REPUBLIC OF THE PHILIPPINES

Department of Agriculture
PHILIPPINE RURAL DEVELOPMENT PROJECT

PROVINCE OF BOHOL

CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING


ENTERPRISE BUILDING

Location: Poblacion, San Miguel, Bohol


REPUBLIC OF THE PHILIPPINES

TABLE OF CONTENTS OFFICE OF THE BUILDING OFFICIAL


MUNICIPALITY OF GETAFE

COVER PAGE

PERSPECTIVE, TABLE OF CONTENTS, SUMMARY OF QUANTITIES A1 1/16 RECOMMENDING APPROVAL:

MAP OF THE PHILIPPINES, MAP OF BOHOL, LOCATION PLAN A2 2/16


HEAD, ARCHITECTURAL SECTION DATE
GROUND FLOOR PLAN, DOORS AND WINDOW DETAIL, RAMP LAYOUT, RAMP LONGITUDINAL AND APPROVED:
A3 3/16
LATITUDINAL SECTION
RIGHT-SIDE ELEVATION, FRONT ELEVATION, LEFT-SIDE ELEVATION, REAR ELEVATION,
A4 4/16
TOILET AND PANTRY LAYOUT,PANTRY LAYOUT, TYPICAL MALE AND FEMALE TOILET ROOM SECTION DETAIL BUILDING OFFICIAL DATE
ROOFPLAN,CEILINGPLAN,ENDFLASHINGCONNECTIONTOPARAPETWALLDETAIL, RECOMMENDING APPROVAL:
A5 5/16
ENDFLASHINGDETAIL,CEILINGSECTION,CEILINGPERSPECTIVE,PANTRYSECTIONDETAIL,PROJECTBILLBOARD
LONGITUDINALSECTIONDETAIL,LATITUDINALSECTIONDETAIL,WINDOWSCREENDETAIL,
A6 6/16
DISPLACEDISOMETRICVIEWOFWINDOWSCREEN,ROOMSCHEDULE,STAIRDETAIL,DRYWALLPARTITIONDETAIL
LAND USE
GENERAL CONSTRUCTION NOTES S1 7/16 AND ZONING
GENERAL CONSTRUCTION NOTES S2 8/16

FOUNDATION PLAN, ROOF BEAM FRAMING PLAN, WALL FOOTING DETAIL, TYPICAL STAIR SECTION DETAIL, HEAD DATE
S3 9/16
STAIR FOOTING 1 LAYOUT DETAIL, STAIR FOOTING 2 LAYOUT DETAIL, 1METER CONCRETE PAVEMENT RECOMMENDING APPROVAL:
AROUND OUTSIDE WALL

ROOF FRAMING PLAN, ROOF EAVE DETAIL, TRUSS 1 WITH END WALL ELEV. DETAIL, FASCIA FRAME
ELEV. DETAIL, MAJOR CROSS BRACE DETAIL, MINOR CROSS BRACE DETAIL, TRUSS ANCHORAGE DETAIL,
S4 10/16
GUSSET PLATES DETAIL,TYPICAL CROSS BRACES CONNECTION TO TRUSS DETAIL LINE AND GRADE

GRADE BEAM SECTION DETAIL, GRADE BEAM ELEV. DETAIL, LINTEL BEAM SECTION DETAIL, LINTEL BEAM
ELEV. DETAIL, C1 / F1 SECTION DETAIL, C1 COLUMN LAYOUT DETAIL, F1 FOOTING LAYOUT, S5 11/16
CONCRETE COVE DETAIL, SLAB EDGES THICKENING DETAIL, PERIMETER WALL SECTION DETAIL HEAD DATE
RECOMMENDING APPROVAL:
END WALL FRAME ELEV. DETAIL, END WALL FRAME ELEV. DETAIL-CALLOUT 1, END WALL FRAME ELEV.
DETAIL - CALLOUT 2, TYPICAL TIE BEAM SECTION DETAIL, TYPICAL ROOF BEAM SECTION DETAIL,
S6 12/16
CONTINOUS BEAM SECTION, LINTEL ROOF BEAM (LRB) SECTION, TIE BEAM SECTIONS, ROOF BEAM
SECTIONS,PLANTED COLUMN SECTION
ARCHITECTURAL
CERTIFICATION, SPECIFICATION, SANITARY PLUMBING LAYOUT PLAN,WATERLINE LAYOUT PLAN,
ISOMETRIC PLUMBING LAYOUT, SEPTIC VAULT LAYOUT, SEPTIC VAULT SECTION DETAIL, JOINT DETAIL, P1 13/16

DOWNSPOUT LAYOUT PLAN, CATCH BASIN LAYOUT PLAN, CATCH BASIN DETAIL, SITE DEVELOPMENT PLAN P2 14/16 HEAD DATE
RECOMMENDING APPROVAL:
ELECTRICAL SPECIFICATION, ELECTRICAL LAYOUT PLAN (LIGHTINGS),
E1 15/16
ELECTRICAL LAYOUT PLAN (CONVENIENCE OUTLET)
SCHEDULE OF LOADS AND COMPUTATION, ALUMINUM REFLECTOR LIGHTS LAY-OUT DETAILS,
E2 16/16
ALUMINUM SHALLOW REFLECTOR DETAILS
STRUCTURAL

HEAD DATE
RECOMMENDING APPROVAL:

SANITARY

Perspective 1 HEAD
RECOMMENDING APPROVAL:
DATE

NDTS A101

ELECTRICAL

HEAD DATE
RECOMMENDING APPROVAL:

MECHANICAL

HEAD DATE

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE Perspective
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER Table of contents A1
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
Summary of quantity

Municipality of San Miguel PRC No:


PTR No:
Validity:
Date issued:
1 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
THIS SITE

5
3.0
S 74°
20.
57' E
000

N 15
3.0
1

00
0
PROPOSED SILAGE

18.
10.

° 21'
000
PRODUCTION &
MAKETING

BU STING
ING
ENTERPRISE

ILD

AD
BUILDING

SO TING
EX
34

DR AR
R
10.

RO
YE
IS
L
EX

7' W

IOR
3.00
MAP OF BOHOL 3

2° 2

ER
NDTS

S2

INT
EXI
STI
NG
P
N7 AVE
ME
0° 2 NT

AY
7' W

LO
THIS SITE THIS SITE
LOT TECHNICAL DESCRIPTION
LINE BEARING DISTANCE
1-2 S 22° 27' W 43.00 m 2
2-3 N 70° 27' W 62.01 m
3-4 N 15° 21' W 37.78 m
N
4-1 S 74° 57' E 67.15 m

W E
CATHOLIC
CEMETERY
SITE DEVELOPMENT PLAN
1:300

S
SAN MIGUEL
TECHNICAL
VOCATIONAL
SCHOOL

MAP OF THE PHILIPPINES LOCATION PLAN


NDTS NDTS
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE MAP OF PHILIPPINES
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER MAP OF BOHOL A2
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
LOCATION MAP
SITE DEVELOPMENT PLAN
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
LOT DESCRIPTION 2 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
4

4 A102 3 A
3.70
SHUTTER
ROLL-UP DOOR

0.46

0.46
Interior Side
LEGEND: 1.10 0.90 0.70
SCHEDULE OF FLOOR FINISHES 1.00 0.80 0.60
FF-1 Ceramic Floor Tiles, 60cm x 60 cm, Polished
2"X4" Wooden 2"X4" Wooden PVC Door Frame
FF-2 Ceramic Floor Tiles, 60cm x 60 cm, Non-Skid Door Jamb Door Jamb
D1
FF-3 Power Floor, Paint Finish
Wooden Door Leaf - PVC Door Leaf
D1 Wooden Door Leaf -

3.00

3.00
Panel Type
Panel Type

2.15

2.15

2.15
2.10

2.10

2.10
A103
2
2 A105
1 2 3 4 5 6 EXTERIOR
F.F.L. SIDE F.F.L. F.F.L. F.F.L. F.F.L.
4.00 4.00 4.00 4.00 4.00 INTERIOR SIDE 0.400 0.400 0.400 0.400 0.400
3
A102 2.70
150mm Thk.CHB
(EXTERIOR WALL)
DOOR 1 DETAIL 3 DOOR 1 DETAIL 4 DOOR 2 DETAIL DOOR 3 DETAIL DOOR 4 DETAIL
1.00 METER CONCRETE(10mm thk)
W1 W1 W1 W1 W4 1:40 A102 1:40 A102 1:40 A102 1:40 A102 1:40 A102
D3 E
REF. 1.20

1.94
W2 Paint finish on
100mm Thk.CHB D3 FF-2
Pantry 0.20M X 0.40M
3.63

W1 (INTERIOR WALL)
Concrete Louver
150mm Thk.CHB D4 Male
Toilet

1.69
(EXTERIOR WALL)
W3 200mm x 250mm
FF-2 Lintel Beam

1.25
D
Female

1.58
100mm Thk.CHB W3 4
(INTERIOR WALL) D4
Toilet
FF-2
3 4

0.25
A102
5

3.00
1.00 METER CONCRETE(10mm thk)
3.63

W1 Dry Wall
4
2
150mm Thk.CHB Partition D2 W2

1.00 METER CONCRETE(10mm thk)


A102
(EXTERIOR WALL) Storage Area 1.20 0.58 1.20
2.06 1.84 2"X 6" Aluminum frame -
FF-3 D1

14.50
(Powder Coated White) Aluminum Frame - 2"X 6" Aluminum frame -

4.50

1.50
A103 4 C 3 A103 INTERIOR SIDE
window jamb (Powder Coated (Powder Coated White)
Office window jamb

5.68
White)
FF-1 ¼" Thk Clear Glass

0.70
1 W2 A Slide Slide

1.15
A105 W2
3.63

Slide Slide

1.35
W1 Slide Slide Aluminum Frame -
150mm Thk.CHB EXTERIOR SIDE
150mm Thk.CHB Dry Wall (EXTERIOR WALL) (Powder Coated White)
(EXTERIOR WALL) Partition
3.70

2.15

2.15

2.15
¼" Thk Clear Glass
¼" Thk Clear Glass
B

1.50

1.45
150mm Thk.CHB
D2
2"X 6" Aluminum frame -

1.00
(EXTERIOR WALL) Aluminum Frame -

0.80
W2 (Powder Coated White) (Powder Coated White)
Receiving Area window jamb
3
3.63

3.63
W1 A102
D1
FF-1 F.F.L. F.F.L. F.F.L. F.F.L.
W2
150mm Thk. 150mm Thk. 0.400 0.400 0.400 0.400
CHB
W2
CHB

W1 W1 W2
A DOOR 1 BLOW-UP DETAIL 1 WINDOW 1 DETAIL WINDOW 2 DETAIL WINDOW 3 DETAIL WINDOW 4 DETAIL
W1
1.00 METER CONCRETE(10mm thk) 1.00 METER CONCRETE(10mm thk) 1:40 A102 1:40 A102 1:40 A102 1:40 A102 1:40 A102

3.70 1.00 3.00 F.F.L.


0.10m THK CONCRETE RAMP SLAB

0.10m THK. CONCRETE MATTING


0.400
BARS SPACED AT 0.30M O.C. B.W

1.00
1 RAMP-01

A103
BACKFILL BACKFILL N.G.L.

0.20
4.00 4.00 4.00 4.00 4.00
10.00 10.00 0.15 0.000

3.00

3.8
T.O.T.B.

2
GROUND FLOOR PLAN 1 WF WF 100mm CHB
10mm DIA. TEMPBARS SPACED -0.200
AT 0.300m OC, BW
1:100 A102 EL.-0.400 EL.-0.400
RAMP-01 LAYOUT 1
RAMP-01 LAYOUT
1:40 A102
1:75 A102
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE GROUND FLOOR PLAN
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER DOORS DETAIL A3
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
WINDOWS DETAIL
RAMP-01 DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
3 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
ROLL-UP SHUTTER DOOR (2.15M X 3.65M)

6" THK CHBWALL, EXTERIOR WALL CONCRETE DECORATIVE LOUVER WITH 5 6


PLASTERED SMOOTH WITH PAINT FINISH WINDOW SCREEN AT THE BACK (3.00M X 1.20M) 6" THK CHBWALL, EXTERIOR WALL
200MM X 250MM
PLASTERED SMOOTH WITH
GRADE BEAM
PAINT FINISH
PRE-PAINTED SPANISH TYPE GUTTER, SLIDING WINDOW
0.40MM X 0.95M PRE-PAINTED
0.40MM X 0.610M X 2.44M
GALVALUME LONSPAN G.I ROOFING(RIB TYPE) SLIDING WINDOW 4.00 150mm Thk.CHB
350MM X 400MM (EXTERIOR WALL)
SLIDING WINDOW 1 METER CONCRETE PAVEMENT CONCRETE COLUMN
2
OUTSIDE WALL(SEE DETAIL )
1 2.70
1 2 3 4 A105
5 6 A B A105
C D E
200MM X 250MM
250MM X 350MM LINTEL BEAM
ROOF BEAM APEX LINE APEX LINE W4
8.870 8.870
200MM X 250MM
D3
GRADE BEAM

2.91
3.62

3.62
REF.

1.94
sink
W2
CERAMIC FLOOR TILES,

1.06
T.O.R.B. T.O.R.B.
D3 Pantry 60cm x 60cm,NON-SKID,
5.250 5.250 FLOOR FINISH
8.87

8.87

8.87
1.55

150mm Thk.CHB
D4 (EXTERIOR WALL)
100mm Thk.CHB

5.25
(INTERIOR WALL) f.d

1.69
D1 W2 w.c
W3 W3 W3
W1 W1 W1 W2 W2 W2 W2 W2 F.F.L. lav.
WATER CLOSET, CERAMIC FLOOR TILES,
0.400 60cm x 60cm,NON-SKID,
F.F.L. ELONGATED TYPE,
COMPLETE WITH FITTINGS FLOOR FINISH

0.15
0.400 N.G.L.
0.000
0.15

N.G.L.
0.000 WALL LAVATORY
WITH LEVER
lav. TYPE LAVATORY

1.58
w.c W3 FAUCET,COMPLETE
100mm Thk.CHB
FRONT ELEVATION 1 RIGHT SIDE ELEVATION 3 (INTERIOR WALL) f.d
D4
WITH FITTINGS

1:100 A103 1:100 A103

CERAMIC FLOOR TILES, 100mm Thk.CHB


60cm x 60cm,NON-SKID,
1.84 (INTERIOR WALL)
FLOOR FINISH

TOILET AND PANTRY LAYOUT 5


PRE-PAINTED G.I RIDGE ROLL, PRE-PAINTED SPANISH TYPE GUTTER,
0.40MM X 0.610M X 2.44M 0.40MM X 0.610M X 2.44M 350MM X 400MM 1:40 A103
6" THK CHBWALL, EXTERIOR WALL CONCRETE DECORATIVE LOUVER WITH CONCRETE COLUMN 250MM X 350MM
PLASTERED SMOOTH WITH PAINT FINISH WINDOW SCREEN AT THE BACK (3.00M X 1.20M) ROOF BEAM
250MM X 250MM
1 METER CONCRETE PAVEMENT LINTEL ROOF BEAM
OUTSIDE WALL(SEE DETAIL ) 6" THK CHB EXTERIOR WALL 200MM X 250MM
SEE CEILING DETAIL
WOODEN FLUSHED, 0.40MM X 0.95M PRE-PAINTED WITH 1" THK CEMENT PLASTER AND LINTEL BEAM
SWING DOOR GALVALUME LONSPAN G.I ROOFING(RIB TYPE) PAINT FINISH
2 1 4" THK CHB WALL,
6 5 A105
4 3 2 1 E D C A105
B A INTERIOR WALL
250MM X 350MM
PLASTERED SMOOTH 0.40MM X 19MM X 25MM
ROOF BEAM 1 METER CONCRETE PAVEMENT WITH PAINT FINISH SINGLE FURRING,HANGER
OUTSIDE WALL(SEE DETAIL )
APEX LINE APEX LINE CONNECTED TO C-PURLINS
8.870 8.870 150mm Thk.CHB
200MM X 250MM
CEILING LINE (EXTERIOR WALL)
WATER CLOSET,

2.91
GRADE BEAM ELONGATED TYPE, CERAMIC FLOOR TILES,

3.62

3.62
3.62

3.62
COMPLETE WITH FITTINGS 60CM X 60CM,POLISHED,

WALL PARTION HEIGHT


WALL TILES, 3 LAYERS
TOILET PAPER
HOLDER

CEILING HEIGHT
1.06
T.O.R.B. T.O.R.B.
WALL LAVATORY WITH
5.250 5.250

2.70
LEVER TYPE LAVATORY FAUCET,
1.60

8.87
8.87

200MM X 250MM COMPLETE WITH FITTINGS

2.15
LINTEL BEAM
1.55 0.15

1.80
w.c

5.25

5.25
5.25

0.85
lav.
3.65

W4
D3 W1 W1 W1 W1 W1 W1 W1 W1 F.F.L.
0.400
F.F.L.

0.15
0.400 N.G.L.

N.G.L. 0.000
0.000

REAR ELEVATION 2 LEFT SIDE ELEVATION 4 MALE AND FEMALE TOILET


1:100 A103 1:100 A103
TYPICAL SECTION DETAIL 6
1:40 A103

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE FRONT ELEVATION
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
REAR ELEVATION A4
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER

Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
LEFT SIDE ELEVATION
RIGHT SIDE ELEVATION
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
TOILET TYPICAL DETAILS 4 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
0.40MM X 19MM X 25MM SINGLE FURRING,
HANGERS AT A MAXIMUM SPACING OF 1M.
(CONNECTED TO PURLINS )
0.40MM X 19MM X 50MM
DOUBLE FURRING, CEILING JOIST
SPACED AT 0.60M, BOTHWAYS
5
X ½" BLIND RIVETS PRE-PAINTED G.I END FLASHING,
32 0.25 0.40MM X 0.610M X 2.44M 0.40MM X 19MM X 25MM SINGLE FURRING, 0.80MM X 12MM X 38MM,
HANGERS, CONNECTED TO PURLINS CARRYING CHANNEL

0.050
TEKSCREW

0.42
ANCHORED AT THE WALL

0.145
PRE-PAINTED G.I END FLASHING, 0.40MM X 25MM X 25MM,
0.40MM X 19MM X 50MM DOUBLE FURRING, 0.80MM X 12MM X 38MM,

5
WALL ANGLE (CORNER)

0.050
0.40MM X 0.610M X 2.44M

03
CEILING JOIST SPACED AT 0.60M, BOTHWAYS CARRYING CHANNEL 0.40MM X 25MM X 25MM,

0.
WALL ANGLE (CORNER)
PRE-PAINTED G.I RIDGE ROLL, 0.40MM X 25MM X 25MM,
0.40MM X 0.610M X 2.44M FIREWALL WALL ANGLE

0.230
0.280
0.80MM X 12MM X 38MM,
0.40MM X 0.95M PRE-PAINTED CARRYING CHANNEL
GALVALUME LONSPAN SPACED AT 1.20M,AT SHORT SPAN

5
03
G.I ROOFING(RIB TYPE)

0.
0.280
WALL
0.330 PARTITION
0.33
0.60 0.60 0.60 0.60

1.20 1.20 DRY WALL PARTITION WALL PARTITION

END FLASHING CONNECTION 4.5MM X 4' X 8'

TO PARAPET WALL DETAIL END FLASHING DETAIL CEMENT FIBER CEILING BOARD

4.5MM X 4' X 8'

1:10 A104 1:10 A104 CEILING SECTION CEMENT FIBER CEILING BOARD

1:40 A104 CEILING PERSPECTIVE


1:40 A104
20.00
20.00
PRE-PAINTED G.I RIDGE ROLL, PRE-PAINTED SPANISH TYPE GUTTER, 4.00 4.00 4.00 4.00 4.00 Name of Agency
Business Address
0.40MM X 0.610M X 2.44M 0.40MM X 0.610M X 2.44M
0.40MM X 0.95M PRE-PAINTED PRE-PAINTED SPANISH TYPE GUTTER,
GALVALUME LONSPAN G.I ROOFING (RIB TYPE) 0.40MM X 0.610M X 2.44M 0.40mm X 0.110M METAL CEILING BOARD, Name of Project : Cost :
2
2 SPANDREL, WHITE USING 0.40MM X 19MM X 50MM Location : Fund Source/s : LP, GOP, LGU
250MM X 250MM Implementing Agency/ies :
A105 250MM X 250MM A105 DOUBLE FURRING, AND 0.40MM X 25MM X 25MM
LINTEL ROOF BEAM Development Partner/s :

LINTEL ROOF BEAM 9W Led Bulb E27 POWDER COATED WHITE, WALL ANGLE Contractor/Supplier :

9W Led Bulb E27 Brief Description of Project :

4.5MM X 4' X 8' Project Details:

1.75
HARDIFLEX CEMENT BOARD
Duration Started Target Date of Percentage of As of Cost Incurred Date
Completion Completion (Date) to Date Completed

E E 6
For particulars or complaints about this project, please contact the Regional Office
or Cluster which has audit jurisdiction on this project :

5W Led Bulb E27 COA Regional Office No./Cluster : Local

3.63
Address : Corner V. Sotto, MJ Cuenco Ave., Cebu City

3.63
Contact No. : (038) 411 - 3055 or 500 - 1640 or Text COA Citizen's Desk at 0915-5391957

0.40MM X 19MM X 50MM 1.40 0.10 1.08 World Bank Anti-Corruption Hotline : 105-11-1-800-831-0463

12W Led Bulb E27 12W Led Bulb E27 12W Led Bulb E27 12W Led Bulb E27 DOUBLE FURRING, CEILING JOIST
SPACED AT 0.60M, BOTHWAYS

D D
SLIDING WINDOW
5W Led Bulb E27

3.63

3.63
T.O.L.B.
9W Led Bulb E27
3.400
Open - No Ceiling

14.50

14.50
C C
1 1
Granite Fin. on 100mm Thk.
A105 Concrete Slab Counter W4
3.63 A105

3.63
4.5MM X 4' X 8'
Reinforced by 10mm Ø W2
HARDIFLEX CEMENT BOARD Mat. Bars Spaced at
12W Led Bulb E27 12W Led Bulb E27 12W Led Bulb E27 12W Led Bulb E27 100mm O.C., B.W.
9W Led Bulb E27
D3
B B

0.10
0.40MM X 19MM X 50MM REF

0.75
3.63

DOUBLE FURRING, C

3.63
6
6 EILING JOIST SPACED
S104 S104 AT 0.60M, BOTHWAYS
9W Led Bulb E27 F.F.L.
A 0.400
A
1.75

9W Led Bulb E27

PRE-PAINTED G.I END FLASHING, 0.40mm X 0.110M METAL CEILING BOARD,


0.40MM X 0.610M X 2.44M SPANDREL, WHITE USING 0.40MM X 19MM X 50MM
PRE-PAINTED SPANISH TYPE GUTTER, 9W Led Bulb E27 9W Led Bulb E27
0.40MM X 0.610M X 2.44M DOUBLE FURRING, AND 0.40MM X 25MM X 25MM
10.00 10.00 POWDER COATED WHITE, WALL ANGLE
PANTRY SECTION DETAIL
1 2 3 4 5 6 1 2 3 4 5 6
1:30 A104

ROOF PLAN 1 CEILING PLAN 2 PROJECT BILLBOARD DETAIL


1:100 A104 1:100 A104 1:40 A104

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE ROOF PLAN
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
CEILING PLAN A5
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER

Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
PROJECT BILLBOARD DETAIL
CEILING DETAILS
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
5 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
4" THK CHBWALL, INTERIOR WALL
PLASTERED SMOOTH WITH PAINT FINISH

4.5MM X 4' X 8' HARDIFLEX CEMENT BOARD,


Room Schedule
(DOUBLE WALLING) ON 2"X3" LIGHT METAL FRAME
WALL STUDS SPACED AT 0.60M,BOTHWAYS Unbounded
Number Name Level Area Volume Perimeter Height Base Finish Ceiling Finish Floor Finish Wall Finish
E D C B A
1 Office F.F.L. 18.64 m² 48.46 m³ 17.428 m 2.800 m Paint Finish at 150mm Depth Paint on Cement Board Ceiling Ceramic Floor Tiles, 60cm x 60 cm, Polished Paint on Drywall
APEX LINE
2 Receiving Area F.F.L. 15.39 m² 40.02 m³ 15.702 m 2.800 m Paint Finish at 150mm Depth Paint on Cement Board Ceiling Ceramic Floor Tiles, 60cm x 60 cm, Polished Paint on Drywall
8.620 3 Female Toilet F.F.L. 2.63 m² 6.84 m³ 6.496 m 2.800 m Paint Finish at 150mm Depth Paint on Cement Board Ceiling Ceramic Floor Tiles, 60cm x 60 cm, Polished 24" x 24" Polished Tiles at Height of 1800mm
4 Male Toilet F.F.L. 2.63 m² 6.84 m³ 6.496 m 2.800 m Paint Finish at 150mm Depth Paint on Cement Board Ceiling Ceramic Floor Tiles, 60cm x 60 cm, Non- Skid 24" x 24" Polished Tiles at Height of 1800mm
5 Pantry F.F.L. 4.35 m² 11.31 m³ 8.528 m 2.800 m Paint Finish at 150mm Depth Paint on Cement Board Ceiling Ceramic Floor Tiles, 60cm x 60 cm, Non- Skid Paint on Concrete Finish
3.62

6 Storage Area F.F.L. 231.22 m² 1302.02 m³ 64.290 m 7.065 m Paint Finish at 150mm Depth N/A Power Floor, Paint Finish Paint on Concrete Finish

T.O.R.B.
5.000
8.62

1.60

1.20
0.05 1.10 0.05

0.05
TOP OF WALL PARTITION 4.5MM X 4' X 8' 2"X 4" LIGHT METAL
3.650 CEMENT FIBER BOARD, WALL STUDS AND TRACKS Barrel and Bolt
4.85

DOUBLE WALL(DRY WALL) SPACED AT 0.60M, BOTHWAYS


CEILING HEIGHT LINE WITH PAINT FINISH
3.450
Mosquito screen

2.80
3.25

9.14
W2 W2
D1

0.83

0.93
D3 D2 D2 0.26 0.58 0.58 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.53
F.F.L.
Storage Area 0.400
2"X 2"Alum. Frame Alanok
0.40

0.05
N.G.L.
0.000

0.05
0.05
T.O.T.B.

0.58
-0.200

3.00

0.83

0.93
SEE DRY WALL PATITION
BLOW-UP DETAIL

0.60

0.05
LATITUDINAL SECTION DETAIL 1

0.60

0.05
3.00
W2 W2

0.05
1:100 A105

0.83

0.93
D2 D2

0.60

0.05
2"X 2"Alum. Frame

0.60
W1 Alanok
Interior Side
2"X 2"Alum. Mosquito screen
Frame Alanok
6" THK CHBWALL, EXTERIOR WALL
PLASTERED SMOOTH WITH Aluminum

1.50
PAINT FINISH Barrel Handle
WINDOW SCREEN(SEE DETAIL) DRYWALL PARTITION BLOW-UP DETAIL and Bolt
4.5MM X 4' X 8' CEMENT FIBER BOARD,
DOUBLE WALL(DRY WALL) WITH PAINT FINISH
1:100 A105
F.F.L.
1 2 3 4 5 6
0.400

APEX LINE 4.5MM X 4' X 8' 2"X 4" LIGHT METAL


CEMENT FIBER BOARD, WALL STUDS AND TRACKS
8.870 DOUBLE WALL(DRY WALL) SPACED AT 0.60M, BOTHWAYS

3.62
WITH PAINT FINISH

3.79
WINDOW SCREEN DETAIL
0.60 0.60 0.60 0.60 0.60 0.60 0.19
1:100 A105

T.O.R.B.
5.250
8.62

0.58
1.60

TOP OF WALL PARTITION


3.650
W1

0.60
4.85

CEILING HEIGHT LINE


3.450
3.25
3.05

W2 W2

0.60
3.00
W1 W1 W1 W1 F.F.L.
Storage Area Office 0.400
0.40

N.G.L.
0.20

0.60
0.000
T.O.T.B.
-0.200

0.60
T.O.F.
0.25
-0.750
DISPLACED ISOMETRIC VIEW
LONGITUDINAL SECTION DETAIL 1 DRYWALL PARTITION BETWEEN OF WINDOW SCREEN
1:100 A105 OFFICE AND STORAGE AREA 1:100 A105
1:100 A105
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE LATITUDINAL CROSS SECTION DETAIL
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER LONGITUDINAL CROSS SECTION DETAIL A6
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
DRY WALL PARTITION DETAIL
WINDOW SCREEN DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
6 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
GENERALCONSTRUCTIONNOTES
GENERAL NOTES NOTES ON CONCRETE MIXES & PLACING
1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY EIGHT 3. IF SLABS AR E REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED
1.0 STANDARDS AND REFERENCES
(28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMP AS FOLLOWS. BELOW THOSE ALONE THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR
THE FOLLOWING SHALL GOVERN THE DESIGN FABRICATION AND CONSTRUCTION OF THE PROJECT.
MAX. SIZE OF REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN STRIPS
1.1 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (N.S.C.P 2015) VOL. 1, SEVENTH EDITION. LOCATION 28 DAYS STRENGTH AGGREGATE MAX SLUMP SHALL NOT BE MORE THAN ONE AND A HALF ( 1 12 ) SLAB THICKNESS.
2.0 DESIGN CRITERIA ALL OTHERS, INCLUDING 20 mm 100mm 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND

CONF. REINF.
4000 PSI (27.6 MPa)
2.1 LOADINGS SUSPENDED SLABS SHALL NOT BE LESS THAN 0.0025 X GROSS-SECTIONAL AREA (Ag) OF THE SLAB. JOINT HOOP SPACE @ "2Sh" WHEN
COLUMNS 4000 PSI (27.6 MPa) 20 mm 100mm ( SEE SCHEDULE BELOW)
A. DEAD LOAD

D JOINT REINF. D PER SCHEDULE D JOINT REINF. D


THERE ARE BEAMS HAVING WIDTH OF
BEAMS 4000 PSI (27.6 MPa) 20 mm 100mm AT LEAST ONE-HALF THE COLUMN
CONCRETE 23.56 kN/m 3 20 mm 100mm
SLAB ON FILL 2500 PSI (17.5 MPa) SCHEDULE OF MINIMUM SLAB REINFORCEMENT WIDTH & DEPTHS NOT LESS THAN
STEEL 76.93 kN/m 3
THREE QUARTERS OF THE DEEPEST

CONF. REINF.
150 mm THK. CHB WALL 2.73 kPa 2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS. MINIMUM TEMPERATURE BARS BEAM THAT FRAME INTO FOUR
100 mm THK. CHB WALL 2.11 kPa SUSPENDED SLABS 20mm 100 mm 10mm Ø @250mm EACH WAY SIDES OF THE COLUMN. ALL OTHER
B. LIVE LOAD SLAB ON GRADE 40mm 125 mm 10mm Ø @250mm EACH WAY CONDITIONS USE HOOPS @ "Sh" CENTERS.

Sh
WALLS ABOVE THE GRADE 25mm

COLUMN TIES AS
ROOF 1.00 kPa 150 mm 10mm Ø @250mm EACH WAY
CLASSROOMS 1.90 kPa BEAM STIRRUPS AND COLUMN TIES 40mm
WHERE CONCRETE IS EXPOSED TO 175 mm 10mm Ø @250mm EACH WAY
TOILETS 1.90 kPa FOR COL. BAR SPLICES SEE TABLE
EARTH BUT POURED AGAINST FORMS 200 mm 10mm Ø @250mm EACH WAY OF MIN. LAP SPLICE LENGTH OF
CORRIDORS ABOVE, STAIRS 3.80 kPa 50mm
WHERE CONCRETE IS DEPOSITED COLUMN REINFORCEMENT
CORRIDORS ON GROUND 4.80 kPa

CONF. REINF. CONF. REINF.


DIRECTLY AGAINST EARTH 75mm 5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED WITH 10mm Ø
C. WIND LOAD AT 250mm O.C. EACH WAY TO CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL

Sh
BUILDING CATEGORY = 1 (ESSENTIAL FACILITIES) 3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSISITON WITHOUT SEGREGATION. RE-HANDLING NOT BE LESS THAN 3.65 METER APART.
OPTION 1 OPTION 2 OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES , BUCKETS OR WHEELBARROWS, 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB ( TWO ADJACENT DISCONTINUOES EDGES) NOTE:
(URBAN OR SUBURBAN AREAS WITH NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUIGGIES, ALL CONCRETE REINF. DETAIL SHOULD
EXPOSURE CAT. D (FLAT UNOBSTRUCTED AREAS AND/OR
NEAR BODIES OF WATER) B NUMEROUS CLOSELY SPACED OBSTRUCTIONS) AS SHOWN BELOW.
WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX (6) METERS BE DONE IN ACCORDANCE WITH ACI
WIND VELOCITY V=340 KPH V=270 KPH 7. CONCRETE SLAB REINFORCEMENT BE PROPERLY SUPPORTED WITH 10mm STEEL CHAIR DETAILING MANUAL (LATEST EDITION)
IN AGGREGATE LENGTH. OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS.
P = qh [(GCpf)-(GCpi)] (DESIGN WIND PRESSURE)
4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS
WHERE: qh = VELOCITY PRESSURE (kPa) AUTHORIZED IN WRITING DESIGNER AND ONLY FOR UNUSUAL CONDITIONS WHERE VIBRATIONS
GCpf = EXTERNAL PRESSURE COFFECIENT Ø12X1000 LONG AT
ARE EXTREMELY DIFFICULT TO ACCOMPLISH. MID-DEPTH OF SLAB
GCpf = INTERNAL PRESSURE COFFECIENT
5. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS SHALL BE PROPERLY POSITIONED & SECURED TYPICAL COLUMN ELEV. SHOWING
D. SEISMIC LOAD IN PLACE PRIOR TO PLACING OF CONCRETE. DOWN INTO EDGE BEAM. EXTENDED AT EACH CORNER DOWELS AND TIES SPACING
4-Ø 12 @ 1800 LONG TOP BARS BEND 1-Ø12 TOP AND
(DESIGN BASE SHEAR) 6. ALL CONCRETE SHALL BE KEPT MOST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS IMMEDIATELY BARS MIN. OF 1,200 (4'-0") INTO BARS.
V =Cvl W BOTT. BARS
RT AFTER POURING BY THE USE O WET BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER
APPROVED METHODS. 4-Ø12 BOTT. BARS
Vmax = 2.50CaI W

400
Vmin = 0.11 CalW
RT 7. STRIPPING OF FORMS AND SHORES: LAP SPLICE LENGTH:
Vmin = 0.80 ZNvI W (ZONE 4) FOUNDATION 24 HOURS AT ANY LEVEL NO MORE THAN
0

CONF. REINF. TIES LAT. TIES H (CLEAR HEIGHT OF COL.)


R SUSPENDED SLAB EXCEPT WHEN 8 DAYS 60 SLAB 38mm ALTERNATE BARS SHOULD BE

0
WHERE: W = TOTAL DEAD LOAD OPENING CLEAR SPLICED. MIN. DISTANCE BET.

60
ADDITIONAL LOADS ARE IMPOSED
T = NATURAL PERIOD = Ct (h) 21 DAYS TWO ADJACENT BARS SPLICES
WALLS SHALL BE 600mm.

400
WHERE: C = NUMERICAL COEFFICIENT BEAMS 14 DAYS
h = BUILDING HEIGHT 21 DAYS L
COLUMNS

WITHIN CENTER
I = IMPORTANCE FACTOR = 1.50

HALF OF "H"
IN TWO WAY SLAB EXTEND
R = NUMERICAL FACTOR = 8.50 8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE BARS UP TO BEAM SUPPORT

60
SEISMIC COEFFICIENT Cv = 0.44 Nv CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE

0
0.25L
POURING FOR APPROVAL. OMIT TRIMMER BARS WHERE
Ca = 0.64 Nv OPENING IS FRAMED BY BEAM TOP BARS @ SUPPORT (CONT.)
NEAR SOURCE FACTOR (5 km) Nv = 1.6 9. THE CONTRACTOR SHALL FURNISH AND MAITAIN ADEQUATE FORMS AND SHORINGS UNTIL THE TYPICAL CORNER SLAB DETAIL REQ'D. BOTT. BARS @ SUPPORT

JT. REINF.
Na = 1.2 CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. TYPICAL SLAB
Z = SEISMIC ZONE = 0.40 (ZONE 4) OPENING DET.
S = SOIL TYPE = D
NOTES ON FOOTINGS
2.2 DESIGN STRESSES 1. FOOTINGS ARE DESIGNED FOR AN ALLOWANCE SOIL BEARING PRESSURE OF 96 KPa (2000psf).
CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRITING ,THE ACTUAL SOIL CONDITIONS
NOTES ON COLUMNS 0.165L SPLICE
BOTTOM BARS
A. CONCRETE COMPRESSIVE STRENGTH @ 28 DAYS: AT MID SPAN
a. FOOTINGS, COLUMNS, BEAMS AND SLABS f'c = 27.6 MPa (4,000 psi) UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. 1. PROVIDE EXTRA SETS OF TIES AT 100 O.C. FOR TIED COLUMN REINFORCEMENT ABOVE 0.22L EXTRA TOP BARS
b. SLAB ON FILL f'c = 17.5 MPa (2,500 psi) 2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LINE UNLESS OTHERWISE AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF CONNECTION @ SUPPORT
C. SLAB f'c = 27.6 MPa (4,000 psi) INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL EQUAL TO GREATER OF THE OVERALL THICKNESS OF COLUMN, 1/6 THE CLEAR HEIGHT OF
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR CONCRETE COLUMN OR 450mm.
B. REINFORCING STEEL BARS
DEPOSITED THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST A FORMWORK.
a. FOR BARS 16mm AND GREATER (INTERMEDIATE GRADE DEFORMED BAR) fy = 414 MPa (60,000 psi) 2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST TYP. DETAIL OF COL. LAP SPLICE
4. IN CASES WHERE THE SOIL CONDITION IS SUCH THAT THE MINIMUM ALLOWABLE SOIL PRESSURE
b. FOR BARS LESS THAN 16mm (STRUCTURAL GRADE DEFORMED BAR) fy = 275 MPa (40,000 psi) MONOLITHICALLY WIT HTHE CORE WITH A MINIMUM THICKNESS OF 40mm AND NOT LESS
OF 96KPa (2000 psf) CAN NOT BE ATTAINED AT A PRACTICAL DEPTHS THE USE OF MICROPILES ,
C. STRUCTURAL STEEL ASTM-A36
BORED PILES, OR DRIVEN PILES MAY BE ADOPTED IN LIEU OF STANDARD ISOLATED FOOTINGS. THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS. & EXT. GIRDER TO COL. CONNECT.
FOR TRUSSES, BRACINGS , & STRUTS fy = 248 MPa (36,000 psi) 3. WHERE COLUMNS CHANGE IN SIZE ,VERTICAL REINFORCEMENT SHALL BE OFFSET AT A
D. PURLINS SLOPE MONOLITHICALLY WITH THE CORE WITH MINIMUM THICKNESS OF 40mm AND
COLD FORMED LIGHT fy = 248 MPa (36,000 psi) NOTES ON REINFORCEMENT NOT LESS THAN 40 TIMES THE MAXIMUM SIZE COARSE AGGREGATE IN MILLIMETERS
E. MASONRY UNIT (CHB)
NON - LOADING BEARING CHB WALLS fm' = 3.45 MPa (500 psi)
1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS SHALL BE: 4. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR VERTICAL COLUMN NOTES ON BEAMS AND GIRDERS
A. FOOTINGS , FOOTING BEAMS AND GIRDERS fy = 414 MPa ( 60,000 psi ) REINFORCEMENT SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND
F. WELDS E - 60XX ELECTRODE
B. COLUMNS AND SHEAR WALLS fy = 414 MPa ( 60,000 psi ) THE SPLICE LENGTH SHALL BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED 1. UNLESS, OTHERWISE NOTED IN PLANS , CAMBER ALL BEAMS AND GIRDER AT
G. STRUCTURAL BOLTS ASTM- A307 a. Ft = 96.60 mPa (14, 000 psi) fy = 414 MPa ( 60,000 psi )
C. BEAMS AND GIRDER 6MM Ø FOR EVERY 4.50M OF SPAN EXCEPT CANTILEVERS FOR WHICH
b. Fv= 69.00 mPa (10, 000 psi) MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS
D. NON-LOAD BEARING WALL PARTITIONS ,BEDDED SLABS , FLOOR & ROOF SLABS, THE CAMBER SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER
3.0 IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN. PARAPETS ,CATCH BASIN,SIDE WALK fy = 275 MPa ( 40,000 psi ) ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL DISTANCES
BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm. BUT IN NO CASE LESS THAN 20 mm FOR EVERY 3.0 M OF FREE SPAN.
DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTIONS PURPOSES 2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH THE ASTM A-706
2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR BEAMS SHALL BE AS
4.0 IN REFERENCES TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS IN FLOOR BARS SMALLER THAN 10mm MAY BE PLAIN.
3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE w/ TABLE B SHOWN IN FIG. B-1
SLABS , OPENINGS IN THE WALLS AND SLABS , INTERIOR PARTITIONS , LOCATIONS OF DRAINS ETC.
(TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWNON DRAWINGS , SPLICES SHALL BE H
5.0 IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS AND ELEVATIONS BETWEEN THE STAGGERED WHENEVER POSSIBLE.
STRUCTURAL PLANS AND ARCHITECTURAL DRAWINGS, THE CONTRACTORS SHALL NOTIFY BOTH THE CROSS-TIE

350mm. MAX.
STRUCTURAL ENGINEER AND ARCHITECTS. NOTES ON CONCRETE SLABS L1 L2
6.0 ALL CONCRETE WORKS AND CONCRETE REINFORCEMENTS SHALL BE DONE IN ACCORDANCE WITH THE 1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM THE TOP OF SLAB. 1 1 1 1
L1 3 L1 3 L2 3 L2 3
ACI.318-14M BUILDING CODE REQUIREMENT AND ALL STRUCTURAL STEEL WORKS ACCORDING WITH THE 2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS ELEVETED SLAB SHALL BE CUT AS FOLLOWS:

10

H
WITH THE AISC-05 IN SOFAR AS THEY DO NOT CONFLICT WITH THE LOCAL BUILDING CODE REQUIREMENT.

d
m
7.0 ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC REFERS TO AMERICAN INSTITUTE OF STEEL

in
.
CONSTRUCTION AND ASTM REFERS TO AMERICAN SOCIETY FOR TESTING MATERIALS. BENT BAR
8.0 CONSTURCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR L1 L2 1 1 1 1
L1 5 L1 5 L2 5 L2 5
NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. L1/4 L1/4 L2/4 TOP BARS
TOP BAR      WEB BARS
9.0 SHOP DRAWING WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, MISCELLANEOUS BOTTOM BARS
IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGINEERS APPROVAL BEFORE FABRICATION.
10. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEUOS CURBS, SILLS , STOOLS EQUIPMENT AND FIGURE B-1
MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL , ELECTRICAL AND MECHANICAL DRAWINGS.
11. ALL RESULTS OF THE MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL STEEL MUST BOTTOM BAR
BE NOTED & APPROVED BY THE MATERIALS ENGINEER/STRUCTURAL DESIGNER.

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE GENERAL CONSTRUCTION NOTES
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
S1
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
7 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
GENERALCONSTRUCTIONNOTES
TABLE 'A' TABLE 'B'
REINFORCING CONCRETE LINTEL BEAMS IN NOTES ON STIRUPS
4-Ø16 VERT. BARS
TENSION BARS COMPRESSION BARS CONCRETE BLOCK WALLS SEE CONSTRUCTION NOTES 1. ALL REINFORCEMENT SHALL BE BENT COLD UNLESS

550
FOR MASONRY WALL REIN- 4-Ø16 VERT. BARS
TABLE OF LAP SPLICE & ANCHORAGE LENGTH (mm) TABLE OF LAP SPLICE & ANCHORAGE LENGTH (mm) FORCEMENTS (TYPICAL) OTHERWISE PERMITTED BY THE STRUCTURAL ENGINEER.

550
600 (MIN.) VARIES
FIN. FLR. LVL.
fc`= 20.7MPa(300psi) fc`= 27.6 MPa (4000psi) fc`= 20.7MPa(300psi) fc`= 27.6 MPa (4000psi)
LINTELS IN BLOCK WALLS 2. AS SHOWN IN THE DESIGN DRAWINGS OR
BAR SIZES BAR SIZES PERMITTED BY THE STRUCTURAL ENGINEER.
(DEFORMED MM)
EMBEDMENT LAPPED EMBEDMENT LAPPED (DEFORMED MM)
EMBEDMENT LAPPED EMBEDMENT LAPPED CLEAR TOTAL MIN. HEIGHT OF REINFORCEMENT NAT. GRD. LVL.
SPAN LENGTH fc' LINTEL DOWEL BARS TO MATCH 3. TIES & CLOSE STIRRUPS MUST BE AT 135.
Ø10 300 300 300 300 Ø10 225 300 200 300 (L) (L+0.40M) (MPa) (mm) BOTTOM TOP STIRRUPS CHB VERTICAL BARS 550 550
Ø10 BOTT. BARS
Ø12 300 300 300 300 Ø12 275 300 250 300 180 DEG. HOOKS
@ 300 O.C.

250
1.20 M 1.60 M 200 1-Ø10 1-Ø10 Ø6 mm @ 200mm
Dbar

D+12db
Ø16 300 400 300 400 Ø16 350 400 325 400 1.50 M 1.90 M 14.0 200 1-Ø10 1-Ø10 Ø6 mm @ 200mm 3-Ø10 BOTT. BARS TYPICAL CONNECTION DETAIL
Ø20 400 550 350 500 Ø20 450 500 475 500 1.80 M 2.20 M 200 1-Ø12 1-Ø10 Ø6 mm @ 200mm

550 550
OF R.C. WALL AT CORNERS
Ø25 600 800 750 Ø25 550 625 625 400
2.10 M 2.50 M 250 1-Ø12 1-Ø10 Ø6 mm @ 200mm
Ø28 750 1000 650 850 Ø28 625 675 625 675 2.40 M 2.90 M 17.0 250 1-Ø12 1-Ø10 Ø6 mm @ 200mm 4db OR 65mm
1-Ø16 1-Ø12 Ø10 mm @ 200mm
Ø32 950 1300 850 1100 Ø32 700 775 700 775 2.70 M 3.10 M 250
DOWEL TO MATCH
NOTES ON WELDS
3.00 M 3.40 M 300 1-Ø16 1-Ø12
90 DEG. HOOKS
NOTES: NOTES: Ø10 mm @ 200mm CHB VERT. BARS 1. USE E60xx ELECTRODES FOR ALL MEMBERS WELDED. Dbar
1. TOP PLAIN BARS, MULTIPLY VALUE BY 2 1. TOP PLAIN BARS, MULTIPLY VALUE BY 2 3.30 M 3.70 M 20.0 300 1-Ø16 1-Ø12 Ø10 mm @ 200mm
2. NOT MORE THAN 33% OF THE BARS SHALL BE 2. NOT MORE THAN 33% OF THE BARS SHALL BE 3.60 M 4.00 M 300 1-Ø20 1-Ø12 Ø10 mm @ 200mm 300 2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS

DOWEL

L
OTHERWISE SHOWN OR DETAILED IN THE DRAWINGS.

12db
SPLICED WITHIN THE REQUIRED LAP LENGTH SPLICED WITHIN THE REQUIRED LAP LENGTH (TYP.)

400
3. VALUES GIVEN ABOVE CAN ALSO BE USED FOR COLUMNS
12 THK. EXPANSION JOINT
FIN. FLR. LVL. D
WITH MASTIC FILLER
NOTES ON STRUCTURAL STEEL

250
1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS

(DOWEL)
3. IF THE BEAM REINFORCING BARS END IN A WALL, THE CLEAR DISTANCE FROM THE BAR TO THE FARTHER FACE OF THE 1-Ø16 VERT. BARS 6-Ø10 BARS(AS SHOWN)
STRUCTURE SHALL COMPLY WITH ALL THE PERTINENT PROVISION OF AISC MAIN BAR END HOOKS
Ø10 BOTT. BARS

400
WALL IS NOT LESS THAN 25mm. EMBEDMENT LENGTH SHALL BE SHOWN IN A TABLE 'A' FOR TENSION BARS AND TABLE 'B' CHB WALL 400 SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL (ALL GRADES)
1-Ø16 VERT. BARS @ 300 O.C.
FOR COMPRESSION BARS UNLESS UNLESS SPECIFIED IN PLAN. TOP BARS AND SHALL NOT BE SPLICED WITHIN THE FOR SIZE AND SPACING STEEL FOR BUILDING LATEST EDITION. BAR SIZE DIAMETER 180° HOOK 90° HOOK
COLUMN OR TWO STIRRUPS SHALL BE PROVED AT ALL SPLICES. OF HOR. & VERT. BARS (DEFORMED) (mm)
FOR SIZE AND SPACING SEE CONSTRUCTION NOTES. 2. ALL STRUCTURAL STEEL SHAPES SHALL CONFORM TO ASTM A36 STRUCTURAL D+2db L L
4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USED 25mm BAR SEPARATORS SPACED AT 1.0M ON OF HOR. & VERT. BARS DOWEL TO MATCH STEEL UNLESS OTHERWISE INDICATED. 10 mm Ø 60 75 125 150
SEE CONSTRUCTION NOTES. CHB VERT. BARS
ON CENTER ON NO CASE SHALL THERE BE THAN TWO (2) SEPARATORS BETWEEN LAYERS OF BARS 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE 12 mm Ø 75 100 150 200
CHB WALL WHERE DEPRESSED
5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BE AS SHOWN IN FIGURE B-2 300 SLAB OCCURS MEMBERS CONNECTED.
16 mm Ø 95 125 175 250

DOWEL
UNLESS ELSEWHERE. (TYP.) 4. UNLESS OTHERWISE SPECIFIED ALL WELDING RODS SHALL CONFORM WITH

400
CORNER WALL OPENING OR END WALL E60 ELECTRODES. 20 mm Ø 115 150 200 300

FIN. FLR. LVL. 5. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A 307 BOLTS. 25 mm Ø 150 200 230 450

250
28 mm Ø 240 300 350 550
MAIN REINFORCEMENT MAIN REINFORCEMENT
6-Ø10 BARS(AS SHOWN) NOTES ON EMBBED PIPES
t OR 1/4 D

t OR 1/4 D
32 mm Ø 300 335 450 600
CHB WALL R.C. COLUMN OR WALL Ø10 BOTT. BARS
SLEEVES FOR UTILITY 400
@ 300 O.C.
t

t
SLEEVES FOR UTILITY 1-Ø16 VERT. BARS DOWEL BARS TO MATCH 1. ALL EMBEDED PIPES FOR UTILITIES ETC. THAT PASS THRU BEAMS SHALL NOT
PIPES MAX. 1/5 D PIPES MAX. 1/5 D CHB HOR. BARS
D

D
12 THK. EXPANSION JOINT EXCEED 100mm IN DIAMETER OR 1/3 BEAM DETPH WHICHEVER IS LESS, UNLESS
WITH MASTIC FILLER 12 THK. EXPANSION JOINT TYPICAL CHB FOOTING DETAILS OTHERWISE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
PROVIDE 3-Ø10 EXTRA STIRR. PROVIDE 3-Ø10 EXTRA STIRR. WITH MASTIC FILLER
EACH SIDE OF SLEEVES EACH SIDE OF SLEEVES ( WHERE APPLICABLE ) 2. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY. 135 DEG. HOOKS

L
3. NO PIPES SHALL BE EMBEDDED IN COLUMNS.

(DOWEL)
400
LE
TYP. DET. FOR SLEEVES TYP. DET. FOR SLEEVES FOR SIZE AND SPACING
THRU CONCRETE BEAM THRU CONCRETE BEAM OF HOR. & VERT. BARS NOTES ON CONSTRUCTION JOINTS IN CONCRETE D
SEE CONSTRUCTION NOTES. 400

VERIFY DEPRESSION

6d
(DOWEL) 1. WHERE A CONSTRUCTION JOINT IS TO BE MADE, THE SURFACE OF CONCRETE

b
FIG. B-2 FIG. B-3
30 BAR DIA. 30 BAR DIA. SHALL BE CLEANED AND ALL LAITANCE AND STANDING WATER REMOVED SHEAR
INTERSECTION WALL INTERSECTING R.C. COLUMN OR WALL (min.) (min.)

D=FOR BEAM
KEY SHALL BE PROVIDE AT THE JOINT.

t=FOR SLAB
L1
L
MAIN REINFORCEMENTS TO BE
6. WHEN A BEAM CROSSES A GIRDER , REST BEAM ON TOP OF GIRDER BARS, BEAM REINFORCING BARS SHALL BE TYPICAL CONNECTION DETAIL OF MASONRY WALL CONTINUOUS (TOP & BOTT. BARS)
SYMMETRICAL ABOUT THE CENTER LINE WHENEVER POSSIBLE. MAIN REINFORCEMENTS WHERE JOINTS IS AT POINT OF
TO BE CONTINUOUS STRESS, PROVIDE SHEAR RODS
7. GENERALLY, NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING STRESSES OCCUR, SPLICES WITH ENGINEERS APPROVAL STIRRUP AND THE TIE HOOKS
(ALL GRADES)
WHERE SO PERMITTED SHALL BE INDICATED IN TABLE 'A' AND 'B'. WELDED SPLICES SHALL DEVELOP IN TENSION AT D=FOR BEAM Ø10X1000 LONG
200 (MIN) 200 (MIN)
LEAST 125% OF THE SPLICED YIELD STRENGTH OF THE BAR NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION @ 300 O.C. BAR SIZE DIAMETER 180° HOOK 90° HOOK
2t=FOR SLAB
50 (DEFORMED) (mm) D+2db L L
IS ALLOWED TO BE SPLICED THEREIN. (MIN.) (MIN.)
30 BAR DIA. (min.) 40

D/3
Ø10 STIRRUPS 10 mm Ø 40 125 85 100
TYPICAL DETAIL FOR BEAM

D/3
t/3 t/3
@ 150 O.C.

D
t/3
12 mm Ø 50 165 115 115

D/3
OR SLAB CHANGE SOFFIT SLAB
16 mm Ø 65 200 140 150
NOTES ON CONCRETE HOLLOW BLOCKS WALLS CHB WALL FOR SIZE AND SPACING BEAM
20 mm Ø 115 300 165 300
OF HOR. & VERT. BARS
1. UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCKS SHALL BE REINFORCED SEE CONSTRUCTION NOTES
TYPICAL SLAB & BEAM

(DOWEL)
OPENING 1-Ø16 VERT. 32 mm Ø 150 335 230 405
AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCK REINFORCEMENT.

400
BARS TYPICAL DOWEL BARS TO MATCH
CHB VERT. BARS
CONSTRUCTION JOINT DET.
2. PROVIDE 150mm X 300mm STIFFENER COLUMN REINFORCED WITH 4-12mm WITH 10mmØ TIES AT 150mm ON CENTER
WHERE CONCRETE HOLLOW BLOCK TERMINATES AND AT EVERY 3.0M LENGTH OF CONCRETE HOLLOW BLOCK 2-Ø12 TOP BARS NOTES ON CONCRETE WALLS

200
WALLS UNLESS NOTED IN STRUCTURAL PLANS. FIN. FLR. LVL.
2-Ø12 BOTTOM BARS 1. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL
REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS.
NOTE:
ELEVATION SECTION PROVIDE THESE ADDITIONAL BARS FOR
ALL OPENINGS PLUS BARS (NOT
NOTES ON CONCRETE HOLLOW BLOCKS WALLS REINFORCEMENTS TYP. DET. OF LINTEL BEAM AT CHB WALL OPENING WALL REINFORCEMENT SHOWN) PARALLEL TO SIDE OF OPENING
VERTICAL EQUAL TO THE NUMBER OF TERMINATED
BLOCK THICKNESS REINFORCEMENT NOTES THICKNESS HORIZONTAL VERTICAL REMARKS SECTION BARS AT OPENING
HORIZONTAL LAPPED 100mm Ø10mm @ 250mm O.C Ø10mm @ 300mm O.C HORIZONTAL BARS
A. MINIMUM LAPS AT SPLICE= 0.25 M VER. BARS SEE ARCHITECTURAL & MECHANICAL
125mm Ø10mm @ 200mm O.C Ø10mm @ 250mm O.C AT CENTERS VERTICAL PLANS FOR SLAB OPENING LOCATION.
75 mm 10mm Ø EVERY 3RD LEVEL 10mm Ø @600mm O.C B. PROVIDE RIGHT ANGLED REINFORCEMENT DOWEL BARS TO BARS STAGGED OUT HOR. BARS
AT CORNERS 0.92 m LONG FLR. SLAB OR BEAM MATCH VERT. BARS 150mm Ø12mm @ 250mm O.C Ø12mm @ 300mm O.C
125 mm 10mm Ø EVERY 3RD LEVEL 10mm Ø @600mm O.C

(DOWEL)
C.WHERE CHB OR CER. BLK. WALL DOWELS

VERIFY ARCHITECTURAL
WITH THE SAME SIZE AS VER. OR HOR. DOOR
150mm 10mm Ø EVERY 3RD LEVEL 10mm Ø @600mm O.C REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT FOR

400
1. ALL JOINTS AND CELLS OPENING
REINFORCEMENT SHALL BE PROVIDED
200 mm 12mm Ø EVERY 3RD LEVEL 10mm Ø @600mm O.C CONTAINING REINFORCING WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE PROVIDED AND FOR
BARS SHALL BE FILLED EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM SHALL BE 50mm CLEAR.
WITH CONCRETE GROUT. 38mm CLEAR WINDOW
2. FOR REINFORCEMENTS SEE 2. CARRY VERTICAL BARS AT LEAST 60mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN NECESSARY OPENING
CONSTRUCTION NOTES. STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL ENDS VERTICAL AND HORIZONTAL BARS
SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL TO 30 DIAMETERS AND WIRED SECURELY WITH 16 G.I. WIRE

(DOWEL)
1-Ø16 CONT. HOR. BARS PROVIDED THAT SPLICES IN ADJACENT BARS ARE STAGGERED AT LEAST 1.50M O.C.

400
FOR FLOOR SLAB ONLY
3. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER SHALL BE REINFORCED
AROUND WITH 2-20mm Ø BARS. FOR 225mm, 200mm, 175mm, 150mm THICK WALLS, USED 2-16mmØ. FOR 125mm AND
100mm THICK WALLS, USED 2-12mmØ BARS.ALL WALLS SPANNING SHALL HAVE VERTICAL REINFORCEMENT BENT
TYP. EXTERIOR WDW. & DOOR OPENING
TYP. SECTION OF MASONRY A U-FORM LIKE STIRRUPS AND SPACED ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED.
PARTITION REINFORCEMENTS

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE GENERAL CONSTRUCTION NOTES
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
S2
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
8 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
4" Thk. CHB 10mm Ø Vert. Bars
Spaced at 400mm O.C.

10mm Ø Hor. BarsSpaced


at every 2 Layers
10mm Ø Cut Bars
ON FILL 0.15M
Spaced at 200mm O.C.
1.00 METER CONCRETE(10MM THK) N.G.L.
1.00 4.00 4.00 4.00 4.00 4.00
C1 Stair Footing 1 0.000

0.40
EL.-0.800 RB RB
F1

0.20
C1 C1 C1 EL.-1.200 C1
C1 4.00 4.00 4.00 4.00 4.00
F1
T.O.T.B.

1.75

1.75
1.00

ON FILL 0.15M

WF
EL.-1.200
1.00 METER CONCRETE(10MM THK) C1 C1 C1 C1 C1 C1
TB TB TB TB
E E
F1 TB
-0.200

1.94
EL.-1.200 ON FILL RB RB RB RB RB

WF
F1 F1 F1 0.40M.
EL.-1.200 EL.-1.200 Stair Footing 1 100MM THK
EL.-1.200 3 - 12mm Ø Straight Bars
3.63

WF
TB

EL.-0.800 RB GRAVEL BED

3.63

3.63
F1
150mm Thk.

TB
EL.-1.200 C1 RB
CHB

1.69
ON FILL
0.40M. F1
EL.-1.200 C1
0.30

WF
WF
150mm Thk. Concrete Slab on Duly Compacted
Suitable Material with 12mm Ø Matting Bars D D
Spaced at 300mm O.C., B.W.

1.58
ON FILL
C1 100mm Thk. 0.40M. C1
Note: Provide 100mm Thk. Gravel Bedding CHB
1.00 METER CONCRETE(10mm thk)

1.00 METER CONCRETE(10mm thk)


3.63

TB

TB
10MM THK RB
WALL FOOTING DETAIL

3.63

3.63
WF
CONCRETE
F1
EL.-1.200 0.86 1.84 PAVEMENT
RB
0N FILL 0.15M

2.70

0N FILL 0.15M
C1 1:100 S102
14.50

14.50
ON FILL 0.40M.
C1 C C

5.00
C1
C1 F1
3.63

EL.-1.200 RB
TB

TB

3.63

3.63
150mm Thk. F1
CHB EL.-1.200
RB

-1.200
C1
B B
C1 C1
C1 150MM THK CHB

4.30
F1 RB (EXTERIOR WALL)
3.63

TB

TB
6 EL.-1.200

3.63

3.63
F1 F1 SLAB THICKENING
150mm Thk. 6 CONCRETE COLUMN
S104 C1 EL.-1.200 EL.-1.200 RB
CHB C1 F1 S104
C1 C1 EL.-1.200 F1
EL.-1.200
RB RB RB RB RB
TB TB ON FILLTB
0.15M TB TB
A A
GRADE BEAM(SEE DETAIL) 100MM THK
GRAVEL BED
1.00 METER CONCRETE(10MM THK)
C1 C1 C1 C1 C1 RB C1

1.75

1.75
F1 C1
EL.-1.200 1 C1
RB 150MM THK
S104
10.00 10.00 CONCRETE PAVEMENT
COMPACTED
10MM THK CONCRETE 2 20.00 12MMØ MATTING BARS
PAVEMENT EARTHFILL
S104 SPACED AT 0.40M,BOTHWAYS

20.00

0.10
1 2 3 4 5 6

0.15 0.15
2

0.05
N.G.L GRAVEL BED
S103

1 2 3 4 5 6
TIE-BEAM(SEE DETAIL)
100MM THK
GRAVEL BED
0.15
100MM THK

FOUNDATION PLAN ROOF BEAM FRAMING PLAN 1.00 GRAVEL BED

1:100 S102 1:100 S102

CONCRETE PAVEMENT
AROUND THE BUILDING
1:100 S102

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE FOUNDATION PLAN
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
ROOF BEAM FRAMING PLAN
CONCRETE PAVEMENT DETAIL
S3
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO WALL FOOTING DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
9 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
T.O.R.B.
5.250 1.50 C1 L C1

13 2 - 16mm Ø Top Cont. Bars


A102
2 - 16mm Ø Bot. Cont. Bars 2 - 16mm Ø Top Cont. Bars

0.250
T.O.L.B.
8 - 20mm Ø Matting Bars
3.650

0.250
Spaced Evenly, Bothways
2 - 16mm Ø Bot. Cont. Bars

1.60
10mm Ø Stirrups Spaced at 5 - 50mm. 5 - T.O.R.B.
100mm, 5 - 150mm and Rest at 175mm
0.200
O.C., Bothways 5.250

LINTEL BEAM DETAIL LINTEL BEAM SECTION DETAIL


10 - 20mm Ø Vertical Bars
with 10mm Ø Lateral Ties 1:20 S104 1:20 S104 10
Spaced at 5 - 50mm, 5 - S104 200mm x 250mm
100mm, 5 - 150mm and Rest 10mm Ø Stirrups Spaced at 5 -
Lintel Beam
50mm. 5 - 100mm, 5 - 150mm and C1
at 175mm O.C., Bothways
Rest at 175mm O.C., Bothways
0.200

2 - 16mm Ø Top Cont. Bars

0.250
12 150mm Thk.
S104 CHB
2 - 16mm Ø Bot. Cont. Bars
F.F.L.
F1 FOOTING DETAIL 0.400

0.250

2.15
1:20 S104
1.50 100MM THK 10mm Ø Vertical Bars Spaced
GRAVEL BED at 400mm O.C.
2 - 16mm Ø Bot. Cont. Bars
2 - 16mm Ø Top Cont. Bars 10mm Ø Horizontal Bars Spaced at
3 every 2 Layers of CHB
F.F.L. 100MM THK
S104
GRAVEL BED
0.400 F1
EL.-1.200
Grade Beam 0.60 GRADE BEAM DETAIL GRADE BEAM SECTION DETAIL F.F.L.
0.400
N.G.L. 1:20 1:20 S104
0.55

100mm Thk Gravel Bed


200mm x 250mm
0.000 10 - 20mm Ø Vertical
0.20

Grade Beam
Bars with 10mm Ø Lateral 4
Ties Spaced at 5 - 50mm, S104
0.40
1.60

5 - 100mm, 5 - 150mm Concrete Corner Nosing


N.G.L.
T.O.T.B. and Rest at 175mm O.C.,
Bothways 0.000
0.75

0.35

-0.200 5
10mm Ø Bend Bars 10mm Ø Matting Bars
S104
Space at 400mm, O.C. Space at 400mm O.C., T.O.T.B.
0.60
1.20

Bothways
TB -0.200

0.100
10mm Ø Straight Bars
T.O.F. F.F.L.
100MM THK

0.175 0.125
F.F.L. GRAVEL BED
-0.750 0.400
0.45

0.400

0.58 0.35 0.58 200mm x 250mm


Grade Beam 200mm x 250mm
Grade Beam
0.100 Concrete Corner Nosing

8 - 20mm Ø Matting bars 100mm Thk Gravel Bed


PERIMETER WALL SECTION DETAIL
Spaced Evenly, Bothways 0.300 0.175
100MM THK C1 COLUMN DETAIL 1:25 S104
GRAVEL BED 0.475
1:20 S104
1.60
SLAB EDGE THICKENING DETAIL CONCRETE COVE DETAIL 1
C1/F1 SECTION DETAIL 1:15 S104 1:8 S104
1:20 S104

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE COLUMN DETAIL
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
FOOTING DETAIL
LINTEL BEAM DETAIL
S4
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO WALL DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
GRADE BEAM DETAIL 10 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
10mm Ø Stirrups Spaced at

A B C D E
5 - 50mm, 5 - 100mm, 5 -
150mm and Rest at 175mm
E
14 12
S105 S105
9.00 9.00 LRB 2 - 16mm Ø Top Cont. Bars

1.75 3.63 3.63 3.63 3.63 1.75 2 - 16mm Ø Bot. Cont. Bars
C
2 - 16mm Ø Top Cont. Bars
C1 LRB
2 - 16mm Ø Bot. Cont. Bars
9.46 10
11
S105
13
S105
S105
LRB
2.91

T.O.R.B.
100mm Thk. 10mm Ø Stirrups
CHB 5.250 Spaced at 5 - 50mm, 5 -

3.90
100mm, 5 - 150mm and C1
C1
C1 Rest at 175mm O.C.,
C1
LRB Bothways
RB 5 - 20mm Ø Top Cont. Bars

C1 C1
5 - 20mm Ø Bot. Cont. Bars
0.71
1.06

1.250 0.300
T.O.R.B.
5.250 1.550
0.35

RB RB RB RB
RB RB
250mm x 300mm
Planted Column
250mm x 300mm
END WALL FRAME ELEV. END WALL FRAME ELEV.
Planted Column END WALL FRAME ELEV. DETAIL DETAIL-CALLOUT DETAIL-CALLOUT
1:50 S105 1:25 S105 1:20 S105

10mm Ø Stirrups
Spaced at 5 - 50mm, 5 - L1 L2 L1 L2
100mm, 5 - 150mm and
Rest at 175mm N.G.L. 0.250
3
L1 (0.25) L1 (0.30) L2 (0.30) L2 (0.30) 0.250
4
0.000 10mm Ø Stirrups Spaced at 5 -
S105 S105
6 7 8 50mm, 5 - 100mm, 5 - 150mm and
T.O.T.B. Rest at 175mm 3 - 20mm Ø Top Cont. Bars

0.55
S105 S105 S105
0.35

0.350
-0.200 2 - 16mm Ø Top Cont. Bars

0.250
2 - 16mm Ø Top Cont. Bars
T.O.R.B.
T.O.F. 2 - 16mm Ø Bot. Cont. Bars
5.250 3 - 20mm Ø Bot. Cont. Bars
-0.750 2 - 16mm Ø Bot. Cont. Bars
100MM THK L1 (0.125) L2 (0.125)
GRAVEL BED
F1 F1 0.40
F1
EL.-1.200 EL.-1.200 EL.-1.200
100MM THK 100MM THK 100MM THK
GRAVEL BED GRAVEL BED GRAVEL BED
CONTINUOUS BEAM SECTION LINTER ROOF BEAM SECTION
TYPICAL TIE BEAM SECTION DETAIL TYPICAL ROOF BEAM SECTION DETAIL 1:15 S105 1:15 S105
1:50 S105 1:50 S105

0.250 0.250 0.250 0.250


0.250 0.300
4 - 16mm Ø Vertical Bars with
3 - 20mm Ø Top hor. Bars 3 - 20mm Ø Top Hor. Bars 10mmØ Lat. Ties Spaced at 5 -
3 - 20mm Ø Top Hor. Bars 3 - 20mm Ø Top Hor. Bars

0.250
3 - 20mmØ Top Hor. Bars 2 - 16mm Ø Top Cut Bar 2 - 16mm Ø Top Cut Bars 50mm O.C., Bothways
0.350

0.350

0.350
0.350

0.350

2 - 16mm Ø Bot. Cut Bars 2 - 16mm Ø Bot. Cut Bars


3 - 20mm Ø Bot. Hor. Bars 3 - 20mm Ø Bot. Hor. Bars
3 - 20mmØ Bot. Hor. Bars 3 - 20mm Ø Bot. Hor. Bars 3 - 20mm Ø Bot. Hor. Bar

100MM THK 100MM THK


GRAVEL BED GRAVEL BED

TIE BEAM AT MIDSPAN TIE BEAM AT SUPPORT ROOF BEAM AT END SUPPORTS ROOF BEAM AT MIDSPAN ROOF BEAM AT SUPPORTS PLANTED COLUMN SECTION
1:15 S105 1:15 S105 1:15 S105 1:15 S105 1:15 S105 1:15 S105

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE END WALL FRAME DETAIL
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
ROOF BEAM DETAIL
TIE BEAM DETAIL
S5
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
11 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
E D C B A
0.20
0.20 12MM THK GUSSET PLATE, 12MM THK GUSSET PLATE, 4 - L 76.2mm x 6mm King Post
0.15
FULLY WELDED TO TRUSS FULLY WELDED TO TRUSS 12MM THK GUSSET PLATE,
12MM THK GUSSET PLATE,
FULLY WELDED TO TRUSS 12MM THK GUSSET PLATE, FULLY WELDED TO TRUSS
FULLY WELDED TO TRUSS 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.59 0.78 0.78

0.63
0.16

0.13

0.21
9.04

0.21

0.15
0.17
Pre - Painted Spanish
0.40mm x 950mm Pre -

0.15
Gutter - 0.40mm x

0.84
6

0.26
4
Painted Galvalume

0.21
610mm x 2440mm

0.1

2.91
S103 Longspan G.I. Roofing

0.400
0.14

0.16
See Detail @ A

0.20
Fire Wall
T.O.R.B.

0.15

2.99
0.15
3
5.250 S103

0.050
2 - L 76.2mm x 6mm Top Chord

0.20 2 - L 76.2mm x 6mm Bottom Chord See Detail @ B


0.20 DETAIL @ A DETAIL @ B 0.25 DETAIL @ C DETAIL @ D RB Fascia Frame
DETAIL @ D
2 - L 63.5mm x 4mm Diag. 150mm x 50mm x 2mm C - Purlins
Spandrel 150mm x 0.40mm and Vert. Web Members Space at 600mm

1.06
1.225

0.21
T.O.R.B.

GUSSET PLATE DETAIL See Detail @ C


5.250

1:40 S106 ROOF EAVE DETAIL See Detail @ D


3.63 3.63 3.63 3.63
1:20 S106
12mmØ 1.35 14.50 1.35
Plain round bar, Sagrod
8.60 8.60
16mm Ø Sway 150mm x 50mm x 2mm C - Purlins 17.20
L 25.40mm x 3.5mm Top Chord
Brace with Space at 600mm 0.30
Turnbuckle L 25.40mm x 3.5mm Vert. Web Members
NOTE:ALL TRUSS MEMBERS SHALL BE PAINTED WITH PRIMER PAINT
EPOXY GRAY PRIMER WITHOUT LED CONTENT

0.40
4.00 4.00 4.00 2 4.00 3.75
A105

L 25.40mm x 3.5mm Bot. Chord


TRUSS-1 WITH END WALL DETAIL
1:40 S106

FASCIA FRAME ELEV. DETAIL 0.15


12MM THK GUSSET PLATE,
FULLY WELDED TO TRUSS
0.20

2 - L 76.2mm x
1:40 S106 6mm Top Chord 2 - L 76.2mm x 6mm Top Chord

2 - L 76.2mm x 6mm Top Chord

0.23
Minor Cross Brace
2 - L 76.2mm x 6mm Top Chord 2 - L 63.5mm x 4mm Diag.
12MM THK GUSSET PLATE,
and Vert. Web Members
2 - L 76.2mm x 6mm Bot. Chord FULLY WELDED TO TRUSS

0.15
2 - L 76.2mm x 6mm Top Chord TRUSS 1 (SEE DETAIL)

0.67 2 - L 63.5mm x 4mm Web Members

0.15
2 - L 76.2mm x 6mm Bot. Chord CROSS BRACE
2 - L 76.2mm x
2 - L 63.5mm x 4mm Web Members 0.68 0.67 0.67 0.67 0.67 0.65 6mm Bottom Chord (SEE DETAIL)
12MM THK GUSSET PLATE, 2 - L 76.2mm x 2 - L 76.2mm x 6mm Bottom Chord

0.15
12MM THK GUSSET PLATE, 0.15
FULLY WELDED TO TRUSS 6mm Bot. Chord 0.20
FULLY WELDED TO TRUSS 12MM THK GUSSET PLATE,
FULLY WELDED TO TRUSS

0.52
Major Cross Brace
17.20

MINOR CROSS BRACE DETAIL


Truss 1 Truss 1
1 Truss 1 Truss 1
A105 Truss 1 Truss 1 Truss 1 Truss 1 (See Detail) (See Detail)
(See Detail) (See Detail) 1:20 S106
4.00
4.00 0.152

MINOR CROSS BRACE DETAIL


Truss 1
MAJOR CROSS BRACE DETAIL 0.350
0.100 0.100
1:40 S106
Minor Cross Brace
1:40 S106
6 12mm Thk. Base Plate
S104 12mm Thk. Base Plate 4 - 16mm Ø Hooked
12mm Thk. Base Plate Anchor Bolts
T.O.R.B.

0.400
T.O.R.B.

0.250
5.250
5.250 6 - 16mm Ø Hooked

0.350
12mm Thk. Base Plate
9 Anchor Bolt Nuts
S103
4 - 16mm Ø Hooked Anchor Bolts 6 - 16mm Ø Hooked
7 Anchor Bolts
S103
20.00
0.250
0.352
1 2 3 4 5 2 6
S103

TRUSS ANCHORAGE TO TRUSS ANCHORAGE TO TRUSS ANCHORAGE TO TRUSS ANCHORAGE TO TO


ROOF FRAMING PLAN ROOF BEAM SECTION DETAIL COLUMN SECTION DETAIL COLUMN LAYOUT ROOF BEAM LAYOUT
1:100 S106 1:15 S106 1:15 S106 1:15 S106 1:15 S106

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE GUSSET PLATE DETAIL
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT
ENTERPRISE BUILDING
ARCHITECT/ ENGINEER
Signed and Sealed Over Printed Name
ROOF FRAMING PLAN
TRUSS ANCHORAGE DETAIL
S6
Province of Bohol Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO CROSS BRACING DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
12 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
Inlet
3.400
SPECIFICATION: LEGEND :
500mm x 500mm
Certification: Manhole

0.100
W.C WATER CLOSET
1. ALL PLUMBING INSTALLATION SHALL CONFORM WITH ALL THE
LAV. LAVATORY

CO

CO
RULES AND REGULATIONS OF THE NATIONAL PLUMBING CODE AND

Outlet
LOCAL HEALTH AUTHORITIES. KS KITCHEN SINK

CO
It has been certified that there is no existing artesion

10mm Ø Mat. Bars


Spaced at 150mm
F.D FLOOR DRAIN

O.C., Bothways
CO
2. ALL SOIL AND WASTE PIPES SHALL BE NO. 40 PVC JOINTS FITTING well within the radius of twenty five (25.00) meters from VTR VTR VENT THRU ROOF
SHALL BE PROPERLY APPLIED WITH PVC SOLVENT CEMENT AND 2"X 2" Ø PVC Tee -

the proposed septic vault.

1.700

1.500
Sched. 40
SET TO ITS APPROVED SLOPE. 2" Ø PVC Elbow- GT GREASE TRAP
Sched. 40

3. EACH WATER CLOSET SHALL BE PROVIDED WITH SEPARATE BV BALL VALVE


SHUTT-OFF VALVE. CB CATCH BASIN
SV SEPTIC VAULT
4. PIPING SHALL BE CONCEALED WHENEVER POSSIBLE; WHEN
CT CISTERN TANK

0.100
PIPES CAN'T BE CONCEALED, THEY SHALL RUN PARALLEL TO AND
CLOSE TO THE FLOOR AS POSSIBLE. Master Plumber 2" Ø PVC Elbow-
Sched. 40 DS DOWN SPOUT
2" Ø PVC Elbow-

0.100 0.750 0.100 0.750 0.100 1.500 0.100


Sched. 40
C.O CLEAN OUT
5. NO TRAP SHALL BE PLACED MORE THAN 5 FT. (1.50 M.) HORIZONTALLY 2"X 2" Ø PVC Tee -
Sched. 40

DEVELOPED LENGHT FROM ITS VENT. GV GATE VALVE


2" Ø PVC Elbow-

6. ALL PLUMBING INSTALLATIONS SHALL BE DONE UNDER THE DIRECT SEPTIC VAULT LAYOUT 2" Ø PVC Elbow-
2"X 2" Ø PVC Tee -
Sched. 40 2" Ø PVC Elbow-
Sched. 40 CV CHECK VALVE

SUPERVISION OF A DULY LICENSED MASTER PLUMBER.


Sched. 40 Sched. 40
HB HOSE BIB
1:25 P101 F
2"X 2" Ø PVC Tee -
MV MAIN VENT
3.400 2" Ø PVC P-Trap
Sched. 40
Sched. 40 2" Ø PVC Elbow-
Sched. 40
WS WATER SYSTEM
0.100 0.750 0.100 0.750 0.100 1.500 0.100 C.O VTR SINK
4" Ø PVC Clean-out
Sched. 40
SH SHOWER HEAD
2"X 4" Ø PVC Tee -
Sched. 40
10mm Ø Grab Bar 10mm Ø Mat. Bars Spaced at 2" Ø PVC Elbow- 4" Ø PVC Elbow-
2" Ø PVC Elbow-
Sched. 40 F FAUCET
150mm O.C., Bothways Sched. 40 Sched. 40

CO CO CO CO 2"X 4" Ø PVC Wye -


Sched. 40
UR URINAL

0.100
N.G.L. VTR
4" Ø PVC Sanitary F
F.D

0.300
4"X 4" Ø PVC Wye -

0.350
0.000

0.400
Tee - Sched. 40 Sched. 40

5 6 5 6
4" Ø PVC Sanitary
Tee - Sched. 40
WS
2"X 4" Ø PVC Tee - 4" Ø PVCSanitary Pipe-
Sched. 40 4" Ø PVC P-Trap Sched. 40
Outlet F Sched. 40

4" Ø PVC Sanitary C.O F 4" Ø PVC P-Trap Sched. 40

Inlet
4" Ø PVC Sanitary
Tee - Sched. 40
Tee - Sched. 40
4" Ø PVC Clean-out
F.D
Sched. 40 2" Ø PVC P-Trap
4" Ø PVC Elbow- Sched. 40
Sched. 40
C.O WS LAV. 2"X 2" Ø PVC Wye -
Sched. 40 4" Ø PVC 81 Bend
4"X 4" Ø PVC Wye -
Sched. 40

Leaching Chlorination Digestive Chamber Sched. 40

2.050
4" Ø PVC Clean-out 4"X 4" Ø PVC Wye -
Sched. 40 Sched. 40

Chamber Chamber F
4" Ø PVC Elbow-
Sched. 40
W.C 4" Ø PVC 81 Bend
Sched. 40
2"X 4" Ø PVC Wye -
4" Ø PVC 81 Bend Sched. 40
10mm Ø Vert. Bars Spaced 2"X 4" Ø PVC Tee -
Sched. 40

at 400mm O.C. Sched. 40

4" Ø PVCSanitary Pipe-


Sand Sched. 40

Thickness
VTR 4" Ø PVC P-Trap
F.D
Sched. 40

0.100
TO WATER SOURCE 10mm Ø Hor. Bars Spaced

Slab
4" Ø PVC 81 Bend
Charcoal 4"X 4" Ø PVC Wye -
Sched. 40 4"X 4" Ø PVC Wye -
at every 2 Layers of CHB Sched. 40 Sched. 40
2" Ø PVC Elbow- 4"X 4" Ø PVC Wye -
F

Thickness
C.O KS Sched. 40 Sched. 40
TO
Gravel 1% Slope
BV

0.150

0.100
WA

Slab
4" Ø PVCSanitary Pipe-
Sched. 40
BV TE
C.O R
SO
F.D 0.300
4" Ø PVC 81 Bend
Sched. 40
4" Ø PVC 81 Bend UR
Sched. 40
CE
SEPTIC TANK 10mm Ø Mat. Bars Spaced at 300mm O.C., Bothways C.O 4"X 4" Ø PVC Wye -
Sched. 40

F
SEPTIC VAULT SECTION DETAIL
2" Ø PVC Elbow-
F.D
1:25 P101 Sched. 40
4" Ø PVCSanitary Pipe-

W.C C.O Sched. 40

C.O C.O 1/8 BEND 4" Ø PVC Clean-out


LAV. WS F B.V Sched. 40
VTR 2"X 4" Ø PVC Tee -
W.S. Sched. 40

2" Ø 1/8 BEND 4" Ø 1/4 BEND 4" Ø PVC 81 Bend


Sched. 40

LAV. WS F
C.O C.O
W.C B.V
2" Ø
4" X 4"O SANITARY WYE
NOTES:
F.D 1/4BEND 2"X4"Ø WYE
HORIZONTAL TO HORIZONTAL
F 1. ALL PVC SANITARY PIPES
SHALL BE ORANGE COLOR
2"X2"Ø TEE
VTR C.O.
4" Ø 1/4 BEND 2"Ø PVC PIPE 1½"Ø P-TRAP
2. ALL PVC WATER-LINE PIPES
4"X2"Ø TEE SHALL BE BLUE COLOR
C.O 1/8 BEND 4" X 2"Ø SANITARY TEE

4"Ø P-TRAP

4" Ø 1/4 BEND C.0


Inlet

ISOMETRIC PLUMBING LAYOUT


W.S.

3.400
4" X 2"Ø
4"X4"Ø WYE 4" X 4"Ø SANITARY WYE SANITARY DNTS P101
2"X2"Ø TEE WYE
VERTICAL TO HORIZONTAL

SANITARY PLUMBING LAYOUT PLAN WATERLINE LAYOUT PLAN


1:50 P101 1:50 P101 JOINT DETAIL
DNTS P101
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE SANITARY PLUMBING LAYOUT PLAN
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER WATERLINE LAYOUT PLAN P1
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
ISOMETRIC PLUMBING LAYOUT
SEPTIC VAULT DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
13 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
0.12
4-10MMØ DEF. BARS BOTHWAYS
STEEL LIFT HANDLE
0.06 CONCRETE COVER
8" PVC-PIPE

0.10
FROM

0.60

0.40
DOWNSPOUT
3"Ø PVC PIPE

8-10MMØ VERT. & HOR. BARS


SHAPE AS SHOWN

0.10
SECTION
4-10MMØ MATTING BARS ,B.W.
SHAPE AS SHOWN
0.60

0.10 0.40 0.10

1 2 3 4 5 6 12-10MMØ VERT. & HOR. BARS


SHAPE AS SHOWN
STEEL LIFTING HANDLE

0.10
3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC
DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT
SCHED.40 SCHED.40 SCHED.40 SCHED.40 SCHED.40 SCHED.40

0.40

0.60
CB CB CB CB CB CB INLET
TO WATER SEWER 3"Ø PVC DOWNSPOUT 3"Ø PVC DOWNSPOUT 3"Ø PVC DOWNSPOUT
SCHED.40 SCHED.40 SCHED.40
E E

0.10
8"Ø PVC-PIPE
PLAN

D D
CATCH BASIN DETAIL
4
1:20 P102

5
3.0
S 74°
C C 20.
57' E
000

N 15
SEPTIC TANK
3.0
1

00
0
PROPOSED SILAGE

18.
10.

° 21'
000
PRODUCTION &
MAKETING

BU TING
ING
B B ENTERPRISE

ILD
IS

AD
BUILDING

SO TING
EX
34

DR AR
R
10.

RO
YE
IS
L
EX

7' W

IOR
3.00
3

2° 2
A A

ER
3"Ø PVC
3"Ø PVC
DOWNSPOUT

S2
DOWNSPOUT

INT
SCHED.40 EXI
SCHED.40 STI
NG
P
3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC 3"Ø PVC CB CB CB CB CB CB N7 AVE
ME
0° 2 NT

AY
DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT DOWNSPOUT TO WATER SEWER
SCHED.40 SCHED.40 SCHED.40 SCHED.40 SCHED.40 SCHED.40 7' W

LO
1 2 3 4 5 6 NOTE: ALL PVC DRAINAGE PIPES SHALL BE ORANGE COLOR
SITE DEVELOPMENT PLAN 2
NOTE: ALL PVC DOWNSPOUT SHALL BE ORANGE COLOR

ER
1:50 P102

STE AT
SY EL W
M
IGU
PROPOSED WATER SOURCE
DOWNSPOUT LAYOUT PLAN CATCH BASIN LAYOUT PLAN

NM
1:50 P102 1:50 P102

SA
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE DOWNSPOUT LAYOUT PLAN
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER CATCH BASIN LAYOUT PLAN P2
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
SITE DEVELOPMENT PLAN
CATCH BASIN DETAIL
Municipality of San Miguel PRC No:
PTR No:
Validity:
Date issued:
14 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
ELECTRICAL SPECIFICATION
1. All electrical works on this plan shall be done in accordance 6. All convenience outlet shall be installed not lower than 300mm 11. All non carrying metal parts of electrical equipments shall be properly
with all applicable provisions of the current edition of the Phi- from the finished grade while special- purpose and counter grounded in accordance with the provisions of article 2.50 "grounding"
lippines Electrical Code and shall conform to the requirements outlet shall be mounted according to their individual location philippine electrical code, volume 1, 2000 edition.
and company with jurisdiction over this project. and requirements.

2. The nature of power supply for this installation 230 volts,AC 12. Main disconnecting means of PB shall be 50 amp. double pole, single phase circuit breaker
single phase,60 hz,two (2) wire. 7. Should conduit run as shown in this plan proved impractical bolt on type. Branches consist of 15amp. for lighting circuits and 20 amp. for
re-routing on site shall be done in conjunction with other runs the convenience outlet.
3. All electrical materials,devices,fixtures,fittings,hardware and services.
shall be of the suitable and approved type for the location and
purpose. 8. All works for this installation shall be done under the direct
supervision of a duly licensed electrical engineer. 13. The main PB shall be properly grounded. One grounding rod 3/4" dia.copper, with 8 feet in
lenght, grounding conductor must be 1-5.5 mm² THW stranded wire clamped at the
4. Except for special purpose outlet and light switch return line
grounding rod.
all wire shall have THHN or THW type of insulation and no 9. N
power line smaller than 3.5 mm ( # 12 AWG) shall be used.
10. The main feeder wire must be 2-8.0 mm² THWN, from the power source up to
5. All wall switches shall be installed 1.5 meters from the finished
floor surface and no further than 200mm from the door jamb
the main panel board, DP. Size of conduit will be 25mm diameter. W E
edge on the lock door side unless noted. 4
S

5
3.0
1 2 3 4 5 6 1 2 3 4 5 6 S 74°
20.
57' E
000

N 15
4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00
3.0
1

00
2.70 2.70 0
PROPOSED SILAGE

18.
10.

° 21'
000
PRODUCTION &
9w 9w 9w MAKETING

BU TING
ING
E E ENTERPRISE

ILD
IS

7' W

AD
BUILDING

SO TING
EX
S1 V V

34

DR AR
R
9w
C3

10.

RO
YE
IS
L
3.63

3.63

2° 2
EX

IOR
3.00
S1

S2
5w

D
C6
D
3

ER
12w 12w 12w 12w
S1

INT
EXI
C1
5w
LEGEND: STI
NG
PAV
N7
3.63

3.63
EM
0° 2 EN

AY
-12W LED DOWNLIGHT FIXTURE T
12w
12w 7' W

LO
S1
C4
C C -DUPLEX CONVENIENCE OUTLET
9w PB
ACU
-PANELBOARD
2
3.63

3.63
EXISTING ELECTRICAL POST
12w
M -KILOWATTHOUR METER

-HOMERUN TO PANELBOARD
C1

12w 12w 12w


B B
12w S1 12w -LIGHTING POWER LINE
PB PB
ACU -SWITCH LINE
SITE DEVELOPMENT PLAN
3.63

3.63

C2
12w
S1 -SINGLE SWITCH
DNTS E101
S2 S2 -2gang SWITCH
A C5 A
S2
ACU -AIR CONDITIONING UNIT 1.5HP
9w 9w 9w
V
-VACUUM 1200W

ELECTRICAL LAYOUT PLAN (LIGHTING) ELECTRICAL LAYOUT PLAN (CONVENIENCE)


1:100 E101 1:100 E101
PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE ELECTRICAL SPECIFICATIONS
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER ELECTRICAL LAYOUT PLAN E1
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
SITE DEVELOPMENT PLAN

Municipality of San Miguel PRC No:


PTR No:
Validity:
Date issued:
15 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN:
SCHEDULE OF LOADS
SEAWEEDS STORAGE BUILDING
DESCRIPTION OF LOAD LIGHTING BRANCH CIRCUIT
SWITCHES POWER VOLTAGE CURRENT CONDUCTOR CONDUIT
AND POWER FIXTURES PROTECTION
CKT. NO.
A B C C.O. ACU VACUUM S1 S2 S3
(12W) (9W) WATTS VOLTS ABC CKT. WIRE GROUND WIRE PVC DEVICE POLE KAIC
(5W) (2-180W) (1117.5W) (1200W) (a) (b) (b)
C1 8 1 96 220 0.44 2 - 3.5 mm² THW 20 mm ∅ PVC 15 AT 2P 10 KA
C2 4 2 2 5 76 220 0.35 2 - 3.5 mm² THW 1 - 2.0 mm² TW 20 mm ∅ PVC 20 AT 2P 10 KA
C3 6 1 54 220 0.25 2 - 3.5 mm² THW 1 - 2.0 mm² TW 20 mm ∅ PVC 20 AT 2P 10 KA
C4 6 2160 220 9.82 2 - 8.0 mm² THW 1 - 2.0 mm² TW 25 mm ∅ PVC 40 AT 2P 10 KA
C5 2 2235 220 10.16 2 - 8.0 mm² THW 1 - 2.0 mm² TW 25 mm ∅ PVC 40 AT 2P 10 KA
C6 2 2400 220 10.91 2 - 8.0 mm² THW 1 - 2.0 mm² TW 25 mm ∅ PVC 40 AT 2P 10 KA
TOTAL 12 8 2 6 2 2 5 2 0 7021 220 31.91 2 - 14.0 mm² THW 2 - 2.0 mm² TW 30 mm Ø BSC 60 AT 2P 10 KA

COMPUTATION:

CONDUCTOR: USE; PROTECTIVE DEVICE:


Ic = [(IT) + (HL x 25%)] (DF = 80%) 2 - 14.0 sq.mm. THW Ip = [(IT) + (HL x 200%)] (DF = 80%) 1 - 60AT, 2P, 220V, 60 Hz
Ic = [(31.91) + (10.91 x 0.25)] (0.80) 2 - 14.0 sq.mm. THW Ip = [(31.91) + (10.91 x 2)] (0.80) 10 KA BOLT-ON TYPE
Ic = 27.71 A IN 30mm Ø RSC Ip = 42.98 A

4" THK CHBWALL, INTERIOR WALL


PLASTERED SMOOTH WITH PAINT FINISH

4.5MM X 4' X 8' HARDIFLEX CEMENT BOARD,


(DOUBLE WALLING) ON 2"X3" LIGHT METAL FRAME
WALL STUDS SPACED AT 0.60M,BOTHWAYS
FROM SOURCE

E D C B A
67 mm dia.
M
APEX LINE
95 mm
8.620
2-8.0mm 2 STRANDED THHN COPPER WIRE
ON 3/4"DIA. ELECTRICAL CONDUIT PIPE
3.62

10" dia.
254 mm dia.
2.00

T.O.R.B.
5.000 RSC PIPE 34" Ø
8.62

MAIN CIRCUIT BREAKER


50 AMP, 3"Ø,230V, 2 WIRE

ALUMINUM SHALLOW REFLECTOR


4.60

15 AMP/2P 20 AMP/2P
4.00

LIGHTING C1 C2 LIGHTING
20 AMP/2P 20 AMP/2P
LED GLOBAL BULB 12W
F.F.L. LIGHTING C3 C4 CONVENIENCE
0.400 20 AMP/2P 20 AMP/2P
0.40

N.G.L. CONVENIENCE C5 C6 SPARE


0.000
T.O.T.B.
-0.200

ALUMINUM REFLECTOR LIGHTS LAYOUT DETAILS ALUMINUM SHALLOW REFLECTOR DETAILS RISER DIAGRAM
1:75 E102 1:75 E102 DNTS E102

PROJECT TITLE: PREPARED AND SUBMITTED: CHECKED: REVIEWED: RECOMMENDING APPROVAL: APPROVED: SHEET CONTENT SHEET NO.
Republic of the Philippines
DEPARTMENT OF AGRICULTURE ALUMINUM REFLECTOR LIGHTS LAYOUT DETAIL
CONSTRUCTION OF BOHOL SILAGE PRODUCTION & MARKETING Date:
PHILIPPINE RURAL DEVELOPMENT PROJECT ARCHITECT/ ENGINEER ALUMINUM SHALLOW REFLECTOR DETAILS E2
Province of Bohol
ENTERPRISE BUILDING Signed and Sealed Over Printed Name
Address: EUSTAQUIO G. CALIAO CAMILO L. GASATAN JOHN TITUS J. VISTAL HON. ERICO ARISTOTLE C. AUMENTADO
RISER DIAGRAM

Municipality of San Miguel PRC No:


PTR No:
Validity:
Date issued:
16 16
ADDRESS: POBLACION, SAN MIGUEL, BOHOL ENGINEER IV-PEO I-BUILD HEAD PPMIU HEAD GOVERNOR
Issued at: TIN: