Simulation Research on Transformer Saturation


Hysteresis Characteristics Based on PSCAD
Kaimin Huang Guoxing Wu Fan Zhang
Shenzhen Power Supply Shenzhen Power Supply Shenzhen Power Supply
Bureau Co.Ltd Bureau Co.Ltd Bureau Co.Ltd
Shenzhen, China Shenzhen, China Shenzhen, China
2021 IEEE Sustainable Power and Energy Conference (iSPEC) | 978-1-6654-1439-5/21/$31.00 ©2021 IEEE | DOI: 10.1109/iSPEC53008.2021.9735472

huangkaimin@sz.csg.cn wuguoxing@sz.csg.cn zhangfan@sz.csg.cn

Jianbing Xu Yuan Pu*


Shenzhen Power Supply School of Electrical
Bureau Co.Ltd Engineering
Shenzhen, China Southwest Jiaotong University
xujianbing@sz.csg.cn Chengdu, China
puyuan1998@foxmail.com
Abstract—In order to study the saturation hysteresis iron core is half-wave saturated and the excitation current is
characteristics of transformers, based on the PSCAD platform, distorted. Saturation characteristics and hysteresis
this paper uses the transformer Saturation module and the characteristics are important factors that affect the size of the
Hysteresis module to establish a transformer model of the excitation current of the transformer in the DC bias state.
saturation hysteresis characteristics and simulate and analyze However, establishing an accurate transformer model is the
the saturation parameters in the transformer module and the key to studying the above problems, so consider building a
improved J-A model parameters. First, the influence of transformer model that takes into account saturation
saturation parameters in the transformer Saturation module hysteresis.
on the excitation current is analyzed; then the influence of the
improved JA model on the shape of the hysteresis loop, the Literature [7] selects the UMEC transformer model in the
influence on the excitation current, and the influence of the PSCAD simulation platform for the transformer DC bias
degree of DC bias are analyzed. The simulation results show simulation experiment, but the UMEC transformer model
that The air-core reactance value has the greatest impact on only considers the saturation characteristics of the iron core
the transformer excitation current ; the nine parameters in the and does not consider the hysteresis characteristics;
improved J-A theory have different effects on the hysteresis Literature [8-9] selects Matlab/Simulink software As a
loop and the excitation current. Changing any parameter may simulation platform, only saturation characteristics are
cause the transformer hysteresis characteristics to occur considered; literature [10] proposes a new model of
change, so that the degree of DC bias of the transformer is
PSCAD/EMTDC electromagnetic transient simulation of
changed. The transformer model in the PSCAD V4.6 platform
considers both saturation characteristics and hysteresis
transformers with hysteresis characteristics. On the basis of
characteristics. If its parameter settings can be close to the the classic model, an excitation branch considering hysteresis
actual transformer operating parameters, it can simulate the is added, and at the same time Taking into account the
excitation characteristics of the transformer under DC bias, saturation and hysteresis characteristics of the transformer, it
which has engineering significance. is necessary to measure the parameters of the hysteresis loop,
and the simulation custom modeling is very complicated, and
Keywords—Transformer model; saturation characteristics; it is not convenient to analyze the characteristics of the
hysteresis characteristics; J-A model transformer under the bias magnetic field; the literature [11]
derives the DC bias field The Jiles-Atherton modified model
I. INTRODUCTION of the transformer core magnetization characteristics under
With the rapid development of my country's rail transit the conditions, the model is more convenient to solve the
industry, the problem of subway stray current leakage has excitation current and core loss; Literature [12] proposed an
become increasingly serious. Stray current will flow into the electromagnetic transient transformer model based on JA
grid through the grounding transformer[1-2]. After the stray simulation transformer hysteresis, using the method of
current flows through the transformer, the magnetization injection current source J-A hysteresis model This method is
curve of the transformer core will shift, and the transformer conducive to the realization of the program and improves the
will produce DC bias. DC bias will cause the transformer's calculation efficiency, but it is too complicated to simulate
temperature rise, noise and vibration increase, excitation the DC bias of the transformer in the area power grid.
current distortion and other hazards. The phenomenon of DC Therefore, it is necessary to consider the saturation hysteresis
bias has seriously threatened the safe and stable operation of characteristics of the transformer at the same time.
transformers and even power systems[3-6]. As for the study of Based on the PSCAD simulation platform, this paper
transformer DC bias, the saturation hysteresis characteristics establishes a transformer simulation model. Analyze the
of the transformer core are the first to be studied. influence of each parameter setting in the Saturation module
When the transformer is in normal operation, its iron core on the transformer excitation current, and give the specific
works in the linear region. In order to make the transformer range of parameter setting. Using the J-A model in the
utilization rate higher, the iron core working point tends to be Hysteresis module newly added in PSCAD/EMTDC V4.6,
saturated. When the transformer is in the DC bias state, the according to the law of conservation of energy, the formula
for the improved J-A model is derived, and the parameters in
This research was financially supported by the Science and the improved J-A model are analyzed.
Technology Project of CSG(090000KK52200132)

978-1-6654-1439-5/21/$31.00 ©2021 IEEE


Paper No. iSPEC 2021CP0385 Page 1/6 2634

Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on November 02,2022 at 13:14:18 UTC from IEEE Xplore. Restrictions apply.
2021 NANJING

II. MODEL ESTABLISHMENT 2) Saturation Parameter Setting


Build the transformer DC bias model on the Saturation current is selected to be directly injected into
PSCAD/EMTDC simulation platform. When the transformer winding 1; the air-core reactance value is set to 0.26[pu], the
is in the DC bias state, the core is nonlinear. Considering that excitation current is 0.25%; the remanence is set to 0; the
the saturation hysteresis characteristic of the transformer has rated magnetic flux is set to 1.75T.
a great influence on it, the Classical transformer in the C. Transformer Hysteresis Parameter Setting
PSCAD software library is selected for modeling.
1) Introduction of Transformer Hysteresis Module
A. Transformer Model Establishment Since the classic transformer in the Hysteresis module in
Since this article focuses on the saturation hysteresis the Saturation module of the transformer model in
characteristics of the transformer, a transformer is selected PSCAD/EMTDC cannot well reflect the excitation
for research in the model. The simulation diagram of the characteristics of the transformer in the DC bias state, the JA
transformer is shown in Fig. 1. model is a widely used model in the field of magnetic
modeling, so The Hysteresis module in the transformer
Infinite power 10/230kV Line 220/121/11kV Load chooses the JA model to describe the hysteresis of the iron
Y Y core.
Y Load The J-A model is widely used in the field of magnetic
modeling because of its few parameters and clear physical
Fig. 1. Transformer simulation diagram meaning. The J-A model was first proposed in 1983, and
scholars have continuously revised and improved the J-A
In order to get closer to the transformer used in the actual model. The J-A model is based on the theory of magnetic
project, this article selects a certain area of 220kV domains. The magnetization component is divided into a
transformer nameplate parameters for setting. The reversible magnetization component Mrev and an irreversible
transformer used in the simulation is a classic three-phase magnetization component Mirr. Finally, the correct
three-winding transformer, Y/Y/D11 connection mode, the expression is derived from the energy conservation formula.
Y-type connection of the transformer is grounded, the The theory of JA model assumes three conditions: 1)
transformation ratio is 220/121/11kV, the transformer Assuming that the domain wall is horizontal, ignoring the
capacity is 150MVA, and the leakage reactance value is thickness of the magnetic domain wall; 2) Ignoring the
calculated as the high-voltage winding-medium Voltage spatial position of the magnetic domain; 3) The work done to
winding: 0.2 [pu]; high voltage winding-low voltage winding: overcome the obstacle of the pinning point has a certain
0.136 [pu]; medium voltage winding-low voltage winding: proportional relationship with the magnetic field strength[14].
0.072 [pu]. The saturation module setting and hysteresis
module setting are described in detail below. a) Traditional J-A model
B. Transformer Saturation Parameter Setting The traditional J-A model is based on the magnetic
domain theory and uses the improved Langevin function to
1) Introduction to Transformer Saturation Module obtain the expression of the non-hysteresis magnetization:
The core saturation in PSCAD simulates the saturation
characteristics of the classic transformer model by injecting a He a
M an  M s [coth( ) ] (1)
compensation current source into the winding where it is a He
located. The parameters that directly affect the saturation
characteristics of the transformer are: air-core reactance, He  H   M (2)
knee-point voltage, and excitation current. Among them, In the formula: He is the effective magnetic field strength;
adjusting the air-core reactance value will affect the slope in is the average field parameter, used to reflect the coupling
Fig. 2; adjusting the knee point voltage will affect the within the magnetic domain; Man is the magnetization
intercept of the asymptotes on the Y axis; adjusting the without hysteresis; a is the shape parameter of the
excitation current will determine the effective knee point magnetization curve without hysteresis; Man is the saturation
horizontal position along the voltage line of Vs=1.0pu[13] . magnetization; H is Magnetic field strength.
However, since the Hysteresis module in the Saturation It can be obtained from the law of conservation of energy:
module chooses to use the J-A model, the knee voltage value the actual magnetized magnetostatic energy is equal to the
cannot be set, so this is explained. magnetostatic energy without hysteresis minus the hysteresis
loss of the pinch point, and the following expression can be
Vs obtained:
Slope is based on air-core reactance dM irr
Knee point
0  MdH e =0  M an dH  0 k  ( )dH e (3)
e dH e
1.0

Among:
dH / dt  0,  1
 (4)
dH / dt  0,  1
Excitation current Is
In the formula: μ0 is the vacuum permeability; k is the
percentage hold-down coefficient, which characterizes the strength
of hysteresis; δ is the directional coefficient.
Fig. 2. Iron core saturation curve
From the simplification of the above formula, we can get:

Paper No. iSPEC 2021CP0385 Page 2/6 2635

Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on November 02,2022 at 13:14:18 UTC from IEEE Xplore. Restrictions apply.
2021 NANJING

dM irr (5)
M  M an   k 0.4
dH e
From M=Mirr+Mrev and Mrev=c(Man-Mirr), we can get: 0.2

Excitation current (A)


dM M M dM an (6)
0
 (1  c) an   c
dH e k dH e
-0.2
In the formula: c is the reversible magnetization coefficient,
a parameter that characterizes the elastic displacement -0.4 0.1[pu]
0.2[pu]

movement of the magnetic domain. 0.2 0.22 0.24 0.26 0.28


0.3[pu]
0.3
Time (s)
After simplification, the final expression can be obtained:
Fig. 3. Comparison of simulation waveforms of excitation current under
dM M M dM dM an (7) different air-core reactance
 (1  c) an (1   )c
dH k dH dH
b) Improve the J-A Model It can be seen from Fig. 3 that changing the value of the
air-core reactance, the excitation current waveform remains
In version 4.6 of PSCAD software, a new module to unchanged, and the value changes. When the air-core
consider transformer hysteresis is added, and the J-A model reactance is 0.1, the value of the excitation current is the
is improved. The traditional J-A model has five parameters largest, and the air-core reactance value is 0.2 compared with
to describe the hysteresis loop in the above discussion, and 0.3. The reactance changes from 0.1 to 0.2 to be small, so the
the J-A model in the PSCAD software uses 9 parameters to size of the air-core reactance determines the size of the
describe the hysteresis loop. The improved J-A model excitation current. The empirical approach is that the air-core
modifies the pinch factor k and the non-hysteresis reactance is approximately twice the leakage reactance.
magnetization.
2) Nominal Flux Density
The traditional J-A model believes that the restraint
The most commonly used iron core material in my
coefficient is constant, but in the actual magnetization
country is cold-rolled silicon steel sheet, and its saturation
process, the restraint coefficient k is constantly changing
magnetic density is 1.9~2.0T. The working magnetic density
with the magnetization process. In order to make the
of small and medium-sized transformers is often relatively
simulation closer to the actual situation, the restraint
low, 1.55~1.65T, while the working magnetic density of
coefficient k needs to be modified:
large-capacity transformers is usually closer to the saturation
2 magnetic density, 1.7~1.75T.
M 
k '  k[1     ] (8) When the rated magnetic flux is 1.7T, 1.75T, 1.8T, the
 Ms  transformer excitation current is shown in Fig. 4.
The traditional J-A model uses the Langevin function to
describe the non-hysteresis magnetization, while the 0.2

improved J-A model in the PSCAD software uses a new


function to describe the non-hysteresis magnetization[15-17]. 0.1
Excitation current (A)

a1 H e  H eb 0

M an  M s (9)
a3  a2 H e  H eb -0.1

In the formula: a1、a2、a3、bare all shape parameters of non- -0.2 1.7T


1.75T
hysteresis magnetization, and a1>0,a2≥a1,a3≥0,b≥1; because 0.2 0.22 0.24 0.26 0.28
1.8T
0.3
there are 4 shape parameters in the improved J-A model to Time (s)

describe the non-hysteresis magnetization Compared with Fig. 4. Comparison of simulation waveforms of excitation current under
the 1 parameter of the traditional J-A model, the improved J- different rated magnetic fluxes
A model can better describe the non-hysteresis
magnetization curve. It can be seen from the figure that the waveform of the
excitation current remains unchanged, and the value of the
2) Hysteresis Parameter Setting excitation current does not change much, so the rated
The parameters of the J-A model are set as follows : magnetic flux has little effect on the excitation current within
c=0.1,k=5.0 × 10-5, β=0.96, α=1.325 × 10-5,Ms=1.72 × a reasonable range. Because the transformer in the model is a
106,a1=2730, a2=3209, a3=20294,b=2. 220kV large transformer, the rated magnetic flux setting
value is 1.75T.
III. SIMULATION ANALYSIS
3) Magnetizing Current
When the transformer rated parameters are determined, The excitation current is approximately equal to the no-
the parameters affecting the saturation characteristics and load current, which can be obtained from the transformer
hysteresis characteristics of the transformer are analyzed nameplate parameters.
respectively.
B. Transformer Hysteresis Parameters
A. Transformer Saturation Parameters
1) The Influence of Improved J-A Model Parameters on
1) Air Core Reactance
Hysteresis Loop
When the air-core reactance value is 0.1, 0.2, 0.3, the
transformer excitation current is shown in Fig. 2. The hysteresis loop indicates the relationship between the
magnetic field intensity M and the magnetic induction

Paper No. iSPEC 2021CP0385 Page 3/6 2636

Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on November 02,2022 at 13:14:18 UTC from IEEE Xplore. Restrictions apply.
2021 NANJING

intensity B during the repeated magnetization of a The parameters Ms、k、c、α of the original J-A model
ferromagnetic substance. The hysteresis loop is an important and the improved JA model have the same influence on the
tool for simulating the characteristics of the iron core. The hysteresis loop. The saturation magnetization Ms is an
different shapes of the hysteresis loop simulate the core inherent property of the material itself, which mainly affects
characteristics of different materials of the transformer. The the maximum magnetization, and the irreversible loss
magnetization process of the transformer core is shown in the coefficient k mainly Affects the area of the hysteresis loop,
figure. the area of the hysteresis loop represents the core loss; the
B
reversible magnetic susceptibility c and the irreversible loss
coefficient k have the opposite effects on the hysteresis loop;
Br
B C
the average field parameter α is a coefficient reflecting the
A coupling between magnetic domains, Mainly affect the
inclination of the hysteresis loop.
2 2
Hcm 0 H
1.5 1.5

1 1

Magnetic induction (T)

Magnetic induction (T)


0.5 0.5

0 0

-0.5 -0.5

-1 -1
a1  2730 a2  3209
a1  2930 a2  3409
Fig. 5. Magnetization curve -1.5
a1  3130
-1.5
a2  3609
-2 -2
-150 -100 -50 0 50 100 150 -800 -600 -400 -200 0 200 400 600 800
Magnetic field strength (A/m) Magnetic field strength (A/m)

Place the magnetic material in a magnetic field with a 2


(a)Influence of parameter a1
2
(b)Influence of parameter a2

magnetic field intensity of 0, and gradually increase the 1.5

1
1.5

magnetic field intensity. The magnetic induction intensity

Magnetic induction (T)

Magnetic induction (T)


0.5 0.5

will increase along the OAB. After the magnetic induction 0 0

intensity reaches point B, the magnetic material is in a -0.5

-1
-0.5

-1
saturated state. After that, the magnetic field intensity and -1.5
a3  20294
a3  21294 -1.5
b 1
b  1.5

magnetic induction intensity are increased. Basically -2


-150 -100 -50 0 50
a3  22294

100 150
-2
-150 -100 -50 0 50 100
b2
150

unchanged. OAB is called the initial magnetization curve. If Magnetic field strength (A/m)
(c)Influence of parameter a3
Magnetic field strength (A/m)
(d)Influence of parameter b

the magnetic field intensity is reduced, the magnetization Fig. 7. The influence of improved J-A model parameters on hysteresis
curve no longer returns along the original path of the initial loop
magnetization curve OAB, but the magnetic induction
intensity B lags behind the magnetic field intensity H and 2

changes, which is the hysteresis phenomenon of magnetic 1.5


materials. When the magnetic field intensity H is reduced to 1
0, the magnetic induction intensity is not equal to 0. To
Mag netic induction (T)

reduce the magnetic induction intensity to 0, a reverse 0.5

magnetic field Hc must be added, and the magnetic induction 0


intensity is 0, where Hc is called the coercive force. -0.5

The nine parameters of the improved J-A model in -1


β 0
PSCAD describe the hysteresis curve together, and the -1.5 β  0.5
different combinations of the nine parameters describe β  0.96
different hysteresis loops. Except that the correction -2
-200 -150 -100 -50 0 50 100 150 200
coefficient is 0.96, the influence of the other eight parameters Magnetic field strength (A/m)

on the characteristics of the transformer core is discussed.


Fig. 8. The influence of parameter β on hysteresis loop
Using the controlled variable method, keeping seven of the
parameters unchanged, changing one parameter, and TABLE I. THE INFLUENCE OF J-A MODEL ON HYSTERESIS LOOP
discussing its impact on the hysteresis loop one by one.
Maximum Loop
2 2
Parameter Coercivity remanence
1.5 1.5 magnetization area
1 1
MS   —  —
Magnetic induction (T)

Magnetic induction (T)

0.5 0.5

0 0 k —   
α — —  —
-0.5 -0.5

-1 -1
Ms 1.710-6A/m c  0.1
-1.5 Ms 1.810-6A/m
Ms 1.910-6A/m
-1.5 c  0.2
c  0.3
c —   
-2 -2
-150 -100 -50 0 50
Magnetic field strength (A/m)
100 150 -150 -100 -50 0 50
Magnetic field strength (A/m)
100 150
a1   —  —
(a)Influence of parameter Ms (b)Influence of parameter c
2 2
a2   —  —
1.5 1.5

1 1 a3   —  —
Magnetic induction (T)
Magnetic induction (T)

0.5 0.5
b    —
0 0

-0.5 -0.5 β — — — 
Improve the newly added parameters in the J-A model,
-1 -1
k  410 5A/m   1.32510 5
-1.5 k  510 5A/m -1.5   1.325106
  1.32510 7
except that β is the modified irreversible loss coefficient k,
5
k  610 A/m
-2 -2
-150 -100 -50 0 50 100 150 -150 -100 -50 0 50 100 150

in order to better fit the shoulder area of the hysteresis loop,


Magnetic field strength (A/m) Magnetic field strength (A/m)
(c)Influence of parameter k (d)Influence of parameter 

Fig. 6. The influence of the original J-A model parameters on the


without the influence of the shape parameters a1, a2, and a3
hysteresis loop of the hysteresis magnetization curve The trend is opposite.

Paper No. iSPEC 2021CP0385 Page 4/6 2637

Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on November 02,2022 at 13:14:18 UTC from IEEE Xplore. Restrictions apply.
2021 NANJING

0.4
When the shape parameter a1 increases, the maximum 0.15

magnetization and remanence value both increase, and the 0.1


0.3

Excitation current (A)


loop area is basically unchanged. When the shape parameter

Excitation current (A)


0.2
0.05
b is in the range of 1~2, the hysteresis loop basically does 0.1
not change. 0
Time s 0
2) The Influence of Improved J-A Model Parameters on (a) b=2
-0.05
Excitation Current -0.1

To study the excitation characteristics of a transformer -0.1


1.4 1.42 1.44 1.46 1.48 1.5
-0.2
1.4 1.42 1.44 1.46 1.48 1.5
under DC bias, first, the transformer model parameters need Time (s)
(a) Waveform diagram of excitation current when b=3
Time (s)
(b) Waveform diagram of excitation current when b=2
to be set correctly, and the transformer model must be
verified. The transformer winding current is very dependent Fig. 10. The influence of parameter b on the degree of DC bias
on the connected load, so the excitation current is to verify
that the transformer model is correct. The key to it or not. It can be seen that if a certain parameter is simply
The following figure discusses the influence of the improved changed, the hysteresis characteristics of the transformer
J-A model parameters on the excitation current. Due to space may change, and the degree of DC bias will also have a
limitations, the four parameters that have the greatest impact certain influence. In the DC bias simulation experiment, the
on the excitation current are selected. result is wrong. Improving the determination of 9 parameters
0.25 0.25
in the J-A model is actually a problem of simultaneous
0.2 0.2 optimization of 9 nonlinear variables. Traditional
0.15 0.15
mathematical methods are difficult to solve, and intelligent
Excitation current (A)

Excitation current (A)

0.1 0.1
0.05 0.05 algorithms are generally used to solve such problems. In
-0.05
0 0
-0.05
engineering, simulated annealing and artificial fish school
-0.1 -0.1 algorithms are generally used to solve such problems.
-0.15 -0.15
-6
Ms  1.710 A/m
-0.2 M s  1.810-6A/m -0.2 a1  2730
-6 a1  2930
M s  1.910 A/m a1  3130
-0.25 -0.25
1.4 1.42 1.44 1.46 1.48 1.5 1.4 1.42 1.44 1.46 1.48 1.5
Time (s) Time (s)
2
(a)Influence of parameter Ms
0.25
(b)Influence of parameter a1 IV. CONCLUSION
0.2
1.5
0.15 This article fully considers the saturation characteristics
and hysteresis characteristics of the transformer. Through
1
Excitation current (A)

Excitation current (A)

0.1
0.5
PSCAD simulation analysis, the air-core reactance value has
0.05
0 0

-0.5
-0.05 the greatest influence on the excitation current. In the setting
-1
-0.1
-0.15
of three-phase three-winding transformer, the empirical
-1.5 a2  3209
a2  3409
a2  3609
-0.2 b1
b2
b3
practice is to set the air-core reactance value to twice the
-2
1.4 1.42 1.44 1.46
Time (s)
1.48 1.5
-0.25
1.4 1.42 1.44 1.46
Time (s)
1.48 1.5 leakage reactance of the high and middle windings. In the
(c)Influence of parameter a2 (d)Influence of parameter b
improvement of J-A model parameter settings, the hysteresis
loop of the transformer can be determined by determining 9
Fig. 9. The influence of improved J-A model parameters on hysteresis parameters. From the simulation results, it can be known that
loop
when the shape parameter b changes between 1 and 2, the
shape of the hysteresis loop basically does not occur. The
It can be seen that the four parameters Ms、a1、a2 and b
degree of transformer DC bias beyond this interval will also
have a greater impact on the amplitude of the excitation change; and in addition to the shape parameter b, the new
current. Among them, the non-hysteresis magnetization shape parameters of the improved JA model are more
curve shape parameter a2 has the greatest impact on the sensitive to the effect of the hysteresis loop, and have a
transformer excitation current. greater impact on the shape of the hysteresis loop, the
When the transformer is in normal operation, the modified parameter can adjust the shoulder area of the
excitation current is positive and negative symmetrical. hysteresis loop according to the change of the magnetic field
When the stray current flows in from the neutral point of the strength, so that the simulated hysteresis loop is closer to
transformer, a DC component appears in the transformer reality.
windings, and the transformer core appears half-wave
saturated. The excitation current is no longer positive and REFERENCES
negative symmetrical, but is biased to the time axis once, the
excitation current Distortion occurs. If the parameters of the [1] Shi Yuntao, Zhao Liping, Lin Sheng, Ren Yonghao, Wang Aimin,
improved JA model are set unreasonably, no matter how Wu Guoxing. The distribution law of subway stray current in urban
power grid and analysis of influencing factors [J]. Power System
much current is injected into the neutral point, the excitation Technology, 2021, 45(05): 1951-1957.
current of the transformer will basically not change. For
[2] WANG Aimin,LIN Sheng,HU Ziheng,et al.Evaluation model
example, when 500A DC is injected into the neutral point of of DC current distribution in AC power systems caused by stray
the transformer the difference between the two. current of DC metro systems[J].IEEE Trans.Power Del.,[2020-
02-20].
[3] Liu Weiguo, Zhou Weihua, Ye Huisheng, et al. Research on the
Influence of Changsha Metro Rail Transit on AC Power Grid and
Treatment Measures [J]. Hunan Electric Power, 2017, 37(1): 7-9, 13.
[4] W. Xu, Y. Wu, F. Wu, X. Shen and J. Ruan, "Study on the influence
factors of power transformer DC magnetic bias," 12th IET
International Conference on AC and DC Power Transmission (ACDC
2016), 2016, pp. 1-6, doi: 10.1049/cp.2016.0416.

Paper No. iSPEC 2021CP0385 Page 5/6 2638

Authorized licensed use limited to: Universiti Teknikal Malaysia Melaka-UTEM. Downloaded on November 02,2022 at 13:14:18 UTC from IEEE Xplore. Restrictions apply.
2021 NANJING

[5] J. E. T. Villas, C. M. Portela. “Calculation of electric field and conditions [J]. Transactions of the Chinese Society of Electrical
potential distributions into soil and air mediafor a ground electrode of Engineering, 2017, 32(19): 193-201.
a HVDC system”, IEEE Transactions on Power Delivery, vol.18, no.3, [12] Hong Chao, Zhang Qinghua, Zhang Ye, Tu Liang, Li Junjie, Zhang
pp.867-873, 2003. Dongyuan, Leng Yongjie. High-efficiency electromagnetic transient
[6] J. T. Quan, X. Tong, X. S. Wen, et al. “Mitigation of transformer DC transformer modeling based on JA hysteresis model[J]. Southern
bias in complicated operation conditions”, High Voltage Engineering, Power Grid Technology, 2020, 14(02): 75-83.
vol.41, no.7, pp.2464-2472, 2015. [13] Le Jian, Mao Tao, Wu Min, etc. PSCAD V4.6 circuit design and
[7] Zhang Xuesong, Huang Li. Simulation research of transformer DC simulation from entry to master[M]. Beijing: Machinery Industry
bias based on PSCAD/EMTDC[J]. Power System Protection and Press, 2019.
Control, 2012, 40(19): 78-84. [14] Tantai Leyan, Han Xiaoqing, Wang Lei, Yuan Tiejiang. An improved
[8] Tian Zhen. Simulation ana lysis of transformer operation based on Jiles-Atherton model used in transformer DC bias state [J]. Power
Matlab/Simulink[J]. Science and Technology Innovation and System Technology, 2020, 44(01): 122-132.
Application, 2019, {4}(26): 9-11. [15] U. D. Annakkage, P. G. McLaren, E. Dirks, R. P. Jayasinghe and A.
[9] Xie Dongguang, Ma Zhonghua. Simulation Research on Transformer D. Parker, "A current transformer model based on the Jiles-Atherton
DC Bias[J].Heilongjiang Electric Power,2013,35(05):388-390. theory of ferromagnetic hysteresis," in IEEE Transactions on Power
[10] Wu Jiaqi, Li Xiaohua, Chen Zhong, Ding Xiaobing, Tian Qing. Delivery, vol. 15, no. 1, pp. 57-61, Jan. 2000, doi: 10.1109/61.847229.
Transformer PSCAD/EMTDC electromagnetic transient simulation [16] Chen Y , Ouellette D S , Forsyth P A , et al. Parameter Estimation
modeling method and excitation difference analysis considering for a Jiles-Atherton based Current Transformer core model.
hysteresis characteristics [J]. Proceedings of the Chinese Society of [17] Yang Fenyan, Wang Bao. Transformer model considering hysteresis
Electrical Engineering, 2017, 37(05) :1543-1552. based on PSCAD V4.6 [J]. Guangdong Electric Power, 2017, 30(06):
[11] Li Changyun, Liu Yakui. Jiles-Atherton modified model of 67-72+85.
transformer core magnetization characteristics under DC bias

Paper No. iSPEC 2021CP0385 Page 6/6 2639