ean uracil CRC. ee Start Complete Exam Preparation Daily Live ocd Tao sterClasses Cress Exc D> Download App Question A3-phase, 50 Hz generator supplies power of 3 MW at 17.32 kV to a balanced 3-phase inductive load through an overhead line. The per phase line resistance and reactance are 0.25 O and 3.925 Q respectively. If the voltage at the generator terminal is 17.87 kV, the power factor of the load is GATE EE 2017 Official Paper: Shift 2 ed Solution Below) 0.75 - 0.85 eter Teale] Crack GATE Electrical with India's Super Teachers Bre Detailed Solution Sending end voltage (Vs) = 17.87 kV Receiving end voltage (V,) = 17.32 kV oO" R=0.250 G XL = 3.9250 "s REF XF = 3.933 2 0° P, = WA cos (8 — 6) — ¥ cose xer = Mllvel — fj — 2 = WAM cos (6 — 8) ~ ¥2 (#) = 3 = (17.82)(0787) 0-8 2 NV 210787) cos (9 — 5) = (6-6) = 87.276" Q, = MlMl sin (6 — 6) = Y2 sine = Will sin (0 — 5) — ¥2 (2) (17.87)(17.32) < __ (17.32)?x3.925 _ 7 sin (84.276) ; = 2.185 MVar Power factor = cos (tant ( &)) = 0.8 lag