Question
A3-phase, 50 Hz generator supplies power of 3 MW at 17.32 kV to a balanced 3-phase
inductive load through an overhead line. The per phase line resistance and reactance are
0.25 O and 3.925 Q respectively. If the voltage at the generator terminal is 17.87 kV, the
power factor of the load is
GATE EE 2017 Official Paper: Shift 2
ed Solution Below) 0.75 - 0.85
eter Teale]
Crack GATE Electrical with
India's Super Teachers
Bre
Detailed Solution
Sending end voltage (Vs) = 17.87 kVReceiving end voltage (V,) = 17.32 kV oO"
R=0.250 G
XL = 3.9250 "s
REF XF = 3.933 2 0°
P, = WA cos (8 — 6) — ¥ cose xer
= Mllvel — fj — 2
= WAM cos (6 — 8) ~ ¥2 (#)
= 3 = (17.82)(0787) 0-8 2 NV
210787) cos (9 — 5)
= (6-6) = 87.276"
Q, = MlMl sin (6 — 6) = Y2 sine
= Will sin (0 — 5) — ¥2 (2)
(17.87)(17.32) < __ (17.32)?x3.925 _
7 sin (84.276) ; = 2.185 MVar
Power factor = cos (tant ( &)) = 0.8 lag