Inverter-Driven
Induction Motors
Shaft and Bearing
Current Solutions
Table of Contents
Executive Summary
The vast majority of bearing failures in electric motors are due to mechanical and thermal
causes. Potential causes of these types of failures include misalignment of the motor and load,
vibration, incorrect lubrication, excessive radial or axial loading, lubricant contamination or
inadequate maintenance. In a small fraction of electric motor applications, bearings prematurely
fail due to electrical causes.
Currents flowing through induction motor bearings have the potential of creating premature
failure of these bearings. Shaft and bearing currents in sine wave driven motors are well
understood. These currents are either localized in the bearing or are driven through the bearing
due to asymmetries in the motor material properties or construction. The low frequency nature
of bearing and shaft currents in sine wave driven motors results in current paths through what
are generally considered to be conductive materials (motor shafts, frames, bearing races and
bearing balls). Interrupting the conducting current path with insulating materials can eliminate
these low frequency shaft and bearing currents.
Electric motors powered by fast switching pulse width modulated (PWM) voltage source
inverters experience high frequency voltage pulses with respect to motor ground. At these high
frequencies (up to several MHz transitions) capacitively coupled currents can flow through
paths that would normally be considered to be insulators. Currents now can flow through the
magnet wire insulation, stator slot liners, motor air gap, bearing grease and stator slot top sticks.
These high frequency current paths offer new opportunities for shaft and bearing current flow
that can result in premature bearing failure. With inverter driven motors, a clear understanding
of high frequency current paths from the motor terminals back to the inverter and to ground is
It should be pointed out that inverter-induced bearing currents have not been found to cause
significant problems in the majority of applications. This report focuses on that small percentage
of installations and applications in which damage as a result of bearing currents is possible.
Topics to be presented include:
1) root causes of inverter induced motor bearing currents,
2) potential current paths of capacitively coupled currents,
3) bearing damage due to these currents,
4) preferred current paths for capacitively coupled currents,
5) examples of application problems and solutions,
6) field measurements of important voltages and currents,
7) remediation methods and
8) on-going research into motor bearing current modeling.
Proper grounding of the motor frame is also it is difficult to accurately measure current flow
through the bearing. This difficulty arises
important. Capacitively coupled currents from
because it is not possible to place a current
the stator winding to the motor frame are the
transducer in the part of the bearing where the
largest potential component of bearing current
current actually flows. Therefore, field
in applications with conductive shaft couplings
measurements are largely relegated to methods
(shaft extension current in Figure 6). Besides
that will provide insight into symptoms of
the cable’s low impedance ground path from the
potential bearing current problems. Many field
motor to the inverter, ground straps should also
measurements are done after bearing damage has
be connected between the motor frame and the
occurred, where causes are being determined so
driven load equipment frame to allow a low
that the proper remediation action can be taken.
impedance, alternate path for shaft currents. This
Since the source of the high frequency bearing
is particularly important in applications where a
currents is the common mode voltage transitions
conductive coupling connects the motor shaft to
from the inverter, it is important to reference all
the driven equipment and where the motor and
system measurements to the common mode
driven equipment are NOT on a common metal
voltage wave form. Shaft to ground voltage
baseplate. High frequency ground strap
measurement (both magnitude and wave shape)
impedance is lowest for straps with fine
provides insight into potential bearing current
conductors and the largest width to length ratio.
flows. Although bearing currents cannot be
Therefore, the widest ground strap that is
directly measured, current flow through various
practical should be used for this ground
grounding and ground current return paths can
connection. In all cases, ground straps should
and should be measured, including current
be connected directly metal to metal (not through
flowing through the motor drive shaft to the load.
a painted surface) to provide the lowest
Typical field measurement goals include:
impedance path for high frequency currents.
1) determine common mode voltage level
and wave shape,
2) compare shaft to frame voltage
Common mode voltage High voltage, high frequency 50 MHz Tektronix P5210
voltage probes differential probe
Yokogawa 70924
differential probe
Shaft to frame voltage High bandwidth passive 100 Megasamples/sec Tektronix P6139A
probes 50 MHz bandwidth Yokogawa 700998
Agilent 10074C
Common mode current High frequency current 100 Megasamples/sec Tektronix A6303/
probes 50 MHz bandwidth CT-4/AM503B,
A6302/AM503B
current probes,
PEM high frequency
Rogowski Coil
Net cable current High frequency current 100 Megasamples/sec scope Tektronix A6303/
probes 50 MHz bandwidth CT-4/AM503B,
A6302/AM503B
(large cable diameter) current probes,
PEM high frequency
Rogowski Coil
Motor drive shaft current High frequency current 5 to 10 MHz bandwidth PEM high frequency
probes Rogowski Coil
Internal, circulating, due to Motor design optimized for Design electromagnetics to achieve maximum symmetry and
magnetic dissymmetry leading symmetry minimize net flux linking the shaft.
to net flux linking shaft
(fundamental frequency or sine Insulate one bearing Insulating just one bearing interrupts flow. Since coupled
wave) equipment can also provide a path from shaft to ground,
usually choose opposite drive end bearing to insulate. Need
to avoid “defeating” the bearing insulation, so (a) no ground
brush at same end as a single insulated bearing, and (b)
insulated coupling/mounting of accessories (e.g. encoder) at
the end with a single insulated bearing.
Common mode (ground) Insulate both bearings Bearing insulation has to be of sufficient thickness to present
current (induced by common a high impedance to this high frequency current.
mode dv/dt) taking a return
Coupling insulation must provide a high impedance at high
path via the motor shaft Insulate coupling
extension and coupled frequencies.
equipment By bonding the motor frame and the coupled equipment
Bonding strap between together, a path is provided that should be much lower
frames impedance than that through the shaft and bearings. To this
end, the bonding must be a low impedance strap well
terminated at each end.
By providing the lowest impedance path back to the source,
Well terminated cable ground the tendency for any current to take a path through the shaft /
connections bearings/coupled equipment is minimized.
Discharge through bearing of Motor design to reduce By controlling the internal design of the motor, the ratio of the
capacitively coupled common voltage ratio shaft voltage to common mode voltage can be minimized.
mode voltage (scaled by Faraday shield By interposing a grounded conductor between the stator
capacitor divider) winding and the rotor, the capacitive coupling can be “shorted
to ground,” reducing the bearing voltage to prevent damage.
Insulate both bearings Since a bearing goes from a non-conducting to a conducting
mode in a very short time, this presents a high frequency
event — so the insulation needs to be a significant
impedance at high frequencies.
Shaft ground brush This can be effective, but presents maintenance issues.
Capacitively coupled common Insulate coupling Coupling insulation must provide a high impedance to high
mode voltage causing frequencies. Preferred path may now be through motor
discharge through or bearings.
conduction through load
Shaft ground brush This can be effective, but presents maintenance issues.
bearings
By interposing a grounded conductor between the stator
Faraday shield winding and the rotor, the capacitive coupling can be “shorted
to ground,” reducing the bearing voltage to prevent damage.
It is possible, of course, to
insulate both bearings on the
motor, protecting both from
current flow. In this
instance, the bearings are
Figure 19: One insulated bearing, shaft brush and ground strap.
protected even if the shaft
grounding brush should
fail. Figure 20 shows this
remedy. To eliminate
current flow down the shaft
with this system, a good
high frequency ground from
motor to load is required
Figure 20: Two insulated bearings and shaft grounding brush.
An electrostatically
shielded induction motor
(ESIM) can prevent rotor
Figure 21: Two insulated bearings with shaft ground brush and ground strap.
charge and discharge in
(see Figure 21) or, better yet, good high installations where the motor is not coupled in a
frequency grounds between the motor and drive conductive way to driven equipment (see Figure
and motor and load (see Figure 7). 22).
R ockwell Automation
developed this tech-nology
and has several patents in
this area, both in concept
and application. The basic
goal is to create a grounded
conductive path between
the stator and the rotor that
will bleed off capacitive
coupled current. While
Figure 22: Electrostatically shielded induction motore (ESIM).
ESIM technology
eliminates stator to rotor
coupling, it doesn’t
eliminate the potential of
coupling from the stator
winding to the frame and
through the bearing as can
be seen in Figure 23.
Concern still exists about
Figure 23: Bearing currents with ESIM.
mode current produced by the inverter. Figure connections from the stator core to the conduit
24 shows how the addition of a motor/load box ground stud are also standard practice.
ground strap can protect load bearings by
shunting the currents away from the bearings in For small and medium AC motors, bearings
the entire system. Also, a good high frequency can be insulated and ground brushes applied and
ground between the motor and drive is another an electrostatically shielded product is available.
solution (see Figure 7).
Rockwell provides a variety of insulated
Standard Practice For bearing technologies that create an insulating
Bearing Protection barrier between the frame of the motor and the
outer race of the bearing (see Figure 25). The
Rockwell Automation’s Reliance Electric
group has standards in place for
preventing bearing current damage
with inverters. On large AC
motors, insulated bearings are
provided on the drive end and
opposite drive end, as well as a
grounding brush (see Figure 26),
on either the drive end or opposite
drive end. For large AC
applications, the grounding brush
is typically installed on the drive
end. Enhanced ground Figure 25: Insulated bearing.
A typical shaft brush installation is shown in Plant management had not realized that the
Figure 26. bearing at the opposite drive end was insulated
(as a precaution against internally generated, sine
wave based, circulating shaft / bearing current).
By adding the grounding brush at the opposite
drive end, the drive end bearing became
significantly imperiled. In fact, a drive end
bearing failure occurred very quickly after the
addition of the aftermarket kit. The solution then
chosen was to insulate both bearings. The kit
was put back in place at the opposite drive end
and another drive end shaft grounding brush was
Figure 26: Shaft grounding brush. also added. There were also measurements made
that revealed 30-40 volt peaks from point-to-
Field Experiences point within the ground system, which would
imply opportunity for current to flow between
Examples of specific field experiences range, various points in the ground system, including
essentially, from fan applications with a belt
either a motor or gear box bearing. The use of
driven load (i.e. a motor that does not have other
two insulated bearings (and two shaft grounding
conductive paths from its shaft to ground), to
brushes) did prove to be successful.
coupled applications where shaft extension
currents may be an issue.
At the same installation, measurements of the
common mode currents in the leads did not
Systems/Process Line Installation – Motors
match up well with measurements of the current
coupled to gearboxes or other machinery in the power cable ground conductors (that
(Case 1) would be the preferred path). There was a
significant discrepancy in that the “PE wires” in
At this installation, one particular motor, frame the cable did not carry anywhere near the sum
size E5010, had a bearing failure after about 2½ total of the common mode current. There was
Case 1A
As a point of
comparison,
another similar
application Trace 3 : Common mode current. (5 amps/div)
which had a
more rigorous Figure 27: Common mode current
and ground current wave forms.
attention to
cabling/
grounding/
Trace 1: Ground current. (5 amps/div)
Source of Current
Internal, circulating,
due to magnetic
dissymmetry leading
to net flux linking Avoid
X X
shaft (fundamental without
frequency or sine opposite
wave). Generally bearing
occurs on motors insulated
above NEMA 400
frame.
Figure 2
Avoid
Common mode without
(ground) current insulated
(induced by common coupling or
X X X X
mode dv/dt) taking a bonding
return path via the strap
motor shaft between
extension and motor and
coupled equipment. load to
protect
Figure 4 – gold driven
current equipment
May cause
Discharge through increased
bearing of Only if in motor
Only if in bearing
X X
capacitively-coupled combination
combination with motor current
common mode with motor without
shaft ground
voltage (scaled by shaft ground brush or motor shaft
capacitor divider). brush insulated ground
Figure 4 – red and coupling brush,
faraday
green current
shield or
insulated
motor
bearings
X indicates that the remedy will, by itself, reduce or eliminate motor bearing current damage and current
flow to coupled equipment.
• J. M. Erdman, Russel J. Kerkman, David W. Schlegel and Gary L. Skibinski, “Effect of PWM Inverters
on AC Motor Bearing Currents and Shaft Voltages,” IEEE Applied Power Electronics Conference (APEC),
Dallas, TX, March 6-9, 1995, pp. 24-33. IEEE Transactions on Industry Applications, Vol. 32, No. 2,
March/April 1996, pp. 250-259.
• Doyle Busse, Jay Erdman, Russel J. Kerkman, Dave Schlegel, and Gary Skibinski, “Bearing Currents
and Their Relationship to PWM Drives,” IEEE Industrial Electronics Conference (IECON), Orlando, FL,
Nov. 6-10, 1995, pp. 698-705. IEEE Transactions on Power Electronics, Vol. 12, No. 2, March 1997, pp.
243-252.
• Doyle Busse, Jay Erdman, Russel J. Kerkman, Dave Schlegel and Gary Skibinski, “The Effects of PWM
Voltage Source Inverters on the Mechanical Performance of Rolling Bearings,” IEEE Applied Power
Electronics Conference (APEC), San Jose, CA, March 3-7, 1996, pp. 561-569. IEEE Transactions on
Industry Applications, Vol. 33, No. 2, March/April 1997, pp. 567-576.
• Doyle Busse, Jay Erdman, Russel J. Kerkman, Dave Schlegel and Gary Skibinski, “System Electrical
Parameters and Their Effects on Bearing Currents,” IEEE Applied Power Electronics Conference (APEC),
San Jose, CA, March 3-7, 1996, pp. 570-578. IEEE Transactions on Industry Applications, Vol. 33, No.
2, March/April 1997, pp. 577-584.
• Doyle Busse, Jay Erdman, Russel JKerkman, Dave Schlegel and Gary Skibinski, “An Evaluation of the
Electrostatic Shielded Induction Motor: A Solution for Rotor Shaft Voltage Buildup and Bearing Current,”
IEEE Industry Application Society Conference, San Diego, CA, October 6-10, 1996, pp. 610-617. IEEE
Transactions on Industry Applications, Vol. 33, No. 6, November/December 1997, pp. 1563-1570.
• R. Kerkman, D. Schlegel and G. Skibinski, “An Examination of Rotor Shaft Voltage and the Resulting
Bearing Current: A Consequence of PWM Inverter Operation,” IEEE Industry Applications Magazine,
Vol. 3, No. 6, November/December 1997, pp. 21-32.
• D. Schlegel, R. Kerkman and G. Skibinski, “Turning The Tables On Shaft Voltage And Bearing Cur-
rents,” EC&M, June 1998, pp. 60-71.
• Sidney Bell, Timothy J. Cookson, Steven A. Cope, Richard A. Epperly, Annika Fischer, David W. Schlegel
and Gary L. Skibinski, “Experience With Variable Frequency Drives and Motor Bearing Reliability”, IEEE
IAS Petroleum and Chemical Industry Conference (PCIC), Indianapolis, IN, Sept. 28-30, 1998.
The discussion of PWM inverter-sourced bearing motor frame and the frame of coupled machinery.
currents inevitably involves some discussion of Non-zero impedances between points in the ground
grounding. While “grounding” in the classic sense system can easily result in transient voltage
of a conductor to “earth ground” is an issue, it is not excursions that can then drive ground system
the major one. The first issue is the provision of a currents. To avoid these currents utilizing a path
low impedance path (within the power lead cable) through bearings and shafts, a “bond strap” between
for the safe return of common mode currents to the (interconnected) grounded pieces of equipment can
inverter. This is best done by the ground and shield be used.
conductors in the power cable, so it could be called
“properly grounding the motor.” However, it is NOT Finally, the grounding of the motor frame to the
equivalent to a good “safety ground” of the motor inverter ground needs to be more than just a low
to earth. It might be better described as “bonding” frequency safety ground. In addition to requiring low
the motor ground to the inverter ground (via a good impedance (at the high frequencies represented by
high frequency path). fast rising edges), the ground path should also be
free from “intermittent” ground impedance changes
Also in regard to bonding, another consideration (such as might occur with some types of flexible
is bonding to equalize potentials (on a transient conduit). Such changes in ground impedance can
basis) between points within the ground system. An result in higher than normal voltages on bearings.
important location for such bonding is between the
Vibration analysis of anti-friction bearings can The frequencies of vibration generated by the PWM
identify incipient faults and give ample notice for waveforms are unfortunately in the same range as
their timely replacement. Vibration signals are often those generated by bearing defects. A PWM inverter
viewed in a frequency domain (rather than time will typically create motor phase currents with
domain). Formulas for calculating the frequencies frequency content including sidebands around the
generated by various types of faults are well carrier frequency and multiples (including half
published and the experience database for multiples). The sidebands are spaced from these
documenting these faults is over 30 years old.
Typical frequencies include those associated with
Diagnosis of Damaged Bearings – normally not shiny (grind marks are not visible).
Cautions
Motor bearing currents due to inverter excitation are the element. The impedance of the capacitor is a
the result of current flow through parts of the motor function of the frequency of the applied voltage.
that can be modeled as capacitors. These include
the electrical insulation materials (slot liners, magnet Consider the current and voltage relationship for the
wire enamel, insulating varnish or resin), the motor capacitor in equation (1). If the voltage applied is a
air gap and the lubricant film between the bearing constant frequency sine wave with peak value Vm
balls and races. and frequency f then:
where C is the capacitance and dv/dt is the rate of The capacitor is seen to have an AC impedance of:
change of voltage with respect to time (instantaneous
slope of the voltage versus time waveform). Zc = 1/(2πfC) (5)
Capacitors consist of two conducting surfaces The capacitive current flow is therefore directly
separated by an insulating layer. If each of the two proportional to the frequency of the applied voltage
conducting surfaces has surface area equal to A and and the capacitive impedance is inversely
two surfaces are separated by a distance d, then: proportional to the applied frequency. With the fast
switching speeds (transistor turn-on and turn off
C = ε0ε´A/d (2) times) of today’s inverters, high frequency content
voltage waveforms are applied to the motor terminals
where ε0 is the permitivity of vacuum and å´ is the which results in increased capacitive current flow with
dielectric constant of the material in the insulating the potential for damaging current flow in the motor
layer. Typical dielectric constants for insulating bearings.
materials in an electric motor (slot liners, magnet wire
enamel) are in the range of 2 to 10. The dielectric The magnitude of current flow through capacitive
constant of air is 1. Bearing lubricants have dielectric paths within the motor depends upon the rate of
constants in the range of 2 to 5. change of voltage and the value of capacitance in
that circuit path as shown in equation (1). Notice
Another way to look at the magnitude of current flow that the faster the voltage across the capacitor
through a capacitor is to consider its AC impedance. changes with time, the larger the magnitude of the
The impedance of a circuit element is the resistance current through that element. From equation (2) the
to current flow when alternating currents flow through value of capacitance is inversely proportional to the