Professional Documents
Culture Documents
Exh 2100
Exh 2100
Exh 2100
Abstract
This section discusses types of cooling water systems, types of cooling towers and
cooling tower components and provides a list of contacts and references for more
information on cooling water systems.
The Cooling Tower Institute (CTI) has developed the industry standards for cooling
towers. The commonly used standards are referenced in Specification EXH-MS-
1317, included in this manual. Copies of the CTI manual or the CTI specifications
can be obtained from:
Cooling Tower Institute
P.O. Box 73383
Houston, TX 77273
(713) 583-4087
Contents Page
2152 References
Note Figures 2100-6 through 2100-10 are 11 × 17 foldouts at the end of the
section.
assure 100% water circulation rate during a power failure. Under normal
circumstances, the electric motor-driven pump and one turbine-driven pump
operate while the other remaining turbine-driven pumps are on automatic standby.
The pumps take suction from the forebay and discharge to a common header. A
common minimum flow recirculation line, directly back to the tower, is provided at
the pump discharges for pump protection and initial prestartup conditioning.
Chemicals are used to control scaling, corrosion, and fouling. The most important
chemical is the corrosion inhibitor. Chemicals and components of the water treating
package are discussed in Section 2400.
Counterflow Design
See Figure 2100-1. The induced-draft fan pulls the air into the inlet louvers at the
bottom of the tower and up through the tower. In the counterflow tower, the
returning hot water is piped to a distribution system of headers and lateral piping
connected to pressure flow nozzles, which are located below the top of the tower
just below the mist eliminators. The nozzles spray the water as droplets that then
fall across the fill which acts as baffles to allow surface contact between the drop-
lets and the rising air. The primary advantage of the counterflow tower is its effi-
ciency. The coldest water contacts the driest air, and the warmest water contacts the
moist humid air.
Crossflow Design
See Figure 2100-2. The induced-draft fan pulls the air into the inlet louvers placed
along the tower’s sides, spanning its entire length and height. Air is introduced
perpendicular to the falling water. The crossflow tower uses risers to pipe the
returning hot water to the top of the tower where it is discharged to open gravity
distribution decks adjacent to the shroud protecting the fan. The floor of this deck
contains gravity flow nozzles, and the water level in the deck controls the rate of
water flow onto the fill.
The water falls through orifices in the nozzles, and as it flows it is distributed across
the fill. The fill acts as baffles to allow surface contact between the droplets and the
crossflowing air. Mist eliminators, forming a “V” at the center of the tower, mini-
mize drift and windage losses as the air is pulled up to the fans in the center of the
tower.
Since the early 1970s, counterflow towers have used a lower pressure spray system,
coupled with large plenum areas. In most cases, this feature has made counterflow
towers preferable to crossflow towers because they are less expensive to install and
operate than crossflow towers. Crossflow towers are often specified when a low
flow rate or potentially contaminated air atmosphere is involved.
2141 Fills
The two most significant decisions when purchasing a new cooling tower are:
1. Should we buy counterflow or crossflow?
2. Should we buy “splash” fill or “film” fill?
Section 2130 above compares the relative merits of counterflow and crossflow
towers. This section discusses splash fill and film fill.
If there is no plugging problem (i.e., good water treating) and no serious hydro-
carbon attack, the counterflow tower with polyvinyl chloride (PVC) film fill usually
will have the lowest overall cost (installed cost + fan power cost + pumping cost.)
Most large crossflow towers use splash fill (normally a PVC material). However,
some companies have small crossflow towers which stack thin sheets of plastic fill
on very close centers and can be considered film fill.
Figures 2100-3 and 2100-4 illustrate the two basic types of cooling tower fill. Fill
material is used to maintain an even distribution of water across the horizontal
plane of the tower and to create as much water surface area as practical to enhance
evaporation and sensible heat exchange. The water/air interface ratio can be
improved by creating either a large number of droplets or many thin vertical sheets
of water. Fill materials are commercially manufactured from wood, PVC, polysty-
rene, cellulose, and before environmental constraints, from asbestos cement board.
Splash Fill
For years splash fill was the standard fill for cooling towers. Splash fill is
constructed of successive layers of staggered impact surfaces. Small droplets are
formed as the warm water falls through the fill and splashes off each layer.
Typical splash fill consists of redwood battens in thicknesses of 3/8 inch to 1 inch
and 1.5-inch to 2-inches deep, installed vertically on the narrow edge. These battens
are on 0.25-inch to 2.5-inch centerline and form a deck that is usually installed hori-
zontally in the cooling tower on from 12- to 24-inch vertical centers. Each row in
elevation is rotated 90 degrees to the row above it. The battens are 6 feet long. The
decks formed are 3 feet by 6 feet and two of them fill the 6-foot cross-sectional area
between the columns in the tower. Typically, there are about 20 decks in a tower.
Where conditions permit, these splash decks are also made in egg-crate type injec-
tion molded polypropylene and PVC. They have the following advantages over film
fill discussed below:
1. There is no plugging as the spacing is far more open than in a film fill.
2. Inspection of every component of the tower is greatly simplified by moving
sections of the deck out a piece at a time, and by being able to move easily
down the inside of the tower.
Film Fill
Film fill came into use in cooling towers about 15 years ago (see Figure 2100-4). It
has a honeycomb configuration and is usually a PVC material. This fill spreads the
water droplets into thin sections throughout the cells of the fill, thereby cooling a
large surface area for the same energy. If the water is always clean, it behaves as
predicted. As film fill is more efficient than splash fill, it takes up much less volume
in the tower. Two to 3 feet of film will provide the equivalent surface of 20 to 30
feet of wood splash fill, making the return header and the elevation of the tower
much lower. This results in lower head required and lower pumping costs.
Cooling tower support posts are normally on 6-foot centers. Typical film fill is
manufactured in 3-foot by 6-foot cross-sectional areas with layer thicknesses of 6,
12, and 18 inches. Total depth in the tower typically ranges from 1 foot to 6 feet. As
an example, where icing could be a problem, a 6-foot thickness could have a 1-foot
clear elevation at each 2-foot interval to allow for extra heavy supports under each 2
feet of fill. Film fill is manufactured with various size flutes (openings) and sheet
thicknesses.
Film fill is most commonly used in counterflow towers and is normally installed
just above the intake louver opening. In a retrofit it is usually installed just below
the existing water distribution system. Good water distribution is very important
with film fill. The use of film fill is not recommended where there is potential for
hydrocarbon leakage into the fill, particularly waxy or heavy hydrocarbon. A tower
has collapsed due to hydrocarbon contaminating the middle 12 inches of a 30-inch
fill. The “mushy” condition in the middle could not be observed from the top or
bottom. Biofouling is another serious consideration for film fill. Bacterial growth is
most rapid at 98.6°F. For many of our towers, this is about half way through the
film fill. Bacteria thrive on hydrocarbon, ammonia, nitrates, sulfates, etc. See
Section 2440 for more information on biological fouling and control.
2152 References
Industry Specifications:
Cooling Tower Institute, Inc.
P. O. Box 73383
Houston, Texas 77273
(713) 583-4087
Company Documents:
Johnsen, C. W., “FCC Cooling Tower Electronic Vibration Switches,” 1/31/89. IMI,
Richmond Refinery.
Outside Documents:
1. Hydraulic Institute Standards for Centrifugal, Rotary & Reciprocating Pumps,
14th Edition, Hydraulic Institute, 1983.
2. Nystrom, James B., et al., “Modeling Flow Characteristics of Reactor Sumps,”
Journal of the Energy Division, ASCE, Vol. 108, No. EY3, November 1982.
3. Padmanabhan, M., and G. E. Hecker, “Scale Effects on Pump Sump Models,”
Journal of Hydraulic Engineering, ASCE, Vol. 110, No. 11, November 1984.
4. Prosser, M. J., The Hydraulic Design of Pump Sumps and Intakes, British
Hydromechanics Research Association/Construction Industry Research and
Information Association, 1980.
5. Sweeney, Charles E., et al., “Pump Sump Design Experience: Summary,”
Journal of the Hydraulics Division, ASCE, Vol. 108, No. HY3, March 1982.
Fig. 2100-9 Counterflow Cooling Tower: Perspective—Typical Parts and Framing (Courtesy of Custodis-Ecodyne, Santa Rosa, CA)
Fig. 2100-10 Crossflow Cooling Tower: Transverse Elevation—Typical Parts and Framing (Courtesy of Custodis-Ecodyne, Santa Rosa, CA)