Installation & Wiring Guide

Four Door Access Controller


MCP-040 V2.0

Doc. Ver. : V2.0


2014.10.23
R&D Center
Union Community Co., Ltd.
1. Power Connector connection

BAT(-)
Backup Battery
Interface BAT(+)

DC 15V OUT DC 15V OUT

15V GND 15V GND

12V G 12V G

PWR+ PWR- 5V G 12V G

15V GND 5V GND 15V GND

DC 15V 6A DC 5V OUT DC 15V OUT


Power Adapter

Installation for MCP-040 V2.0


2. Main Board Feature

SW301
Battery Power On Switch JP151/JP152 RS485 Termination
Resistor Select Switch

Switch Setting I [ Lock Type Selection ]


JP201 : NO [ Normal Open Relay Contact ]
NC [ Normal Close Relay Contact ]
JP202 : NO [ Normal Open Relay Contact ]
NC [ Normal Close Relay Contact ]
JP203 : NO [ Normal Open Relay Contact ]
NC [ Normal Close Relay Contact ]
JP204 : NO [ Normal Open Relay Contact ]
NC [ Normal Close Relay Contact ]

Switch Setting II [ Lock Type Selection ]


JP205 : Lock Power Contact / Lock No Power Contact
JP206 : Lock Power Contact / Lock No Power Contact
JP207 : Lock Power Contact / Lock No Power Contact
JP208 : Lock Power Contact / Lock No Power Contact

Switch Setting III [ RS485 T_Resistor Selection ]


JP151 : ON [ 120ohm termination resistor ]
OFF [ Open the termination resistor ]
JP152 : ON [ 120ohm termination resistor ]
OFF [ Open the termination resistor ]

JP201~JP204
JP205~JP208
Lock Type Switch

Installation for MCP-040 V2.0


Installation for MCP-040 V2.0

Ethernet
GND
G

GND
G

12V

15V OUT
12V

15V OUT
3. Connection of Wires to terminal blocks

IN4

IN4
BELL-

BELL-
GND
G
BELL+

BELL+
IN3

IN3
EXPB

EXPB-
-

IN2

IN2
EXPA
+

EXPA+
GND
G
RDRB

RDRB-
-

IN1

IN1
RDRA

RDRA+
+

GND
G
G

GND
5V

5V OUT
12V

15V OUT
NC COM NC COM

COM
GND
G

NO/

NO/NC LOCK#4
GND
G

COM
Z4/
Z8

ZONE4/ZONE8
NO/

GND NO/NC LOCK#3


G

COM

COM
Z3/
Z7

ZONE3/ZONE7
NO/
NC COM NC

NO/NC LOCK#2
Z2/
Z6

ZONE2/ZONE6
COM
G

GND
NO/
NO/NC LOCK#1
Z1/
Z5

ZONE1/ZONE5
D14 OUT7 OUT8
D13 OUT5 OUT6
OUT6 OUT8
OUT7
OUT5
D14
D13
D04

D04
D03

D03

D12 OUT3 OUT4


D11 OUT1 OUT2
OUT4
OUT2
OUT1 OUT3
D12
D11 D02

D02
D01
D01

PWR+ PWR-
GND
15V IN
4. Connecting Virdi Reader

Virdi
Reader
J253
Virdi
Reader
BELL-
BELL+

EXPB-
EXPA+
RDRB-
RDRA+

J252 or J254

GND
12V

Virdi
Reader
ON OFF 1:RED : +15V
2:Black : GND Max Virdi Reader 8ea
RDR JP151
3:Green : 485A+ (AC6000*4EA + VS-R20D*4EA)

4:Blue : 485B- *SR100 : DC 5V Input


ON OFF

EXP JP152

RS-485 Termination Resistor Select S/W : SW151

Installation for MCP-040 V2.0


5. Connecting Wiegand Reader
J255

OUT2
OUT1 Wiegand
Reader1
D01
D11
J255

OUT4
Wiegand
OUT3
Reader2
D02
D12
J256

OUT6
Wiegand
OUT5
Reader3 1:RED : +15V
D03 2:Black : GND
D13 3:Brown : Wiegand IN1
4:Pink : Wiegand IN0
J256 5:Green : Buzzer or LED
OUT8 6:Violet : Buzzer or LED

OUT7 Wiegand
Reader4
D04
D14

J252 or J254
GND
12V

Installation for MCP-040 V2.0


6. Connecting PGM(Open Collector)
J255 +12 VDC

OUT2
- Coil +

OUT1
D01 NO

NC
D11
Relay COM

J255

OUT4
OUT3
D02
D12
J256

OUT6
+12 VDC
OUT5
D03 - Coil +

D13
NO
J256 NC

OUT8 Relay COM

OUT7
D04
Ensure a common ground is
D14 connected between relay power
supply and MCP040

Installation for MCP-040 V2.0


7. Connecting Zone

Installation for MCP-040 V2.0


8. Connecting BELL/Siren

J253

BELL-
BELL+

EXPB
EXPA
RDRB
RDRA Bell/Siren

Bell Supervision Resistor 2200Ω 5%

Installation for MCP-040 V2.0


9. Connecting Dead-
Dead-Bolt Type Door Lock (Fail Safe)
Safe)
J251
LOCK4
COM
NO/NC
COM
NO/NC
COM Red : Lock (+)
NO/NC Black : Lock (-)
COM Green : Door Monitor (NO)
NO/NC LOCK3 Gray : Ground (Door Status Com)
J251
GND
GND
Z4/Z8
GND Lock Type Select S/W
Z3/Z7
Z2/Z6 LOCK2 JP201
GND
Z1/Z2 NC C NO
Lock1
JP205
Nor nPWR

LOCK1 JP202
Lock2 NC C NO
JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


10. Connecting Dead-
Dead-Bolt Type Door Lock (Fail Safe)
Safe)
J251
**Use external DC Power adapter
LOCK4
COM
NO/NC
COM
NO/NC
COM Red : Lock (+)
NO/NC Black : Lock (-)
COM Green : Door Monitor (NO)
NO/NC LOCK3 Gray : Ground (Door Status Com)
J251
GND
GND
Z4/Z8
GND Lock Type Select S/W
Z3/Z7
Z2/Z6 LOCK2 JP201
GND
Z1/Z2 NC C NO
Lock1
JP205
Nor nPWR

LOCK1 JP202
(+) External (-) Lock2 NC C NO
Power JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


11. Connecting EM Type Door Lock (Fail Safe)
Safe)
J251
LOCK4
COM Red : Lock (+)
NO/NC
COM Black : Lock (-)
NO/NC Orange : Door Monitor
COM
NO/NC
COM
NO/NC LOCK3
J251
GND
GND
Z4/Z8
GND Lock Type Select S/W
Z3/Z7
Z2/Z6
LOCK2 JP201
GND
Z1/Z2 NC C NO
Lock1
JP205
Nor nPWR

LOCk1 JP202
Lock2 NC C NO
JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


12. Connecting EM Type Door Lock (Fail Safe)
Safe)
**Use external DC Power adapter
J251
LOCK4
COM
NO/NC
COM Red : Lock (+)
NO/NC
COM
Black : Lock (-)
NO/NC Orange : Door Monitor
COM
NO/NC LOCK3
J251
GND
GND
Z4/Z8
GND Lock Type Select S/W
Z3/Z7
Z2/Z6
LOCK2 JP201
GND
Z1/Z2 NC C NO
Lock1
JP205
Nor nPWR

LOCk1 JP202
(+) External (-) Lock2 NC C NO
Power JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


13. Connecting Strike Type Door Lock (Fail Safe)
Safe)
J251
COM
NO/NC
COM
NO/NC LOCK4
COM : Lock (+)
Red
NO/NC
COM Black : Lock (-)
NO/NC Orange : Door Monitor
J251
GND
GND
Z4/Z8
LOCK3
GND
Lock Type Select S/W
Z3/Z7
Z2/Z6 JP201
GND
NC C NO
Z1/Z2 LOCK2 Lock1
JP205
Nor nPWR

JP202
LOCK1 Lock2 NC C NO
JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


14. Connecting Strike Type Door Lock (Fail Safe)
Safe)
**Use external DC Power adapter
J251
COM
NO/NC
COM
NO/NC LOCK4
COM : Lock (+)
NO/NC
Red
COM Black : Lock (-)
NO/NC Orange : Door Monitor
J251
GND
GND
Z4/Z8
LOCK3
GND
Lock Type Select S/W
Z3/Z7
Z2/Z6 JP201
GND
NC C NO
Z1/Z2 LOCK2 Lock1
JP205
Nor nPWR

JP202
(+) External (-) LOCK1 Lock2 NC C NO
Power JP206
Nor nPWR
J253
IN4 Inside Door JP203
GND Open S/W4 NC C NO
IN3 Lock3
IN2 Inside Door JP207
GND
Open S/W3 Nor nPWR
IN1
Inside Door JP204
Open S/W2 NC C NO
Lock4
Inside Door JP208
Open S/W1 Nor nPWR

Installation for MCP-040 V2.0


15. Connecting Auto-
Auto-Door ( Contact Control )

Auto Door Operating Part Auto Door Motor Auto Door Operating Part Auto Door Motor

Sensor Input Line Sensor Input Line

Auto-Door Monitor Auto-Door Monitor


Auto-Door Sensor Auto-Door Sensor
COM N.O. COM N.O.

J251 LOCK4 Inside Door LOCK3 Inside Door


COM Open S/W Open S/W
NO/NC
COM
NO/NC
COM
Lock Type Select S/W
NO/NC
COM JP201
NO/NC Lock1
NC C NO

JP205
Nor nPWR

JP202
Auto Door Operating Part Auto Door Motor Auto Door Operating Part Auto Door Motor Lock2 NC C NO

JP206
Nor nPWR

Sensor Input Line Sensor Input Line JP203


NC C NO
Lock3
JP207
Auto-Door Monitor Auto-Door Monitor Nor nPWR
Auto-Door Sensor Auto-Door Sensor
COM N.O. COM N.O. JP204
NC C NO
Lock4
JP208
Inside Door LOCK2 Inside Door Nor nPWR

Open S/W Open S/W


LOCK1

Installation for MCP-040 V2.0


16. Wiring Guide System Overview

Installation for MCP-040 V2.0


18. Wiring/Cable Recommendations

1. RS485 (RDR+, RDR-


RDR-)
22AWG – 2 Pair Twisted, Mylar screened
Home run, maximum distance 1000m

2. Ethernet
Standard CAT5 cable
Note: Cross over cable is required for direct connection to PC

3. Lock Monitoring , IN1-


IN1-4, OUT1-
OUT1-8, ZN1-
ZN1-8
22AWG~24AWG – 2 Pair Twisted, Mylar screened

4. +12Vdc Supply to Readers, Locks, etc


22AWG – 2 Pair Twisted, Mylar screened
-15Vdc @ 300ma, 22AWG = 250meters , voltage at device ~ 11.03Vdc
-15Vdc @ 1000ma, 22AWG = 75meters , voltage at device ~ 11.03Vdc

NOTE: If distance is to be exceeded then an external power supply


should be used for powering the device. Voltage at the reader and locks should be higher than
11Vdc.

Please visit http://www.calculator.net/voltage-drop-calculator.html for calculating approximate distance with


current and voltage requirements for your device.

Installation for MCP-040 V2.0


17. Factory Reset

J252 or J254

GND
12V

Resistor 2200Ω & 3900 Ω


J255
OUT2
OUT1
D11
D01

J253
IN4
GND
IN3
IN2
GND
IN1

1) Power down the MCP040.


2) Connect a wire between 12V+Resistor+OUT1+IN1 (J252/J255/J253).
3) Power up the MCP040.
4) After about one second remove the piece of wire.
5) All parameters and users will now be at factory reset state.