Professional Documents
Culture Documents
Sas Lesson 2 Ele 103
Sas Lesson 2 Ele 103
Sas Lesson 2 Ele 103
Productivity Tip:
Where you study matters. If you have a private room, it's fairly easy to shut the door
and concentrate on what you're doing.
A. LESSON PREVIEW/REVIEW
1) Introduction (2 mins)
In the previous lessons branch-circuit are classified according to type of Load into five categories:
Lighting Branch circuit, Receptacle Branch circuit, Equipment Branch circuit, Heating and cooling
loads Branch circuit and Motor Branch circuit.
We also learned the design calculations for the first type: lighting branch circuits
In this lesson you will gain knowledge in the design calculations for the second type: Receptacle
branch circuits.
Receptacles are one of the most popular terms in the NEC code because of its importance especially
in dwelling units and in non-dwelling units as it is the device responsible for feeding power to most
of equipment. NEC code includes large number of rules that are assigning the receptacle
1
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
requirements for special locations, special loads, special installation methods etc.
B. MAIN LESSON
1) Activity 2: Content Notes (13 mins)
1. Introduction
1.1. Essential Definitions
Receptacle: A receptacle is a contact device installed at the outlet for the connection of an
attachment plug.
Attachment Plug (Plug Cap) (Plug): A device that, by insertion in a receptacle, establishes a
connection between the conductors of the attached flexible cord and the conductors connected
permanently to the receptacle
2
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Note that…
Attachment plug contact blades have specific shapes, sizes, and configurations so that a
receptacle or cord connector will not accept an attachment plug of a voltage or current
rating different from that for which the device is intended.
Multi-outlet Assembly are metal or non-metallic raceways that are usually surface, flush, or
freestanding mounted designed to hold branch circuit conductors and receptacles, assembled in
the field or at the factory.
3
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
The definition of multi-outlet assembly includes a reference to a freestanding assembly with multiple
outlets, commonly called a power pole as shown in below image.
4
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
In no case shall the load exceed the branch-circuit ampere rating. The following are the permissible
Receptacle Branch circuit ratings in dwelling buildings:
2. Only utilization equipment: with condition that the combined load for all utilization
equipment must not exceed the branch circuit rating.
3. Combination of both: in the case the permissible rating of the utilization equipment will
depend on its type as follows:
• If it is not fastened-in-place, it can have a rating of up to 80 % of the branch circuit
rating as in TABLE 210.21(B)(2).
• If it is fastened-in-place, other than luminaires, it shall not exceed 50 % of the branch-
circuit ampere rating.
Important!!!
Using fastened-in-place equipment is not permitted for the small-appliance branch
circuits, laundry branch circuits, and bathroom branch circuits required in a dwelling unit
and these branch circuits shall supply only their receptacle outlets required by the code.
Important!!!
A single receptacle installed on an individual branch circuit shall have an ampere rating
not less than that of the branch circuit.
5
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
As per NEC section 220.14(I), Receptacle outlets load (see below image) shall be calculated at not
less than:
• 180 volt-amperes for each single receptacle,
• 180 volt-amperes for each multiple receptacle (duplex or triplex) on one yoke,
• 90 volt- amperes per receptacle for multiple receptacles (four or more).
6
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Important!!!
If a receptacle is dedicated for a specific device, then the actual load is
used and If this dedicated load is continuous, then the 125% overrate is
appropriate.
To calculate the Maximum allowable number of receptacles on a branch circuit, make the
following steps:
• Step#1: Determine the maximum circuit power by Multiply the branch circuit voltage and
amperage.
• Step#2: Then divide by 180 volt-amperes.
The result from Step#2 = the Max. Allowable single, duplex, or triplex receptacles or a combination
of them on a branch circuit.
7
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Example#1:
How many receptacles can be placed on a 120-volt, 20-amp circuit? How many can be placed on a
120-volt, 15-amp circuit?
Solution:
Step#1:
Determine the maximum circuit power (for 20-amp circuit) = 120 V × 20 A = 2400 VA
Determine the maximum circuit power (for 15-amp circuit) 120 V × 15 A = 1800 VA
Step#2:
So,
8
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
In the broad sense, Receptacle in dwelling units may serve one of the following loads:
9
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Receptacles shall be installed such that no point measured horizontally along the floor
line of any wall space is more than 1.8 m (6 ft) from a receptacle outlet.
Definition:
The wall space is a wall unbroken along the floor line by doorways, fireplaces, archways,
and similar openings and may include two or more walls of a room (around corners), as
illustrated in Exhibit 210.27. The Minimum length for a wall space is 2 ft.
Important!!!
10
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
The wall space behind the swing of a door is included in the measurement. This does not
mean that the receptacle outlet must be in that space, only that the space is included in
the wall-line measurement.
Receptacle designed for intended utilization equipment or practical room use may be
placed in corners, may be grouped, or may be placed in a convenient location. For
11
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
example, receptacles in a living room and family room that are intended to serve home
entertainment equipment or home office equipment.
Receptacle outlets in floors shall not be counted as part of the required number of
receptacle outlets unless located within 450 mm (18 in.) of the wall.
Rule#5: kitchen and dining areas counters receptacles other than that used for
small appliances (see above image)
12
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Receptacle outlets installed to serve kitchen or dining area counters (for small
appliances) cannot also be used as general-use receptacles for an adjacent wall space
and in this case general-use receptacle branch circuits must be added to serve such
locations.
The following receptacles can't be used as general-use receptacles (rule#1 will not apply
for it):
A receptacle that is Part of a luminaire or appliance, or
A receptacle that is controlled by a wall switch, or
A receptacle that is Located within cabinets or cupboards, or
A receptacle that is located more than 1.7 m (5.5 ft) above the floor.
Important!!!
A receptacle controlled by a switch may result in the occupant using an extension cord,
run from an outlet or device that is not controlled by a switch, to supply appliances or
equipment that require continuous power, such as an electric clock. So, this receptacle
not considered as general-use receptacle.
Rule#7: hallways
As per NEC section 210.52(H), In dwelling units, hallways of 3.0 m (10 ft) or more in length
shall have at least one receptacle outlet.
The hallway length shall be considered the length along the centrelines of the hallway
without passing through a doorway.
Important!!!
Rule#7 does not apply to common hallways of hotels, motels, apartment buildings,
condominiums, and similar occupancies.
Rule#8: foyers
As per NEC section 210.52(I), Foyers that are not part of a hallway in accordance with
210.52(H) and that have an area that is greater than 5.6 m2 (60 ft2) shall have a
receptacle(s) located in each wall space 900 mm (3 ft) or more in width and unbroken by
doorways, floor-to-ceiling windows, and similar openings.
13
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Rule#9: Bathroom
14
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
As per NEC Section 210.52(D), in dwelling units, at least one receptacle outlet shall be
installed in bathrooms in one of the following locations:
1. Within 900 mm (3 ft) (36 inch) of the outside edge of each basin.
2. on the side or face of the basin cabinet not more than 300 mm (12 in.) below the
basin countertop.
Definition:
A bathroom is defined in Article 100 as “an area including a basin with one or more of the
following: a toilet, a urinal, a tub, a shower, a bidet, or similar plumbing fixtures.”
Important!!!
As per NEC section 406.9(C), it is prohibited to install a receptacle within or directly over a
bathtub or inside a shower stall even if the receptacles are installed in a weatherproof
enclosure.
Important!!!
As per NEC section 210.11(C)(3), At least one 20-ampere branch circuit shall be provided
to supply bathroom receptacle outlet(s). This circuit is permitted to supply the required
receptacles in more than one bathroom as show in above image (bottom).
Important!!!
If the circuit supplies the required receptacle outlet in only one bathroom, it is allowed to
also supply fastened-in-place equipment (lighting and an exhaust fan) in that bathroom,
provided the lighting and fan load does not exceed 50 % of the branch-circuit ampere
rating as per NEC section 210.23(A)(2).
15
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
As per NEC section 210.52(E), Outdoor receptacle outlets shall be installed in accordance
with the following:
For a one family dwelling and each unit of a two-family dwelling that is at ground level, at
least one receptacle outlet accessible while standing at grade level and located not more
than 2.0 m (6.5 ft) above grade shall be installed at the front and at the back of each
dwelling.
For each dwelling unit of a multifamily dwelling where the dwelling unit is located at
grade level and provided with individual exterior entrance/ egress, at least one
receptacle outlet accessible from grade level and not more than 2.0 m (6.5 ft) above
grade shall be installed.
16
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Important!!!
Where outdoor heating, air conditioning, or refrigeration (HACR) equipment is located at
grade level , the receptacle outlets required by this section “which shall be located on the
same level” can be used to comply with the receptacle outlet requirement of 210.63,
provided that at least one of the outlets is located within 25 ft of the HACR equipment.
Important!!!
The receptacle outlet required for Balconies, Decks, and Porches can also be used to
meet the above outdoor receptacle requirements of One-Family, Two-Family and
Multifamily Dwellings.
17
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
As per NEC section 210.52(G), For a one-family dwelling, the following provisions shall
apply:
At least one receptacle outlet, in addition to those for specific equipment (Laundry for
example), shall be installed in each basement, in each attached garage, and in each
detached garage or accessory building with electric power.
Where a portion of the basement is finished into one or more habitable rooms, each
separate unfinished portion shall have a receptacle outlet installed in accordance with
this section.
18
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Important!!!
Where detached garages are not supplied with electricity, receptacle outlets do not have
to be installed.
So, no additional load calculation is required for general-use receptacle loads i.e.
general use receptacle loads (after applying the general lighting load unit value from
table 220.12) = Zero.
Example#1:
A homeowner wants to add 10 numbers general-purpose Receptacles, what is the
additional load to the service?
Solution:
No additional load calculation is required for these general-use receptacle loads, the
additional load to be added = Zero.
In each dwelling unit, two or more 20-ampere small-appliance branch circuits shall be
provided.
19
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
All Receptacle Outlets In the kitchen, pantry, breakfast room, dining room, or similar area
of a dwelling unit which serve Portable appliances used at a kitchen counter, such as
toasters, coffee makers, skillets, mixers, and the like and after applying exceptions made
by rules#6.
Rule#3: Receptacle Outlets served by small appliances branch circuits (see fig.1)
The following receptacle outlets are permitted to be served by small appliance branch
circuits:
1. All wall and floor receptacle outlets covered by 210.52(A) after applying
exceptions made by rules#6,
2. All countertop outlets covered by 210.52(C),
3. Receptacle outlets for refrigeration equipment (see Rle#4).
4. Electric clock in any of the areas specified in Rule#2,
5. Supplemental equipment and lighting on gas-fired ranges, ovens, or counter-
mounted cooking units.
The small appliance branch circuits are not permitted to serve any other outlets, such as
might be connected to exhaust hoods or fans, disposals, or dishwashers.
Rule#4: Receptacle outlet for refrigeration equipment (see fig.1)
The receptacle outlet for refrigeration equipment located in a kitchen or similar area
shall be permitted to be supplied from one of the following circuits:
1. 20-A small appliance branch circuit,
2. An individual branch circuit rated 15 amperes or greater especially, when the
receptacle outlet for the refrigerator is located so that it cannot be used to serve
countertop surfaces.
20
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Fig.1
Small-appliance branch circuits must supply the required receptacles by rule#3 in the
following way:
• The counter area receptacle outlets in the kitchen are required to be supplied by
minimum two small-appliance branch circuits.
• The wall receptacle outlets in the kitchen and dining room are permitted to be
supplied by one or both small-appliance branch circuits that supply the counter
area.
• If there are many kitchens in same dwelling unit, no small-appliance branch
circuit shall serve more than one Kitchen.
21
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Receptacle outlets in floors shall not be counted as part of the required number of
general-purpose receptacle outlets unless located within 450 mm (18 in.) of the wall.
Otherwise, these Floor Receptacles will be counted as part of the small appliance branch
circuits.
Rule#7: kitchen and dining areas counters receptacles other than that used for
small appliances (see fig.1)
Receptacle outlets installed to serve kitchen or dining area counters (for small
appliances) cannot also be used as general-use receptacles for an adjacent wall space
and in this case general-use receptacle branch circuits must be added to serve such
locations.
2) Activity 3: Skill-building Activities (with answer key) (18 mins + 2 mins checking)
Problem Solving. Solve the following problem completely. Write your solution in a separate short
bond paper. BOX your final answer.
Problem 1.
What is the general lighting and receptacle calculated load, after demand factors, for a40x50ft
(2,000 sq ft) dwelling unit?
22
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
C. LESSON WRAP-UP
1) Activity 6: Thinking about Learning (5 mins)
2.
3.
2.
FAQs
KEY TO CORRECTIONS
23
ELE 103: Electrical Systems and Illumination Engineering Design
Student Activity Sheet #2
Activity 3
1. General Lighting = 40x50ft
General Lighting = 2,000 sq. ft. x 3VA per sq ft
General Lighting = 6,000 VA
First 3,000 VA at 100% 3,000 VA x1.00= 3,000 VA
Next 117,000 VA at 35% 3,000 VA x0.35= + 1,050 VA
General Lighting and General-Use Receptacles
Calculated Load = 4,050 VA
24