Light-Pak N2LPS LED Cl. I, Div.

2, Groups B, C, D
Cl. I, Zone 2 9L
emergency lighting system Cl. II, Div. 2, Groups F, G (N2LPS only)
Marine & Wet Locations
NEMA 4, 4X

Applications: Certifications and


Light-Pak™ N2LPS LED emergency compliances:
lighting systems are used: NEC/CEC:
• To provide reliable illumination for egress • Class I, Division 2, Groups B, C, D
areas during failure or interruption of • Class I, Zone 2
power to the normal lighting system
• Class II, Division 2, Groups F, G (N2LPS
• In areas where flammable gases or vapors only)
may become present due to abnormal,
unusual or accidental conditions • NEMA 4, 4X
• In manufacturing plants, refineries, • Marine and wet locations suitability
petrochemical and chemical plants, UL standards:
waste and sewage treatment facilities, • UL1598A – Supplemental Requirements
oil terminals, food processing facilities, for Luminaires for Installation on Marine
breweries and other industrial Vessels
manufacturing or process industry facilities
subject to wet or corrosive conditions • UL924 – Emergency Lighting and Power
Equipment
• To illuminate machinery or panels during a
loss of AC power • UL844 – Electric Luminaires Hazardous
Locations
• Where moisture, dirt, dust or corrosion
CSA standards:
Electrical ratings:
will limit the life and reliability of ordinary
emergency lighting systems • C22.2 No. 141-M1985 •  Power supply:
• Where required by the National Electrical • C22.2 No. 137-M1981 Input – 120-277 VAC, 50 or 60 Hz; 6W
Code®, the Life Safety Code® or other maximum
NFPA:
applicable codes Output – 12 VDC
• Life Safety Code NFPA101 – Section 5-9
• Outdoor applications (Emergency Lighting) • LED luminaire heads:
Voltage – 12 VDC
Features: Standard materials: Lamp – 1W LED, 6W maximum
• Non-metallic, enclosed, gasketed housing •  Power supply and remote luminaire Maximum 6 lamp heads
– provides corrosion protection in the enclosure – Krydon fiberglass-reinforced
most extreme environments
• Durable and marine rated LED lamp head
polyester Options:
• LED lamp head assembly – epoxy powder
assemblies – provide protection against Description Suffix
coated aluminum
water ingress, corrosion and impact • Breather/drain..................................... S931
• Exterior hardware – nylon, plastic coated,
• Nickel cadmium battery – high and stainless steel • External battery disconnect switch.... S932
temperature rated nickel cadmium battery
for reliable operation up to 55°C ambient • Cover gasket – Hypalon synthetic rubber
• Reduced maintenance costs – self-test, Photometrics:
monitoring and diagnostics reduce costly Temperature performance •  Refer to www.eaton.com (under the
maintenance checks Resources tab of each product family) for
data: specific photometric IES files
• Remote mountable lamp heads – lamp Class I & II,
heads can be mounted independently Cat. # Division 2
from the enclosure, allowing you to focus N2LPS (all models)
light where you need it T6
N2RF (all models)
• Solid state battery charger – ensures Note:  Ambient temperature at which the Light-Pak system
long life and reliable battery operation; is rated is -20°C to 55°C. Operation at temperatures
prevents deep discharge by automatically outside this range will affect the battery life and/or
charging performance.
disconnecting the battery from the
luminaire
• N2RF includes 3/4” hub Ordering information:
Description Cat. #
28W, 12V power supply, two 1W LED lamp heads N2LPSM212222
28W, 12V power supply, less luminaire heads N2LPSM212220
9L

Remote luminaire assembly, one LED lamp head N2RFM21221


Remote luminaire assembly, two LED lamp heads N2RFM21222
6W, 12V power supply with exit sign (single sided) N2LPSM212222 UX71SDHAZA
6W, 12V power supply with exit sign (double sided) N2LPSM212222 UX72SDHAZA

AClass I, Division 2 only.

www.eaton.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2022 Eaton 411


Light-Pak N2LPS LED Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2 9L
emergency lighting system Cl. II, Div. 2, Groups F, G (N2LPS only)
Marine & Wet Locations
NEMA 4, 4X

Weights: Detail indication logic:


Cat. # Weight (lbs.) Weight (kg.) Status indication Status description Status definition
N2LPSM212222 12.00 7.26 No light AC power removed from circuit
N2LPSM212220 10.00 5.44 * Steady light (no blinks) Fully charged or test in process
N2RFM21221 7.00 3.63 *-* Light blinks once Battery charging
N2RFM21222 8.00 4.08 **-** Light blinks twice Battery failure
***-*** Light blinks three times Circuit failure
****-**** Light blinks four times Lamp failure

Dimensions (in inches):


14.91

25.63

12.40

UX71SDHAZ option – single sided


9L

UX72SDHAZ option – double sided

412 www.eaton.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2022 Eaton