Lift Load Calculations
P * m * g *s * (1-CF) = 8 * 68.00
8 Lift Motor Size (M) =
ɳ = 0.85
Power requirement of
9 Automatic Rescue Device for = = Say 5
battery charging
= 8
= 1.0 m/sec
= 40 % Quite common it is
considered as 40%
= 9.81 m/sec2
Combined efficiency of
= 85.00 % the installation
* 9.81 * 1.0 * 0.60
= 3767.04 W
0.85
= 3.77 KW
of Lift motor
% size = 0.19 KW
= 0.50 KW Approx
= 5.97 HP
Say 6.00 HP
Consider 3 min requirement of ARD & charging of batteries in 1 hour.
So Power requirement will be (3/60)/1 = 5% of motor power