Waterfront Integrated Resort Project

HKN Joint Venture


No.130, Glennie Street
Colombo
02 Sri Lanka

MAIL TYPE MAIL NUMBER REFERENCE NUMBER


Engineers Advice BSC-EA-002896 GTEC-CONAD-000053

Fwd: GTEC - IRE - 0059_OBSERVATION REPORT ON IMPERFECTIONS OBSERVED RELATED TO


ELEVATORS

From Mr Aruna Amarasena - Balmond Studio - Colombo

To
(4) Mr Yoonjong Hwang - HKN Joint Venture (+3 more...)

Cc
(74) Mr Jeremy Mayhew - Balmond Studio - Colombo (+73 more...)

Sent Tuesday, 14 December 2021


2:06:37 PM IST (GMT +05:30)

Respond by 20/12/2021

Status Responded


FILE ATTACHMENTS
(1)

File Name


Observation Report GTEC-IRE-0059.pdf


ATTRIBUTES

Attribute 1 Building 4 - Residential & Carpark

Attribute 2 EL-Electrical


MESSAGE

Dear YJ Hwang /DY Won ,

Please find the attached Engineer's observation report regarding the "non-conformance related to 1) corrosion on lift accessories 2) Lift door
details are differ from approved model  3) unprotected  control panel 4) openings at fire separation walls at machine rooms and elevators of
building 4" which is self explanatory. 

The Engineer advises HKN to address the non-conformances reported in the attached report.

Further, Contractor is advised to submit no later than 20th December 2021, rectification plan/preventive measures and program that
includes start and completion dates.

Regards

Aruna Amarsena

 
 
1.1.1.1.1 Project : WATERFRONT INTERGRATED RESORT
Reference : GTEC - IRE - 0059

REPORT

OBSERVATION REPORT ON IMPERFECTIONS OBSERVED RELATED TO


ELEVATORS
Building – 04

Report on Elevator Installation


Date: 10/12/2021

Revision History

00 12th December 2021 TWA FOR REFERENCE GNA GBE


Revision Date Prepared by Reference Checked by Approved by
Building /Level Building 04

Location Lift Shaft


Observation Pitting corrosion/ rusting emerged in the Lift shaft accessories.
Note: Below photographs attached relate to few locations

Recommendation Severely damaged components shall be replaced and remains shall be treated to
prevent condition get worst.

Image 01–Guide Rails Image 02–Buffer Jacks

Image 03- Lift pit baseplates Image 04- Lift pit baseplates
Image 05- Lift pit baseplates Image 06- Lift Car Roller supports

Image 07- Rusting/discoloration of suspension rope (PL Image 08- Sill cover plates
4.4)
Building /Level Building 04

Location Lift Landing doors


Observation As per the elevator door fire test certificates in the HKN-MSB-LE-0002 Sup 01, door
Jamb and door edges shall have special enclosing arrangement as extracted below to
prevent fire propagation

However, it is observed that the lift landing door end construction is differ than the
proposed model in the MSB, and also at some portions even clear gap can be seen
without end plate.

Sketch 01- Enlarged detail of


End connection

Image 09- Lift Landing Door


(Image taken from the Lift shaft)
Recommendation Landing Doors shall be replaced with approved model.
Building /Level Building 04

Location Lift Machine Room


Observation Lift machine rooms are not cleaned and free from dust/debris. Also, significant dust
accumulation in lift control panels which are in operation.

Recommendation Rooms shall be cleaned and all the control panels shall be vacuumed with immediate
interruption. Present situation could lead to permanent damage of electronic and
electrical components.

Image 10- Machine Room Image 11- Dust in Lift Control Panels

Building /Level Building 04

Location Lift Machine Room


Observation Passive Fire protections are not applied.

Recommendation Passive Fire protections shall be applied to form fire separation.

Image 12- Unprotected Openings with PFP Image 13- Unprotected Openings with PFP