D04FCT Stability

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 15

Commissioning Service Department

Commissioning Standard Test Formats


Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:1 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

1. GENERAL DATA AND INFORMATION:


Reference Panel D04 CT supervision setting 14V
REB650 MAIN-1
Under testing Panel GANTRY OUTDOOR CT BOX Bus Bar Relay
MICOM P142 MAIN-2
CT ratio 1200/1 Relay current setting 0.1 A
2. Series resistor 1500 Ω Shunt resistor 140 Ω
Relay voltage setting 150 V CT supervision time setting 5 SEC
STABILITY TEST : MAIN-1

Reference Panel (D04) Testing Panel (GANTRY OUTDOOR CT BOX)

Primary Location: XDBC4 Location: XCT1


Phase Current
(A) R:2 Y:4 B:6 N:7 R:2 Y:4 B:6 N:7

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 

R-E 300 A 252 -34 0 0 0 0 252 -214 253 -214 0 0 0 0 253 -34
300 A
Y-E 0 0 252 -34 0 0 251 -214 0 0 257 -214 0 0 255 -34
300 A
B-E 0 0 0 0 253 -34 252 -214 0 0 0 0 254 -214 254 -34

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:2 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

D04+R1 D04+R1
Primary Location:X1A Location:X1B
Phase Current
(A) R :1 Y: 3 B: 5 N: 7 R :1 Y: 3 B: 5 N: 7
I(mA) I(mA) I(mA) I(mA) I(mA) I(mA) I(mA) I(mA)
       

R-E 300 A 252 -34 0 0 0 0 252 -214 254 -214 0 0 0 0 253 -34

Y-E 300 A 0 0 253 -34 0 0 251 -214 0 0 257 -214 0 0 255 -34

B-E 300 A 0 0 0 0 254 -34 252 -214 0 0 0 0 255 -214 254 -34

D04+R1
Location: TS1

R :3B Y: 4B B: 5B N: 6B
I(mA) I(mA) I(mA) I(mA)

0 0 0 0

0 0 0 0

0 0 0 0

D04+R1 D04+R1
Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:3 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

D04+R1 D04+R1
Primary Location: Metrosil Location: Main Relay REB650
Phase Current
(A) R: R4 Y: R5 B: R6 R:X101:1 Y:X101:3 B:X101:5 N:X102:2
I(mA) V I(mA) V I(mA) V I(mA) I(mA) I(mA) I(mA)
R-E 300 A 0 0 0 0 0 0 0 0 0 0
Y-E 300 A 0 0 0 0 0 0 0 0 0 0
B-E 300 A 0 0 0 0 0 0 0 0 0 0

SENSITIVITY TEST :

SWAP IN (GANTRY CT BOX) (Rph=XCT1: 20 , 11 & Yph = XCT1: 21, 12 & Bph = XCT1: 22 , 13)

Phase Primary
Reference Panel (D04) Testing Panel (GANTRY OUTDOOR CT BOX)
Current
(A)
Location: XBDC4 Location: XCT1

R:2 Y:4 B:6 N:7 R:2 Y:4 B:6 N:7

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:4 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 

R-E 300 A 252 -34 0 0 0 0 252 -214 253 -34 0 0 0 0 253 -214
300 A
Y-E 0 0 252 -34 0 0 251 -214 0 0 256 -34 0 0 255 -214
300 A
B-E 0 0 0 0 253 -34 252 -214 0 0 0 0 255 -37 254 -214

D04+R1 D04+R1
Primary Location:X1A Location:X1B
Phase Current
(A) R :1 Y: 3 B: 5 N: 7 R :1 Y: 3 B: 5 N: 7

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 

R-E 300 A 252 -34 0 0 0 0 252 -214 253 -34 0 0 0 0 254 -214

Y-E 300 A 0 0 252 -34 0 0 251 -214 0 0 254 -34 0 0 255 -214

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:5 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

B-E 300 A 0 0 0 0 252 -34 252 -214 0 0 0 0 255 -37 254 -214

D04+R1
Location: TS1

R :3B Y: 4B B: 5B N: 6B

I(mA) I(mA) I(mA) I(mA)

504 0 0 504

0 507 0 506

0 0 507 503

Location: D04+R1 Location: D04+R1

Primary Location: SHUNT RESISTOR Location: SERIES RESISTOR


Phase Current
(A) R: SHR1 Y: SHR2 B: SHR3 R: R1 Y: R2 B: R3

I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V

R-E 300 A 457 64.2 0 0 0 0 42.1 64.2 0 0 0 0

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:6 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV
300 A
Y-E 0 0 456 64.1 0 0 0 0 41.9 64.2 0 0
300 A
B-E 0 0 0 0 547 64.2 0 0 0 0 42.1 64.2

D04+R1 D04+R1

Primary Location: Metrosil Location: Main relay REB650


Phase Current
(A) R: R4 Y: R5 B: R6 R:X101:1 Y:X101:3 B:X101:5 N:X102:2
I(mA) V I(mA) V I(mA) V I(mA) I(mA) I(mA) I(mA)

R-E 300 A 0 64.2 0 0 0 0 42.3 0 0 42.4

Y-E 300 A 0 0 0 64.2 0 0 0 42.3 0 42.3

B-E 300 A 0 0 0 0 0 64.2 `0 0 42.1 42.1

During ct supervision operated

D04+R1

Location: Main relay REB650

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:7 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

R:X101:1 Y:X101:3 B:X101:5 N:X102:2

I(mA) I(mA) I(mA) I(mA)

0 0 0 0

0 0 0 0

0 0 0 0

CT SUPERVISION WORKED @ INJECTED CURRENT 66A, 14.0 V

1. STABILITY TEST : MAIN-2

Reference Panel (D04) Testing Panel (GANTRY OUTDOOR CT BOX)


Primary Location: XDBC3 Location: XCT2
Phase Current
(A) R:2 Y:4 B:6 N:7 R:2 Y:4 B:6 N:7

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 


R-E 300 A 252 -34 0 0 0 0 252 -214 254 -214 0 0 0 0 254 -34

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:8 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

Y-E 300 A 0 0 254 -34 0 0 255 -214 0 0 255 -214 0 0 255 -34

B-E 300 A 0 0 0 0 253 -34 252 -214 0 0 0 0 254 -214 254 -34

D04+R1 D04+R1
Primary Location:X1C Location:X1D
Phase Current
(A) R :1 Y: 3 B :5 N: 7 R :1 Y: 3 R :5 Y: 7

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 


R-E 300 A 252 -34 0 0 0 0 254 -214 254 -214 0 0 0 0 255 -34
Y-E 300 A 0 0 255 -34 0 0 253 -214 0 0 256 -214 0 0 255 -34
B-E 300 A 0 0 0 0 255 -34 252 -214 0 0 0 0 255 -214 254 -34

D04+R1
Location: TS3
R :21 Y: 23 B: 25 N: 27
I(mA) I(mA) I(mA) I(mA)

0 0 0 0

0 0 0 0

0 0 0 0

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:9 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

Location: D04+R1 Location: D04+R1


Primary Location: MERTOSIL Location: SERIES RESISTOR
Phase Current
(A) R- B2:2 Y- B2:4 B- B2:6 R: R04 Y: R05 B: R06

I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V

R-E 300 A 0 0 0 0 0 0 0 0 0 0 0 0
300 A
Y-E 0 0 0 0 0 0 0 0 0 0 0 0
300 A
B-E 0 0 0 0 0 0 0 0 0 0 0 0

Phase Primary D04+R1 D04+R1


Current
(A) Location: Main relay MICOM P142
Location: SHUNT RESISTOR
R: RS4 Y: RS5 B: RS6 R:C3 Y:C6 B:C9 N:C11

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:10 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

I(mA) V I(mA) I(mA) V I(mA) I(mA) I(mA) I(mA) I(mA)

R-E 300 A 0 0 0 0 0 0 0 0 0 0

300 A
Y-E 0 0 0 0 0 0 0 0 0 0

300 A
B-E 0 0 0 0 0 0 0 0 0 0

SENSITIVITY TEST :

SWAP IN (GANTRY CT BOX) (Rph=XCT2: 20 , 11 & Yph = XCT2: 21, 12 & Bph = XCT2: 22 , 13)

Phase Primary Reference Panel (D04+R1) Testing Panel (GANTRY OUTDOOR CT BOX)

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:11 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

Location: XDBC3 Location: XCT2

Current
R:2 Y:4 B:6 N:7 R:2 Y:4 B:6 N:7
(A)
I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 

R-E 300 A 252 -34 0 0 0 0 252 -214 253 -34 0 0 0 0 255 -214
300 A
Y-E 0 0 252 -34 0 0 253 -214 0 0 253 -34 0 0 255 -214
300 A
B-E 0 0 0 0 254 -34 252 -214 0 0 0 0 255 -37 255 -214

D04+R1 D04+R1

Primary Location:X1C Location:X1D


Phase Current
(A) R :1 Y: 3 B: 5 N: 7 R :1 Y: 3 B: 5 N: 7

I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA)  I(mA) 

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:12 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

R-E 300 A 253 -34 0 0 0 0 255 -214 254 -34 0 0 0 0 256 -214
300 A
Y-E 0 0 255 -34 0 0 254 -214 0 0 255 -34 0 0 255 -214
300 A
B-E 0 0 0 0 254 -34 257 -214 0 0 0 0 255 -37 255 -214

D04+R1
Location: TS3
R :21 Y: 23 B: 25 N: 27
I(mA) I(mA) I(mA) I(mA)

506 0 0 505
0 509 0 507
0 0 508 507

Location: Shunt Resistor Location: Series Resistor


Primary
Phase Current R: RS4 Y: RS5 B: RS6 R: R04 Y: R05 B: R06
(A)
I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V I(mA) V

R-E 300 A 455 64.2 0 0 0 0 456 64.1 0 0 0 0

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:13 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV
300 A
Y-E 0 0 456 64.2 0 0 0 0 455 64.1 0 0
300 A
B-E 0 0 0 0 455 64.2 0 0 0 0 456 64.1

D04+R1 D04+R1

Primary Location: Metrosil Location: Main relay MICOM P142


Phase Current
(A) R- B2:2 Y- B2:4 B- B2:6 R:C3 Y:C6 B:C9 N:C11

I(mA) V I(mA) V I(mA) V I(mA) I(mA) I(mA) I(mA)

R-E 300 A 0 64.2 0 0 0 0 42.2 0 0 42.2

Y-E 300 A 0 0 0 64.2 0 0 0 42.1 0 42.1

B-E 300 A 0 0 0 0 0 64 0 0 42.3 41.9

During ct supervision operated

8TE.C0.1AB+R1
Location: Main relay MICOM P 142
Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:14 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV
R:C3 Y:C6 B:C9 N:C11
I(mA) I(mA) I(mA) I(mA)
0 0 0 0

0 0 0 0
0 0 0 0

CT SUPERVISION WORKED @ INJECTED CURRENT 66A, 13.99 V

CALCULATION

I total =600/1200 =0.5 A = 500 mA

R total = (1500*140) / (1500+140) = 128 Ω

V = I total * R total = 0.500*128 = 64 v

I sh =64/140 = 457.2 mA

I s = 64 /1500 = 42.6 mA

Test Equipment’s Used:

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats
Description: 132KV BUS DUCT PROTECTION STABILITY Record No.:
Panel Under Test: D04- FREE STANDING CT Drawing ref.: Sheet:15 of 15
Contractor: Al Babtain Contracting Contract no.: 4400011600 Substation No : DOWMAT AL-JANDAL 380/132/13.8KV

ITEM Description Make S/N Calib. Date Calib. Due Date


1 ODEN AT/35 Programa 1402314 16-JUL-2020 16-JUL-2021
2 MULTIMETER FLUKE 27430274 14-JUL-2020 14-JUL-2021
3 POWER QUALITY ANALYZER FLUKE 24183119 03-JUN-2020 03-JUN-2021
4 MINICLAMP Mini 05 N129211JFC 08-MAR-2021 08-MAR-2022

Tested ABC by: ENG. MOHAMED NASR BAB-070 Witnessed by: CSD-ENG. MOAMEN MOUSTAFA

Signature & Date: Signature & Date: