Professional Documents
Culture Documents
EPR420S Lecture Notes - Unit Protection of Feeders
EPR420S Lecture Notes - Unit Protection of Feeders
Penti Paulus
1
1. INTRODUCTION
• The time- and current-graded over-current systems, though
pleasantly simple in principle, do not meet all the protection
requirements of a power system.
2
INTRODUCTION (CONT.)
• In most cases a unit protection system involves the (i) measurement of fault
currents (and possibly voltages) at each end of the zone, and the (ii)
transmission of information between the equipment at zone boundaries.
• One form of ‘Unit Protection’ is known as ‘Differential Protection’.
The principle is to sense the difference in currents between the incoming and
outgoing terminals of the unit being protected.
3
2. CONVENTION OF DIRECTION
• This direction can only be expressed on a comparative basis, and such a
comparative measurement is the common factor of many systems, including
directional comparison protection and distance tele-protection schemes
with directional impedance measurement.
• Hence the notation of current flow shown in Figure 2.1.; the section GH carries
a through current which is counted positive at G but negative at H, while the
in- feeds to the faulted section HJ are both positive.
4
CONVENTION OF DIRECTION (CONT.)
5
3. CIRCULATING CURRENT SYSTEM
• The principle of this system is shown Figure 3.1.
• For a fault within the protected zone the CT secondary currents will not
balance, compared with the through- fault condition, and the difference
between the currents will flow in the relay.
8
CIRCULATING CURRENT SYSTEM (CONT.)
• If the current transformers are ideal, the functioning of the system
is straight forward.
3.1. The circulating-current principle applied to a
system element having several connections.
• The principle can still be applied where a power transformer is involved, but, in
this case, the ratios and connections of the CT’s on opposite sides of the power
transformer must be such as to compensate for the magnitude and phase-angle
change between the power transformer currents on either side.
11
The ‘Percentage Differential’ Type of Relay(cont.)
15
The ‘Percentage Differential’ Type of Relay (cont.)
• Figure 3.6 shows the comparison of a simple over-current relay with a
percentage-differential relay under such conditions.
• An over-current relay having the same minimum pick-up as a
percentage-differential relay would operate undesirably when the
differential current barely exceeded the value X, whereas there would
be no tendency for the percentage differential relay to operate
• Each of the three restraining coils of Figure 3.7 has the same
number of turns, and each coil produces restraining torque
independently of the others and their torques are added
arithmetically.
• The percent-slope characteristic for such a relay will vary with the
distribution of currents among the three restraining coils.
18
The ‘Percentage Differential’ Type of Relay (cont.)
The current and voltage transformers will have errors arising from both
that cause deviation from the ideal, and the interconnections between them
may have (iii) Unequal impedances.
• This can give rise to a ‘spill’ current through the relay even without a fault
being present, thus limiting the sensitivity that can be obtained. See Figure
3.8.
20
CIRCULATING CURRENT SYSTEM (CONT.)
3.4.Transient Instability
• The 'spill' current in the relay arising from the various sources of error,
mentioned in 3.3 and 3.4, is dependent on the magnitude of the through
current, being negligible at low values of through-fault current but sometimes
reaching a disproportionately large value for more severe faults.
• Setting the operating threshold of the protection above the maximum level of
spill current produces poor sensitivity.
24
Bias (cont.)
• Figure 3.9 illustrates a typical bias characteristic for a modern relay that
overcomes the problem.
• At low currents, the bias is small, thus enabling the relay to be made
sensitive.
• At higher currents, such as would be obtained from inrush or through fault
conditions, the bias used is higher, and thus the spill current required to cause
operation is higher.
• The relay is therefore more tolerant of spill current at higher fault currents and
therefore less likely to mal- operate, while still being sensitive at lower current
levels.
25
Bias (cont.)
• For new installations the balanced voltage system has been almost completely
superseded by circulating current schemes.
• It is the dual of the circulating current protection,
• The system is shown in figure 4.1
27
4. BALANCED VOLTAGE SYSTEM
28
BALANCED VOLTAGE SYSTEM (CONT.)
30
5. PILOT-WIRE RELAYS
• For the protection of power lines, applications of simplified circuits such as that shown in Figure 3.1 are not
practical as the length of protected section of line may constitute tens of kilometers.
• In such cases instead of one relay, two relays (Figure 5.1) are used, each affecting a power circuit-breaker
which is nearest to it.
• Pilot wires between the relays have high resistance exceeding by ten-fold acceptable bounds for the load of
even the most powerful CTs. For instance, for a length of 10 km, the resistance of a pilot copper wire with a
section of 1.5 sq.mm is 130 Ω, while the permissible load for CT‘s is 1 to 2 Ω.
• This difficulty can be overcome with the help of auxiliary CT‘s, CT1-1 and CT2-1 (Figure 5.2).
• The use of the second relay connected parallel (according to Figures 5.1 and 5.2) causes considerable
changes in the conditions of the operation of the protection.
31
PILOT-WIRE RELAYS (CONT.)
32
PILOT-WIRE RELAYS (CONT.)
33
PILOT-WIRE RELAYS (CONT.)
• Current applied from each of the CT‘s to each of the relays is distributed in
inverse proportion to the resistance of their circuits.
• The circuit of the remote‘‘ relay (for CT1, the remote‘‘ relay is Relay 2 and for
CT2 - Relay 1) includes pilot wires with high resistance, which is why current
received at the remote‘‘ relay is less than current received at the local relay.
• As a result, the currents applied to the relays will be unbalanced even if perfect
(ideal) CT‘s are used.
• Every protection of this kind, depending on its sensitivity, has a maximum
allowable impedance for the pilot wires.
• If this impedance is exceeded, the protection will not operate properly.
• However, even if the impedance of the pilot wires were zero, each of the parallel
connected relays will receive only half of the current, which is why the sensitivity
of such a protection scheme decreases.
34
PILOT-WIRE RELAYS (CONT.)
• Due to the difficulties encountered in the application of the circulating-current principle for the
protection of long power lines, the balanced-voltage principle was used (Figure 5.3).
• In normal conditions in the circuit with the balanced-voltage system, the total impedance of the series
circuit turns out to be very high, and the voltages induced in the secondary windings of the CT‘s are
mutually compensated (balanced), therefore, there will be no current in this series circuit (or in the
windings of the relays).
• This absence of current in the circuit and also in the pilot wires in the normal operating conditions is a
great advantage of the balanced- voltage system in comparison with the balanced-current system, as
it reduces the requirements for pilot wires and eliminates the limitations on the size of the protected
area.
• However, owing to the fact that a demagnetising flux does not exist in the CT‘s, the entire current-
transformer primary current is a magnetising current.
35
PILOT-WIRE RELAYS (CONT.)
36
PILOT-WIRE RELAYS (CONT.)
• For these cases, incorporated in the scheme are auxiliary CT‘s that have
their primaries connected in the main current-transformer secondary
circuit (providing normal operating conditions for the main CT‘s).
• The number of turns of the primary windings is taken in the following proportion: I : II : III = 1 : 1 : 3
• If the number of turns between the outlets of phases R–S and S–T is the same, the number of turns
between the outlets of phases R-T will be doubled.
38
PILOT-WIRE RELAYS (CONT.)
• This causes unequal sensitivity of protection to different combinations of damaged phases
when a short-circuit occurs.
Figure 5.5a: Circuit of the three-phase induction relay of HO4 type for the
balanced-voltage longitudinal differential protection system
(GEC Measurements, now ALSTOM).
1- Summation winding; 2 - secondary winding; 3 - bias loop; 4 - pilot wires.
41
Biased Electro-mechanical
Balanced-Voltage system - Translay
43
PILOT-WIRE RELAYS (CONT.)
• The pilot links between relays have been treated as an auxiliary wire circuit that interconnects
relays at the boundaries of the protected zone.
• In many circumstances, such as the protection of long transmission lines or where the route
involves installation difficulties, it is too expensive to provide an auxiliary cable circuit for this
purpose, and other means are sought.
• The solution was to use the main line conductors as the inter- connecting conductors of a
longitudinal differential protection.
• The need for special inter-connecting conductors (cables) then disappears and it hence
becomes possible to set up a longitudinal differential protection on lines of any length.
• This is the basis of what are called carrier-current protections‘ or Power Line Carrier
Channel/Communications (PLCC)‘ For Carrier Unit Protection Schemes.
44
6. CARRIER UNIT PROTECTION SCHEMES
6.1. Power Line Carrier Channel (PLCC)
• To make the transmission of commercial-frequency load-current possible and at the same time use
the main line wires as the inter- connecting conductors of the differential protection, it is necessary
to use a current of higher frequency in order to transmit current impulses from one end of the
line to the other.
• For this purpose, it is usual to employ auxiliary current having a frequency of 50 kHz to 150 kHz,
generated by a special high- frequency transmitter and received at the other line end by a high-
frequency receiver.
• The protected power line must then be accordingly equipped to handle the high frequency current
within its confines, this equipment comprises high-frequency traps (HFT), inter-posed in the line
conductors at both ends of the protected line, and coupling filters (capacitors) (Fig. 6.1).
45
CARRIER UNIT PROTECTION SCHEMES
46
CARRIER UNIT PROTECTION SCHEMES
• It hence presents high reactance to the high-frequency carrier current, but relatively low reactance to the
power-frequency current.
• The high-voltage coupling capacitor connects the high- frequency receiver–transmitter to one
of the line conductors and simultaneously serves to isolate the receiver–transmitter from the
high power-line voltage.
• It presents a relatively low reactance to the high frequency and a high reactance to the power-
frequency.
• Carrier systems are generally insensitive to induced power system currents since the systems are
designed to operate at much higher frequencies, but each medium may be subjected to noise at the
carrier frequencies that may interfere with its correct operation. 47
CARRIER UNIT PROTECTION SCHEMES
48
CARRIER UNIT PROTECTION SCHEMES
• There are a number of ways of coupling the carrier frequency signal to one or more of the conductors
of the transmission line.
• The simplest, and most common, on high-voltage (HV) transmission lines is to use one phase of the
power line with ground as the return path.
• The return path is usually the overhead ground wire although the ground itself can be used, with
accompanying higher attenuation. 49
Carrier Frequency Coupling
• Coupling between any two phases of the transmission line is an alternative, referred to as 'phase-to-
phase' or 'line-to-line' coupling when the coupling is on the same three-phase transmission line, or
'inter-phase' coupling when the coupling is between adjacent lines on the same tower.
• Phase-to-phase coupling appears to have an advantage in that a ground on one of the phases
would not affect the communication signal as it would seem to do with phase-to-ground coupling.
• Actually, however, there is enough electrostatic and electro- magnetic coupling between the
conductors to transfer enough energy around the ground to maintain a useful signal.
• The preferred method for EHV lines is to couple to all three phases.
• The three modes of coupling, in decreasing order of attenuation and increasing order of reliability
and cost, are phase-to-ground coupling using the center phase, phase-to-phase coupling between
the outside phases and coupling to all three phases.
50