Ert Sunsorce Tuljapur Maharashtra 15.11.2021

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 32

2022-23

OFFSHORE INFRASTRUCTURE LIMITED


EARTH RESISTIVITY TEST REPORT

NAME OF THE PROJECT DESIGN, ENGINEERING, SUPPLY, ERECTION AND


COMMISSIONING OF 18 OS 33/11 KV SUB-STATION WITH ASSOCIATED 33KV &
11 KV LINES AND CONSTRUCTION OF 7 INDEPENDENT 33KV LINES UNDER
PACKAGE 04 OF PHASE-IV, ODSSP WITHIN THE JURISDICTION STATE OF
DISCOM-TPWODL ON TURNKEY CONTRACT BASISOFFSHORE INFRASTRUCTURE
LIMITED DEOGARH DISRICT
LOCATION:KHAIRAPALLI,KARALOGA,DEOGARH

Report Ref. No: ICRPL/REP/202210001/FD-ERT/2022-23/4337

TESTING AGENCY:
IDAX CONSULTING & RESEARCH PVT.LTD.
Plot No. - 5016, Duplex-E, Brundaban Enclave, VSS Nagar,
Bhubaneswar-751007, Odisha (INDIA).
Tel: 7735599991
E-mail: info@idaxconsulting.com
Web: www.idaxconsulting.com

Date of Test: 12.10.2022


Date of Submission of Report: 17.10.2022
IDAX CONSULTING & RESEARCH PVT. LTD.

1. INTRODUCTION:

The Earth Resistivity Test (ERT) of soil was carried out at site for EARTH
RESISTIVITY TEST WORK AT TULJAPUR SITE MAHARASHTRA. with the aim to
determine an average value of electrical resistivity of soil for design of safe earthing
system. The Earth resistivity field test were done in 02.11.2021 at FIVE locations
given as directed by the client.

2. PURPOSE OF INVESTIGATION:
The purpose of this investigation is to determine an average value of electrical
resistivity of subsurface for design of safe earthing system with the help of
Microprocessor based electrical resistivity meter model DET-Auto.

3. GEOPHYSICAL INVESTIGATION:
Geophysical investigation was carried out as per IS: 3043-1987 on the basis of Earth
Resistivity meter model no. DET-Auto. Wenner’s four-electrode method is used to
determine the earth resistivity.

4. WENNER’S CONFIGURATION:
This is one of the most commonly used arrays proposed by Wenner in 1916. Four
electrodes A, B, M, and N are placed at the surface of the ground along a straight
symmetrically about a point O. The observation point in such a way that the distance
between AM = MN =NB = a., Where ‘a’ is called electrode separation see fig. 1.
Current ‘I’ is sent generally through outer electrodes A and B and the potential
difference (V) is measured between M and N. The instrument multiplication factor is f.

Electrode shall be driven in to the earth to a depth ‘B’. The depth ‘B’ should be ideally less
than 1/20 of spacing ‘A’.

Apparent Resistivity, = 2aR (As per IS: 3043 – 1987, Clause No. : 36.3.1.2)

Project Code_202109004-ERT A M N B Page 1 of 31


a a a
IDAX CONSULTING & RESEARCH PVT. LTD.

5. Survey Procedure:
Resistivity sounding is used to make investigations along the depth. In this method
the center of configuration is kept fixed and measurements are made by successively
increasing electrode spacing. The apparent resistivity values obtained with increasing
values of electrode separations are used to estimate the thickness and resistivity of
the subsurface formations. In Wenner’s configuration all the four electrodes are
arranged in a line at a equal distance ‘a’ between the consecutive electrodes.
Measurements were taken at 1m,2m,3m,5m & 10m. Current is sent through the
outer electrodes and the potential difference is measured between the inner
electrodes. The Resistance (R = V/I) is measured for each electrode separation and
apparent resistivity is calculated by multiplying value of ‘R’ with Wenner configuration
factor (2a), where ‘a’ is the uniform distance between the electrodes. The
computation of the sounding data is discussed in the subsequent section.

6. Computation of Earth Resistivity:


When the earth resistivity readings for different electrode spacing in a direction are
within 20 to 30%, the soil is considered to be uniform. When the spacing is increased
gradually from low values, at a stage, it may be found that the resistivity readings are
more or less constant irrespective of the increase in the electrode spacing. The
resistivity for this spacing is noted and taken as the resistivity for that direction. In a
similar manner, resistivity for at least one equally spaced direction from the center of
the site are measured. These resistivity are plotted in a graph sheet in the appropriate
directions choosing a scale. A closed curve is plotted on the graph sheets jointing all
the resistivity points plotted to get the polar resistivity curve. The area inside the polar
resistivity curve is measured and equivalent circle of the same area is found out. The
radius of this equivalent circle is the average resistivity of the site under consideration.
The average resistivity thus obtained may be used for the design of the earthing grid
at that particular depth.

Project Code_202109004-ERT Page 2 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

7. Results:
I. The electric resistivity test of the site were performed in 02.11.2021 at FIVE locations
as suggested by client.

II. Measured surface resistivity data is attached separately.

III. Average Resistivity / Equivalent Radius from polar curve are 130.935 Ohm-m.

8. LIMITATION
The Electrical resistivity testing has been carried out at the location chosen by the
client. In general resistivity values are influenced by water, presence of dissolved ions
in soil media and nature of strata. Recommendations made in the report are hence
valid only for tested locations only. However if there is any change in subsoil
conditions and properties at places beyond chosen test locations, the soil consultants
to be contacted for further guidance.

For IDAX CONSULTING & RESEARCH PVT. LTD.

(Technical Head- Civil)

Project Code_202109004-ERT Page 3 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

DETERMINATION OF EARTH RESISTIVITY

CLIENT: SUNSOURCE ENERGY PVT.LTD.

PROJECT : ERT FOR 06 MW SOLAR PV PLANT

LOCATION: TULJAPUR,MAHARASTRA

CO-ORDINATES: N-1983731.271 E-598269.741


TEMPERATURE: 29°C HUMIDITY :53%

PROJECT CODE.: 202109004

METHOD OF RESISTIVITY SURVEY : Wenner's Method as per IS:3043-1987

Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.300 1 89.850
3.00 1.00 2.00 9.520 1 119.632
4.50 1.50 3.00 7.840 1 147.781
7.50 2.50 5.00 5.220 1 163.991
15.00 5.00 10.00 2.560 1 160.850

Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 13.110 1 82.373
3.00 1.00 2.00 8.780 1 110.333
4.50 1.50 3.00 6.740 1 127.046
7.50 2.50 5.00 5.360 1 168.389
15.00 5.00 10.00 2.710 1 170.274

Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.050 1 94.562
3.00 1.00 2.00 10.350 1 130.062
4.50 1.50 3.00 6.680 1 125.915
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.600 1 163.363

Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.190 1 89.158
3.00 1.00 2.00 8.740 1 109.830
4.50 1.50 3.00 6.740 1 127.046
7.50 2.50 5.00 5.280 1 165.876
15.00 5.00 10.00 2.920 1 183.469

Project Code_202109004-ERT Page 4 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.700 1 92.363
3.00 1.00 2.00 8.820 1 110.835
4.50 1.50 3.00 7.510 1 141.560
7.50 2.50 5.00 5.660 1 177.814
15.00 5.00 10.00 2.580 1 162.106

Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.550 1 91.420
3.00 1.00 2.00 8.710 1 109.453
4.50 1.50 3.00 6.510 1 122.711
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.690 1 169.018

Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.030 1 88.153
3.00 1.00 2.00 8.540 1 107.317
4.50 1.50 3.00 6.210 1 117.056
7.50 2.50 5.00 5.180 1 162.734
15.00 5.00 10.00 2.500 1 157.080

Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.280 1 89.724
3.00 1.00 2.00 9.700 1 121.894
4.50 1.50 3.00 7.520 1 141.749
7.50 2.50 5.00 5.950 1 186.925
15.00 5.00 10.00 2.560 1 160.850

Project Code_202109004-ERT Page 5 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Results of Electrical Resistivity


Wenner Method (IS-3043)
Project No: 202109004

Client: SUNSOURCE ENERGY PVT.LTD.


Project: ERT FOR 06 MW SOLAR PV PLANT
Co-ordinates: N-1983731.271 E-598269.741
Temperature: 29°C HUMIDITY :53%

Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method

Electric Resistivity: r in ohm-meter = 2paR (Ω.m)

where a = Distance between two succes ive electrodes in meter (m)


R = V/I = Resistance in ohm (Ω)

Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth

m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)

1 1.50 0.50 1.00 14.300 1 89.850 13.110 1 82.373 15.050 1 94.562 14.190 1 89.158 14.700 1 92.363 14.550 1 91.420 14.030 1 88.153 14.280 1 89.724 89.700 94.562 82.373

2 3.00 1.00 2.00 9.520 1 119.632 8.780 1 110.333 10.350 1 130.062 8.740 1 109.830 8.820 1 110.835 8.710 1 109.453 8.540 1 107.317 9.700 1 121.894 114.919 130.062 107.317

3 4.50 1.50 3.00 7.840 1 147.781 6.740 1 127.046 6.680 1 125.915 6.740 1 127.046 7.510 1 141.560 6.510 1 122.711 6.210 1 117.056 7.520 1 141.749 131.358 147.781 117.056

4 7.50 2.50 5.00 5.220 1 163.991 5.360 1 168.389 5.340 1 167.761 5.280 1 165.876 5.660 1 177.814 5.340 1 167.761 5.180 1 162.734 5.950 1 186.925 170.157 186.925 162.734

5 15.00 5.00 10.00 2.560 1 160.850 2.710 1 170.274 2.600 1 163.363 2.920 1 183.469 2.580 1 162.106 2.690 1 169.018 2.500 1 157.080 2.560 1 160.850 165.876 183.469 157.080

Average Resistivity in Direction 136.421 131.683 136.333 135.076 136.936 132.073 126.468 140.228 134.402

Project Code_202109004-ERT Page 6 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 7 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

DETERMINATION OF EARTH RESISTIVITY

CLIENT: SUNSOURCE ENERGY PVT.LTD.

PROJECT : ERT FOR 06 MW SOLAR PV PLANT

LOCATION: TULJAPUR,MAHARASTRA

CO-ORDINATES: N-1983649.570 E-598471.916


TEMPERATURE: 31°C HUMIDITY :43%

PROJECT CODE.: 202109004

METHOD OF RESISTIVITY SURVEY : Wenner's Method as per IS:3043-1987

Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.650 1 79.482
3.00 1.00 2.00 8.960 1 112.595
4.50 1.50 3.00 8.410 1 158.525
7.50 2.50 5.00 5.010 1 157.394
15.00 5.00 10.00 2.600 1 163.363

Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.400 1 77.911
3.00 1.00 2.00 8.560 1 107.568
4.50 1.50 3.00 7.690 1 144.953
7.50 2.50 5.00 5.160 1 162.106
15.00 5.00 10.00 2.590 1 162.734

Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.960 1 68.864
3.00 1.00 2.00 7.200 1 90.478
4.50 1.50 3.00 6.350 1 119.695
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.690 1 169.018

Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 7.260 1 91.232
4.50 1.50 3.00 6.540 1 123.276
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.320 1 145.770

Project Code_202109004-ERT Page 8 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 6.240 1 78.414
4.50 1.50 3.00 5.420 1 102.165
7.50 2.50 5.00 5.090 1 159.907
15.00 5.00 10.00 1.520 1 95.504

Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.370 1 65.157
3.00 1.00 2.00 7.810 1 98.143
4.50 1.50 3.00 6.980 1 131.570
7.50 2.50 5.00 5.420 1 170.274
15.00 5.00 10.00 2.740 1 172.159

Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.130 1 63.649
3.00 1.00 2.00 7.720 1 97.012
4.50 1.50 3.00 6.910 1 130.250
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.840 1 178.442

Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.990 1 75.335
3.00 1.00 2.00 8.960 1 112.595
4.50 1.50 3.00 8.370 1 157.771
7.50 2.50 5.00 5.620 1 176.558
15.00 5.00 10.00 2.600 1 163.363

Project Code_202109004-ERT Page 9 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Results of Electrical Resistivity


Wenner Method (IS-3043)
Project No: 202109004

Client: SUNSOURCE ENERGY PVT.LTD.


Project: ERT FOR 06 MW SOLAR PV PLANT
Co-ordinates: N-1983649.570 E-598471.916
Temperature: 31°C HUMIDITY :43%

Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method

Electric Resistivity: r in ohm-meter = 2paR (Ω.m)

where a = Distance between two successive electrodes in meter (m)


R = V/I = Resistance in ohm (Ω)

Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth

m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)

1 1.50 0.50 1.00 12.650 1 79.482 12.400 1 77.911 10.960 1 68.864 11.350 1 71.314 11.350 1 71.314 10.370 1 65.157 10.130 1 63.649 11.990 1 75.335 71.628 79.482 63.649

2 3.00 1.00 2.00 8.960 1 112.595 8.560 1 107.568 7.200 1 90.478 7.260 1 91.232 6.240 1 78.414 7.810 1 98.143 7.720 1 97.012 8.960 1 112.595 98.505 112.595 78.414

3 4.50 1.50 3.00 8.410 1 158.525 7.690 1 144.953 6.350 1 119.695 6.540 1 123.276 5.420 1 102.165 6.980 1 131.570 6.910 1 130.250 8.370 1 157.771 133.526 158.525 102.165

4 7.50 2.50 5.00 5.010 1 157.394 5.160 1 162.106 5.340 1 167.761 5.500 1 172.788 5.090 1 159.907 5.420 1 170.274 5.500 1 172.788 5.620 1 176.558 167.447 176.558 157.394

5 15.00 5.00 10.00 2.600 1 163.363 2.590 1 162.734 2.690 1 169.018 2.320 1 145.770 1.520 1 95.504 2.740 1 172.159 2.840 1 178.442 2.600 1 163.363 156.294 178.442 95.504

Average Resistivity in Direction 134.272 131.055 123.163 120.876 101.461 127.461 128.428 137.124 125.480

Project Code_202109004-ERT Page 10 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

D4 D3 D2

180.000

134.272 131.055
137.12
4
120.000

60.000

D5 D
-128.428 123.163 1
0.000
-180.000 -120.000 -60.000 0.000 60.000 120.000 180.000

-60.000

-120.000
-120.876
-101.461
-
127.461

-180.000 D8
D D
6 7
Inside Area of Polar Curve = 13 Units
Equivalent Radius ( I.e. a.v. resistivity) =125.480Ohm-m

Project Code_202109004-ERT Page 11 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

DETERMINATION OF EARTH RESISTIVITY

CLIENT: SUNSOURCE ENERGY PVT.LTD.

PROJECT : ERT FOR 06 MW SOLAR PV PLANT

LOCATION: TULJAPUR,MAHARASTRA

CO-ORDINATES: N-1983586.308 E-598269.727


TEMPERATURE: 33°C HUMIDITY :52%

PROJECT CODE.: 202109004

METHOD OF RESISTIVITY SURVEY : Wenner's Method as per IS:3043-1987

Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 8.220 1 103.296
4.50 1.50 3.00 7.520 1 141.749
7.50 2.50 5.00 5.110 1 160.535
15.00 5.00 10.00 1.950 1 122.522

Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.920 1 68.612
3.00 1.00 2.00 7.180 1 90.227
4.50 1.50 3.00 6.230 1 117.433
7.50 2.50 5.00 5.440 1 170.903
15.00 5.00 10.00 2.610 1 163.991

Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 9.840 1 61.827
3.00 1.00 2.00 8.710 1 109.453
4.50 1.50 3.00 5.360 1 101.034
7.50 2.50 5.00 5.160 1 162.106
15.00 5.00 10.00 2.500 1 157.080

Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.080 1 63.335
3.00 1.00 2.00 8.460 1 106.311
4.50 1.50 3.00 5.630 1 106.123
7.50 2.50 5.00 5.200 1 163.363
15.00 5.00 10.00 2.350 1 147.655

Project Code_202109004-ERT Page 12 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.520 1 72.382
3.00 1.00 2.00 7.880 1 99.023
4.50 1.50 3.00 6.230 1 117.433
7.50 2.50 5.00 5.170 1 162.420
15.00 5.00 10.00 2.040 1 128.177

Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.000 1 69.115
3.00 1.00 2.00 8.330 1 104.678
4.50 1.50 3.00 5.590 1 105.369
7.50 2.50 5.00 5.060 1 158.965
15.00 5.00 10.00 2.170 1 136.345

Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.290 1 70.937
3.00 1.00 2.00 8.550 1 107.442
4.50 1.50 3.00 5.700 1 107.442
7.50 2.50 5.00 5.120 1 160.850
15.00 5.00 10.00 2.350 1 147.655

Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 8.290 1 104.175
4.50 1.50 3.00 6.820 1 128.554
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.090 1 131.319

Project Code_202109004-ERT Page 13 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Results of Electrical Resistivity


Wenner Method (IS-3043)
Project No: 202109004

Client: SUNSOURCE ENERGY PVT.LTD.


Project: ERT FOR 06 MW SOLAR PV PLANT
Co-ordinates: N-1983586.308 E-598269.727
Temperature: 33°C HUMIDITY :52%

Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method

Electric Resistivity: r in ohm-meter = 2paR (Ω.m)

where a = Distance betwe n two suc es ive electrodes in meter (m)


R = V/I = Resistance in ohm (Ω)

Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth

m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)

1 1.50 0.50 1.00 11.640 1 73.136 10.920 1 68.612 9.840 1 61.827 10.080 1 63.335 11.520 1 72.382 11.000 1 69.115 11.290 1 70.937 11.640 1 73.136 69.060 73.136 61.827

2 3.00 1.00 2.00 8.220 1 103.296 7.180 1 90.227 8.710 1 109.453 8.460 1 106.311 7.880 1 99.023 8.330 1 104.678 8.550 1 107.442 8.290 1 104.175 103.076 109.453 90.227

3 4.50 1.50 3.00 7.520 1 141.749 6.230 1 117.433 5.360 1 101.034 5.630 1 106.123 6.230 1 117.433 5.590 1 105.369 5.700 1 107.442 6.820 1 128.554 115.642 141.749 101.034

4 7.50 2.50 5.00 5.110 1 160.535 5.440 1 170.903 5.160 1 162.106 5.200 1 163.363 5.170 1 162.420 5.060 1 158.965 5.120 1 160.850 5.340 1 167.761 163.363 170.903 158.965

5 15.00 5.00 10.00 1.950 1 122.522 2.610 1 163.991 2.500 1 157.080 2.350 1 147.655 2.040 1 128.177 2.170 1 136.345 2.350 1 147.655 2.090 1 131.319 141.843 163.9 1 122.522

Average Resistivity in Direction 120.248 122.233 118.300 117.357 115.887 114.894 118.865 120.989 118.597

Project Code_202109004-ERT Page 14 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

D4 D3 D2

140.000
120.98 120.248 122.23
9 3

70.000

D5 D
-118.865 118.300
0.000 1
-140.000 -70.000 0.000 70.000 140.000

-70.000

-114.894 -115.887
-117.357
-140.000 D8
D D
6 7
Inside Area of Polar Curve = 05 Units
Equivalent Radius ( I.e. a.v. resistivity) =118.597Ohm-m

Project Code_202109004-ERT Page 15 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

DETERMINATION OF EARTH RESISTIVITY

CLIENT: SUNSOURCE ENERGY PVT.LTD.

PROJECT : ERT FOR 06 MW SOLAR PV PLANT

LOCATION: TULJAPUR,MAHARASTRA

CO-ORDINATES: N-1983429.381 E-598417.235


TEMPERATURE: 33°C HUMIDITY :61%

PROJECT CODE.: 202109004

METHOD OF RESISTIVITY SURVEY : Wenner's Method as per IS:3043-1987

Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.050 1 94.562
3.00 1.00 2.00 9.350 1 117.496
4.50 1.50 3.00 6.990 1 131.758
7.50 2.50 5.00 5.420 1 170.274
15.00 5.00 10.00 2.850 1 179.071

Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.670 1 98.458
3.00 1.00 2.00 9.210 1 115.736
4.50 1.50 3.00 6.430 1 121.203
7.50 2.50 5.00 5.790 1 181.898
15.00 5.00 10.00 2.800 1 175.929

Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.200 1 101.788
3.00 1.00 2.00 10.340 1 129.936
4.50 1.50 3.00 8.170 1 154.001
7.50 2.50 5.00 6.890 1 216.456
15.00 5.00 10.00 2.990 1 187.867

Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.370 1 102.856
3.00 1.00 2.00 11.000 1 138.230
4.50 1.50 3.00 9.410 1 177.374
7.50 2.50 5.00 6.700 1 210.487
15.00 5.00 10.00 2.870 1 180.327

Project Code_202109004-ERT Page 16 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.540 1 103.924
3.00 1.00 2.00 10.950 1 137.602
4.50 1.50 3.00 9.370 1 176.620
7.50 2.50 5.00 6.280 1 197.292
15.00 5.00 10.00 2.590 1 162.734

Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.490 1 97.327
3.00 1.00 2.00 10.270 1 129.057
4.50 1.50 3.00 8.630 1 162.672
7.50 2.50 5.00 5.430 1 170.588
15.00 5.00 10.00 2.800 1 175.929

Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.270 1 95.944
3.00 1.00 2.00 9.410 1 118.250
4.50 1.50 3.00 7.630 1 143.822
7.50 2.50 5.00 5.950 1 186.925
15.00 5.00 10.00 2.880 1 180.956

Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.080 1 94.750
3.00 1.00 2.00 8.240 1 103.547
4.50 1.50 3.00 6.560 1 123.653
7.50 2.50 5.00 5.390 1 169.332
15.00 5.00 10.00 2.850 1 179.071

Project Code_202109004-ERT Page 17 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Results of Electrical Resistivity


Wenner Method (IS-3043)
Project No: 202109004

Client: SUNSOURCE ENERGY PVT.LTD.


Project: ERT FOR 06 MW SOLAR PV PLANT
Co-ordinates: N-1983429.381 E-598417.235
Temperature: 33°C HUMIDITY :61%

Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method

Electric Resistivity: r in ohm-meter = 2paR (Ω.m)

where a = Distance betwe n two suc es ive electrodes in meter (m)


R = V/I = Resistance in ohm (Ω)

Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth

m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)

1 1.50 0.50 1.00 15.050 1 94.562 15.670 1 98.458 16.200 1 101.788 16.370 1 102.856 16.540 1 103.924 15.490 1 97.327 15.270 1 95.944 15.080 1 94.750 98.701 103.924 94.562

2 3.00 1.00 2.00 9.350 1 117.496 9.210 1 115.736 10.340 1 129.936 11.000 1 138.230 10.950 1 137.602 10.270 1 129.057 9.410 1 118.250 8.240 1 103.547 123.732 138.230 103.547

3 4.50 1.50 3.00 6.990 1 131.758 6.430 1 121.203 8.170 1 154.001 9.410 1 177.374 9.370 1 176.620 8.630 1 162.672 7.630 1 143.822 6.560 1 123.653 148.888 177.374 121.203

4 7.50 2.50 5.00 5.420 1 170.274 5.790 1 181.898 6.890 1 216.456 6.700 1 210.487 6.280 1 197.292 5.430 1 170.588 5.950 1 186.925 5.390 1 169.332 187.907 216.456 169.332

5 15.00 5.00 10.00 2.850 1 179.071 2.800 1 175.929 2.990 1 187.867 2.870 1 180.327 2.590 1 162.734 2.800 1 175.929 2.880 1 180.956 2.850 1 179.071 177.736 187.867 162.734

Average Resistivity in Direction 138.632 138.645 158.010 161.855 155.635 147.115 145.179 134.071 147.393

Project Code_202109004-ERT Page 18 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

DETERMINATION OF EARTH RESISTIVITY

CLIENT: SUNSOURCE ENERGY PVT.LTD.

PROJECT : ERT FOR 06 MW SOLAR PV PLANT

LOCATION: TULJAPUR,MAHARASTRA
D4 D3 D2
CO-ORDINATES: N-1953319.906 E-598412.491
TEMPERATURE: 34°C HUMIDITY :65%

PROJECT CODE.: 202109004 200.000


METHOD OF RESISTIVITY SURVEY : Wenner's Method as per IS:3043-1987

138.632
Direction:
134.07 North 150.000 138.645
1
Test Electrodes Test Electrodes Distance
Resistance, Ohm Current Factor
Apparent
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 100.000 12.400 1 77.911
3.00 1.00 2.00 9.560 1 120.135
4.50 1.50 3.00 7.180 1 135.340
7.50 2.50 5.00 5.190 1 163.049
15.00 5.00 10.00
50.000 2.470 1 155.195

D5 Direction: North-East D
-145.179 158.01 1
Test Electrodes Test Electrodes Distance 0.000 Apparent
Resistance, Ohm Current Factor0
AB / 2 MN / 2 'a' Resistivity
-200.000 -150.000 -100.000 -50.000 0.000 50.000 100.000 150.000 200.000
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 -50.000 8.300 1 104.301
4.50 1.50 3.00 6.840 1 128.931
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.330 1 146.398
-100.000
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
-150.000
in m in m in m R=V/I f 'r' = 2paRf
-147.115
1.50 0.50 1.00 11.690 1 73.450
-155.635 -161.855
3.00 1.00 2.00 8.410 1 105.683
4.50 1.50 -200.000 6.980
3.00 1 D8
131.570
D D
7.50 2.50 5.00 5.440 1 170.903
6 Inside 7
Area of Polar Curve = 27 Units
15.00 5.00 10.00 2.500 1 157.080
Equivalent Radius ( I.e. a.v. resistivity) =147.393Ohm-m
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.410 1 77.974
3.00 1.00 2.00 8.570 1 107.694
4.50 1.50 3.00 8.110 1 152.870
7.50 2.50 5.00 5.620 1 176.558
15.00 5.00 10.00 2.590 1 162.734

Project Code_202109004-ERT Page 19 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 20 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 7.250 1 91.106
4.50 1.50 3.00 6.540 1 123.276
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.480 1 155.823

Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.650 1 73.199
3.00 1.00 2.00 8.240 1 103.547
4.50 1.50 3.00 6.980 1 131.570
7.50 2.50 5.00 5.770 1 181.270
15.00 5.00 10.00 2.630 1 165.248

Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.350 1 77.597
3.00 1.00 2.00 8.390 1 105.432
4.50 1.50 3.00 7.540 1 142.126
7.50 2.50 5.00 5.820 1 182.841
15.00 5.00 10.00 2.370 1 148.911

Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.210 1 76.718
3.00 1.00 2.00 9.460 1 118.878
4.50 1.50 3.00 6.210 1 117.056
7.50 2.50 5.00 5.540 1 174.044
15.00 5.00 10.00 2.400 1 150.796

Project Code_202109004-ERT Page 21 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Results of Electrical Resistivity


Wenner Method (IS-3043)
Project No: 202109004

Client: SUNSOURCE ENERGY PVT.LTD.


Project: ERT FOR 06 MW SOLAR PV PLANT
Co-ordinates: N-1953319.906 E-598412.491
Temperature: 34°C HUMIDITY :65%

Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method

Electric Resistivity: r in ohm-meter = 2paR (Ω.m)

where a = Distance between two successive electrodes in meter (m)


R = V/I = Resistance in ohm (Ω)

Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth

m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)

1 1.50 0.50 1.00 12.400 1 77.911 11.640 1 73.136 11.690 1 73.450 12.410 1 77.974 11.350 1 71.314 11.650 1 73.199 12.350 1 77.597 12.210 1 76.718 75.163 77.974 71.314

2 3.00 1.00 2.00 9.560 1 120.135 8.300 1 104.301 8.410 1 105.683 8.570 1 107.694 7.250 1 91.106 8.240 1 103.547 8.390 1 105.432 9.460 1 118.878 107.097 120.135 91.106

3 4.50 1.50 3.00 7.180 1 135.340 6.840 1 128.931 6.980 1 131.570 8.110 1 152.870 6.540 1 123.276 6.980 1 131.570 7.540 1 142.126 6.210 1 117.056 132.842 152.870 117.056

4 7.50 2.50 5.00 5.190 1 163.049 5.340 1 167.761 5.440 1 170.903 5.620 1 176.558 5.500 1 172.788 5.770 1 181.270 5.820 1 182.841 5.540 1 174.044 173.652 182.841 163.049

5 15.00 5.00 10.00 2.470 1 155.195 2.330 1 146.398 2.500 1 157.080 2.590 1 162.734 2.480 1 155.823 2.630 1 165.248 2.370 1 148.911 2.400 1 150.796 155.273 165.248 146.398

Average Resistivity in Direction 130.326 124.105 127.737 135.566 122.861 130.967 131.381 127.498 128.805

Project Code_202109004-ERT Page 22 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

D4 D3 D2

150.000
127.49 130.326 124.105
8

75.000

D5 D
-131.381 127.737
0.000 1
-150.000 -75.000 0.000 75.000 150.000

-75.000

-122.861
-130.967 -135.566
-150.000 D8
D D
6 7
Inside Area of Polar Curve = 05 Units
Equivalent Radius ( I.e. a.v. resistivity) =128.805Ohm-m

Project Code_202109004-ERT Page 23 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

FIELD DATA SHEET

Project Code_202109004-ERT Page 24 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 25 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 26 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 27 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 28 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

Project Code_202109004-ERT Page 29 of 31


IDAX CONSULTING & RESEARCH PVT. LTD.

FIELD PHOTOGRAPHS

Project Code_202109004-ERT Page 30 of 31