GDI PREVENTIVE MAINTENANCE INSTRUCTION Date: 15/04/10 Rev: 0

Maximo Ref. MPM-573-01-52 SFI Code 573-01


Equip.
Air Conditioning-Vertical Unit-SCR House
Description
Manufacturer Trane Corp. Equip. Location SCR House

Model TWA 1000

MAINTENANCE SPECIFICATIONS

Frequency 3 Monthly Estimated Duration 3 Hours

Criticality 5 Area Authority Chief Electrician

Class Structure 2401 Failure Code ACSP

Craft Chief Electrician No. of Craft 1

SAFETY NOTES

• Complete required Permit-To-Work (PTW).


• Lockout / Tag-out Permit required.
• Review / Complete Job-Safety-Analysis (JSA).
• Inform Area authority if work is carried out on critical equipment for ongoing
operation.
• Do not wear jewellery when working around rotating machinery.
• Wear all proper safety equipment.

JOB PLAN INSTRUCTION

1. Check the control circuit connections for signs of overheating and tightness.
2. Check the main circuit breaker connections for overheating and tightness.
3. Check thermostat and thermostat settings.
Check the compressor motor, condenser fan motor and evaporator fan motor cables for loose
4.
connections and signs of overheating.
Check the evaporator fan pulley and motor pulley alignment and also ensure there is no shaft
5.
wear. (See figure 1)
6. Clean all fan blades and grease all the bearings. (See figure 2)
7. Check the supply and discharge air vents for trash build up. Ensure they are clear and clean.
8. Check the compressor protection devices for correct operation. If applicable.
9. Ensure all cables are correctly and safely run.
10. Check the cable entries into the main unit.
Check the ground connections to all electrical equipment and ensure they are secure and
11.
corrosion free.
12. Check the main body and frame for corrosion.
13. Megger the compressor motor and record the reading.
14. Measure the compressor motor current on Phase A and record the reading.
15. Measure the compressor motor current on Phase B and record the reading.
16. Measure the compressor motor current on Phase C and record the reading.

1
GDI PREVENTIVE MAINTENANCE INSTRUCTION Date: 15/04/10 Rev: 0

Maximo Ref. MPM-573-01-52 SFI Code 573-01


Equip.
Air Conditioning-Vertical Unit-SCR House
Description
Manufacturer Trane Corp. Equip. Location SCR House

Model TWA 1000

JOB PLAN INSTRUCTION

17. Megger Condenser fan motor and record the reading.


18. Measure Condenser fan motor current on Phase A and record the reading.
19. Measure Condenser fan motor current on Phase B and record the reading.
20. Measure Condenser fan motor current on Phase C and record the reading.
21. Megger Evaporator fan motor and record the reading.
22. Measure Evaporator fan motor current on Phase A and record the reading.
23. Measure Evaporator fan motor current on Phase B and record the reading.
24. Measure Evaporator fan motor current on Phase C and record the reading.

2
GDI PREVENTIVE MAINTENANCE INSTRUCTION Date: 15/04/10 Rev: 0

Maximo Ref. MPM-573-01-52 SFI Code 573-01


Equip.
Air Conditioning-Vertical Unit-SCR House
Description
Manufacturer Trane Corp. Equip. Location SCR House

Model TWA 1000

CHECKS AND MEASUREMENTS


MAXIMO ALLOWABLE UPPER/LOWER LIMITS
Recorded Lower Value Lower Value Upper Value Upper Value
Description Unit
Readings Action Alarm Action Alarm

Compressor MΩ 8 10 99999 9999


Compressor Phase A Amp 9.75 10.5 16.5 15
Compressor Phase B Amp 9.75 10.5 16.5 15
Compressor Phase C Amp 9.75 10.5 16.5 15

Condenser fan motor MΩ 8 10 99999 9999

Condenser Phase A Amp 1.69 1.82 2.86 2.6

Condenser Phase B Amp 1.69 1.82 2.86 2.6

Condenser Phase C Amp 1.69 1.82 2.86 2.6

Fan Evaporator Motor MΩ 8 10 99999 9999

Evaporator Phase A Amp 1.43 1.54 2.42 2.2

Evaporator Phase B Amp 1.43 1.54 2.42 2.2

Evaporator Phase C Amp 1.43 1.54 2.42 2.2

3
GDI PREVENTIVE MAINTENANCE INSTRUCTION Date: 15/04/10 Rev: 0

Maximo Ref. MPM-573-01-52 SFI Code 573-01


Equip.
Air Conditioning-Vertical Unit-SCR House
Description
Manufacturer Trane Corp. Equip. Location SCR House

Model TWA 1000

FIGURES/DRAWINGS

Figure 1 –Fan Pulley and Compressor Alignment.


Correct
Incorrect

Figure 2 – Typical Pedestal Bearing Assembly.

Check Mounting Bolts

Grease Nipple