Professional Documents
Culture Documents
VDS 2095 Guidelines For Automatic Fire Detection and Fire Alarm Systems - Planning and Installation
VDS 2095 Guidelines For Automatic Fire Detection and Fire Alarm Systems - Planning and Installation
8529928001-2018-08-15 10:32
Extracts from DIN VDE 0833-2 (VDE 0833-2):2009-06 are reproduced by permission 192.010 of
DIN Deutsches Institut für Normung e.V. (German Institute for Standardization) and VDE Verband
der Elektrotechnik Elektronik Informationstechnik e.V. (Association for Electrical Electronic and
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Information Technologies). Any further reproductions or editions are subject to separate permission.
Relevant for applying the standards are their latest editions, available from VDE VERLAG GMBH,
Bismarckstr. 33, 10625 Berlin and Beuth Verlag GmbH, Burggrafenstr. 6, 10787 Berlin.
CONTENTS
Preface VdS 2095en .......................................................................................................... 5
General .............................................................................................................................. 5
Validity .............................................................................................................................. 5
Changes ............................................................................................................................. 6
Previous editions .............................................................................................................. 6
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
1 Scope ................................................................................................................... 7
2 Normative references ......................................................................................... 7
3 Terms and abbreviations ................................................................................... 9
3.1 Terms and definitions............................................................................................ 9
3.2 Abbreviations ...................................................................................................... 11
4 Basic requirements for components of fire detection and fire
alarm systems ................................................................................................... 11
4.1 General ............................................................................................................... 11
4.2 Fire detectors ...................................................................................................... 12
4.3 Monitored transmission paths ............................................................................. 12
4.4 Control and indicating equipment (CIE) .............................................................. 13
4.5 Power supply ...................................................................................................... 13
4.6 Signalling devices .............................................................................................. 13
5 Requirements for the triggering of fire protection systems......................... 13
6 Rules for the planning and installation of fire detection and fire
alarm systems ................................................................................................... 14
6.1 Principles ............................................................................................................ 14
6.2 Planning .............................................................................................................. 21
6.3 Alarm ................................................................................................................... 41
3
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
4
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Validity
These guidelines will become operative on May 1st, 2010 superseding the edition
VdS 2095en:2005-02 (06).
Fire detection and fire alarm systems planned up to one year after publication of these
VdS 2095en Guidelines on the basis of the former Guidelines (VdS 2095en:2005-02)
may be completed, commissioned and operated on the basis of the former Guidelines.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
5
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Changes
With respect to DIN VDE 0833-2 (VDE 0833-2):2004-02 the following changes were made:
a) this version has been revised editorially on the basis of the European working results
of CEN TC 72. The terms and definitions have been adapted to the set of standards
EN 54, where available;
b) the terms two signal and two zone dependency have been replaced by the term
“coincidence detection type A” and coincidence detection type B” relevant in DIN EN 54-2;
c) the specification regarding the arrangement of manual call points has been worded more
precisely. The instruction for the marking of decommissioned manual call points has been
adopted;
d) the exceptions from the monitoring of system floors, false floors or porous screed have
been worded more precisely;
e) Table 1 has been supplemented with smoke detectors according to DIN EN 54-12 and
heat detectors according to DIN EN 54-22;
f) Table 2 has been supplemented with aspirating smoke detectors according to DIN EN
54-20 and line type heat detectors according to DIN EN 54-22. The restriction of 128
detectors to one transmission path has been cancelled, since inconsistent with DIN
EN 54-2. The number of flooding zones to be triggered by a loop has been added and
specified with a maximum number of 8;
g) also the specification of a maximum number of 4 fire compartments in cases where
only manual call points are operated via a loop has been added;
h) the specification of number and arrangement of automatic fire detectors under 6.2.7.1
has been worded more precisely and a note on the consideration of perforated
ceilings has been added;
i) Table 3, specifying the maximum width to height ratio of the monitoring area for point
type smoke and heat detectors has been added;
j) details of the arrangement of line type heat detectors (6.2.7.12), the arrangement of
multipoint heat detectors (6.2.7.13) as well as the arrangement of detectors in
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Previous editions
DIN VDE 0833-2(VDE 0833-2): 1982-08, 1992-07, 2000-06, 2004-02
DIN VDE 0833-2 Amendment 1 (VDE 0833-2 Amendment 1): 2000-12
VdS 2095 : 2005-02, 2001-03, 1995-06, 1993-08
6
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
1 Scope
These guidelines together with DIN VDE 0833-1 (VDE 0833 Part 1) and DIN 14675 are
applicable to the planning, installation, extension, modification and operation of fire
detection and fire alarm systems. It provides specifications for fire detection and fire alarm
systems for the protection of life and property in buildings.
NOTE 1 Basically the routing of fire alarms to the response authorities, reference is made to
the set of standards EN 50136 "Alarm systems – Alarm transmission systems and
equipment" and to DIN 14675 "Fire detection and fire alarm systems – Design and operation".
These guidelines do not contain any specifications for the interaction of fire detection and
fire alarm systems with other systems not fulfilling any functions in terms of fire protection.
A proper interaction of all parts of a fire detection and fire alarm system with other
systems – insofar as required for an unrestricted function of the fire detection and fire
alarm system – shall be ensured, however, in any case.
NOTE 2For more information please see DIN VDE 0833-1 (VDE 0833 Part 1): 2009-09, Cl. 1.
Alarm systems according to DIN V VDE V 0826-1 (VDE V 0826-1, VdS 3431 and VdS
3438 as well as networked or non-networked smoke alarm devices according to EN
14604 are no fire detection and fire alarm systems in the sense of these guidelines.
2 Normative references
The documents quoted below are absolutely required for the application of this document.
Dated references refer to the issue to which reference is made. Undated references refer
to the latest applicable issue of the document to which reference is made (including all
amendments).
DIN 1450:1993-07, Lettering, legibility
DIN 4066, Information signs for fire brigade
DIN 4102-1, Fire behaviour of building materials and building components, Part 1:
Building materials, concepts, requirements and tests
DIN 14623, Signs for orientation at automatic fire detectors
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
DIN 14661, Fire fighting equipment – Fire brigade control panel for fire detection and fire
alarm systems
DIN 14662, Fire fighting equipment – Fire brigade indication panel for fire detection and
fire alarm systems
DIN 14675:2003-11, Fire detection and fire alarm systems – Design and operation
DIN 14675/A1:2006-12, Fire detection and fire alarm systems – Design and operation;
Amendment A1
DIN 14675/A2:2009-06, Fire detection and fire alarm systems – Design and operation;
Amendment A2
DIN 14678, Manual call points (fire detectors) type K for use in potentially explosive
operation rooms by gases or dust
DIN 33404-3, Danger signals for workplaces, auditory danger signals, unified emergency
signal, technical requirements of safety, testing
DIN EN 54 (all parts), Fire detection and fire alarm systems
DIN EN 54-4, Fire detection and fire alarm systems – Part 4: Power supply equipment;
German version EN 54-4: 1997/A1:2002
7
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
DIN EN 54-5:2001-03: Fire detection and fire alarm systems – Part 5: Heat detectors –
Point detectors; German version EN 54-5:2000
DIN EN 54-7:2001-03, Fire detection and fire alarm systems – Part 7: Point detectors
using scattered light, transmitted light or ionisation, German version EN 54-7:2000
DIN EN 54-11:2001-10, Fire detection and fire alarm systems- Part 11: Manual call
points, German version EN 54-11:2001
DIN EN 14604, Smoke alarm devices
DIN EN 50086-1 (VDE 0605-1), Electric wiring conduits, Part 1: General requirements
DIN EN 61000-4-3 (VDE 0847-4-3) : 2008-06: Electromagnetic compatibility (EMC) – Part
45-3: Testing and measurement techniques; radiated, radio-frequency electromagnetic
field immunity test (IEC 61000-4-3:2006 + A1: 2007); German version EN 61000-4-
3:2006 + A1:2008)
DIN EN 62305-1 (VDE 0185-305-1): 2006-10: Protection against lightning – Part 1:
General principles (IEC 62305-1:2006); German version EN 62305-1:2006
DIN EN 62305-3 (VDE 0185-305-3), Protection against lightning: Physical damage to
structures and life hazard
DIN EN 62305-4 (VDE 0185-305-4), Protection against lightning – Part 4: Electrical and
electronic systems within structures
DIN EN ISO 3098-0: Technical product documentation – lettering – Part 0: General
requirements
DIN VDE 0100-718) Erection of low voltage installations – Requirements for special
installations or locations – Part 718: Installations for gathering of people
DIN VDE 0815(VDE 0815): Wiring cables for telecommunication and data processing
systems
DIN VDE 0833-1 (VDE 0833-1): 2003-05 2009-09: Alarm systems for fire, intrusion and
hold-up, General requirements
DIN VDE 0833-4 (VDE 0833-4): 2007-09: Alarm systems for fire, intrusion and hold-up –
Requirements for voice alarm systems in case of fire
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
8
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
9
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
NOTE: These are in general the indicating and control facilities of the control and
indicating equipment, a detached indicator and control panel or the fire brigade indicator
panel and fire brigade control panel.
3.1.12 Line type smoke detector using transmitted light, in short: line type
smoke detector
Detector responding to smoke by attenuation and/or changing attenuation of an optical
beam and which consists of at least a transmitter and a receiver and which may be
equipped with reflectors.
3.1.16 Interface
Virtual or physical transition point between two functional units based on agreed rules for
the transfer of data and signals
10
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
3.2 Abbreviations
The following abbreviations are used for the application of this standard these guidelines:
FDASfire detection and fire alarm system
FDSfire detection system
CIEcontrol and indicating equipment
MAmonitoring area
SHEVSsmoke and heat exhaust ventilation system
FCPfire brigade control panel
FIPfire brigade indicator panel
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
FRCfire-resisting closure
FESfire extinguishing system
FZflooding zone
SHVsmoke and heat vent
TEtransmission equipment
11
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
a resulting fault is signalled to the control and indicating equipment (e.g. standardised
interface for extinguishing systems).
NOTE 2: Signals and information from other systems transmitted by the transmission
paths of the fire detection and fire alarm system shall not affect the function of the fire
detection and fire alarm system.
In cases where non-exclusive transmission path used for hazard alarm purposes may be
affected by external signals, provision shall be made for a second option for transmission.
The continuous actuation of a manual call point or the continuous release of a fire
detector shall not result in an automatic repetition of the alarm.
Faults such as open or short circuits on a transmission path or a fault on a section of the
transmission path between the individual CIEs and faults on the transmission paths to the
higher level CIE(s) or indication and actuation devices shall not affect the proper function
of the system.
A section of a transmission path is that part of the transmission path to which in the case
of a fault the effects are limited e.g. by short circuit isolators or otherwise.
NOTE 3: Faults on more than one transmission path or on more than one section of a
transmission path through which one or several CIEs are linked to a higher level CIE or to
a higher level indicating and control place may jeopardise the function of the system.
12
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Warnings and information such as extinction and release signals of triggering devices of the
fire detection and fire alarm system to the fire extinguishing system shall be transmitted
separately for each single flooding zone. Fault warnings from the fire extinguishing system
to the fire detection and fire alarm system (control and indicating equipment) shall be
transmitted at least as a general fault.
In the case of triggering fire extinguishing systems it is to be ensured that as a result of a
fault of the triggering device of the CIE not more than one flooding zone fails or a release in
error occurs in maximum one flooding zone.
NOTE 2: For fire extinguishing systems which could cause a hazard to life it is important to
ensure that the measures for the protection of life are observed both in the case of a
release under fire conditions and a release in error.
Detectors and other parts of the FDAS may be used in hold-open systems of fire-resisting
closures (FRC). In this case the following shall be met:
– The guidelines of DIBt are to be applied.
– Additional triggering of FRC by other fire detectors or detector groups is accepted.
– Fire detectors of FRC shall not trigger any transmission devices.
– In the case of an alarm (fire alarm), fault (interruption, short circuit, power failure) or a
manual release, the control device shall activate (de-energise) the connected hold-
open device reliably and without delay
13
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
operated manually. The user who is in charge of the fire detection and fire alarm concept
is expected to define the action plan in cooperation with the authorities in charge, the
planner and if appropriate also with the installer of the FDAS.
The following shall be ensured in particular:
– alerting of persons exposed to the hazard and guidance as basically of escape
routes, if necessary;
– fire alarm transmitted to the fire brigade in charge and/or to the fire fighting and
rescue forces on site;
– prevention of a rapid spread of the fire by actuation of the fire protection devices, e.g.
FRC;
– opening of the access routes for the fire brigade.
Fire alarms and fault warnings shall be indicated and transmitted as appropriate so as to
ensure that the responsible staff is informed as early as possible.
Faults warnings shall be transmitted immediately to the maintenance person.
14
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
15
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
– inaccessible cable ducts and shafts that have fire-resistant separation (F 90 A) are
separated from other areas by non-combustible structural elements of at least 90 min
fire resistance according to the national certificate of suitability;
– shelters not used for any other purpose;
– outdoor loading ramps;
– rooms protected by an automatic fire extinguishing system with alarms transmitted to
a remote station; unless the fire detection and fire alarm system is required for the
triggering of a fire extinguishing system or for other purposes, e.g. alerting of
persons;
NOTE: This exception is cancelled, when a fire detection and fire alarm system is
required for the triggering of fire extinguishing systems or for other reasons, e.g. alerting
of persons.
– other small areas, unless critical for reasons of fire load, where neither hazard to life
nor smoke spread are possible.
Exceptions from monitoring are also acceptable for false ceilings and false floors
provided that all of the following conditions are met:
– the enclosing elements (ceiling, floor, wall) shall be fire-resistant (building material
class A according to DIN 4102-1);
– the spaces shall be subdivided by fire-resistant elements so as to result in
compartments of maximum 10 m in width and 10 m in length, and the spaces above
and below corridors of less than 3 m in width shall be subdivided by non-combustible
material fire-resistant structural elements so as to result in compartments of a length
not exceeding 20 m;
– the fire load shall be less than 25 MJ, related to an area of 1 m x 1 m.
System floors, double floors and porous screed are exempt from monitoring, provided
that all of the following conditions are met:
– height not exceeding 0.2 m;
– not used for room ventilation.
The area to be protected shall be subdivided into detection zones. The detection zones
shall be defined so as to allow immediate and unambiguous identification of the location
of the alarm and of the fire. This can be accomplished by combining the fire detectors of
one detection zone to form detector groups.
16
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Smoke, heat and flame detectors or a combination of various types of fire detectors may
be used where an open, rapidly developing fire is expected in the incipient phase (strong
development of heat, radiation of flames and/or heavy development of smoke).
NOTEUV detectors should not be used in environments exposed to dust, UV absorbing
vapours and condensation on the detector. IR flame detectors operating in the CO2-
emission band of the hot flame may not be used for the detection of fires involving
inorganic substances and metals.
Where an outbreak burst of a fire associated with a strong development of smoke is expected,
UV detectors should not be used or if at all in combination with smoke detectors only.
6.1.5.3 Room height
The higher a room or the greater the distance between the seat of the fire and the ceiling,
the larger is the zone of uniform but lower concentration of smoke.
The relationship between the suitability of the individual types of detectors and the room
height is reflected in Table 1.
Higher parts of the ceiling, covering an area of less than 10 % of the aggregate ceiling
surfaces shall remain unconsidered, provided these parts of the ceiling do not exceed in
size 0.6 times the maximum monitoring area of a detector. Otherwise the areas at higher
ceiling heights shall be considered as separate spaces.
Limitations of room height for use of point type smoke detectors
The application of point type smoke detectors is generally limited to a room height of 12 m.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
17
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Room Point type Line type Aspirating Point type Line type Point type
height smoke smoke smoke heat heat flame
detectors detectors detectors detectors detectors detectors
DIN EN 54-7 DIN EN 54-12 DIN EN 54-20 DIN EN 54-5 DIN EN 54-22 DIN EN 54-10
Classes Classes Classes Classes
A, B and C A1, A2, B, C, A1, and A2, 1, 2 and 3
D, E, F and G B, C, D, E, F
a, b and G
b, e
up to 45 m c
Class A
up to 20 m d c
only d
Classes A
up to 16 m unsuitable and B only c
d
up to 12 m
up to 9 m Class A1 only
up to 6 m
unsuitable
suitable depending on occupancy and ambient conditions (e.g. rapid development of fire and
smoke spread)
suitable
b Classes B, C, D, E, F and G suitable for equipment local protection monitoring systems only
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
18
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
General
Critical are all areas where deceptive alarms are to be expected due to operational
conditions. This holds true particularly in cases subject to the following conditions:
– dust and lint
– smoke due to operational conditions
– exhaust gases of combustion engines
19
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
– vapours
– other sources of false alarms (e.g. formation of steam etc.)
When smoke detectors are used in critical areas, these detectors shall be switched to
coincidence detection type B. Preference should be given to multi sensor smoke detectors,
line type smoke detectors or aspirating smoke detectors equipped with VdS-approved
separators and/or filters. A combination of smoke detectors and flame detectors is possible
in individual cases as specified in these guidelines or as specifically coordinated with VdS.
Heat detectors may also be used – according to ambient conditions and fire risk involved.
In these cases coincidence detection type B is not required.
NOTE: Also heat detectors may produce false alarms under critical ambient conditions
(e.g. bakeries). Heat radiation and low ambient temperatures shall be considered also.
Instead of coincidence detection type B other techniques may be applied also, provided
that they are VdS-approved.
Examples of critical areas
The following sources of false alarms as well as the following materials may affect the
correct function of smoke detectors:
– dust, in particular dust producing storage goods, e.g. bulk material
– lint, e.g. in the textile industry
– machining of material such as combustible material, wood, plastics etc.
– residual oil and dirt in touch with machine components
– oil mist, vapours of cutting oils
– exhaust gases of combustion engines, in particular diesel engines
– tobacco smoke
– vapours and aerosols of alcohols and solvents in production, processing and storage
areas
3.9.5.1, are not fulfilled for the operating times 4 h and 30 h, it shall be possible to
maintain the specified function of the FDAS for an operating time of at least 72 h.
The required capacity of the battery depends not only on the power demand of the FDAS
in the quiescent condition, but also on
– the time interval between detection of a mains supply failure; and
– the availability of maintenance staff; and
– the provision of spare parts; and
– the availability of an emergency power supply unit.
It shall be possible to keep up the supply of the alarm system in the quiescent condition
by the battery at least for the following operating time:
– 4 hours in cases where an emergency power supply unit and spare parts are
available for the alarm system and failure of the mains supply is detected at any time
(permanently manned location in charge) and the maintenance staff is available at all
times;
– otherwise 30 hours.
In the case of a standby duration (operating time) of 4 hours (see 6.2.8) the emergency
generator shall be able to maintain the operation of the FDAS for at least 30 h.
20
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
6.2 Planning
6.2.1 Control and indicating equipment
A fault of the signal processing unit basically may affect detection zones of a total of
maximum 12 000 m2 in size, however, not more than 512 detectors.
The detector groups shall remain functional in the case of a fault of a signal processing
unit affecting detection zones of more than 12 000 m2 in total size or of more than 512
detectors.
The fire alarm condition shall be indicated by a general visual alarm indication and by an
audible signal at a permanently manned location.
In the case of a fire alarm, it shall be warranted that both the alarm devices and the
transmission device can be triggered. The release of the transmission device shall also
be indicated at a permanently manned location.
A fault of the indicating device basically may affect detection zones of a total area of
maximum 12 000 m2 in size, however, not more than 512 detectors. If the total area is
larger than 12 000 m2 or if the number of detectors is assigned to an indicating device
higher than 512, provision shall be made either for
– an additional indicator panel (including decoding device) as a passive reserve; or
– a fire brigade indicator panel according to DIN 14662; or
– a logging device run in parallel.
The area to be protected may be up to 48 000 m2 in size, provided the above conditions
are observed.
In cases where the control and indicating equipment is equipped with redundant signal
processing and indicating devices, the size of the protected area may be larger than
48 000 m2.
detection zones.
A detection zone shall not exceed a fire compartment and should shall not be larger than
1 600 m2 in size.
Failure of a detector or of a peripheral device shall not affect more than one detection
zone.
Several rooms may be combined to form one detection zone only if
– these rooms are adjacent to each other, the number of these rooms does not exceed
five and the total area of these rooms is not larger than 400 m2; or
– these rooms are adjacent to each other, access can be surveyed easily, the total
area does not exceed 1 000 m2 and well visible optical alarm indications identifying
the room affected by the fire are in place close to the entrances. The optical alarm
indicator shall be mounted – where structurally possible – to the wall above the
access door. Marking shall be in accordance with DIN 14623; or
– these rooms are adjacent to each other, the total area does not exceed 1 000 m2 and
the alarm condition of the individual detectors is indicated on the CIE.
21
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
22
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Number and place of installation of manual call points shall ensure that a person need not
cover a distance of more than 50 m to the next manual call point.
In hazardous workplaces or according to the use and condition of a building, manual call
points shall be arranged in terms of numbers and installation sites so as to ensure that a
person need not cover a distance of more than 30 m to reach the next manual call point.
6.2.6.2 Decommissioning of manual call points
Each manual call point that has been decommissioned shall be marked with a label
"Außer Betrieb" and "Out of order" that cannot be removed from the outside (font height
at least 0.1 times housing height) and, if so, it shall also be marked with a symbol of a
height that is at least 0.15 times the housing height; the font height shall not exceed the
symbol height. The lettering shall be in accordance with EN ISO 3098-0; 1998 with
lettering ISO 3098-BVL.
These symbols and letterings shall be black with the black area not exceeding 30 % of
the total area of the operating face.
NOTE: A suitable black colour is specified in ISO 3864-1. The actuation element of
manual call points that have been decommissioned shall not be recognisable any longer.
Options for marking the decommissioned state shall be available.
23
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
24
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Legend
1 stair landing
2 stairwell: clear width or airspace, enclosed by stair landings and stair heads and often
extending over several floors
3 stairway hole: cut-out for the staircase in the floor ceiling or in a tier of beams
4 fire detector
Figure 2 – Top and sectional view of a stairwell
6.2.7.2 Monitoring area of smoke and heat detectors
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
The number of point type smoke and heat detectors shall be chosen so as to ensure that
the maximum monitoring areas A indicated in Table 2 are not exceeded.
Table 2: Monitoring areas of point type smoke and heat detectors
Roof pitch α
Surface of the room
Type of automatic fire detector Room height
to be monitored up to 20° over 20°
A A
Point type smoke detectors DIN EN 54-7
up to 80 m
2 Aspirating smoke detectors DIN EN 54-20, up to 12 m 80 m
2
80 m
2
a
Classes A, B and C
2 2
Point type smoke detectors DIN EN 54-7 up to 6 m 60 m 90 m
Aspirating smoke detectors DIN EN 54-20, over 6 m
a 2 2
Classes A, B and C 80 m 110 m
up to 12 m
2 Point type smoke detectors DIN EN 54-7
over 80 m over 12 m
Aspirating smoke detectors DIN EN 54-20, 120 m
2
150 m
2
a, f up to 16 m
Classes A and B
Aspirating smoke detectors DIN EN 54-20, over 16 m
Classes A
a, f e e
up to 20 m
25
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Roof pitch α
Surface of the room
Type of automatic fire detector Room height
to be monitored up to 20° over 20°
A A
Point type heat detectors EN 54-5,
c
(Classes A1, A2, B, C, D, E, F, and G)
up to 6 m
Multipoint Line-type heat detectors EN 54-
d, g, h
22, (Classes A1 and A2) 30 m
2
30 m
2
Angle formed by the roof and ceiling inclination to the horizontal; if a roof or a ceiling
α
has different inclinations, e.g. a shed roof, the smallest angle shall count.
a per suction hole
The room height measured at the highest point shall be considered in the case of
b
pitched roofs.
c Also detectors of Suffix R or S
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
26
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
In case of coincidence detection type B the space between two detectors operated in
coincidence detection shall not fall below 2.5 m.
On principle, the detectors shall be assigned so as to ensure that neighbouring detectors
in the same room are operated in coincidence detection. In the case of line type heat
detectors, neighbouring sensor lines shall belong to different detectors.
Coincidence detection of more than 2 alarms for achieving the fire alarm condition is not
allowable – except in substantiated cases.
Basically multi-sensor detectors, i.e. detectors able to detect different fire parameters
(e.g. smoke, heat), the maximum monitoring areas A as indicated in Table 2 shall apply
as a function of VdS approval, room height and area of the room to be monitored. Multi-
sensor detectors – if correspondingly approved by VdS – may be equipped with a facility
for switching-off individual sensors; for the remaining not disabled part of the detector the
maximum monitoring areas A (as a function of room height and surface of the room to be
protected) as indicated in Table 2 continue to apply. Moreover, this single part of the
detector shall comply with the corresponding standard, e.g. DIN EN 54-5 or DIN EN 54-7.
Multi-sensor detectors are not considered to be integrated coincidence detection type B,
since the sensors are not spatially separated from each other.
NOTEIf detectors are used, which detect different phenomena of fire, the time until
indication of the fire alarm condition may become longer.
In individual cases deviating specifications may apply to the prevention of false alarms.
6.2.7.3 Split of the space to be monitored into monitoring areas
The detectors by splitting of the space to be monitored into monitoring areas (Table 2)
should be arranged so as to ensure that the largest distances of the detectors (also
sensor points or suction holes) to randomly selected points with all detectors at ceiling
level are almost the same in rooms and corridors.
For the largest distance (horizontal distance) between an automatic point type smoke and
heat detector (also sensor point or suction hole) and a randomly selected point at ceiling
level is called the DH dimension.
Either adherence to the DH dimension or adherence to the maximum width to height ratio
shall be checked for changing a monitoring area from the ideal square surface to a
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
27
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Legend
A maximum monitoring area per detector (or suction hole)
D largest horizontal distance of a randomly selected point at ceiling level to the next detector (or suction hole)
H
α angle of the roof/ceiling pitch to the horizontal plane; where a roof or ceiling has various angles of
inclination, e.g. shed roofs, it is the smallest existing angle of inclination that counts
Figure 3: Horizontal distances for point type smoke detectors according to DIN EN 54-7
or DIN EN 54-20
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Legend:
A Maximum monitoring area per detector (or sensor point)
D Largest horizontal distance of a randomly selected point at ceiling level to the next detector (or sensor point)
H
α Angle of roof/ceiling pitch to the horizontal plane; where a roof or a ceiling has various angles of
inclination, e.g. shed roofs, it is the smallest existing angle of inclination that counts
28
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Figure 4: Horizontal distances for point type or multipoint heat detectors according to DIN
EN 54-5 or DIN EN 54-22
In the absence of the ideal monitoring area of square shape, the following ratios of width
to height a and b shall be observed:
b/[m]
12
11
10
7
60 m², DH=5,7 m
6
5 40 m², DH=4,7 m
30 m², DH=4,1 m
4 a/[m]
4 5 6 7 8 9 10 11 12
18
77 m², DH = 8 m 80 m², DH = 8,2 m
16
90 m², DH = 8,7 m
14
110 m², DH = 9,6 m
12
10
4 63 m², DH = 7,2 m
45 m², DH = 6,1 m
55 m², DH = 6,8 m
2
2 4 6 8 10 12 14 16 18 a/[m]
29
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
b/[m]
6 30 m², DH = 4,4 m
21 m², DH = 3,6 m
3 20 m², DH = 3,5 m
15 m², DH = 3,1 m
10 m², DH = 2,5 m 14 m², DH = 3 m
2
2 3 4 5 6 7 8 a/[m]
13
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
11
40 m², DH = 8 m
7 30 m², DH = 5,7 m
28 m², DH = 5,5 m
5 21 m², DH = 4,7 m
30
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
For exact values of the DH values resulting from the different applications, please refer to
Tables 3a and 3b.
Table 3a: DH-values as a function of the maximum monitoring area for point type smoke
detectors and points of aspirating smoke detectors
Table 3b: DH –values as a function of the maximum monitoring area for point type and
multipoint heat detectors
Roof pitch α
A: up to 20° α>20°
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
DH
31
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
6.2.7.4 Arrangement of point type smoke and heat detectors (also sensor points
or suction holes) on ceilings with ceiling joists
cases where the individual ceiling bay formed by subdividing elements to be considered
is larger than 0.6 A, each ceiling bay shall be equipped with detectors (also sensor points
or suction holes).
NOTE: Where 1.2 times the maximum monitoring area A indicated in Table 2 is applied,
the corresponding maximum horizontal distance DH for smoke detectors according to
Figure 3 and Table 3a and for heat detectors according to Figure 4 and Table 3b shall be
determined related to this increased monitoring area.
Smoke detectors (or suction holes) may be installed on the subdividing elements where
the distance of the subdividing elements to each other is less than 1 m.
32
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
In cases where subdividing elements attached to the ceiling need not be considered,
point type smoke detectors (or suction holes) may be installed on these subdividing
elements.
6.2.7.5 Arrangement of point type smoke and heat detectors (also sensor points
or suction holes) in narrow aisles and narrow ceiling bays
In corridors and ceiling bays up to 3 m in width, detectors may be spaced as follows:
Heat detectors (or sensor points) up to 10 m apart from each other, in the case of
coincidence detection type B up to 5 m ,
Smoke detectors (or suction holes) up to 15 m apart from each other, in the case of
coincidence detection type B up to 11 m or 7.5 m when triggering fire extinguishing
systems.
Smoke detectors may be installed on the subdividing elements where the distance of the
subdividing elements to each other is less than 1 m.
In this case the maximum monitored area of each point type smoke detector shall not be
exceeded. The distance of the detector (distance of the sensors or suction holes also) to
the front end of the aisle or of the ceiling bay shall not be greater than half of the
distances specified above. Provision shall be made for always one detector (also sensor
point or suction hole) in areas of crossings, junctions and corners of aisles. The area of
junctions also includes recesses of more than 1 m in depth and maximum 3 m in width.
6.2.7.6 Distance of point type smoke and heat detectors (also sensor points or
suction holes) to walls
The distance of detectors (also sensor points or suction holes) to walls shall not be less
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
than 0.5 m, except for aisles, tunnels and similar structures of less than 1 m in width.
Where subdividing elements, beams or air conditioning ducts are mounted below the
ceiling reaching closer than 0.25 m to the ceiling, the lateral distance to these elements
shall also be 0.5 m at a minimum.
6.2.7.7 Distance of point type smoke and heat detectors (also sensor points or
suction holes) to stored goods, equipment and fixed components
On principle, the horizontal and vertical distance of the detectors (also sensor points or
suction holes) to stored material or equipment shall not be less than 0.5 m at any point. In
the case of distances of the detectors (also sensor points or suction holes) shorter than
0.5 m to fixed components such as ducts, pipework or lighting fixtures, but also in the
case of greater distances e.g. in the area of air outlet openings, provision shall be made
to ensure that the phenomenon of fire can reach the detectors (also sensor points or
suction holes) unobstructed.
6.2.7.8 Distance and position of point type smoke and heat detectors (also
sensor points or suction holes) to ceilings and roofs
Basically, point type detectors shall be installed in horizontal position. Where roof pitches
α up to 20° are to be considered, the detectors – unless installed in suspended position –
may be fixed directly to the ceiling considering the same angle of inclination.
Basically, point type heat detectors shall not be installed in suspended position.
33
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Roof pitch α
Room height RH up to 20° over 20°
DL DL
up to 6 m up to 0.25 m 0.2 m to 0.5 m
over 6 m to 12 m up to 0.4 m 0.35 to 1.0 m
a
(over 12 m to 16 m) 0.25 m to 0.6 m 0.5 m to 1.2 m
b
(over 16 m to 20 m) 0.5 m to 0.9 m 1 m to 1.5 m
DL distance of smoke-sensitive element to ceiling or roof
α angle formed by the roof/ceiling pitch to the horizontal plane; in cases where a roof or a ceiling
has various angles of inclination, e.g. shed roofs, it is the smallest existing angle of inclination
that counts
allowed for aspirating smoke detectors only, depending on type of use and ambient conditions
(e.g. rapid smoke development and spread), effectiveness of detection to be proven by VdS
Schadenverhütung.
a aspirating smoke detectors of Classes A and B
b aspirating smoke detector of Class A
with 6.2.7.3, or one or, if required, several line type smoke detectors arranged vertically
(perpendicularly) below the roof ridge or below the highest point of the room at a
suspension length of DL – for point type smoke detectors (or suction holes) according to
Table 4, for line type smoke detectors according to Table 5.
In rooms with shed roofs of a shed height HS greater than 0.6 m, each shed – as
illustrated in Figure 6 – shall be equipped with a row of point type detectors (or suction
holes) or with one or as necessary with several line type smoke detectors. The detectors
shall be mounted to the roof surface with the smaller pitch spaced at a distance DV from
the ridge at a suspension length of DL, whereby a distance DV of at least 0.5 m shall be
kept. In the case of shed widths WS greater than 7.5 m, additional detectors shall be
provided as outlined under 6.2.7.1 (see Figure 6).
In cases where additional rows of point or line type detectors are required, distance DL
from the roof as for roof pitches α up to 20° shall be provided for all shapes of roofs.
NOTE: The average inclination α of a vault-shaped ceiling results from the angle formed
by the horizontal plane with a straight line connecting the incipient point of the vault at the
vertical plane with the crown of the vault.
34
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
where
GH = RH − VHheight of vault;
GBwidth of vault.
see Figure 6.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Figure 6: Arrangement and spacing of smoke detector for different roof and ceiling shapes
6.2.7.10 Arrangement of point type smoke and heat detectors below platforms,
grating or similar facilities
Where the height of a room is subdivided by solid platforms or platforms in form of
grating, additional smoke or heat detectors shall be installed below these facilities, in cases
where all three factors of influence (length, width and surface of platform) as a function of
detector mounting height h exceed the limit values of l, b and F indicated in Figure 7.
Grating shall be treated on equal terms to solid platforms, due to potential occupancies.
For detectors mounted below platforms made of grating, the areas of the grating around
the detector shall be closed within a radius of minimum 0.5 m. This doesn´t apply when
such platforms meet the requirements for perforated ceilings according to 6.2.7.1.
In the case of several platforms one on top of the other, no more than the lowest level
shall be equipped with smoke or heat detectors, provided the platform levels above are
exposed to low fire loads only.
35
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Type of
Height h Platform Platform Platform
automatic fire length l width b area F
detector
Heat detectors up to 7.5 m from 2 m from 2 m from 9 m
2
DIN EN 54-5
and
DIN EN 54-22
detectors
DIN EN 54-7,
DIN EN 54-12
over 6 m from 3.5 m from 3.5 m from
and 2
up to 12 m 38.5 m
DIN EN 54-20
depending on type of use and ambient conditions (e.g. rapid fire development and smoke
spread) not suitable
Figure 7: Need for Installation of point type smoke and heat detectors
The centre line of the monitoring beam shall not be closer to walls, equipment or stored
goods than 0.5 m. Recesses in subdividing elements of the ceiling passed by the light
beam are not affected by this rule.
A maximum distance of 100 m between transmitter and receiver or between
transmitter/receiver unit and a reflector is allowable for line type smoke detectors.
NOTE: Condensation and/or icing of optical components e.g. reflector shall be avoided.
Stratification layer below roof surfaces may contribute to preventing rising smoke from
reaching the ceiling. The detector shall therefore be mounted below an expected stratification
layer, which in turn may result in that the guide values for D indicated in Table 5 for D need be
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
exceeded. As a supplement to line type smoke detectors mounted below ceiling level,
additional line type smoke detectors may be mounted in an additional level below.
Where line type smoke detectors are arranged in a coincidence detection type B, the
monitoring areas specified in Table 5 need not be reduced.
Line type smoke detectors installed on ceilings with subdividing elements shall be arranged
as outlined under 6.2.7.4.
Table 5: Spacing and monitoring areas of line type smoke detectors
Room height RH DH A Roof pitch α
DL DL
2
up to 6 m 6m 1,200 m 0.3 m to 0,5 m 0.3 m to 0.5 m
2
over 6 m to 12 m 6.5 m 1,300 m 0.4 m to 0.7 m 0.4 m to 0.9 m
2
over 12 m to 16 m* 7m 1,400 m 0.6 to 0.9 m 0.8 m to 1.2 m
) ) 2
over 16 m to 20 m* ** 7.5 m 1,500 m 0.8 m to 1.1 m 1.2 m to 1.5 m
36
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
DH largest allowable horizontal distance of any point on ceiling level to the next beam
A maximum monitoring area per detector as twice the product of the largest allowable horizontal
distance DH with the largest allowable distance between transmitter and receiver or transmitter/
receiver unit and reflector
DL distance of detector to ceiling or roof
α angle formed by the roof/ceiling pitch with the horizontal plane: where a roof or a ceiling has various angles
of inclination e.g. shed roofs, it is the smallest existing inclination that has to be taken into account
depending on occupancy and ambient conditions (e.g. rapid fire development and smoke spread)
*)
provision of a second monitoring level is recommended at room heights exceeding 12 m; detectors
on the lower monitoring level shall be arranged in staggered configuration in relation to those on the
upper monitoring level
**) acceptable, provided efficacy of detection proven by VdS Schadenverhütung
up to 30 m² 4,4 m 4,4 m
up to 30 m² 3,5 m 5,0 m
DH largest allowable horizontal distance of any point on ceiling level to the nearest sensor line
α angle formed by the roof/ceiling pitch to the horizontal plane; where a roof or a ceiling has various
angles of inclination e.g. shed roofs, it is the smallest existing inclination that counts
37
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Class 1 26 m 45 m
Class 2 20 m 33 m
Class 3 13 m 23 m
)
* corresponds to the maximum edge length of a cube of (a, b or RH) × √3 .
38
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
39
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Legend:
1 air flow
2 detection point
3 diameter d of ventilation duct
4 minimum distance of detection point from bends and elbows
Legend:
1 air flow
2 detection point
3 width W of ventilation duct
4 minimum distance of the detection point from bends and elbows
5 height H of ventilation duct
40
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
where
t1 = autonomy, in hours;
I1 = total current absorbed by the FDAS upon failure of the main power source
at risk of failure, in Ampere;
I2 = total current absorbed by the fire detection and fire alarm system during
alarm period, in Ampere.
Where the fault signal indicating a failure of the main power source at risk of failure is
delayed, the delay time shall be added to the bridging time. The factor 1.25 of this
equation need be considered for bridging times of less than 24 h.
The required power for the individual control operations of fire protection devices shall be
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
considered in an energy budget to be prepared for the entire system. The energy budget
is a component part of the documentation of the system.
Only VdS-approved accumulator batteries may be used in the power supply equipment.
Unless otherwise indicated in the approval certificate, these batteries shall be replaced at
least every four years from the date of manufacture.
No system-external consumers shall be connected to the batteries.
A standby power generator for the supply of the control and indicating equipment shall be
provided with the necessary facilities for an automatic connection.
6.3 Alarm
The alarm devices shall be triggered according to the specifications of the alarm
organisation.
41
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Fire alarms raised by fire detection and fire alarm systems that are not required by the
supervisory building authorities may also be transmitted to a VdS-approved security
company (see VdS 2136, VdS-approved security companies – Directory). The
responsible fire brigade, however, shall at least be informed of the existence of a fire
detection and fire alarm system.
system.
Voice alarm shall be clear and understandable. Voice alarm shall be preceded by the
signal according to DIN 33404-3 lasting for 4 s to 10 s, followed by a pause of 1 s to 2 s
unless the alarm is a silent alarm according to DIN 14675.
DIN VDE 0833-4 (VDE 0833-4) shall be considered in cases where internal alarms are
raised by voice through a voice alarm system.
42
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
6.4 Design
6.4.1 Automatic fire detectors
6.4.1.1 General
Smoke and heat detectors for room monitoring shall not be exposed to the direct intake
airflow of air conditioning and ventilation systems.
6.4.1.2 Heat detectors
Heat detectors shall not be installed at points where due to natural or operational heat
sources the ambient temperature may rise to levels at which an unwanted response of
the detector is likely to occur. Exposure to direct sun radiation shall be avoided and all
equipment likely to produce heat radiation, hot air or hot vapours need be considered.
This applies in particular to integrating line type heat detectors.
Table C.1 contains the service and response temperatures of the individual classes of
heat detectors according to DIN EN 54-5 : 2001-03 and prEN 54-22.
Heat detectors according to DIN EN 54-5 :2001-03 of Suffix R are particularly suitable for
application in unheated buildings characterised by strong variations in temperature,
however, high rates of rise not lasting for long. Heat detectors of Suffix S are particularly
suitable for applications characterised by higher rates of rise in temperatures over longer
periods of time, e.g. in boiler rooms or kitchens.
6.4.1.3 Smoke detectors
Ionisation smoke detectors are suitable for the detection of smoke producing fires, however,
in particular for the detection of small particle size aerosols as released by open fires. The
colour of the particles is of no influence. Exclusively detectors equipped with a mechanical
protection against removal may be installed at easily accessible sites of installation.
NOTE: Easily accessible sites of installation are places where the detector can be
reached by use of easily available ways and means such as a chair, table or ladder.
Optical smoke detectors using scattered light are suitable for the detection of smoke
producing fires releasing particles of large size and bright colour – hence all types of fires
characterised by a bright and visible smoke.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Optical smoke detectors using transmitted light are suitable for the detection of smoke
producing fires releasing particles both of bright and dark colour.
Line-type smoke detectors are suitable for the monitoring of large size halls, high rooms,
cable and utility ducts or rooms with ceilings where no other type of detector may be used
due to special requirements (e.g. art historically of high value).
Line-type smoke detectors shall be arranged so as to provide for a permanent visual
communication between transmitter and receiver respectively transmitter/receiver unit
and the reflector. The optical beam shall not be interrupted by moving objects (e.g. a
travelling crane) since this would result in fault warnings or false alarms. The detectors
shall be mounted on a stable support that is free from vibrations. Account shall be taken
of temperature variations that may cause an expansion of metal structures (e.g. steel
girders) and that may result in that the focussed beam moves away from the receiver –
which in turn would result again in a fault warning or in false alarms.
When smoke detectors are installed in rooms of low height (room heights up to 3 m),
measures shall be taken to make sure that a response of the detectors to cigarette
smoking is avoided.
Measures to achieve this are for instance:
– Arrangement of detectors outside the ceiling areas located directly above fixed
workplaces,
43
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
44
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
6.4.2.3 TM Mode, fire detection and fire alarm systems with technical measures
for the prevention of false alarms
These measures may consist of:
45
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
NOTE: The requirement of the supervisory building authorities for installation of a fire
detection and fire alarm system may be based on a generally applicable regulation or in
the individual case on the building permit. Information on the above mentioned guideline
can be provided by the building authorities in the case of doubt.
6.4.3.3 Fire detection and fire alarm systems not required by the building
authorities
In the case of lines of a fire detection and fire alarm system not required by the
supervisory building authorities, the above-required functional endurance of minimum 30
minutes need not be provided, if these lines
– are routed through rooms monitored by automatic fire detectors or
– are routed through rooms exposed to low fire loads only or
– are protected by other equivalent measures of fire protection or
– are configured as a loop system where
– feed and return wire are routed in separate cables and
– these cables are installed separately in terms of fire protection in buildings and
– a single fault does not compromise the proper function of the transmission path.
6.4.3.4 Alarm devices not required by the supervisory building authorities
For lines of alarm devices not required by the supervisory building authorities, that are,
however, a component part of the fire detection and fire alarm system, a functional
endurance of minimum 30 minutes need not be observed exclusively in cases where
these lines are configured such as a loop and provided that
– feed and return lines are routed in separate cables and
– these cables are installed in buildings separately in terms of fire protection and
– a single fault does not compromise the proper function of the transmission path and
– the approval certificate confirms that alarming will not be interrupted by more than 5 s
in the case of a single fault (e.g. short circuit) of the transmission path.
separate circuit protected by a separate and specially marked fuse. The possibility of an
interruption of the circuit feeding the fire detection and fire alarm system by disconnection
of other equipment shall be excluded.
46
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
The processing times for the indication and transmission of information specified in the
relevant standards shall be observed.
All operating conditions shall at least be visually indicated in form of a general indication
on the superordinated CIE(s) or the indication and actuation devices and provision shall
be made to disclose from which CIE the information has been raised.
The alarm and fault conditions shall be indicated audibly in addition.
Faults in a control and indicating equipment, a slave control unit or in an ancillary
indicating and control device shall not result in impairing another control and indicating
equipment, slave control unit or ancillary indicating and control device.
Faults of the transmission paths between the individual CIEs and the superordinate CIE
or the indicating and control devices shall be indicated on the superordinated devices.
In cases where the same operating conditions are indicated on several CIEs or indicating
and actuating devices, indication is to be allocated unambiguously.
The responsibilities for the operation of the system shall be clearly assigned. Where in
addition to the operation of a higher level CIE or control and indicating devices, provision
is made for the operation of individual CIEs or further control and indicating devices of the
system, the control processes shall be coordinated unambiguously. This may imply that
the operation of lower level equipment is possible not before release by the
superordinated equipment is given.
of the FDAS.
6.4.6.2 Internal signalling devices
Internal signalling devices are installed indoors or within the protected premises. In cases
where visual signalling signals may be confused with other operational information, these
signalling devices shall They should be marked “fire alarm”.
47
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
48
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
polling, and the function of the control signals for the transmission device, alarm and
control devices as well as other equipment to be controlled in the fire alarm condition
shall be illustrated appropriately.
6.5.6 Certificates
If required, results of tests already performed (e.g. use of a FDAS in hazardous areas,
heat and smoke exhaust ventilation triggering, installation of overvoltage protection in the
area of the power distribution board in accordance with VdS 2833) shall be submitted by
the particular specialised companies.
49
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
6.6 Installation
The installation of the FDAS components shall be in accordance with the installation
schedule. DIN VDE 0845-1 (VDE 0845 Part 1) shall be observed where fire detection and
fire alarm systems must be protected against lightning, static charges and overvoltage
from electrical power installations.
Also DIN EN 62305-4 (VDE 0185-305-4) shall be observed for the installation of system
components in buildings equipped with protection against lightning according to
EN 62305-3 (VDE 0185-305-3).
6.6.1 Detectors
The manufacturer's instructions for installation shall be observed for the installation of
detectors. Detectors shall be mounted exclusively on structurally sound, solid planes of
mounting. The detectors shall be fitted so as to minimise the risk of mechanical damage.
Fire detectors shall be serially numbered in each detector group (Example: 3/7 means
transmission path or detector group 3, detector 7) and unambiguously. Confusable
number combinations such as "6/8" shall be provided with dots e.g. "6.8”.
The marking shall be visible, permanent and positioned at a fixed place.
The font shall be a sans-serif (e.g. Arial, Helvetica).
The font size for manual call points shall be at least 5 mm.
Automatic detectors shall be marked with a font size according to DIN EN 1450: 1993-07,
Table 2.
50
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
The transmission device shall be installed in the same room in direct proximity to the CIE
or the remote indicating and control devices.
Lines from the transmission device to the transmission network shall be installed
mechanically protected.
Junction boxes and plug-and-socket connections of the transmission network shall be
covered by mechanically stable enclosures or may be incorporated in the transmission
device.
51
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
1)
Notes on the requirements:
Buildings located on a hill: A building is considered to be located on a hill when the
baseline of the building is located above the ridge or roof level of the other buildings
around.
Region exposed to the hazard of lightning: Information on hazards involved in
lightning is provided for example in DIN V ENV 61024-1 (VDE V 0185 Part 100) in Fig.
NC.1. Depending on the location of the object, regions with an average number of >35
days/year (equivalent to more than 3,67 lightning strokes /km2 /year)(context see DIN EN
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
52
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
7 Approval test
Fire detection and fire alarm systems shall be tested in terms of function and design for
compliance with the requirements of this standard.
An approval test following installation shall ascertain compliance of the fire detection and fire
alarm system with the design documentation and with the specifications of this standard; see
DIN VDE 0833-1 (VDE 0833-1): 2003-05, 3.3 and 4 2009-09, 4.1.2 and 4.1.5.
Additional is to be tested whether the rated capacity of the standby power source at least
fulfils the computed capacity in the case of a failure of the main power source. The power
consumption of the audible signalling device on the CIE need not be considered. at an
operating time of 4 h or 30 h.
systems
In addition to the specifications of DIN VDE 0833-1 (VDE 0833-1): 2003-05, 2009-09,
Clause 5, Clauses 9.1 to 9.67 apply.
9.2 Repairs
Maintenance and repair work need be carried out for warranting a proper operation of the
fire detection and fire alarm system. Maintenance work shall be performed by an installer,
VdS-approved for the corresponding system.
Performance of these activities – on-schedule and in a skilled manner – shall be agreed
between the operator and the installer.
53
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
The installer shall be obliged to start trouble shooting within 24 h to the notification (see
also VdS 2129:2009-05, 5.1.6. m)).
The repair and maintenance work shall be performed so as to keep the functional
interruption of devices and system components shortest possible.
A functional test of the devices and system components that had failed shall be
conducted and documented after completion of the repair work.
9.5 Disablement
Where a system or parts of a system are disabled, the operator shall provide for
surveillance of these spaces until the system or parts of the system are enabled again.
Action shall be taken to keep the time of disablement of the system – hence the time of
absence of monitoring – shortest possible.
See also DIN 14675/A1:2006-12, 11.2.3.
involved shall be checked for possible parameters of influence on the fire detection and
fire alarm system and detectors shall be checked for functional readiness.
NOTE: See also DIN 14675 A1:2006-12, 11.2.
54
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
is limited to direct monitoring of the equipment and permits early detection and early
alarm in the case of incipient fires developing in the equipment.
Planning, design and maintenance of the local protection monitoring and local protection
systems shall be coordinated between the manufacturer of the devices, operator, planner
and fire detection and fire alarm system installer and the installer of the extinguishing
system, if any.
Guidelines VdS 2304 Local application for electric and electronic systems shall be observed.
The complete fire protection concept including local protection depends essentially on the
following factors of influence, which are to be determined by a risk analysis:
– internal and external fire hazards;
– life protection;
– ranking from the operational point of view;
– business interruption;
– replacement time;
– size and location of building, structural separations and technical equipment;
– system size and arrangement;
– attended or unattended operation;
– existing measures of protection.
55
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
All equipment force-ventilated by the air conditioning system shall be included in the
scope of monitoring for warranting an all-comprehensive fire protection.
Considering the individual requirements for safety and protection, the scope of protection
can be defined on the basis of the above factors of influence.
A.3.2 Planning
The local protection monitoring system shall be selected and tailored considering the
operating conditions of the equipment to be protected. The following criteria shall be
observed:
– Operational and environmental factors of influence (e.g. temperature, humidity, dust,
aerosols, vapours, radiation);
– Mode of operation (e.g. monitored and not monitored areas, clear arrangement and
accessibility of devices, short term or continuous operation);
– Type of cooling (natural, forced ventilated and liquid cooled devices);
– electromagnetic influences.
Basically local protection systems, a maximum of five functionally related pieces of
equipment adjacent to each other may be assigned to one flooding zone. At a distance of
the equipment of more than 5 m or not functionally related equipment, separate flooding
zones shall be assigned.
Preferably smoke detectors shall be used since in most cases smoke as a phenomenon
of fire will be produced in an incipient fire.
Depending on the type of construction of the device, special measures of adaptation may
be required for the detector systems if cooling by liquid media is involved.
Service and maintenance shall be carried out as unhindered as possible. The arrangement
of the aspirating smoke detectors shall be coordinated with the manufacturer of the devices.
Where point fire detectors, preferably smoke detectors, are used in the equipment, the
volume to be monitored shall not exceed 2.5 m3 per detector. One detector per piece of
equipment shall be used. If the response of the detector is impeded by integrated
components in the equipment to be monitored, additional detectors shall be provided.
Also point type fire detectors installed outside of the equipment may be used as a local
protection system of each individual pieces of equipment, considering, however, the
airflow conditions in the room, provided
– the detector can be arranged so as to be exposed to the airflow,
– the distance between the detector and the air outlet of the device is less than 1 m,
– the air change rates and airflow rates in the room are negligible.
56
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
57
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
A Aspirating smoke detector Very early detection: the detection of very dilute
providing very high sensitivity smoke for example entering air conditioning ducts to
detect the extremely dilute concentrations of smoke
that might emanate from equipment in the
environmentally controlled area such as a clean room.
B Aspirating smoke detector Early detection: for example special fire detection
providing enhanced sensitivity within or close to particularly valuable, vulnerable or
critical items such as computer or electronic
equipment cabinets.
58
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
°C °C °C °C
A1 25 50 54 65
A2 25 50 54 70
B 40 65 69 85
C 55 80 84 100
D 70 95 99 115
a also for line type heat detectors of Suffix I and N (integrating and non-integrating)
b this temperature is 29 °C below the minimum static response temperature
c this temperature is 4 °C below the minimum static response temperature
This table also applies to line type, integrating and non-integrating heat detectors
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
The static response behaviour of non-integrating, line type heat detectors is related to
a segment of the sensor line of 10 m and the maximum ambient temperature to the
maximum length of the sensor line indicated by the manufacturer.
The static response behaviour and the maximum ambient temperature of integrating,
line type heat detectors are related to the maximum length of the sensor line indicated
by the manufacturer.
59
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
60
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Fig. D.1: Standardised interface for extinguishing systems (minimum number of required
signals shown by use of flooding zone 1 by way of example)
61
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
D.3 Transmission of alarms from the fire detection and fire alarm
system to the extinguishing system
Transmission of the extinguishing signal
T1+ T = triggering signal; 1 = No. of flooding zone or alarm valve station;
+ / - = Polarity of connection
For extinguishing systems comprising more than one flooding zone or alarm valve
station, the number shall be changed, namely:
T2+ flooding zone 2 or alarm valve station 2
T2-
etc.
For extinguishing systems with selective fault warnings from more than one alarm valve
station flooding zone, the number shall be changed (see above); where a common
(general) fault warning is transmitted, this number is not required.
NOTE: In the case of a fault of the monitored paths for the transmission of a release
signal or a fault warning from the fire detection and fire alarm system to the control and
delay device and in the case of a fault on a path for the transmission of a fault warning
from the control and indicating equipment to the control and delay device, the function
mode of the alarm valve station shall be switched-over by the control and delay device
from "pre-action" to "dry system". The fault warning of the fire detection and fire alarm
system shall include all functional impairments for the extinguishing signal, e.g. detector
group disconnection, service test switching etc.
62
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
FA 1 -
NOTE 1: Faults that are not directly related to the function of the extinguishing system shall
not be transmitted to the control and indicating equipment as "extinguishing system fault”
(F). Faults of this type such as an impaired extinguishing effect due to a room closure that
has not been closed, shall be transmitted to the control and indicating equipment as an
extra/additional warning (FA).
NOTE 2: Further optional signals of the electrical control and delay device – not described
in detail at this point – shall be connected to suitable inputs on the control and indicating
equipment (e.g. blocking, manual control). It must be decided for each single signal
whether or not and where to the warning is to be automatically transmitted, e.g. warning of
leakage to the service company of the extinguishing system. The display colour for
conditions deviating from normal operating condition, shall be yellow.
63
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
NOTE 3: The control of elements for room closures and for other systems required for
warranting a proper function and the efficiency of the extinguishing system including
alarm devices is a scope of services to be rendered by the control and delay device of the
extinguishing system. Such control elements shall be provided in addition to the control
and indicating equipment only.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
64
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
65
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
A due time response of the smoke detectors may not be ensured in any case and thus
need be checked by VdS Schadenverhütung (see also 6.1.5.6) even for reduced
monitoring areas e.g. at high air change rates and admixture of fresh air.
Table E.1: Monitoring areas of point type smoke detectors
MA 21
) 2)
MA 1 other rooms
2 2
Area of false ceiling 40 m 60 m
Monitoring according to
2 2
Room 25 m 40 m 6.2.7.1
2 2
Area of false floor 40 m 60 m
MA Monitoring area
1)
Structural separation between MA 1 and MA 2 minimum by non-combustible structural elements of a
fire resistance duration of minimum at least F 30 min. according to the national proof of fitness, otherwise A as
MA 1
2)
Structural separation between MA 2 and other rooms by non-combustible structural elements of a fire
resistance duration of minimum at least F 90 min. according to the national proof of fitness.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
In the case of coincidence detection type B, the monitoring areas A for smoke detectors
indicated in Table E.1 shall be reduced by minimum 30 %.
If coincidence detection type B is intended for the triggering of fixed fire extinguishing
systems, the monitoring areas A indicated in Table E.1 shall be reduced by 50 % per detector.
A ventilation system shall be considered in the monitoring system so as to ensure that
both the inlet and the outlet air are monitored. Provision shall be made for a separate
detector group for the ventilation system.
66
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
67
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
or
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Figure F.1: Arrangement of point detectors in high rack storage (Figure showing double
racks with centre flues)
68
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
Smoke detectors due to a higher mechanical protection shall be installed preferably in the
internal areas of the rack.
The detectors and suction holes shall be arranged or protected so as to exclude the hazard
of mechanical damage by conveyor equipment and stored material and so as to ensure that
operations of the warehouse are not unduly impaired by service and maintenance.
Where smoke detectors are installed within racks, provision shall be made for an
individual indication of the detector's alarm condition at a readily visible point.
The manufacturer's instructions and possible restrictions specified in the approval
certificate shall be observed.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
69
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
The horizontal extension of a detection zone for rack monitoring shall not exceed 26 m.
The horizontal extension of the detector groups shall not exceed 13 m.
Point detectors or aspirating smoke detectors for ceiling monitoring shall be combined to
form separate detector groups. Basically the horizontal extension, the limitation to 13 m
for the detector group or the limitation to 26 m for the detection zone shall not apply to the
detection zones formed by these ceiling detectors.
A detector group – if point detectors are used – may not comprise more than 20
detectors, and – if aspirating smoke detectors are used – not more than 20 suction holes.
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
70
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
71
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
DIN EN 54-17 Fire detection and fire alarm systems – Part 17: Input/output
devices; German version EN 54-17:2005
DIN EN 54-18 Fire detection and fire alarm systems – Part 18: Compatibility
assessment of system components; German version EN 54-
18:2005
prEN 54-22 Fire detection and fire alarm systems – Part 22: Resettable line
type heat detectors (Draft)
DIN EN 54-25 Fire detection and fire alarm systems – Part 25: Components
using wireless connections and system requirements
DIN EN 60849 (VDE Sound systems for emergency purposes (IEC: EN 60849:1998);
0828-1):1999-05 German version EN 60849:1998
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
DIN EN 60950-1 Bbl 1 Safety aspects for xDSL signals in circuits for connection to
(VDE 0805-1 Bbl 1) telecommunication networks – (DSL digital subscriber line) –
(IEC 62367:2004); German version CLC/TS62367: 2005)
72
VdS 2095en : 2010-05 (07) Fire detection and fire alarm systems – Planning and installation
ISO 3864-1 Graphical symbols – Safety colours and safety signs – Part 1:
Design principles for safety signs in workplaces and public
areas
VdS CEA 4001 VdS CEA Guidelines for sprinkler systems, Planning and
installation
VdS 2093 VdS Guidelines for CO2 fire extinguishing systems, Planning
and installation
VdS 2109 VdS Guidelines for deluge extinguishing systems, Planning and
installation
VdS 2304 Local protection for electric and electronic systems, Guidelines
for planning and installation
VdS 2350 VdS Guidelines for mechanical security devices, Key boxes,
Planning, installation and maintenance
VdS 3435 Data sheet for the configuration of aspirating smoke detectors
1)
To be purchased from: Deutsches Institut für Bautechnik, Kolonnenstraße 30, 10829 Berlin
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
73
Fire detection and fire alarm systems – Planning and installation VdS 2095en : 2010-05 (07)
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
74
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32
Normen-Download-Beuth-Dragados Offshore; S.A.-KdNr.7888355-LfNr.8529928001-2018-08-15 10:32