TESTING AGENCY:
IDAX CONSULTING & RESEARCH PVT.LTD.
Plot No. - 5016, Duplex-E, Brundaban Enclave, VSS Nagar,
Bhubaneswar-751007, Odisha (INDIA).
Tel: 7735599991
E-mail: info@idaxconsulting.com
Web: www.idaxconsulting.com
1. INTRODUCTION:
The Earth Resistivity Test (ERT) of soil was carried out at site for EARTH
RESISTIVITY TEST WORK AT TULJAPUR SITE MAHARASHTRA. with the aim to
determine an average value of electrical resistivity of soil for design of safe earthing
system. The Earth resistivity field test were done in 02.11.2021 at FIVE locations
given as directed by the client.
2. PURPOSE OF INVESTIGATION:
The purpose of this investigation is to determine an average value of electrical
resistivity of subsurface for design of safe earthing system with the help of
Microprocessor based electrical resistivity meter model DET-Auto.
3. GEOPHYSICAL INVESTIGATION:
Geophysical investigation was carried out as per IS: 3043-1987 on the basis of Earth
Resistivity meter model no. DET-Auto. Wenner’s four-electrode method is used to
determine the earth resistivity.
4. WENNER’S CONFIGURATION:
This is one of the most commonly used arrays proposed by Wenner in 1916. Four
electrodes A, B, M, and N are placed at the surface of the ground along a straight
symmetrically about a point O. The observation point in such a way that the distance
between AM = MN =NB = a., Where ‘a’ is called electrode separation see fig. 1.
Current ‘I’ is sent generally through outer electrodes A and B and the potential
difference (V) is measured between M and N. The instrument multiplication factor is f.
Electrode shall be driven in to the earth to a depth ‘B’. The depth ‘B’ should be ideally less
than 1/20 of spacing ‘A’.
Apparent Resistivity, = 2aR (As per IS: 3043 – 1987, Clause No. : 36.3.1.2)
5. Survey Procedure:
Resistivity sounding is used to make investigations along the depth. In this method
the center of configuration is kept fixed and measurements are made by successively
increasing electrode spacing. The apparent resistivity values obtained with increasing
values of electrode separations are used to estimate the thickness and resistivity of
the subsurface formations. In Wenner’s configuration all the four electrodes are
arranged in a line at a equal distance ‘a’ between the consecutive electrodes.
Measurements were taken at 1m,2m,3m,5m & 10m. Current is sent through the
outer electrodes and the potential difference is measured between the inner
electrodes. The Resistance (R = V/I) is measured for each electrode separation and
apparent resistivity is calculated by multiplying value of ‘R’ with Wenner configuration
factor (2a), where ‘a’ is the uniform distance between the electrodes. The
computation of the sounding data is discussed in the subsequent section.
7. Results:
I. The electric resistivity test of the site were performed in 02.11.2021 at FIVE locations
as suggested by client.
III. Average Resistivity / Equivalent Radius from polar curve are 130.935 Ohm-m.
8. LIMITATION
The Electrical resistivity testing has been carried out at the location chosen by the
client. In general resistivity values are influenced by water, presence of dissolved ions
in soil media and nature of strata. Recommendations made in the report are hence
valid only for tested locations only. However if there is any change in subsoil
conditions and properties at places beyond chosen test locations, the soil consultants
to be contacted for further guidance.
LOCATION: TULJAPUR,MAHARASTRA
Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.300 1 89.850
3.00 1.00 2.00 9.520 1 119.632
4.50 1.50 3.00 7.840 1 147.781
7.50 2.50 5.00 5.220 1 163.991
15.00 5.00 10.00 2.560 1 160.850
Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 13.110 1 82.373
3.00 1.00 2.00 8.780 1 110.333
4.50 1.50 3.00 6.740 1 127.046
7.50 2.50 5.00 5.360 1 168.389
15.00 5.00 10.00 2.710 1 170.274
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.050 1 94.562
3.00 1.00 2.00 10.350 1 130.062
4.50 1.50 3.00 6.680 1 125.915
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.600 1 163.363
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.190 1 89.158
3.00 1.00 2.00 8.740 1 109.830
4.50 1.50 3.00 6.740 1 127.046
7.50 2.50 5.00 5.280 1 165.876
15.00 5.00 10.00 2.920 1 183.469
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.700 1 92.363
3.00 1.00 2.00 8.820 1 110.835
4.50 1.50 3.00 7.510 1 141.560
7.50 2.50 5.00 5.660 1 177.814
15.00 5.00 10.00 2.580 1 162.106
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.550 1 91.420
3.00 1.00 2.00 8.710 1 109.453
4.50 1.50 3.00 6.510 1 122.711
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.690 1 169.018
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.030 1 88.153
3.00 1.00 2.00 8.540 1 107.317
4.50 1.50 3.00 6.210 1 117.056
7.50 2.50 5.00 5.180 1 162.734
15.00 5.00 10.00 2.500 1 157.080
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 14.280 1 89.724
3.00 1.00 2.00 9.700 1 121.894
4.50 1.50 3.00 7.520 1 141.749
7.50 2.50 5.00 5.950 1 186.925
15.00 5.00 10.00 2.560 1 160.850
Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 14.300 1 89.850 13.110 1 82.373 15.050 1 94.562 14.190 1 89.158 14.700 1 92.363 14.550 1 91.420 14.030 1 88.153 14.280 1 89.724 89.700 94.562 82.373
2 3.00 1.00 2.00 9.520 1 119.632 8.780 1 110.333 10.350 1 130.062 8.740 1 109.830 8.820 1 110.835 8.710 1 109.453 8.540 1 107.317 9.700 1 121.894 114.919 130.062 107.317
3 4.50 1.50 3.00 7.840 1 147.781 6.740 1 127.046 6.680 1 125.915 6.740 1 127.046 7.510 1 141.560 6.510 1 122.711 6.210 1 117.056 7.520 1 141.749 131.358 147.781 117.056
4 7.50 2.50 5.00 5.220 1 163.991 5.360 1 168.389 5.340 1 167.761 5.280 1 165.876 5.660 1 177.814 5.340 1 167.761 5.180 1 162.734 5.950 1 186.925 170.157 186.925 162.734
5 15.00 5.00 10.00 2.560 1 160.850 2.710 1 170.274 2.600 1 163.363 2.920 1 183.469 2.580 1 162.106 2.690 1 169.018 2.500 1 157.080 2.560 1 160.850 165.876 183.469 157.080
Average Resistivity in Direction 136.421 131.683 136.333 135.076 136.936 132.073 126.468 140.228 134.402
LOCATION: TULJAPUR,MAHARASTRA
Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.650 1 79.482
3.00 1.00 2.00 8.960 1 112.595
4.50 1.50 3.00 8.410 1 158.525
7.50 2.50 5.00 5.010 1 157.394
15.00 5.00 10.00 2.600 1 163.363
Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.400 1 77.911
3.00 1.00 2.00 8.560 1 107.568
4.50 1.50 3.00 7.690 1 144.953
7.50 2.50 5.00 5.160 1 162.106
15.00 5.00 10.00 2.590 1 162.734
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.960 1 68.864
3.00 1.00 2.00 7.200 1 90.478
4.50 1.50 3.00 6.350 1 119.695
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.690 1 169.018
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 7.260 1 91.232
4.50 1.50 3.00 6.540 1 123.276
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.320 1 145.770
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 6.240 1 78.414
4.50 1.50 3.00 5.420 1 102.165
7.50 2.50 5.00 5.090 1 159.907
15.00 5.00 10.00 1.520 1 95.504
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.370 1 65.157
3.00 1.00 2.00 7.810 1 98.143
4.50 1.50 3.00 6.980 1 131.570
7.50 2.50 5.00 5.420 1 170.274
15.00 5.00 10.00 2.740 1 172.159
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.130 1 63.649
3.00 1.00 2.00 7.720 1 97.012
4.50 1.50 3.00 6.910 1 130.250
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.840 1 178.442
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.990 1 75.335
3.00 1.00 2.00 8.960 1 112.595
4.50 1.50 3.00 8.370 1 157.771
7.50 2.50 5.00 5.620 1 176.558
15.00 5.00 10.00 2.600 1 163.363
Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 12.650 1 79.482 12.400 1 77.911 10.960 1 68.864 11.350 1 71.314 11.350 1 71.314 10.370 1 65.157 10.130 1 63.649 11.990 1 75.335 71.628 79.482 63.649
2 3.00 1.00 2.00 8.960 1 112.595 8.560 1 107.568 7.200 1 90.478 7.260 1 91.232 6.240 1 78.414 7.810 1 98.143 7.720 1 97.012 8.960 1 112.595 98.505 112.595 78.414
3 4.50 1.50 3.00 8.410 1 158.525 7.690 1 144.953 6.350 1 119.695 6.540 1 123.276 5.420 1 102.165 6.980 1 131.570 6.910 1 130.250 8.370 1 157.771 133.526 158.525 102.165
4 7.50 2.50 5.00 5.010 1 157.394 5.160 1 162.106 5.340 1 167.761 5.500 1 172.788 5.090 1 159.907 5.420 1 170.274 5.500 1 172.788 5.620 1 176.558 167.447 176.558 157.394
5 15.00 5.00 10.00 2.600 1 163.363 2.590 1 162.734 2.690 1 169.018 2.320 1 145.770 1.520 1 95.504 2.740 1 172.159 2.840 1 178.442 2.600 1 163.363 156.294 178.442 95.504
Average Resistivity in Direction 134.272 131.055 123.163 120.876 101.461 127.461 128.428 137.124 125.480
D4 D3 D2
180.000
134.272 131.055
137.12
4
120.000
60.000
D5 D
-128.428 123.163 1
0.000
-180.000 -120.000 -60.000 0.000 60.000 120.000 180.000
-60.000
-120.000
-120.876
-101.461
-
127.461
-180.000 D8
D D
6 7
Inside Area of Polar Curve = 13 Units
Equivalent Radius ( I.e. a.v. resistivity) =125.480Ohm-m
LOCATION: TULJAPUR,MAHARASTRA
Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 8.220 1 103.296
4.50 1.50 3.00 7.520 1 141.749
7.50 2.50 5.00 5.110 1 160.535
15.00 5.00 10.00 1.950 1 122.522
Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.920 1 68.612
3.00 1.00 2.00 7.180 1 90.227
4.50 1.50 3.00 6.230 1 117.433
7.50 2.50 5.00 5.440 1 170.903
15.00 5.00 10.00 2.610 1 163.991
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 9.840 1 61.827
3.00 1.00 2.00 8.710 1 109.453
4.50 1.50 3.00 5.360 1 101.034
7.50 2.50 5.00 5.160 1 162.106
15.00 5.00 10.00 2.500 1 157.080
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 10.080 1 63.335
3.00 1.00 2.00 8.460 1 106.311
4.50 1.50 3.00 5.630 1 106.123
7.50 2.50 5.00 5.200 1 163.363
15.00 5.00 10.00 2.350 1 147.655
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.520 1 72.382
3.00 1.00 2.00 7.880 1 99.023
4.50 1.50 3.00 6.230 1 117.433
7.50 2.50 5.00 5.170 1 162.420
15.00 5.00 10.00 2.040 1 128.177
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.000 1 69.115
3.00 1.00 2.00 8.330 1 104.678
4.50 1.50 3.00 5.590 1 105.369
7.50 2.50 5.00 5.060 1 158.965
15.00 5.00 10.00 2.170 1 136.345
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.290 1 70.937
3.00 1.00 2.00 8.550 1 107.442
4.50 1.50 3.00 5.700 1 107.442
7.50 2.50 5.00 5.120 1 160.850
15.00 5.00 10.00 2.350 1 147.655
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 8.290 1 104.175
4.50 1.50 3.00 6.820 1 128.554
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.090 1 131.319
Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 11.640 1 73.136 10.920 1 68.612 9.840 1 61.827 10.080 1 63.335 11.520 1 72.382 11.000 1 69.115 11.290 1 70.937 11.640 1 73.136 69.060 73.136 61.827
2 3.00 1.00 2.00 8.220 1 103.296 7.180 1 90.227 8.710 1 109.453 8.460 1 106.311 7.880 1 99.023 8.330 1 104.678 8.550 1 107.442 8.290 1 104.175 103.076 109.453 90.227
3 4.50 1.50 3.00 7.520 1 141.749 6.230 1 117.433 5.360 1 101.034 5.630 1 106.123 6.230 1 117.433 5.590 1 105.369 5.700 1 107.442 6.820 1 128.554 115.642 141.749 101.034
4 7.50 2.50 5.00 5.110 1 160.535 5.440 1 170.903 5.160 1 162.106 5.200 1 163.363 5.170 1 162.420 5.060 1 158.965 5.120 1 160.850 5.340 1 167.761 163.363 170.903 158.965
5 15.00 5.00 10.00 1.950 1 122.522 2.610 1 163.991 2.500 1 157.080 2.350 1 147.655 2.040 1 128.177 2.170 1 136.345 2.350 1 147.655 2.090 1 131.319 141.843 163.9 1 122.522
Average Resistivity in Direction 120.248 122.233 118.300 117.357 115.887 114.894 118.865 120.989 118.597
D4 D3 D2
140.000
120.98 120.248 122.23
9 3
70.000
D5 D
-118.865 118.300
0.000 1
-140.000 -70.000 0.000 70.000 140.000
-70.000
-114.894 -115.887
-117.357
-140.000 D8
D D
6 7
Inside Area of Polar Curve = 05 Units
Equivalent Radius ( I.e. a.v. resistivity) =118.597Ohm-m
LOCATION: TULJAPUR,MAHARASTRA
Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.050 1 94.562
3.00 1.00 2.00 9.350 1 117.496
4.50 1.50 3.00 6.990 1 131.758
7.50 2.50 5.00 5.420 1 170.274
15.00 5.00 10.00 2.850 1 179.071
Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.670 1 98.458
3.00 1.00 2.00 9.210 1 115.736
4.50 1.50 3.00 6.430 1 121.203
7.50 2.50 5.00 5.790 1 181.898
15.00 5.00 10.00 2.800 1 175.929
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.200 1 101.788
3.00 1.00 2.00 10.340 1 129.936
4.50 1.50 3.00 8.170 1 154.001
7.50 2.50 5.00 6.890 1 216.456
15.00 5.00 10.00 2.990 1 187.867
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.370 1 102.856
3.00 1.00 2.00 11.000 1 138.230
4.50 1.50 3.00 9.410 1 177.374
7.50 2.50 5.00 6.700 1 210.487
15.00 5.00 10.00 2.870 1 180.327
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 16.540 1 103.924
3.00 1.00 2.00 10.950 1 137.602
4.50 1.50 3.00 9.370 1 176.620
7.50 2.50 5.00 6.280 1 197.292
15.00 5.00 10.00 2.590 1 162.734
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.490 1 97.327
3.00 1.00 2.00 10.270 1 129.057
4.50 1.50 3.00 8.630 1 162.672
7.50 2.50 5.00 5.430 1 170.588
15.00 5.00 10.00 2.800 1 175.929
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.270 1 95.944
3.00 1.00 2.00 9.410 1 118.250
4.50 1.50 3.00 7.630 1 143.822
7.50 2.50 5.00 5.950 1 186.925
15.00 5.00 10.00 2.880 1 180.956
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 15.080 1 94.750
3.00 1.00 2.00 8.240 1 103.547
4.50 1.50 3.00 6.560 1 123.653
7.50 2.50 5.00 5.390 1 169.332
15.00 5.00 10.00 2.850 1 179.071
Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 15.050 1 94.562 15.670 1 98.458 16.200 1 101.788 16.370 1 102.856 16.540 1 103.924 15.490 1 97.327 15.270 1 95.944 15.080 1 94.750 98.701 103.924 94.562
2 3.00 1.00 2.00 9.350 1 117.496 9.210 1 115.736 10.340 1 129.936 11.000 1 138.230 10.950 1 137.602 10.270 1 129.057 9.410 1 118.250 8.240 1 103.547 123.732 138.230 103.547
3 4.50 1.50 3.00 6.990 1 131.758 6.430 1 121.203 8.170 1 154.001 9.410 1 177.374 9.370 1 176.620 8.630 1 162.672 7.630 1 143.822 6.560 1 123.653 148.888 177.374 121.203
4 7.50 2.50 5.00 5.420 1 170.274 5.790 1 181.898 6.890 1 216.456 6.700 1 210.487 6.280 1 197.292 5.430 1 170.588 5.950 1 186.925 5.390 1 169.332 187.907 216.456 169.332
5 15.00 5.00 10.00 2.850 1 179.071 2.800 1 175.929 2.990 1 187.867 2.870 1 180.327 2.590 1 162.734 2.800 1 175.929 2.880 1 180.956 2.850 1 179.071 177.736 187.867 162.734
Average Resistivity in Direction 138.632 138.645 158.010 161.855 155.635 147.115 145.179 134.071 147.393
LOCATION: TULJAPUR,MAHARASTRA
D4 D3 D2
CO-ORDINATES: N-1953319.906 E-598412.491
TEMPERATURE: 34°C HUMIDITY :65%
138.632
Direction:
134.07 North 150.000 138.645
1
Test Electrodes Test Electrodes Distance
Resistance, Ohm Current Factor
Apparent
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 100.000 12.400 1 77.911
3.00 1.00 2.00 9.560 1 120.135
4.50 1.50 3.00 7.180 1 135.340
7.50 2.50 5.00 5.190 1 163.049
15.00 5.00 10.00
50.000 2.470 1 155.195
D5 Direction: North-East D
-145.179 158.01 1
Test Electrodes Test Electrodes Distance 0.000 Apparent
Resistance, Ohm Current Factor0
AB / 2 MN / 2 'a' Resistivity
-200.000 -150.000 -100.000 -50.000 0.000 50.000 100.000 150.000 200.000
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.640 1 73.136
3.00 1.00 2.00 -50.000 8.300 1 104.301
4.50 1.50 3.00 6.840 1 128.931
7.50 2.50 5.00 5.340 1 167.761
15.00 5.00 10.00 2.330 1 146.398
-100.000
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
-150.000
in m in m in m R=V/I f 'r' = 2paRf
-147.115
1.50 0.50 1.00 11.690 1 73.450
-155.635 -161.855
3.00 1.00 2.00 8.410 1 105.683
4.50 1.50 -200.000 6.980
3.00 1 D8
131.570
D D
7.50 2.50 5.00 5.440 1 170.903
6 Inside 7
Area of Polar Curve = 27 Units
15.00 5.00 10.00 2.500 1 157.080
Equivalent Radius ( I.e. a.v. resistivity) =147.393Ohm-m
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.410 1 77.974
3.00 1.00 2.00 8.570 1 107.694
4.50 1.50 3.00 8.110 1 152.870
7.50 2.50 5.00 5.620 1 176.558
15.00 5.00 10.00 2.590 1 162.734
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.350 1 71.314
3.00 1.00 2.00 7.250 1 91.106
4.50 1.50 3.00 6.540 1 123.276
7.50 2.50 5.00 5.500 1 172.788
15.00 5.00 10.00 2.480 1 155.823
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 11.650 1 73.199
3.00 1.00 2.00 8.240 1 103.547
4.50 1.50 3.00 6.980 1 131.570
7.50 2.50 5.00 5.770 1 181.270
15.00 5.00 10.00 2.630 1 165.248
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.350 1 77.597
3.00 1.00 2.00 8.390 1 105.432
4.50 1.50 3.00 7.540 1 142.126
7.50 2.50 5.00 5.820 1 182.841
15.00 5.00 10.00 2.370 1 148.911
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f 'r' = 2paRf
1.50 0.50 1.00 12.210 1 76.718
3.00 1.00 2.00 9.460 1 118.878
4.50 1.50 3.00 6.210 1 117.056
7.50 2.50 5.00 5.540 1 174.044
15.00 5.00 10.00 2.400 1 150.796
Location TULJAPUR,MAHARASTRA
Method of Resistivity Survey: Wenner's Method
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 12.400 1 77.911 11.640 1 73.136 11.690 1 73.450 12.410 1 77.974 11.350 1 71.314 11.650 1 73.199 12.350 1 77.597 12.210 1 76.718 75.163 77.974 71.314
2 3.00 1.00 2.00 9.560 1 120.135 8.300 1 104.301 8.410 1 105.683 8.570 1 107.694 7.250 1 91.106 8.240 1 103.547 8.390 1 105.432 9.460 1 118.878 107.097 120.135 91.106
3 4.50 1.50 3.00 7.180 1 135.340 6.840 1 128.931 6.980 1 131.570 8.110 1 152.870 6.540 1 123.276 6.980 1 131.570 7.540 1 142.126 6.210 1 117.056 132.842 152.870 117.056
4 7.50 2.50 5.00 5.190 1 163.049 5.340 1 167.761 5.440 1 170.903 5.620 1 176.558 5.500 1 172.788 5.770 1 181.270 5.820 1 182.841 5.540 1 174.044 173.652 182.841 163.049
5 15.00 5.00 10.00 2.470 1 155.195 2.330 1 146.398 2.500 1 157.080 2.590 1 162.734 2.480 1 155.823 2.630 1 165.248 2.370 1 148.911 2.400 1 150.796 155.273 165.248 146.398
Average Resistivity in Direction 130.326 124.105 127.737 135.566 122.861 130.967 131.381 127.498 128.805
D4 D3 D2
150.000
127.49 130.326 124.105
8
75.000
D5 D
-131.381 127.737
0.000 1
-150.000 -75.000 0.000 75.000 150.000
-75.000
-122.861
-130.967 -135.566
-150.000 D8
D D
6 7
Inside Area of Polar Curve = 05 Units
Equivalent Radius ( I.e. a.v. resistivity) =128.805Ohm-m