Professional Documents
Culture Documents
Circuit Breaker
Circuit Breaker
2 PhoENix CoNtACt
Contents
1. Why device circuit breakers?
1.1 Benefits and advantages of device
circuit breakers
1.2 Differences between miniature
circuit breakers and device circuit
breakers
1.3 What is a fault?
1.4 System availability
3. Extended functions
3.1 Remote control and signaling
functions
3.2 Nominal currents – Fixed or
adjustable
3.3 Adapted backup fuses
3.4 With or without current limiting
3.5 Electrical isolation
5. Communication
5.1 System transparency
5.2 IO-Link
6. Challenges in applications
9. Glossary
PhoENix CoNtACt 3
The basics of device circuit breakers | Why device circuit breakers?
An electrical system consists of many that are important and critical to circuits not involved remain unaffected
components that must work together system availability. Unscheduled machine by the fault. The supply voltage must
in concert. Many loads are supplied by downtime is to be avoided at all costs. likewise be maintained in the event of
the same power supply in this type of Therefore it is very important to ensure a fault. That is the only way to ensure
arrangement. This creates dependencies that, in the event of a fault, any loads and smooth operation. If an overload or
4 PhoENix CoNtACt
The basics of device circuit breakers | Why device circuit breakers?
1.2 Differences between miniature circuit breakers and device circuit breakers
Miniature circuit breakers (MCBs) circuit breakers are characterized by and established for DC voltage also
Miniature circuit breakers were designed their high short-circuit shutoff capacity, assist in this.
and developed first and foremost to which is necessary for operation on Since device circuit breakers do
provide cable protection in a building. the grid. The electric arc that occurs at not depend directly on the mains, no
They are covered under the standard shutoff is high in energy and needs to be quenching plates are required, as is the
IEC/EN 60898 (Electrical accessories – interrupted during shutoff. This is the case with miniature circuit breakers.
Circuit-breakers for overcurrent only way to ensure a safe shutoff. They are therefore significantly more
protection for household and similar compact, saving space in the control
installations). The current drawn by Device circuit breakers cabinet.
the load is not known at this point. Device circuit breakers are described
Therefore, the wiring is designed such in IEC/EN 60934. They are not just Problems associated with
that it can continuously carry the used for cable protection, but first and MCB-based protection
nominal current of the protective device. foremost for device protection. For this MCBs were designed for different
At the same time, a certain amount reason, their nominal currents start at applications than device circuit breakers.
of inertia is desired, because the cable less than 1 A and they are subdivided Therefore, they need a very high tripping
must be protected and the tripping into small current increments. This makes current:
should not be too fast. For a long time, it possible to adapt the protection to An MCB shutoff is divided into two
lower current values were not used, as the corresponding device as precisely parts: a thermal and a magnetic shutoff.
these are not necessary for the building as possible. A variety of characteristic Thermal shutoff takes place in the lower
installation. Furthermore, miniature curves that have been specially developed seconds to minutes range, whereas
PhoENix CoNtACt 5
The basics of device circuit breakers | Why device circuit breakers?
the magnetic shutoff occurs in the MCBs are designed for the AC grid short-circuit tripping range. Tripping
event of a short circuit and ideally falls (without power limitation): therefore occurs even later, often not
in the 3 to 5 ms range. Depending on miniature circuit breakers were until a current 15 times the nominal
the characteristic curve in use, up to developed for installation in buildings, current has been reached. Thus, in
15 times the normal current needs to be and that is precisely what the currents the case of a C6 quick-break cutout,
flowing for a rapid short-circuit cutoff. and characteristic curves are designed for. a current of up to 90 A must be reckoned
If this current is not available, the entire Therefore, there are no nominal current with for serious events. If this tripping
system can be affected. The required values in the lower amp range, or a slow current is not available downstream of
current may be limited downstream of characteristic curve needs to be selected a switched-mode power supply unit, the
a switched-mode power supply unit or in order to reach the right nominal entire system will experience a voltage
if the line impedance is too high. This current. In principle, the characteristic dip. The same is true for a cable that is
means that the required higher tripping curves were initially established for use too long. It can create a situation where
current may not be reached, causing the only with AC voltages. If these types the current is limited, thus preventing
system voltage to dip. The result is that of fuses are used with DC voltage, prompt tripping, which in turn can also
parallel loads fail. a correction factor of around 1.4 must lead to a voltage dip in this case.
be taken into consideration in the
Overload currents and short-circuit Ideally, the nominal current selected voltages. These largely range between
currents are usually unexpected. They will be close to the nominal current for 12 and 48 V DC. For the primary
cause malfunctions and interrupt the the load. In this way, end devices are applications, 24 V DC has been the
operation of a system. Production optimally protected against damage or control voltage generally used for
downtimes and repair costs are often destruction. System parts that are not many years now. Synchronized power
the unpleasant result. in the affected circuit can continue to supply units are standard equipment in
Effects of this type can be minimized operate without interruption, provided most industries for control voltages.
by protecting individual devices separately the overall process allows it. This ensures This voltage consistently delivers high
or by logically organizing the devices high system availability. efficiency. In addition, the output current
in groups. Since different loads also is limited. The voltage can also be
have different nominal currents (Fig. 1), Voltage dip maintained over great distances using
it makes sense to implement separate Machines and systems for the most DC/DC converters.
protection for each individual circuit. part operate with different supply Like fuses and circuit breakers,
power supplies also come with a variety
of characteristic curves, allowing them
Sensors to meet different system availability
Controllers 0.5 to 2 A demands. Many power supply units use
1 to 8 A
the U/I characteristic curve, for example
Valves
0.5 to 4 A (Fig. 2). The voltage is constant, the
current is variable. If the current exceeds
the nominal range, or if an overload leads
to a voltage dip, the connected loads fail.
Motors
If the PLC (programmable logic
1 to 12 A Relays controller) fails, the only way to find
0.5 to 5 A
and eliminate the error is through an
enormously painstaking search.
6 PhoENix CoNtACt
The basics of device circuit breakers | Why device circuit breakers?
U
UN A A
s ms
IN IStatB. IDynB. I
Fig. 2: Power Supply U/I characteristic curve Fig. 3: Shutdown of overload currents in the Fig. 4: Shutdown of short-circuit currents in the
seconds range milliseconds range
Overload be taken into account. Safe shutdown into general use. Short-circuit currents
Overload currents occur if end devices in the event of an overload should occur need to be safely shut off within a few
unexpectedly require a higher current in the seconds range (Fig. 3). milliseconds in order to prevent any
than the intended rated current. effect on the remaining loads in the
Such situations can arise, for example, Short circuit system (Fig. 4). This is because a short
due to a blocked drive. Temporary Damage to the insulation between circuit generally leads to a voltage dip,
starting currents from machines are conductors which carry operating which can also cause other unaffected
also considered to be overload currents. voltage, e.g. a damaged load feed, can circuits and loads to fail.
The occurrence of these can be cause short circuits. In the past, typical
calculated in principle, but nonetheless protective devices for shutting down
can vary depending upon the machine short-circuit currents included fuses or
load at startup time. When selecting miniature circuit breakers with a variety
suitable fuses or circuit breakers for these of tripping mechanisms. Since then,
types of circuits, these conditions must electronic protective devices have come
PhoENix CoNtACt 7
The basics of device circuit breakers | Why device circuit breakers?
8 PhoENix CoNtACt
The basics of device circuit breakers | Differences between the technologies
Function description
The tripping element of thermal device
circuit breakers is bimetallic. It may
also be a combination of bimetal and an
electrical heating element. The bimetal Circuit diagram
consists of steel and zinc, which is formed
by heat. When a predefined heat level Fig. 6: Structure and functional description of thermal circuit breakers
is reached as a result of an excessively
high current in the heating element,
the thermal bimetal trips the shutdown device circuit breakers represent a simple,
mechanism. cost-effective solution for applications
This thermal tripping element makes the which do not necessarily require fast and
thermal protection more susceptible to precise shutdown (Fig. 6 and 7).
higher ambient temperatures. Thermal
PhoENix CoNtACt 9
The basics of device circuit breakers | Differences between the technologies
1
On/off switch
Spring-loaded
switch rod
Preload setting
Fig. 8: Typical tripping characteristics for thermal
circuit breakers:
t Switch time (in seconds)
xl Multiple of the nominal current/tripping factor
1 Current ranges of the characteristic field
2 Tripping characteristics of the lower temperature
Circuit diagram
range (blue)
3 Tripping characteristics group 1
Fig. 7: Structure and functional description of thermal circuit breakers 4 Tripping characteristics group 2
5 Tripping characteristics of the upper temperature
range (red)
Tripping characteristics to be disconnected from the power circuit breaker trips more easily at a high
The tripping time of thermal device supply (Fig. 8). For circuit breakers with ambient temperature and more slowly at
circuit breakers depends on the overload different nominal currents, but with the a low ambient temperature. This behavior
current that is flowing and the ambient same tripping characteristics, the tripping is indicated by additional characteristic
temperature. The characteristic curves can also be presented in characteristic curves with corresponding information.
show that the tripping time is reached curve fields (Fig. 9). Of course, thermal
faster as the overload increases. With device circuit breakers respond to the
smaller overload currents, it therefore effects of heat. The ambient temperature
takes longer for the connected load can also affect the tripping time. The
Thermomagnetic device circuit remote signaling of the operating state The temperature-dependent part of
breakers are used among other things ensure high availability. The different the mechanism consists of a bimetal
in information and communication characteristic curves for this protection with a heating coil (Fig. 10). Currents
technology as well as process control. technology can even start critical loads that exceed the nominal current of the
Thanks to a variety of versions with while at the same time providing secure protective device generate heat in the
different tripping characteristics, circuit protection in nominal operation. heating coil. This causes the bimetal
breakers are ideally suited for protecting to bend and act on the switching
programmable logic controllers, valves, Function description mechanism. When the limit value is
motors, and frequency converters. Thermomagnetic circuit breakers are reached, the protective device shuts
The reactivation and immediate equipped with two trip mechanisms. down. The devices respond to overload
10 PhoENix CoNtACt
The basics of device circuit breakers | Differences between the technologies
Two examples of characteristic curves for thermal circuit breakers for Example of a characteristic curve field for thermal miniature circuit breakers
different nominal currents
currents with a delay. The thermal part plunger or pivoted armature. Currents the armature actuates the trip mechanism
of this circuit breaker technology also that exceed the nominal current of the and shuts down the protective device.
makes it more susceptible to higher protective device create a magnetic field These devices respond to short-circuit
ambient temperatures. in the coil. The current strengthens the currents and excessive overload currents
The magnetic trip mechanism is magnetic field and attracts the armature. within 3 to 5 milliseconds.
designed with a solenoid coil and a When the preset limit value is reached,
1 11
Switch rod
Circuit diagram
PhoENix CoNtACt 11
The basics of device circuit breakers | Differences between the technologies
Tripping characteristics
Thermomagnetic device circuit breakers SFB technology
are available with different characteristic
curves. This allows them to meet QUINT power supplies from
the wide range of requirements that Phoenix Contact feature Selective
result from different application cases. Fuse Breaking Technology, also
The characteristic curve (Fig. 11) known as SFB. These power
indicates that the thermal trip [a] supplies can supply six times
responds considerably later than the the nominal current for a few
magnetic trip [b]. This can be explained milliseconds. This enables them
by the required heating time of the to provide the necessary current
temperature-dependent trip mechanism. reserve for safe tripping of the
However, even currents that are slightly protective devices.
higher than the nominal current are
identified as overload currents and shut
down. Magnetic tripping responds very Fig. 11: Typical tripping characteristics for
quickly to rapidly rising currents that thermomagnetic circuit breakers
a Operating range for thermal tripping
exceed the nominal current. This is b Operating range for magnetic tripping
particularly advantageous for detecting t Switching time (in seconds)
and switching off short-circuit currents. xI Multiple of the nominal current/tripping factor
1 Current range for which the characteristic curve
Alternating currents trip faster than applies curve is dragged forward on the axis of
DC currents at the same nominal value. 2 DC tripping range (gray) the nominal current multiple. Even at a
3 AC tripping range (blue)
This is depicted by the blue area in lower multiple of the nominal current,
4 Tripping maximum
the curve. This behavior is generally 5 Tripping minimum alternating currents cause the circuit
applicable to all characteristic curves. breaker to trip.
Nevertheless, it is only used for circuit in the event of brief current increases and
breakers with the M1 characteristic starting currents during operation. They F1 characteristic curve
curve. Circuit breakers with the SFB simultaneously prevent unnecessarily Circuit breakers with the
or F1 characteristic curve also trip long, persistent overload currents, which F1 characteristic curve (Fig. 14) trip
so fast with direct current that they may lead to the hazardous generation of quickly. They react very quickly to
would respond overly sensitively during heat in operating equipment. overload situations. However, this
operation with alternating current. can lead to unnecessary shutdowns
M1 characteristic curve during operation. This means they offer
SFB characteristic curve Circuit breakers with the optimal protection for sensitive loads
Circuit breakers with the SFB tripping M1 characteristic curve (Fig. 13) with very low starting current and thus
characteristic (Fig. 12) offer maximum trip later than those with SFB or provide protection over great distances.
overcurrent protection, even in F1 characteristic curves. They withstand End devices, which can be damaged
extensive systems with long cable paths. starting currents for somewhat longer by temporary overloads and slightly
SFB stands for Selective Fuse Breaking, periods but consciously respond less increased operating current, are also
i.e., selective shutdown. Protective swiftly to fault situations. In comparison protected by these circuit breakers.
devices with this characteristic curve to the direct current characteristic curve,
prevent an unnecessarily early switch-off the alternating current characteristic
12 PhoENix CoNtACt
The basics of device circuit breakers | Differences between the technologies
10 10 10
1 1 1
Fig. 12: SFB characteristic curve Fig. 13: M1 characteristic curve Fig. 14: F1 characteristic curve
Electronic circuit breakers are generally place at the switched-mode power supply Function description
used in conjunction with 24 V DC unit and all other circuits can continue The heart of an electronic circuit breaker
switched-mode power supply units. They to operate. These circuit breakers are is its semiconductor electronics (Fig. 15),
are frequently used in machine and ship ideal for protecting things like relays, which nowadays is generally assisted
building, systems manufacturing, and programmable controllers, motors, by intelligent software. The software
automation technology. A combination sensors and actuators, and valves. differentiates between operating currents
of current analysis and rapid tripping in Combining electronic circuit breakers and damaging currents and transmits
the event of a fault prevents the danger with a synchronized power supply can commands to the electronic system
of a switched-mode power supply unit increase the availability of systems and extremely rapidly. This is because it has
overload. The output voltage remains in machines. to ensure that faults are detected and
shut down as quickly as possible while not
shutting off an inrush current or normal
operating current.
The fault detection process passes
Microcontroller through the following steps:
Suppressor diode • Measurement: All electrical variables
are measured continuously in order to
monitor the ongoing situation.
• Analysis: The measured values are
MOSFET
Buttons analyzed to determine whether a fault
has occurred.
Voltage regulator • Classification: The currents are
evaluated and classified.
Backup fuse
• Protect and switch: Depending on
the class of the analyzed current, the
load is started or shut down. The rest
of the system remains in operation
and unaffected.
• Signaling: The operating states
Fig. 15: Structure of a multichannel electronic circuit breaker of all circuits are transmitted
continuously to the superordinate
PhoENix CoNtACt 13
The basics of device circuit breakers | Differences between the technologies
t, s
In the event of overload current or a
short circuit, the devices are promptly 0,1
switched off.
Electronic circuit breakers are in
0,01
some cases equipped with active current
limiting. This function limits the short
circuit and overload currents, depending 0,001
1 2 4 8 16 32 64
on the product range, to a value of
x In
1.25 to 2 times the nominal current.
This protects the power supply against Fig. 16: Short-circuit behavior and dynamic overload detection range
currents that are too high and prevents
the output voltage from dropping at the
switched-mode power supply unit. among different characteristic When it comes to burn-through fuses
Another benefit of this electronic curves. As opposed to thermal or and thermomagnetic circuit breakers,
technology is the ability to virtually thermomagnetic fuses, the electronics the different characteristic curves are
completely plan out the connected load in modern electronic circuit breakers known, such as fast-acting, medium
of any DC power supply. In addition, react dynamically. blow, or slow blow. A modern electronic
longer cable paths between the power Figure 16 shows the various ranges: protective device with intelligent
supply and load are possible without 1. Short circuit behavior (green line): short-circuit detection and dynamic
negatively impacting the shutdown If a short circuit is detected, the fault overload behavior is replacing the wide
behavior. is immediately shut down. To prevent range of characteristics mentioned above.
any negative impact on the loads, this
Tripping characteristics and has to happen without a time delay.
dynamics Particularly with a PLC, a shutdown
Thanks to intelligent current analysis, must occur within 10 ms (see also
modern electronic circuit breakers can controller standard, p. 5).
differentiate between many different 2. Dynamic overload detection range
operating and failure scenarios. The (blue area): Depending on the height
result is a dynamic in the characteristic and course of the flowing current, the
curve. This means that any fault-related intelligent detection also ensures a
shutdown is not dependent solely shutdown in the case of an overload.
on current and time. The load and This process permits the overcurrent
power supply are detected, optimizing to persist for different lengths of
the startup process. In this way, the time, depending on its progression
operation of the electronic protection and the stability of the supply voltage.
is illustrated in a dynamic characteristic The overload is shut down before
curve. Similar to traditional fuses, this a dangerous condition arises. Here
is also done by defining an overload also, the dynamics associated with
and short-circuit range. electronic circuit breakers provide a
Some electronic circuit breakers critical advantage. If a fault is detected,
have different characteristic curves. it is shut down promptly, keeping
The purpose of these differences is the remaining supply in mind. Loads
first and foremost to offer the user can be detected in this way and can
familiar selection options. However, be started even when high starting
it is not necessary to differentiate currents are present.
14 PhoENix CoNtACt
The basics of device circuit breakers | Differences between the technologies
2.4 Which type of circuit breaker is recommended and when should it be used?
Device circuit breakers are selected based protecting a load from short circuits. for protecting systems and machines,
on the nominal voltage, nominal current, They offer a combination of medium-blow but also often provide comprehensive
and, if required, the starting current of overload protection and fast-acting and diagnostic options. Remote maintenance
an end device. In addition, the shutdown reliable short-circuit protection. can be designed to be significantly more
behavior of the device circuit breaker Even very high starting currents are comprehensive.
must correspond to the expected fault no problem for most thermomagnetic Moreover, thanks to its extended
situations. Fault situations are divided into characteristic curves. remote signaling and control options,
short circuit and overload. Electronic circuit breakers are this type of circuit breaker can be used in
A thermal device circuit breaker provides significantly more accurate. Circuit some cases in hard-to-reach applications.
pure overload protection. However, it is breakers with an electronic characteristic
not equipped with a protective mechanism curve are used to create fast-acting
that can quickly and reliably protect the overload and short circuit protection.
application from short circuits. They are used upstream from particularly
This means that increased tripping times sensitive loads and protect not only
occur in the event of short circuits. against overly long, but also against overly
Thermomagnetic circuit breakers are high loading. Electronic circuit breakers are
also significantly better suited for safely therefore not just especially well suited
Thermomagnetic circuit
breakers
PhoENix CoNtACt 15
The basics of device circuit breakers | Extended functions
3 Extended functions
The choice of which device circuit breaker is best suited for a given application is based
not just on the technology and the associated shutdown behavior. In addition to features
such as with or without current-limiting technology or the option to adjust the nominal
current, the type of auxiliary contact or signaling and control signals also plays a role.
Reset or control input when everything is OK, i.e., operational. Individual signaling or group
A reset input can be used to remotely A “HIGH” signal is output when one or signaling
switch a tripped device circuit breaker more device circuit breakers have tripped Multichannel device circuit breakers
back on. A control input can be used not due to a fault. However, this means that are generally equipped with group
just to switch the device circuit breaker wire break detection for the signaling signaling in the form of a potential-free
back on, but also to switch it on and off connection is no longer an option with N/O contact. Single-channel device
during normal operation. This type of these devices. circuit breakers for the most part are
operation is similar to that of a relay also equipped with one N/O contact
that is actuated. N/O or N/C signal contact for single channel signaling. However, in
These types of signal contacts involve the case of a group of individual devices,
Status output 2-position potential-free status contacts they can also be connected in series and
A status output is used to output a that can be individually wired and in this way grouped into a group signaling
voltage level at a terminal point that interconnected. arrangement. This can in some cases
can be sent to a PLC's digital input, An N/O contact is a normally open save several digital inputs on a PLC as
for example. Normally, a “HIGH” signal contact. This means that the contact is opposed to single-channel signaling.
is output when everything is OK, i.e., closed when everything is okay. If the
is operational, and a “LOW” signal is device circuit breaker trips due to a
emitted when the device circuit breaker fault, the contact opens. Wiring all of
has been tripped by a fault. The advantage the contacts in series makes it easy
of this signal level definition is that it also to construct a simple group signaling
covers detection of a wire break in the arrangement for a group of device
signaling connection to the PLC. circuit breakers. In this case, one end
To use fewer PLC inputs, the signal of the series connection must be
levels must be exactly the opposite of the connected to a +24 V source, while the
ones described above. This can be done other must be connected to a digital
by grouping the individual status output PLC input.
signals of multiple single-channel device An N/C contact is a normally closed
circuit breakers into one group signal. contact. This means that the contact
In that case, you need products with an is open when everything is okay. If the
inverted status output. With these types device circuit breaker trips due to a fault,
of products, a “LOW” signal is output the contact closes (Fig. 17).
16 PhoENix CoNtACt
The basics of device circuit breakers | Extended functions
Main contacts
Individual: 1-2
In groups: 1-2 / 3-4 / 5-6 / …
Auxiliary contacts
– Individual N/O contact: 13 - 14
– N/O contacts in groups: 1.13 - 1.14 / 2.13 - 2.14 /
3.13 - 3.14 / …
– Individual N/C contact: 11 - 12
– N/C contacts in groups: 1.11 - 1.12 / 2.11 - 2.12 /
3.11 - 3.12 / …
Fig. 17: Setting for auxiliary contacts based on switching state of the main contact
Power main contact
Signal auxiliary contacts
NO normally open (N/O) contact
NC normally closed (N/C) contact
C common changeover foot contact (common)
The correct nominal current for a latter option allows you to separately the devices are installed. This option is
device circuit breaker can be determined adjust to the nominal current that is available with fixed-value devices only
either at time of purchase or left open right for the application, e.g., using a in cases where the decision is made
up until the time it is installed in the potentiometer, step switch, or one- to use pluggable versions. In that case,
application. This means that the decision button operation. One major advantage the nominal current remains unspecified
involves choosing either a product with of this adjustability is that you still have until the choice of which device circuit
a fixed nominal current or one with an the freedom to respond to adjustments breaker connector to use is made.
adjustable nominal current range. The and revisions in the system up until
In electronic circuit breakers, a backup fuse is considered to be an electrical devices with a low maximum nominal
fuse is built in to serve as a fail-safe device. That means it must also be current are also available, so as to better
element. This is done to cover the rare protected. This can be done via an protect sensors or other sensitive loads.
instance of a technical failure in the main external fuse, but is not necessary
switching element (MOSFET) to protect thanks to the fuse already incorporated
it from thermal destruction. in the electronic circuit breaker.
A fail-safe element is required under the The size of the backup fuse should
American UL standards. An electronic match the application, for which reason
PhoENix CoNtACt 17
The basics of device circuit breakers | Extended functions
Depending on the application, the over-dimensioned cables. In some cases, time. This allows even heavier loads
following decisions have to be made: however, current-limiting technology to start up faster, e.g., motors with
Current-limiting technology has the allows too little current at startup time. high starting torque or capacitive loads.
benefit that it never allows more current However, that is exactly what is needed Intelligent current analysis procedures
than the amount up to the predefined for a trouble-free load startup, e.g., are used for this that can differentiate
limit to flow in the load circuit. The limit in order to create the motor starting between a true hard short circuit and
is generally between 1.25 to 2.0 times torque. high inrush currents. This ensures a
the nominal current. This also prevents safe shutdown before critical system
the power supply from being too severely Device circuit breakers without operation conditions arise.
overloaded. To the power supply, even a current-limiting technology ensure that
hard short circuit appears only as a slight the full amount of current is allowed
overload. There is also no need to lay through in the load direction at startup
In many industries, such as the process principle, when a MOSFET is used as the shutdown and restart process.
industry, actual electrical isolation the switching element in an electronic This protects the contacts of the
is required. This is used to ensure circuit breaker, it is unable to do this. electrical isolation element (relay) from
that there is no longer any physical At the moment of actuation, it is very contact burn-through or fusing. In the
connection to the power supply in high-impedance and cuts the current switched-on operating state, however,
cases such as shunting for maintenance flow off almost completely without the load current is routed virtually
purposes. The current path is broken truly opening the contact. loss-free over the relay.
via complete electrical isolation in the A combination of relays and
event of a fault. MOSFET can also provide a robust
This requirement is not a challenge and long-lasting solution for achieving
for thermal and thermomagnetic device electrical isolation. The load current
circuit breakers. Due to its working is routed over the MOSFET during
18 PhoENix CoNtACt
The basics of device circuit breakers | Influencing factors in the application
PhoENix CoNtACt 19
The basics of device circuit breakers | Influencing factors in the application
currents near the nominal current. If the Cable calculation Values for sample calculation
flowing current is detected as a fault, To ensure that the protective device U = 24 V DC
the shutdown occurs quickly. The cable shuts down safely in the event of a short UCB = 0.14 V DC
resistance that would have acted to circuit or overload current, it is a good xI = 15 > from the
excessively limit the tripping current is idea to calculate the maximum usable M1 characteristic
suddenly no longer a factor (Fig. 19). cable length just to be on the safe side curve
In the case of electronic overcurrent (Fig. 20 and 21). = 2 > from the
protection, currents and voltages are The following data is necessary for the E characteristic
measured and analyzed, fault currents calculation: curve
are detected and shut down accordingly. Rmax Maximum total resistance ICB = 1 A
This places the required fault current U Nominal voltage RCB1A = 1.1 > from table of
in the range of 1.2 to 2.0 times the UCB Voltage drop for device circuit typical internal
nominal current, and not up to 15 times, breaker resistances,
as is the case with mechanical circuit ICB Rated current for device circuit Section 4.3
breakers. This enables much more precise breaker ρ = 0.01786 > copper
protection. However, in the case of long xI Tripping factor in accordance A = 1.5 mm2 > assumed
cables, the voltage drop is much more with the current characteristic/
significant, since it is of little benefit that nominal current multiplier
the current arrives at the load if only RLmax Maximum cable resistance
a slight residual voltage is still present. RCB1A 1 A internal resistance for device
For that reason, the voltage drop must circuit breakers
also be taken into consideration during Lmax Maximum cable length
configuration. A Conductor cross section
ρ Specific cable resistance
Rho, (Cu 0.01786)
U 24 V
Rmax = = = 1,6 Ω U - UCB 24 V - 0,14 V
ICB • xI 1 A • 15 RLmax = = = 11,93 Ω
ICB • xI 1A•2
RLmax = Rmax - RCB1A = 1,6 Ω - 1,1 Ω = 0,5 Ω
RLmax • A 11,93 Ω • 1,5 mm2
RLmax • A 0,5 Ω • 1,5 mm 2 Lmax = = = 1001 m
Lmax = = = 42 m ρ Ω • mm2
ρ 0,01786 •
Ω • mm2 m
0,01786 •
m
Fig. 20: Calculation in three steps: Fig. 21: Cable calculation for electronic circuit breakers
1. Total resistance of the circuit The value calculated is only theoretically possible. In practice, the voltage drop
2. Maximum cable resistance across the line must be taken into consideration.
3. Maximum cable length
20 PhoENix CoNtACt
The basics of device circuit breakers | Communication
5 Communication
The level of automation required is increasing year on year in many branches of industry.
This brings with it a rising demand for communication and networking of components,
including in the area of overcurrent protection.
Device circuit breakers connected to communication interfaces provide tremendous added
value in the industry. The devices can be accessed remotely, making it possible to monitor
and adjust the system process at any time from anywhere.
Connecting to a communication interface to access the system from anywhere circuit breaker against outside tampering.
gives you the option of energizing or in the world by connecting to the right This can be done by locking in the
de-energizing individual channels based interface can raise service and support nominal current setting or locking the
on the process. However, the nominal to a completely new level. Every value, entire device operation.
current can also be conveniently adjusted. from the input voltage to the preset IO-Link is one option for this kind of
Processes can be depicted transparently nominal current right up to the current interface.
right up to the load with the aid of a actually flowing in the channel can be
wide range of monitoring functions. read out.
This makes it possible to detect faults Moreover, it is possible to remotely
early and even prevent them. The ability secure individual channels or the entire
5.2 IO-Link
The first version of the IO-Link circuit breakers. One IO-Link master The cycle time at this selected speed of
communication system was designed and one IO-Link device are required 230 kBaud is 400 μs. Larger frame types
only to connect more intelligent sensors to set up IO-Link communication. The are also possible, enabling exchanges
and actuators. The system was taken connection between these two devices of cyclic process data up to 32 bytes.
from the standard IEC 61131-9 from is point-to-point. However, this always comes at the
the description “Single-drop digital One IO-Link master can have multiple expense of the cycle time.
communication interface for small IO-Link ports. One IO-Link device each
sensors and actuators (SDCI)”. can be connected per port (Fig. 22).
In the meantime, this communication In its default setting, IO-Link uses
protocol is also being incorporated 2 bytes to exchange cyclic process data
into devices such as power supplies or between the master and the device.
PhoENix CoNtACt 21
The basics of device circuit breakers | Communication
ETH 1 ETH 2
LNK LNK
ACT ACT
X21 X22
RDY BF SF
Controller US
PWR IN PWR OUT
UA
X31 X32
30 31
X01 X02
Sensors
32 33
X03 X04
UA UA
X05 X06
UA UA
X07 X08
IP 67 IO-Link master
Device circuit
Power supply
breakers
+ + – – –
Output DC 24V 10 A 1 1
2
OUT+
3
2 4
UOut Signal 1
IN–
29.5V
13
2
L+
14 3
Rem C/Q
SGnd L–
Out 1
CBMC
Out 2 1 -10 A
24V
4
> 100% Boost
> 75%
P
> 50% Out
DC OK
1
IN+
2
QUINT POWER
Input AC 100-240V
N/- L/+ Loads without IO-Link
PE
N
L
22 PhoENix CoNtACt
The basics of device circuit breakers | Challenges in applications
6 Challenges in applications
The demands of normal system greatly, often causing a multiple of the supply must have sufficient reserve
operation in no way represent a current to flow (Fig. 23 and 24). This for this.
challenge when selecting device circuit situation must not result in a shutdown.
breakers. What is more difficult is taking This has to be taken into consideration
the starting behavior of the various both in the choice of device circuit
loads into consideration. This is because breaker as well as the right power supply,
the starting behavior frequently varies the same as a potential fault. The power
t/s
1000
t/s
1000
100 100
10 10
1 1
0,1 0,1
0,01 0,01
0,001 0,001
0,0001 0,0001
0 5 10 15 20 25 30 35 40 45 50 0 5 10 15 20 25 30 35 40 45 50
2 A halogen lamp starting current 2 A halogen lamp starting current
I/A I/A
Tripping curve for 4 A thermomagnetic circuit breaker 4 A CBMC tripping curve
Power supply unit power reserve Power supply unit power reserve
Fig. 23: A 4 A thermomagnetic circuit breaker indeed acts slowly enough to Fig. 24: Thanks to intelligent short-circuit and starting current detection,
start the halogen lamp, but the power supply must also have a lot of reserve electronic circuit breakers can shut down more accurately under identical
power ready. conditions. This means that a much smaller reserve is needed than with
comparable thermomagnetic device circuit breakers (cf. Fig. 23).
PhoENix CoNtACt 23
The basics of device circuit breakers | Challenges in applications
24 PhoENix CoNtACt
The basics of device circuit breakers | Standards and approvals
The IEC/EN 60898 standard covers 5 to 6 kA. This shutoff capacity is not high shutoff capacity, the design is
miniature circuit breakers for building needed for switching devices, however. significantly smaller, which brings a
installations and similar purposes. Device circuit breakers in accordance number of advantages along with it.
Conventional miniature circuit breakers with IEC/EN 60934 are used in this case.
have a high shutoff capacity of up to Since there is no need for a particularly
It is very important to many European potential export simpler, because the if a device is UL Listed, it can be used as
machine building and systems machine can be used in Europe and in the a single component/device. UL Listing is
manufacturers to use devices that have USA without problems. If the devices are accepted in Canada for the most part,
already been UL tested and listed in only UL Recognized, they can be installed so that the country-specific CSA approval
some way. Ideally, the devices used should in a control cabinet or the like, which is not absolutely necessary.
be UL Listed or listed as components can then be submitted to be UL Listed as
(UL Recognized). That makes any a complete system. On the other hand,
PhoENix CoNtACt 25
The basics of device circuit breakers | Standards and approvals
The three following shipping approvals The ambient conditions and influences approved for shipping can be used in
are the most important ones for the on a shipping vessel are significantly most environments without a second
industry: harsher than in common machines and thought.
• DNV-GL systems. For that reason, passing the
(Det Norske Veritas und required tests is very costly. Above all,
Germanischer Lloyd) impact, vibration, and EMC effects are
• LR (Lloyd’s Register of Shipping) tested at a very high level. This means
• ABS (American Bureau of Shipping) that any device circuit breakers that are
26 PhoENix CoNtACt
The basics of device circuit breakers | Standards and approvals
7.5 NEC Class 2
NEC Class 2
1 1
2
OUT+
+ + - - - 3
Output DC 24V 10A
2 4
13
14
UOut 1
Signal 3
IN -
29,5V
13 2
14
Rem CBMC
SGnd 4
Out 1
Out 2
24V
> 100% Boost 1
> 75%
IN +
> 50%
2
DC OK
QUINT POWER
NF C
Input AC 100-240 V
N/- L/+
PE
N
L
PhoENix CoNtACt 27
The basics of device circuit breakers | Safe system operation with products from Phoenix Contact
28 PhoENix CoNtACt
The basics of device circuit breakers | Safe system operation with products from Phoenix Contact
PhoENix CoNtACt 29
The basics of device circuit breakers | Glossary
9 Glossary
30 PhoENix CoNtACt
The basics of device circuit breakers | Glossary
Switching cycles
Sequence of actuations from one position
to another and back.
PhoENix CoNtACt 31
In dialog with customers and partners worldwide
Phoenix Contact is a globally present, Germany-based market leader. Our group
is synonym for future-oriented components, systems, and solutions in the fields of
electrical engineering, electronics, and automation. A global network across more than
100 countries, and 16,500 employees ensure a close proximity to our
customers, which we believe is particularly important.
Iceland Finland
Blomberg, Germany
Poland
Russia
Slovenia
Slovakia
Hungary Moldova
Ukraine Kazakhstan
Romania
infrastructure, process and factory automation. USA
Spain
Portugal
Italy
Croatia
Bosnia and Serbia
Herzegovina Kosovo
Montenegro Bulgaria Georgia
Azerbaijan
South Korea
Japan
Macedonia Turkey Armenia China
Greece
Tunisia
LebanonIraq Iran
Morocco Cyprus Pakistan Taiwan
Kuwait Bangladesh
Mexico Israel
Algeria India Myanmar
Dominican Republic Jordan Bahrain
Guatemala Egypt Qatar Sri Lanka
Honduras Saudi Arabia
Nicaragua Thailand Philippines
Trinidad and Tobago UAE
Costa Rica
Panama Venezuela Oman Malaysia Vietnam
Ghana Nigeria
Colombia Cameroon Uganda Singapore
Kenya
Ecuador
Indonesia
Brazil
Peru Tanzania
Zambia
Bolivia Mozambique Mauritius
Namibia Zimbabwe
Botswana
Paraguay
South Africa
Chile
Uruguay
Australia
Argentina
New Zealand
Flachsmarktstraße 8
32825 Blomberg, Germany
Phone: +49 52 35 3-00
TT 05-18.000.L3