LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* BUS 1 132.000 100.000 0.0 -34.015 60.204 0.000 0.000 BUS 4 -34.015 60.204 302.4 -49.2

* BUS 2 132.000 100.000 54.9 40.000 2.365 0.000 0.000 BUS 5 40.000 2.365 175.3 99.8

* BUS 3 132.000 100.000 54.9 40.000 2.361 0.000 0.000 BUS 6 40.000 2.361 175.3 99.8

BUS 4 11.000 85.808 6.1 0.000 0.000 0.000 0.000 BUS 7 -17.259 24.126 1814.4 -58.2

BUS 8 -17.259 24.135 1814.9 -58.2

BUS 1 34.519 -48.261 3629.4 -58.2

BUS 5 11.000 99.488 49.1 0.000 0.000 0.000 0.000 BUS 7 37.562 -2.766 1987.0 -99.7

BUS 9 2.269 1.121 133.5 89.7

BUS 2 -39.831 1.645 2103.1 -99.9

BUS 6 11.000 99.489 49.1 0.000 0.000 0.000 0.000 BUS 8 37.569 -2.778 1987.4 -99.7

BUS 9 2.262 1.129 133.3 89.5

BUS 3 -39.831 1.650 2103.1 -99.9

BUS 7 11.000 83.788 28.5 0.000 0.000 4.232 2.050 BUS 4 24.567 -15.345 1814.5 -84.8

BUS 5 -28.799 13.296 1987.0 -90.8

BUS 8 11.000 83.791 28.5 0.000 0.000 4.232 2.050 BUS 4 24.571 -15.355 1814.9 -84.8

BUS 6 -28.802 13.306 1987.4 -90.8

BUS 9 11.000 97.271 48.5 0.000 0.000 4.452 2.156 BUS 5 -2.229 -1.074 133.5 90.1

BUS 6 -2.222 -1.082 133.4 89.9


* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA