GTEC-IRE-0201 Observation Report For Witness Inspection Schedule Item NR 3 & 4 On 03.10.2022 - BD 2
GTEC-IRE-0201 Observation Report For Witness Inspection Schedule Item NR 3 & 4 On 03.10.2022 - BD 2
REPORT
HKN Internal inspection Schedule item Nr 2 and 4 Dated 03rd October 2022
Revision History
Page 1 of 4
Introduction
This report refers to non-conformances observed during the internal inspection on 06 July 2022 for
01. Item Nr. 2/03.10.22: ‘Installation of Cables and Wires’ (TN, FD, SA, LT, EM and PA systems) in
Kitchen corridor areas at level 04 in Building 2 (2.30-2.40/2.A-2.L)
02. Item Nr. 4/03.10.22: ‘Installation of Cables and Wires’ (LT, EM, and OE) in Toilet areas at level 07
in Building 2 (2.32-2.36/2.J-2.L)
Figure 1: Smoke detector was mounted on the beam exceeding top 10% void height from top
Figure 2: Smoke detector was mounted close to the beam without maintaining minimum 500mm distance
Page 2 of 4
02. It was observed that several fire detectors are obstructed by mechanical ducts and cable trays.
Below shown is an examples only.
03. Several smoke detectors were not securely fixed to the soffit.
Page 3 of 4
03/03.10.22 - Toilet areas at level 07 (2.32-2.36/2.J-2.L)
Observation:
01. Provision for hand dryer was not provided in the female toilet area. (Grid: 2.34-2.35/2.K-2.L)
Figure 5: Highlighted power provision was not provided as per the HKN-SPD-EL-OE-21107D1
Provision for hand dryer shall be provided as per the spd ref HKN-SPD-EL-OE-21107D1 and upon
completion, the inspection shall be re-raised to witness the rectification.