PEMERIKSAAN VERTICALITY

Lokasi : Fuel Terminal Tanjung Priok Dimensional : OD 30.49, H : 9.14m


Produk : MFO 380 No. Tangki : T.29-6376m3
Point Of Measurment
Subject
0°0'0" 22.5°0'0" 45°0'0" 67.5°0'0" 90°0'0" 112.5°0'0" 135°0'0" 157.5°0'0" 180°0'0" 202.5°0'0" 225°0'0" 247.5°0'0" 270°0'0" 292.5°0'0" 315°0'0" 337.5°0'0" 360°0'0"
HORIZONTAL BOTTOM A 11.602 11.58 11.618 11.669 11.719 11.708 11.74 11.809 11.823 11.753 11.813 11.777 11.591 11.636 11.561 11.529 11.602
HORIZONTAL TOP B 11.662 11.602 11.651 11.688 11.73 11.753 11.777 11.835 11.836 11.798 11.847 11.818 11.647 11.644 11.597 11.548 11.662
Selisih A - B -0.060 -0.022 -0.033 -0.019 -0.011 -0.045 -0.037 -0.026 -0.013 -0.045 -0.034 -0.041 -0.056 -0.008 -0.036 -0.019 -0.060

Legent
1 0° = Utara
2 Arah Clockways
3 Ukuran Dalam M

Peralatan
1 TS TOPCON
2 Auto Level + Rambu Ukur
HasilInspeksi :
1 Berdasarkan hasil pengukuran,kondisi setlement pondasi ( Plat Annular ) Tangki terjadi penurunan tidak merata terhadap jalan pndasi inspeksi.