Professional Documents
Culture Documents
Han 2017
Han 2017
a r t i c l e i n f o a b s t r a c t
Article history: The heat released from the air-conditioners of large public buildings, which has long-term and far-
Received 14 June 2016 reaching influences, not only changes the thermal environment surrounding the buildings but also
Received in revised form profoundly impacts the air-conditioner energy consumption. In this paper, a quantitative evaluation of
24 October 2016
the impact of the heat release modes and positions of air-conditioner external units on both the envi-
Accepted 25 October 2016
Available online 26 October 2016
ronment surrounding the buildings and the air-conditioner energy consumption of large public buildings
is conducted using a coupled simulation of convection, radiation and conduction and air-conditioner
energy cost. Principles for external unit positions are explored as well.
Keywords:
Large public buildings
© 2016 Elsevier Ltd. All rights reserved.
Air-conditioner energy consumption
Heat release
External air-conditioner units
1. Introduction activities, more seriously than higher external units on the roof
[8,9].
Accompanied by the explosion of urbanization, the heat island Unfortunately, external air-conditioner units are still placed
phenomenon in cities has been seriously aggravated with wors- merely in compliance with the visual aesthetics of buildings. Very
ening thermal environments [1]. (Fig. 1). little has been achieved in implementing systematic research of the
To relieve this situation, recent studies have simulated air- relationship between the external units and air-conditioner energy
conditioner energy consumption to reduce this consumption and consumption.
to increase air-conditioner efficiency [2e4]. Research on the effect The impact of various heat release modes and external unit
of air-conditioner heat release on the outside thermal environment positions on the air-conditioner energy consumption is analysed in
is already well known [5]. In contrast, less attention has been paid this study using a coupled simulation of convection, radiation and
to the impact of heat release modes and external air-conditioning conduction and energy cost. A quantitative evaluation is advocated
unit positions on air-conditioner energy consumption. with principles for exploring the external unit positions. This is a
The heat release not only changes the thermal environment beneficial attempt to reduce the air-conditioner energy consump-
surrounding large public buildings but also impacts the air- tion of large public buildings and to improve the thermal envi-
conditioner energy consumption of the buildings due to the large ronment outside.
and long-term heat release in dense cities. Some researchers have
discovered that the air-conditioner cooling energy consumption 2. Research outline
increases when the outdoor temperature increases due to the air-
conditioner heat release [6,7]. Moreover, other researchers have 2.1. Method
indicated that varying the positions of external air-conditioner
units can affect the environment; for example, lower external Due to the variation of the air temperature, humidity and ve-
units will affect the environment, especially the areas of human locity around buildings caused by air-conditioner heat release,
three main methods of energy exchange between the inner build-
ing and outer environment have changed, altering both the sensible
* Corresponding author. and latent heat energy consumption (cooling and dehumidifica-
E-mail address: chhwh@hust.edu.cn (H. Chen). tion) of air-conditioners. These three methods are heat exchange
http://dx.doi.org/10.1016/j.buildenv.2016.10.014
0360-1323/© 2016 Elsevier Ltd. All rights reserved.
48 M. Han, H. Chen / Building and Environment 111 (2017) 47e60
Fig. 1. Air-conditioner heat release intensifying the heat island phenomenon (Top: a picture of air-conditioner external units; bottom: the heat release shown by an infrared
camera).
through the building envelope, heat exchange caused by necessary radiation and conduction with the heat release calculated in step 1
ventilation and heat exchange caused by infiltration due to poor used as the boundary conditions; (3) the new energy consumption
airtightness of the envelope. Some studies indicate that the heat is calculated by simulating the air-conditioner energy consumption
exchange through a building envelope has much less of an impact as affected by the heat release according to step 2.
than the other two ways, approximately 1/400 of the other two Two kinds of computer simulation is used in this research,
[11]. Therefore, only heat exchanges by ventilation and infiltration which are both already been validated and applied. The core
are considered in this research. simulation of this research is called a coupled simulation of con-
Fig. 3 shows the technical route of this research: (1) the initial vection, radiation and conduction. This method is developed by
air-conditioner energy consumption and heat release are simulated Chen and Ooka [10e12] and has been successful validated and
based on the typical local weather condition; (2) the air velocity, applied in several researches [10] for over ten years. The simulation
temperature and relative humidity around the building and the method of air-conditioner energy consumption and heat release
average temperature and humidity of the layer adjacent to the using DeST-C is developed by Tsinghua University, which also
building are simulated using a coupled simulation of convection, successfully has been applied in several researches for almost
without heat release. In addition, considering the various positions 2.3.2. Validation of the boundary conditions
of the external units, the split-type system cases are individually set In this research, the background data used for the solar radiation
up, as shown in Table 2 and the diagram is shown in Fig. 7. simulation are from a field measurement in Wuhan by our research
team lasting for two years that was carried out for two days (July
31-August 1) every summer [15e17]. Data of the hours from 9:00 to
2.3. Boundary conditions 17:00 were adopted. Approximately 10 fixed points are spread out
along the streets in the block besides the Yangtze River, which is the
2.3.1. Boundary conditions for the simulation largest river in China; Fig. 8 shows the sites.
A two-day solar radiation simulation is carried out. The results Among the measurement results, the background is used in this
of 14:00 on the second day is adopted for part of the initial CFD study, as shown as Fig. 9, which characteristically describes Wuhan
condition. The parameters for the initial solar radiation simulation City's weather condition [17].
are shown in Table 3, and the CFD parameters are shown in Table 4. On the other side, the boundary conditions for the air-
The solar radiation background parameters vary over time, so conditioner energy consumption simulation, and the parameters
Table 3 shows 14:00 on the second day as an example. of the building envelope's thermal performance and the air-
M. Han, H. Chen / Building and Environment 111 (2017) 47e60 51
Table 1
Analysis cases for the central air-conditioner system.
Case groups Position of the external units Heat release mode Case name
Fig. 6. Diagram of the different positions of the external central air-conditioner units.
conditioner services are quoted from a Chinese official energy ef- measurement was carried out in an office high-rise in Wuhan city
ficiency architecture design standard [18]. in July 2012, in which the three types of air-conditioner heat release
Third, the parameters of the outlet of the air-conditioning sys- modes were all used: the cooling tower air-conditioner, a few small
tems calculated from the heat release refer to the research by Chen office VRV systems and split-type air-conditioners. The general
Hong, OOKA [12] and real commercial air-conditioner systems. To measurement situation is shown in Table 5 and Fig. 10.
validate the outlet parameters, another air-conditioner field Figs. 11 and 12 show the measurement results. The tendency of
Table 2
Analysis cases for the split-type air-conditioner system.
Fig. 7. Diagram of the different positions of the external split-type air-conditioner units.
Table 4
Boundary conditions for CFD.
Turbulence model Steady standard kε model (including the buoyancy effect)
Inlet
1
Z 4
U ¼ U0 (4)
Z0
U0 ¼ 2:0m=s,Z0 ¼ 10:0m
3 3
Cm k2 1 Z Z4
ε¼ ,l ¼ 4 Cm k 2 0 (6)
l U0
Side Symmetry
through dehumidification and air temperature. Fig. 16 shows the three cases in which the heat release is located on the ground
impact of moisture release on the moisture content of the layer (Case-G-“X”) is much more serious than that of the three cases
adjacent to the building envelope. The moisture variation of the where the heat release is located on the roof of the annex building
54 M. Han, H. Chen / Building and Environment 111 (2017) 47e60
Fig. 9. Wind rose (left) and temperature and humidity (right) results of the background data.
Table 5
Air-conditioner field measurement situation.
Acquisition item point Acquisition item Time and interval Acquisition position
Background weather Temperature, humidity, radiation, velocity 0:00e24:00, Interval of 2 min 6 m above the highest roof of the building
Cooling tower Outlet temperature, outlet humidity 0:00e24:00, Interval of 2 min Vertically to the outlet of the cooling tower
Outlet velocity 0:00e24:00, Interval of 6 min
VRV Outlet Temperature, Outlet Humidity 0:00e24:00, Interval of 2 min Vertically to the outlet of the VRV
Outlet velocity 0:00e24:00, Interval of 6 min
Split-type Outlet temperature, outlet humidity 0:00e24:00, Interval of 2 min Vertically to the outlet of the split-type air-conditioner
Outlet velocity 0:00e24:00, Interval of 6 min
Fig. 13. Environmental moisture content affected by different external unit positions for the cooling tower cases (Top: the 22.5-m-high plan, bottom: the section).
(Case-A-“X”). On the other hand, there is almost no moisture envelope (TNS): (1) If only the relationship between the release
change in the case where the heat release is located on the roof of locations and the wind direction is considered, the trend of the TNS
the high-rise (Case-R-“X”) because the heat is blown into the high addition is downwind > windward > parallel to wind (shown as the
atmosphere. height of the three curves in Fig. 18). (2) If only the relationship
between the heat release locations and the building is considered,
3.2. Split-type air-conditioner systems the tendency of the TNS addition is location in gaps and outlet into
gaps > location in gaps and outlet leaving gaps > location outside of
Fig. 17 shows that the spilt-type external units' influence TNS gaps and outlet to environment (shown as the tendency of each
much more severely compared with the central air-conditioner curve in Fig. 18).
systems due to the large number of external units and their uni-
form distribution on the façade with high outlet temperatures. 4. Variation of energy consumption of the air-conditioner
Enormous difference is also shown among the split-type cases in
Fig. 17. The increase in air temperature is the greatest when the 4.1. Central air-conditioner systems
outlets are located in the gaps of the building and blow into the
gaps (Split-“X”-E) because of the high accumulation of heat in the 4.1.1. Variation of energy consumption caused by sensible heat
gaps that are less influenced by airflow. release
Fig. 18 shows the relationship between the heat release loca- Fig. 19 shows the central air-conditioner energy consumption
tions and the temperature addition of the layer adjacent to the variation caused by air temperature change with heat release
56 M. Han, H. Chen / Building and Environment 111 (2017) 47e60
Fig. 14. Environmental temperature affected by different external unit positions for the VRV cases (Top: the 1.5-m-high plan, bottom: the section).
Fig. 15. Average temperature and average wind velocity in the volume around the building.
Table 6 energy consumption when using a VRV is certainly higher than that
TNS of the VRV cases. when using a cooling tower in all of the cases. This is because
Case name TNS( C) Increase ( C) sensible heat is the main form of VRV heat release, which
tremendously increases the surrounding air temperature, espe-
Case-G-U-F 36.447 0.093
Case-G-D-F 37.025 0.671
cially adjacent to the building envelope, causing energy consump-
Case-G-P-F 36.728 0.375 tion to increase. Nevertheless, latent heat and very little sensible
Case-A-U-F 36.316 0.037 heat with high-speed wind is the main form of the cooling tower's
Case-A-D-F 36.462 0.142 heat release, so that the airflow in the street canyon increases and
Case-A-P-F 36.379 0.026
the temperature decreases around the building, decreasing the air-
Case-R-F 36.328 0.026
conditioner energy consumption.
compared with the referenced case of Case-Up. The diagram shows 4.1.2. Variation of energy consumption caused by latent heat
that the energy consumption increases to varying degrees when release
VRV external units are used, while all cases decrease to varying Table 7 shows the variation of energy consumption caused by
degrees when using cooling tower external units. The absolute latent heat release, which differs significantly from that caused by
M. Han, H. Chen / Building and Environment 111 (2017) 47e60 57
Fig. 16. Impact of the heat release location on the moisture content of the air layer adjacent to the building.
Fig. 18. Relationship between the addition of TNS and the external unit position in the split-type air-conditioner cases.
sensible heat release (Fig. 19). Due to increased humidity around addition by heat release mode and concludes the following: (1)
the building, the cooling tower increases the energy consumption Sensible heat addition, including ventilation and infiltration, is the
for dehumidification, which is considerably more than that caused main method for increasing the air-conditioner energy consump-
by sensible heat release. A large amount of humid air from the tion in the VRV cases, while dehumidification is the main method
cooling tower accumulates around the building, tremendously for the cooling tower cases. (2) If only the sensible heat release is
increasing the indoor humidity through ventilation and infiltration considered, including ventilation and infiltration, there are both
and increasing the air-conditioner energy consumption for dehu- increases and decreases of energy consumption in the VRV cases,
midification. When VRV is used, the latent heat does not increase mainly increasing; the cooling tower cases only decrease due to the
due to their fan-cooled heat release without moisture. high-speed, high-humidity and low-temperature outlet conditions.
(3) The additional energy consumption for dehumidification of the
4.1.3. Total variation of air-conditioner energy consumption cooling tower cases increase dramatically, even more than the
Fig. 20 shows the total energy consumption addition in all decrease in energy caused by the air temperature decreasing
central air-conditioner case groups caused by varying heat release around the building, resulting in an overall severe energy con-
mode. The total energy addition of the cases of the cooling tower is sumption increase, greater than the increases in the VRV cases. (4)
much more than that of the cases that use VRV. Fig. 21 shows the The minimum increase (in Case-A-U-F) is one-sixth the maximum
58 M. Han, H. Chen / Building and Environment 111 (2017) 47e60
Fig. 19. Air-conditioner energy consumption changes caused by sensible heat release (Case-Up's energy consumption change is 0).
Table 7
Air-conditioner energy consumption changes caused by latent heat release.
Fig. 20. Central air-conditioner energy consumption changes due to different external unit positions.
increase (in Case-G-D-V), indicating the significant effect of than that of the central air-conditioner cases in terms of sensible
different heat release modes and external unit positions of central heat. In particular, the increase is the highest when the heat release
air-conditioner systems on the air-conditioner energy location is windward or downward of the building because of the
consumption. heat accumulation adjacent to the building envelope, for which
ventilation contributes the most. In contrast, the energy con-
sumption increase is smaller when the heat release location is
4.2. Split-type air-conditioner systems
lateral to the building or parallel to the wind and increases the least
when the heat release location is on the roof of the high-rise.
Table 8 shows the energy consumption addition of the split-type
air-conditioner cases. It is obvious that the increase is much higher
M. Han, H. Chen / Building and Environment 111 (2017) 47e60 59
Table 8
Split-type air-conditioner energy consumption changes.
Cases Energy consumption addition from ventilation (kW) Energy consumption addition from infiltration (kW) Total increase in energy consumption (kW)
5. Conclusions (2) Fan-cooled sensible heat release, including VRV and split-
type, will increase the air temperature around building,
In this research, a coupled simulation of convection, radiation usually increasing the air-conditioner energy consumption.
and conduction and the energy cost of air-conditioner is used to (3) Due to latent heat release, a cooling tower air-conditioner
discuss the impact of different heat release modes, including a will tremendously increase the humidity around the build-
central air-conditioner (cooling tower and VRV) and a split-type air- ing, enormously increasing the energy consumption for
conditioner, and various external unit positions on air-conditioner dehumidification but with a slight decrease in sensible
energy consumption in large public buildings. cooling energy consumption.
(4) The use of a cooling tower air-conditioner will result in much
(1) A split-type air-conditioner will affect the environment more energy consumption than that of a VRV if sensible and
around the building more seriously but in a smaller area latent heat release are both considered. Otherwise, the
compared with a central air-conditioner. opposite is true if only sensible heat release is considered.
60 M. Han, H. Chen / Building and Environment 111 (2017) 47e60
(5) Different positions of external units will lead to different reduction strategies, Energy Policy 33 (2007b) 721e756.
[2] J. Tanimoto, A. Hagishima, P. Chimklai, An approach for coupled simulation of
energy consumption even using the same heat release mode.
building thermal effects and urban climatology, Energy Build. 36 (2004)
(6) If only wind direction is considered, the energy consumption 781e793.
tendency of both central and split-type air-conditioners is as [3] J. Tanimoto, A. Hagishima, H. Sagara, A methodology for peak energy
follows: downwind > windward > parallel to wind. When requirement considering actual variation of occupants' behaviour schedules,
Build. Environ. 43 (2008) 610e619.
external units are located downwind or windward, the en- [4] T. Ihara, Y. Genchi, T. Sato, K. Yamaguchi, Y. Endo, City-block-scale sensitivity
ergy addition increases much more for the aggravation of of electricity consumption to air temperature and air humidity in business
heat release around the building envelope, especially districts of Tokyo, Japan, Energy Build. 33 (2008) 1634e1645.
[5] M. Bojic, M. Lee, F. Yik, Influence of a depth of a recessed space to flow due to
through ventilation. When located parallel to the wind, the air-conditioner heat rejection, Energy Build. 34 (2002) 33e43.
total energy addition increases less and addition by infiltra- [6] C.M. Hsieh, T. Aramaki, K. Hanaki, The feedback of heat rejection to air con-
tion dominates. However, the impact on the outside envi- ditioning load during the night in subtropical climate, Energy Build. 39
(2007a) 1175e1182.
ronment is more serious. [7] C.M. Hsieh, T. Aramaki, K. Hanaki, Estimation of heat rejection based on the air
(7) In the central air-conditioner cases, locating external units on conditioner use time and its mitigation from buildings in Taipei City, Build.
the ground and at the back of the building forms a vortex Environ. 42 (9) (2007b) 3125e3137.
[8] S. Dhakal, K. Hanaki, Improvement of urban thermal environment by man-
zone that will lead to the greatest increase in energy con-
aging heat discharge sources and surface modification in Tokyo, Energy Build.
sumption, while locating them on the roof will lead to the 34 (2002) 13e23.
smallest increase. In general, if only the positions are [9] R. de Dear, J. Richard, G.S. Brager, Thermal comfort in naturally ventilated
buildings: revisions to ASHRAE Standard 55, Energy Build. 34 (6) (2002)
considered, the trend of the energy consumption increase is
549e561.
as follows: located on the ground > located on top of the [10] Hong Chen, Ryozo Ooka, Study on outdoor thermal environment of apartment
annex > located on top of the high-rise roof. Therefore, the block in Shenzhen, China with coupled simulation of convection, radiation
higher the external units are located, the smaller the air- and conduction, Energy Build. 36 (2004) 1247e1258.
[11] H. Chen, R. Ooka, H. Huang, M. Nakashima, Study on the impact of sensible
conditioner energy consumption increase is. heat flux from building walls and artificial heat release from buildings on
(8) In the split-type air-conditioner cases, the tendency of the outdoor thermal environments using coupled simulations of convection, ra-
energy consumption increase by positions is as follows: diation, and conduction, in: The Six International Conference on Urban Cli-
mate(ICUC6), 2006.
located in gaps with the outlet into the gaps > located in gaps [12] H. Chen, R. Ooka, H. Huang, et al., Study on mitigation measures for outdoor
with the outlet facing out of the gaps > located outside of the thermal environment on present urban blocks in Tokyo using coupled
gaps with the outlet to the environment. The energy con- simulation, Build. Environ. 44 (11) (2009) 2290e2299.
[13] Tianzhen Hong, Yi Jiang, A new multizone model for the simulation of
sumption will be more seriously affected when the external building thermal performance, Build. Environ. 32 (No.2) (1997) 123e128.
units are located in the gaps of the building because of heat [14] D.P. Bloomfield, Y. Jiang, A program documentation system and the work of
accumulation in the gaps. IEA annex 31, in: Proc. Systems Simulation Conference, University of Liege,
December 1990.
[15] M. Han, H. Chen, L. Yuan, et al., CFD analysis on cooling effect on a complex
In conclusion, the heat release modes and positions of the traditional urban area with river wind in summer, in: International Confer-
external units tremendously influence air-conditioner energy ence on Multimedia Technology(ICMT), Hangzhou, China, 2011.
[16] Y. Cai, H. Chen, L. Yuan, et al., Study of comparison between effects on micro-
consumption, so they should be considered with care in the ar-
climate of two sides of Yangtze River with river wind in Wuhan in winter,
chitecture design process. Adv. Mater. Res. 361e363 (2011) 1177e1181.
[17] G. Han, H. Chen, L. Yuan, et al., Field measurements on micro-climate and
Acknowledgement cooling effect of river wind on urban blocks in Wuhan city, in: International
Conference on Multimedia Technology (ICMT), Hangzhou, China, 2011.
[18] Ministry of Housing and Urban-Rural Development of the People’s Republic of
This paper was supported by projects of the National Natural China, Design Standard for Energy Efficiency of Public Buildings (GB50189-
Science Foundation of China Project No. 51538004. 2005), China Architecture and Building Press.
References