack Assembly Axial Movements: to the surrounding geomaterial. The measured pile compres-
8.3.1 Measure the movements of the top and bottom of the sion is typically less than 2.5 mm [0.1 in.] and requires more
jack assembly using individual telltale measurements or a precise displacement indicators to provide useful data for
combination of telltale and jack expansion measurements as analysis.
described below. 8.5.2 To measure pile compression at or above the jack
8.3.2 Telltale Rod Measurements—Install telltale rods (or assembly, install telltale rods that terminate at the desired
rod as applicable) that measure the respective movements of elevation and extend to the pile top, using the pile top as a
the top and bottom of the jack assembly (see Fig. 2) and that reference. Measure the test pile compression to the nearest 0.01
meet the requirements of 8.1. Displacement indicators used to mm [0.0005 in.] or less using telltale rods and displacement
measure these movements shall meet the requirements of 8.1, indicators that meet the requirements of 8.1.
shall have a minimum travel that exceeds the maximum 8.5.3 To measure pile compression below the jack assembly,
anticipated movement of the top and bottom of the jack install displacement indicators and telltale rods within the pile
assembly, and shall measure the axial movements of the top that extend between the desired elevations. Measure the test
10.2.11.11 Benchmark readings (nearest 0.2 mm [0.01 in.] 11. Precision and Bias
or less),
10.2.11.12 Reference beam and wireline movement when 11.1 Precision—Test data on precision is not presented due
measured (nearest 0.2 mm [0.01 in.] or less), to the nature of this test method. It is either not feasible or too
10.2.12 Plots of load versus plate movement above and costly at this time to have ten or more agencies participate in
below the jack assembly, an in situ testing program at a given site.
10.2.13 Relevant field notes and leak checks, 11.1.1 The Subcommittee D18.11 is seeking any data from
10.2.14 Identification and location of all indicators, scales, the users of this test method that might be used to make a
and reference points, limited statement on precision.
10.2.15 Description and explanation of adjustments made to 11.2 Bias—There is no accepted reference value for this test
instrumentation or field data, or both, method, therefore, bias cannot be determined.
10.2.16 Calibration reports for the embedded jack(s), strain
gauges, and displacement indicators, 12. Keywords
10.2.17 Photographs of test instrumentation and setup 12.1 bi-directional load test; deep foundation; displacement;
(optional), and embedded jack; end bearing; field testing; loading procedure;
APPENDIX
(Nonmandatory Information)
X1.1 Potential residual loads in the pile which could influ- friction loads not previously accounted for, and strength losses.
ence the interpreted distribution of load at the pile bottom and
along the pile. X1.7 Type of structure to be supported, including sensitivity
of structure to settlements and relation between live and dead
X1.2 Changes in pore-water pressure in the soil caused by loads.
pile driving, construction fill, dewatering, and other natural and
construction operations that may influence the pile capacity. X1.8 Special testing procedures which may be required for
the application of certain acceptance criteria or methods of
X1.3 Differences between conditions at the time of testing interpretation.
and after final construction, such as changes in grade or
groundwater level. X1.9 Requirement that non tested pile(s) have essentially
identical conditions to those for tested pile(s) including, but not
X1.4 Potential loss of material supporting test pile from limited to, subsurface conditions, pile type, length, size and
such things as excavation and scour. stiffness, and pile installation methods and equipment so that
application or extrapolation of the test results to such other
X1.5 Possible differences in the performance of a pile in a piles is valid.
group or of a pile group from that of a single isolated pile.
X1.10 A bi-directional load test applies the test load within
X1.6 Effects on long-term pile performance of factors such the pile, resulting in profiles of internal pile stress and pile
as creep, environmental effects on pile material, negative displacement that differ from a load test applied at the pile top.
--```,`,,`,,````,``,,`,`,`,,``,-`-`,,`,,`,`,,`---
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222
Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http://www.copyright.com/