Professional Documents
Culture Documents
Uta 22002173
Uta 22002173
125 310
70
70
70
345
180x1260
180x1260
RGP
RGP
RGA
630x1260
1.400
1.260
1.260
710
1.540
SUP
DN50
M5 F9
345
GR50I-ZID.GL.CR
70
70
140
630 220 580 450 1.120 450
1.880 1.570
L1-594kg L2-480kg
3.450
70
70
1.940
1.800
1.800
SUP
ODA
70
70
125
Preliminary drawing
Supply air CTA 20.14 C54 CLIENTE-CUSTOMER: REV.
0 DATA-DATE: User:
PB
Airflow m³/h 18.000 CANTIERE-CONSTRUCTION.: POS.-ID:
Ext. pressure Pa 450 Food Factory - Zeliten
Tot. pressure Pa 1.036 RIFERIMENTO-REF.: Pos.01
Motorpower kW 2x 4,600 OGGETTO-OBJECT: TIPO-TYPE: PROJECT-ID.:
Power supply 400V/3/50Hz CTA 20.14
UTA 22002173
DX-cooling kW 153,97
ROCCHEGGIANI S.p.A?Via 1° maggio,
- .SHEET: -/-
60021 Camerano (AN)Italy scale: TOLL.: DISEGNO-DRAW.:
xx.xx UNI.EN22768-V
DISEGNO DI PROPRIETA' DELLA ROCCHEGGIANI SPA - RIPRODUZIONE E DIFFUSIONE VIETATA AI TERMINI DI LEGGE
THE DESIGN AND DRAWINGS ARE PROPERTY OF ROCCHEGGIANI SPA-UNAUTHORIZED USE/COPY OR ANY FORM OF MODIFICATION IS STRICTLY PROHIBITED
Offer UTA 22002173 Position Pos.01
Project Food Factory - Zeliten From date 31/10/2022
User: Paolo Buglioni
Preliminary drawing
Unit size CTA 20.14 C54 Length [mm] 3.450,0 Net weight [kg] ~1.074,00
Frq.[Hz] 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)]
Total sound power level at the unit inlet [dB] 73,0 80,0 77,0 74,0 70,0 67,0 63,0 63,0 76,2
Total sound power level at the unit outlet [dB] 79,0 89,0 82,0 80,0 74,0 71,0 65,0 61,0 81,3
Break out airborne sound power [dB] 68,0 81,0 73,0 74,0 71,0 69,0 49,0 38,0 76,1
Internal frame material AISI 304 Drain pan material AISI 304
Dampers material Aluminium / Aluminium Drop eliminator material AISI 304 / PPTV
Main data:
Supply Airflow 18.000 [m³/h] External static 450 [Pa] Motor absorbed/nominal power 7,16 /9,200 [kW]
Return Airflow - [m³/h] External static - [Pa] Motor absorbed/nominal power - [kW]
Factor Fs-Pref 0,91 Energy label class designed for wet conditions
Position
Supply air
Unit definition Casing:
Revision panel with turn bolt (Central handle) Dimensions [mm] 180,0 x 1.260,0
1 Pcs Device for pressure drop monitoring to be provided by the customer for compliance to ErP 2018
Position
Fan octave band sound power level (Lokt) [dB] Control Signal (0-10V) 9,10
Position
Noise calculation
Sound power level [dB]
Frq.[Hz] 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)]
Inlet 73,0 80,0 77,0 74,0 70,0 67,0 63,0 63,0 76,2
Outlet 79,0 89,0 82,0 80,0 74,0 71,0 65,0 61,0 81,3
Casing 68,0 81,0 73,0 74,0 71,0 69,0 49,0 38,0 76,1
sound pressure level [dB]
Frq.[Hz] 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)] measuring point at 1 m of distance
Inlet 65,1 72,1 69,1 66,1 62,1 59,1 55,1 55,1 68,3
Outlet 71,1 81,1 74,1 72,1 66,1 63,1 57,1 53,1 73,4
Casing 60,1 73,1 65,1 66,1 63,1 61,1 41,1 30,1 68,2
Delivery sections
no. Width Height Length Net weight
Position
Regulation 1253:14