TABLE OF CONTENTS REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL

SHEET NO. JOB NO. DESCRIPTION TAMPAKAN


SOUTH COTABATO
ARCHITECTURAL

PERSPECTIVE
01 A-1 SITE DEVELOPMENT PLAN

02 A-2 FLOOR PLAN

03 A-3 REFLECTED CEILING PLAN

04 A-4 ROOF PLAN

05 A-5 FRONT ELEVATION LAND USE & ZONING


REAR ELEVATION

06 RIGHT SIDE ELEVATION


A-6
LEFT SIDE ELEVATION
07 A-7 CROSS SECTIONS

08 A-8 SCHEDULE OF DOORS AND


09 A-9 WINDOWS

STR UC TU R A L

CONSTRUCTION NOTES
10 S-1 CONSTRUCTION DETAILS LINE AND GRADE
11 S-2 FOUNDATION LAYOUT PLAN
01 ARCHITECT'S PERSPECTIVE SCHEDULE OF FOOTINGS
A-01 A-09 SCALE NTS SCHEDULE OF COLUMNS
SCHEDULE OF BEAMS
TYPICAL BEAM DETAILS
12 S-3 SLAB ON FILL DETAILS
TYP. BEAM CROSS SECTION
10.00m 77.03m WALL FOOTING SECTION
5.00m 5.00m 22.05m 29.05m 25.93m TYP. FOOTING PLAN
TYP. FOOTING SECTION
13.40m 3.00m 5.65m 5.83m 5.00m 15.10m
CL
13 S-4 ROOF BEAM LAYOUT
14 S-5 ROOF FRAMING- "A" ARCHITECTURAL
ROOF FRAMING LAYOUT B
15 S-6 ROOF FRAMING LAYOUT C

5.19m
ROOF FRAMING LAYOUT- "D"
16 ROOF FRAMING LAYOUT- "E"
S-7
SHELVES

SHO BATH TUB ROOF FRAMING LAYOUT- "F"


GIRT DETAIL

STORAGE
SLIDING CABINET
TABLE

SLIDING CABINET

SHELVES
CABINET
MASTER'S T&B
A = 1 1 . 1 0 S Q . M .

STORAGE
E L E V @ + 2 7 5 M M
V E R A N D A

MASTER BEDROOM LAV


A = 5 3 . 1 7
E L E V @
S Q . M .
+ 2 5 0 M M
17 S-8 HALF TRUSS DETAIL

D = 800MM
A = 4 4 . 4 5 S Q . M . MASTER'S W-I-C WC
A = 1 2 . 9 5 S Q . M .
E L E V @ + 3 0 0 M M
E L E V @ + 3 0 0 M M
BAY BENCH

OVEN
P L U M B I N G

PREP AREA
SINK

D = 800MM
SHELVES

G A R D E N

ISLAND COUNTER

10.01m
TV MODULE

GARDEN

TV MODULAR CABINET

DINING TABLE
TABLE OUTDOOR DINING
A = 5 0 . 0 6 S Q . M .
22.33m

SHELVES

SLIDING CABINET L I V I NG A R E A E L E V @ + 1 0 0 M M
RANGE

STRUCTURAL
A = 1 8 . 7 2 S Q . M .
BAY BENCH

E L E V @ + 3 0 0 M M
K I T C H E N

PREP AREA
STORA GE
STORM DRAINAGE PLAN

SLIDING CABINET
BED A = 1 8 . 5 3 S Q . M .
A = 12.18 SQ .M.

SHELVES
ELE V @ + 300M M
D IN ING A R EA E L E V @ + 3 0 0 M M
A = 2 1 . 7 4 S Q . M .
BEDROOM 1

BREAKFAST NOOK
E L E V @ + 3 0 0 M M
A = 1 7 . 6 9 S Q . M .
E L E V @ + 3 0 0 M M

PROPOSED BUNGALOW BUILDING GENERAL CONDITIONS

SHELVES
SLIDING CABINET

REF

18 P-1

D= 800M M
SHELVES SHELVES
A = 3 8 9 . 8 3 S Q . M . INSTALLATION
D

D = 8 0 0 MM
10.00M)

SHELVES

PLUMBING NOTES
NICHED WALL

WC
D = 800MM
T & B -
A= 7.15 SQ.M.
ELEV @ +27 5MM
1 H
A
E
=
L
A
E
5
V
2
L
.
@
2
L
7
+
W
3
S
0
Q
A
0
. M
M
Y
.
M
W A L K W A Y
A =
E L E V
1 7 . 3 6
@ + 1
S Q . M .
0 0 M
1
M
LEGEND
SHO LAV
SLIDING CABINET

SANITARY DRAINAGE LAYOUT


D = 8 0 0 MM

D = 800MM
G A Z E B O SHELVES
D = 8 0 0 MM CONSOLE TABLE
D = 8 0 0 MM

PUGON
A = 9 . 0 1 S Q . M .
CABINET

E L E V @ + 1 0 0 M M O F F I C E
SLIDING CABINET

19
SLIDING CABINET

P-2
A = 11.35 SQ.M.
EL E V @ +3 0 0M M F O Y E R
SANITARY DRAINAGE ISOMETRIC
TABLE

A= 7.14 SQ.M. P A N T R Y
34.82m

34.82m
E LE V @ + 300 MM A = 1 0 . 5 0 S Q . M .
E L E V @ + 3 0 0 M M

ANNEX KITCHEN
S Q . M .
0 0 M M
LAYOUT
TABLE

D= 800M M

BEDROOM 2
A

A = 1 6 . 5 1 S Q . M . MM SHELVES SLIDING CABINET


00
E L E V @ + 3 0 0 M M 19
P O W DLAV
ER D=
TABLE
SHELVES

+ 3
R O O M D= 800M M

1 0 . 7 1
A= 3. 91 SQ .M. RECEIVING AREA
DOUBLE DECKER SINK
OPEN SPACE
D = 800MM

@
E LEV @ +2 75M M A = 1 6 . 0 3 S Q . M .
WC E L E V @ + 3 0 0 M M

E L E V
SHELVES BAY BENCH
SHELVES
M A I D ' S
WATER DISTRIBUTION LAYOUT

A =
ENTRY PORCH QU A R TE R
A = 1 0 . 0 5 S Q . M .

D = 8 0 0 MM
A= 9.21 SQ.M.

20
E L E V @ + 3 0 0 M M

P-3 WATER DISTRIBUTION ISOMETRIC


EL EV @ +3 0 0MM
SHO.
T & B - 2 ANNEX DINING
A = 3.29 SQ.M. A = 1 7 . 1 1 S Q . M . REF
@

DOUBLE DECKER EL EV @ +2 75 MM E L E V @ + 3 0 0 M M

WC
LAYOUT

11.64m
SHELVES

G A R D E N G A R D E N
O

G A R D E N
W A L K W A Y 2
SEPTIC VAULT DETAILS
(RROW

A = 2 3 . 5 0 S Q . M .
E L E V @ + 1 0 0 M M

21 P-4 CATCH BASIN DETAILS PLUMBING


SYSTEM CALCULATION

S Q . M .
+ 1 0 0 M M
LAUNDRY AREA
4 . 6 2
@
6.51m

E L E V
D R I V E W A Y
A = 2 7 2 . 8 1 S Q . M .

E L E C T R I C A L

A =
E L E V @ + 1 0 0 M M
R

C AR PORT (3 C AR S)
A = 8 3 . 3 6 S Q . M .
E L E V @ + 1 0 0 M M

3.00m
WATER TUB/
RISER DIAGRAM
T O W E R
STORA GE 2
A =
E L E V
4 . 5 5
@
S Q . M .
+ 1 0 0 M M
PUMP ROOM/
G E N S E T
A =
E L E V
4 . 5 5
@
S Q . M .
+ 1 0 0 M M
A = 8 . 8 5
E L E V @
S Q . M .
+ 1 0 0 M M
GENERAL NOTES
SCHEDULE OF LOADS AND
F I R E W A L L
22 E-1 COMPUTATIONS
5.98m

FAULT AND VOLTAGE DROP

4.98m
A C C E S S R O A D T O R E A R L O T ( W = 5 M E T E R S )
CALCULATION

23 E-2 LIGHTING LAYOUT ELECTRICAL


24 E-3 POWER LAYOUT
2.50m 2.50m 3.00m
6.00m 8.00m
43.02m 14.00m 20.01m
77.03m

02 SITE DEVELOPMENT PLAN


A-01 A-09 SCALE 1:200

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
PERSPECTIVE Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING SITE DEVELOPMENT PLAN
A1
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 01 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
A B D E F G H I J K
A C
29.05m
12.55m 11.03m 5.47m
5.63m 3.70m 3.22m 3.45m 2.70m 4.88m

R O O F L I N E

W W W W
11 11 8 4

SHELVES
SHO BATH TUB

STORAGE
SLIDING CABINET
TABLE

SLIDING CABINET

SHELVES
CABINET
MASTER'S T&B
A = 1 1 . 1 0 S Q . M .

STORAGE
E L E V @ + 2 7 5 M M
V E R A N D A
A = 5 3 . 1 7 S Q . M .
FF 04

5.60m
E L E V @ + 2 5 0 M M

W MASTER BEDROOM LAV FF 05

D= 800MM
3 A = 4 4 . 4 5 S Q . M . MASTER'S W-I-C WC
A = 1 2 . 9 5 S Q . M .
E L E V @ + 3 0 0 M M
E L E V @ + 3 0 0 M M

BAY BENCH
2 FF 07 FF 07
D D
3
W W W

OVEN
4 1 1 2

PREP AREA
SINK

D= 800MM
SHELVES
G A R D E N
D

ISLAND COUNTER
TV MODULE
4

TV MODULAR CABINET
W

DINING TABLE
9
TABLE OUTDOOR DINING
A = 5 0 . 0 6 S Q . M .

SHELVES
SLIDING CABINET LIVING AREA E L E V @ + 1 0 0 M M
A = 1 8 . 7 2 S Q . M . RANGE

BAY BENCH

PREP AREA
E L E V @ + 3 0 0 M M
K I T C H E N FF 06
STORAGE

SLIDING CABINET
BED

3.14m
A = 1 8 . 5 3 S Q . M .

14.60m
A= 12.18 SQ.M.

SHELVES
FF 03 D I NIN G A RE A

7.76m
E L E V @ + 3 0 0 M M
ELEV @ +300MM
A = 2 1 . 7 4 S Q . M .
W BEDROOM 1

BREAKFAST NOOK
E L E V @ + 3 0 0 M M
5 A = 1 7 . 6 9 S Q . M .
FF 02 FF 03
E L E V @ + 3 0 0 M M
FF 02 FF 03

SHELVES
SLIDING CABINET
REF
FF 07

D= 800MM
SHELVES SHELVES

D = 8 00 M M
SHELVES
D
D 4
4

12.96m
NICHED WALL
2.51m

WC
9.00m

D = 800MM
T & B - 1 H A L L W A Y D
W D A = 5 2 . 2 7 S Q . M . 3
A= 7.15 SQ.M. W A L K W A Y 1
B 10

SHO
ELEV @ +275MM

FF 04 LAV
4 E L E V @

FF 02
+ 3 0 0 M M
D= 920MM
A =
E L E V
1 7 . 3 6
@ + 1
S Q . M .
0 0 M M

SLIDING CABINET

D= 800MM

D= 800MM
G A Z E B O SHELVES D D = 800MM D

CONSOLE TABLE
D= 800MM

PUGON
A = 9 . 0 1 S Q . M . 4 D 4

CABINET
E L E V @ + 1 0 0 M M O F F I C E 4 D

SLIDING CABINET
DOUBLE DECKER A= 11.35 SQ.M.
FF 02 FF 01 4
EL EV @ +3 00M M F O Y E R
D A= 7.14 SQ.M. P A N T R Y
FF 03 4 ELEV @ +300MM A = 1 0 . 5 0 S Q . M . FF 01
3.35m

SLIDING CABINET
E L E V @ + 3 0 0 M M

ANNEX KITCHEN
S Q . M .
+ 3 0 0 M M
TABLE

D = 80 0 M M
BEDROOM 2
A = 1 6 . 5 1 S Q . M . D MM SHELVES SLIDING CABINET
1 00
E L E V @ + 3 0 0 M M
LAV 19
POWDER D=

TABLE
FF 01

TABLE

5.20m
FF 07 R O O M D = 8 0 0M M
W

1 0 . 7 1
A= 3.91 SQ.M. RECEIVING AREA
12 D

D= 920MM
SINK

@
ELEV @ +275MM A = 1 6 . 0 3 S Q . M .
WC 4
E L E V @ + 3 0 0 M M
D FF 04

E L E V
2
6 SHELVES BAY BENCH M A I D ' S

A =
ENTRY PORCH QUARTER
W W W A = 1 0 . 0 5 S Q . M .

D= 800MM
A= 9.21 SQ.M. D
6 6 7 E L E V @ + 3 0 0 M M
ELEV @ +300MM 4
SHO.
FF 02 FF 01 T & B - 2 ANNEX DINING
A= 3.29 SQ.M. A = 1 7 . 1 1 S Q . M . REF
DOUBLE DECKER ELEV @ +275MM E L E V @ + 3 0 0 M M

FFWC04 FF 01
3.73m

SHELVES

7 G A R D E N G A R D E N
W
1
W
7

G A R D E N
W A L K W A Y 2
A = 2 3 . 5 0 S Q . M .
E L E V @ + 1 0 0 M M

FF 01

S Q . M .
+ 1 0 0 M M
LAUNDRY AREA

7.44m
4 . 6 2
@
E L E V
D R I V E W A Y
A = 2 7 2 . 8 1 S Q . M .

A =
E L E V @ + 1 0 0 M M

FF 06 CARPORT (3 CARS)
A = 8 3 . 3 6 S Q . M . FF 01
E L E V @ + 1 0 0 M M

FF 06

D D
3 3

D = 920MM

D = 920MM
WATER TUB/
T O W E R

2.00m
PUMP ROOM/ A = 8 . 8 5 S Q . M .
E L E V @ + 1 0 0 M M
STORAGE 2 G E N S E T
A = 4 . 5 5 S Q . M .
E L E V @ + 1 0 0 M M A =
E L E V
4 . 5 5
@
S Q . M .
+ 1 0 0 M M
FF 01
FF 01 FF 01

F I R E W A L L

10.60m 3.30m 3.12m 1.98m 2.63m 3.37m 2.10m


13.90m 13.20m
27.10m

01 F L O O R P L A N
A-02 A-09 SCALE 1:100

AREA TABULATION TOTAL LOT AREA: 83,297 SQ.M. TOTAL FLOOR AREA: 864.43 SQ.M. D E S I G N A T I O N S
ENCLOSED AREA 331.64 SQ.M. OPEN AREA 532.79 SQ.M. F L O O R F I N I S H E S
LOCATION AREA LOCATION AREA LOCATION AREA LOCATION AREA LOCATION AREA LOCATION AREA LEGENDS SPECIFICATIONS LEGENDS SPECIFICATIONS LEGENDS SPECIFICATIONS LEGENDS SPECIFICATIONS
FOYER 7.14 SQ.M. OFFICE 11.35 SQ.M. PANTRY 10.50 SQ.M. PUMP ROOM/ GEN. SET 4.55 SQ.M. DRIVEWAY 272.81 SQ.M. OUTDOOR DINING 50.06 SQ.M.
600MM X 600MM MARBLE FINISH 100MM X 1200MM WPC PLANKS, 60MM X 600MM WOOD
HALLWAY 52.27 SQ.M. T&B 1 7.15 SQ.M. RECEIVING AREA 16.03 SQ.M. CARPORT 83.36 SQ.M. VERANDA 53.17 SQ.M. PLAIN POLISHED CONCRETE
FF 01 SLAB FF 03 CERAMIC TILES, OR ANY FF 05 WOOD DECKING, MATIMCO, OR
ANY APPROVED EQUIVALENT
FF 07 CERAMIC TILES, OR ANY
LIVING AREA 18.72 SQ.M. BEDROOM 1 17.69 SQ.M. ANNEX DINING 17.11 SQ.M. ENTRY PORCH 10.05 SQ.M. GAZEBO 9.01 SQ.M. APPROVED EQUIVALENT APPROVED EQUIVALENT
DINING AREA 21.74 SQ.M. BEDROOM 2 16.51 SQ.M. ANNEX KITCHEN 10.71 SQ.M. WALKWAY 1 17.36 SQ.M.
600MM X 600MM OFF WHITE/ 600MM X 600MM GRAY STONE
KITCHEN 18.53 SQ.M. MASTER BEDROOM 44.45 SQ.M. T&B 2 3.29 SQ.M. LAUNDRY AREA 4.62 SQ.M.
FINISH NON SKID CERAMIC HERRINGBONE OR
BEIGE NON SKID CERAMIC TILES
STORAGE 12.18 SQ.M. MASTER'S W-I-C 12.95 SQ.M. MAID'S QUARTER 9.21 SQ.M. WATER TUB/ TOWER 8.85 SQ.M. FF 02 OR ANY APPROVED EQUIVALENT
FF 04 TILES OR ANY APPROVED FF 06 INTERLOCKING PAVERS
EQUIVALENT
POWDER ROOM 3.91 SQ.M. MASTER'S T&B 11.10 SQ.M. STORAGE 2 4.55 SQ.M. WALKWAY 2 23.50 SQ.M.
ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
FLOOR PLAN Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING
A2
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 02 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
A B C D E F G H I J K
A
23.37m
5.48m 3.60m 3.07m 10.92m
1.49m 2.23m 1.75m 0.87m 1.82m 0.91m 0.90m 2.20m 1.60m 2.60m 0.46m 1.37m 1.79m

PL PL PL PL

1 0.61m

PL PL PL PL PL
PL PL

CABINET BELOW

CABINET BELOW
CABINET BELOW
PL PL

3.40m
3.00m

PL PL

PL PL PL PL
5.40m

PL PL

D= 800MM
PL PL
PL PL PL PL S S
2
1.79m

PL

PL PL PL PL PL

D= 800MM
PL PL PL PL PL

CABINET BELOW
3 PL PL

PL
PL PL

PL CH
3.09m
14.40m

7.66m
PL
PL PL PL
PL PL
PL PL PL

16.20m
PL

D= 800MM
PL

4 PL

D= 800MM
0.71m

PL
2.41m

D= 800MM
PL PL PL

B
1.60m

PL PL D= 920MM

PL
CABINET BELOW
PL
PL
5

D= 8 0 0 M M

D= 800MM
D= 800MM
D= 800MM

PL
PL
PL PL
PL PL PL PL PL
PL
PL PL
3.20m

D= 800MM
M CABINET BELOW
0M
190
D=

5.00m
D= 800MM
PL PL PL PL PL PL

D= 920MM
PL

PL PL PL
6

D= 800MM
PL
PL PL PL PL
PL PL PL PL PL
PL
PL
SHELVES BELOW
7 PL PL

PL PL PL PL

2.63m 5.37m
4.90m 3.34m 1.96m 3.30m 2.97m 1.84m 8.00m
26.90m

01 R E F L E C T E D C E I L I N G P L A N
A-03 A-09 SCALE 1:70

D E S I G N A T I O N S
DRAWING SYMBOLS CEILING FINISHES
ITEM DESCRIPTIONS ITEM DESCRIPTIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS

3.5MM THK FIBER CEMENT BOARD ON METAL FRAMES PAINTED FLAT WHITE FINISH INDOOR PVC SLATS CEILING CLADDING TEAK WOOD TEXTURE FINISH 4.5MM THK FIBER CEMENT BOARD OUTDOOR CEILING FLAT WHITE PAINTED FINISH
PL
PINLIGHT; LIGHTING OUTLET PROVISION CHANDELIER; LIGHTING OUTLET PROVISION CF 01 CF 03 CF 05

3.5MM THK FIBER CEMENT BOARD ON METAL FRAMES PAINTED OFF WHITE FLAT
LED STRIP LIGHT; COVE LIGHT PROVISION CF 02 FINISH CF 04 OUTDOOR PVC SLATS CEILING CLADDING MAHOGANY WOOD TEXTURE FINISH

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
REFLECTED CEILING PLAN Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING
A3
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 03 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
DESIGNATIONS
1 2 3 4 5 6 7 1 2 3 4 5 6 7
L E GE N DS SPECIFICATIONS LE GE N DS SPECIFICATIONS
1 3 1 3 3 1
10.78m 16.70m GREY ASPHLAT SHINGLES WITH G24 PLAIN
PRE PAINTED G22 PLAIN SHEET END

1.57m
8.54m
5.45m 1.52m
2.24m
1.50m 1.11m
5.53m
4.42m
3.39m
1.03m
7.78m
5.65m 1.10m
1 SHEET UNDERSHEETING ON 2"X3" CEE
PURLINS, OR ANY APPROVED EQUIVALENT
BY THE ARCHITECT
3 FLASHING, OR ANY APPROVED EQUIVALENT
BY THE ARCHITECT

0.25m 0.25m 0.25m

PRE PAINTED G22 PLAIN SHEET GUTTER, 3" DIA. DOME DRAINE FILTER, ON 3" DIA. PVC

ROOF "B" LINE


2 OR ANY APPROVED EQUIVALENT BY THE
ARCHITECT
4 STORM DRAIN PIPE, OR ANY APPROVED
EQUIVALENT BY THE ARCHITECT

DS

BUILDING LINE
ROOF "A" LINE

GUTTER
ROOF "B" LINE DS

1.50m

1.00m
DS
2 G U T T E R

BUILDING LINE
3.51m

GUTTER

BUILDING LINE
2 DS 4 G U T T E R

4.79m

GUTTER
3
DS

GUTTER
B

10.30m
3.52m

B
GUTTER

14.66m
A

8.80m
DS
DS

10.56m
14.40m

4 DS
C

GUTTER
15.00m

4.78m

GUTTER
G U T T E R

D
3.50m

E
GUTTER

C
DS
G U T T E R D
E

R
E
4 F

T
T
2

U
DS G U T T E R G U T T E R

G
1.55m
DS

GUTTER

27.46m
F
24.73m

24.73m
3.51m

GUTTER
GUTTER

4.79m
DS

M A S T E R R O O F P L A N
2

3.44m
DS

2
DS
3
DS
1 2 3 1 3
DS 7.28m
G 6.23m 1.15m 5.20m 0.92m
3.28m

4.10m 2.13m
GUTTER

12.88m J

GUTTER

BUILDING LINE
14.43m
2 DS

1
4

1.00m
1.04m
DS

4 DS

H G

BUILDING LINE

5.52m
GUTTER
2
10.33m

12.80m
3.28m

6.65m
GUTTER

GUTTER
DS

I DS

DS H
1 1 K

7.66m
2

9.83m

9.83m
GUTTER
1

1.13m
GUTTER

8.83m
3.28m

4
GUTTER

DS

J BUILDING LINE
I
1.55m

DS
3
DS
2 04 ROOF PLAN - "E"

GUTTER
A-04 A-09 SCALE 1:100
DS 4
DS GUTTER DS GUTTER DS
J 1 2
2 4

1.13m
DS
4.67m

F DS GUTTER DS

4.81m 4.81m 0.25m


1.05m 5.18m

BUILDING LINE
0.25m
8.01m 2.50m 6.23m 1

3.40m
2.15m 7.96m 1.50m 10.51m 1.99m
11.62m 12.50m
3
3 2 4 03 ROOF PLAN - "D"
A-04 A-09 SCALE 1:100
G

01 R O O F P L A N - " A " 02 ROOF PLAN - "B" & "C" 05 ROOF PLAN - "F"
A-04 A-09 SCALE 1:100 A-04 A-09 SCALE 1:100
A-04 A-09 SCALE 1:100

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ROOF PLAN Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING
A4
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 04 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
A' A B C D E F G H I J K
1 5 6 5 7 1 3 7 7 8 4 1 7 1 7 4 7 2 3 4 1 8

APEX OF ROOF - "A" @ 6.22M

1.90m
2.01m
APEX OF ROOF - "B" @ 5.05M
APEX OF ROOF - "C" @ 4.76M

APEX OF ROOF - "D" @ 4.32M

0.93m 0.29m
APEX OF ROOF - "E" @ 4.03M

0.71m

6.22m
6.02m

APEX OF ROOF - "F" @ 3.04M

DOOR AND WINDOWS LINE @ 2.45M


A A
4.01m

1.30m
W W
3.27m

OPEN

3.10m
7 S S 7
F F
D
1
D
2

1.13m
W W W
DOOR AND WINDOWS LINE @ 0.30M 6 6 1
DOOR AND WINDOWS LINE @ 0.00M

01 F R O N T E L E V A T I O N
A-05 A-09 SCALE 1:60

K J I H G F E D C B A A'
8 5 1 2 3 7 4 7 5 7 6 7 4 2 7 3 1 7

APEX OF ROOF - "A" @ 6.22M

0.97m
1.61m

APEX OF ROOF - "B" @ 5.05M


APEX OF ROOF - "C" @ 4.76M
0.58m

1.66m
APEX OF ROOF - "D" @ 4.32M
APEX OF ROOF - "E" @ 4.03M
1.49m
6.22m

6.02m
APEX OF ROOF - "F" @ 3.04M
A A A A A A
W W W D
2 1 1 3 W W
DOOR AND WINDOWS LINE @ 2.45M A A
4 8

2.40m
1.32m

3.39m
OPEN S S S S S S S
2.54m

OPEN F F
1.15m

W W

0.80m
DOOR AND WINDOWS LINE @ 0.30M 11 11

DOOR AND WINDOWS LINE @ 0.00M

02 R E A R E L E V A T I O N
A-05 A-09 SCALE 1:60

D E S I G N A T I O N S
LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS
4" THK CHB WALL, SMOOTH PLASTERED, PAINTED WITH SEMI GLOSS PRE PAINTED CHARCOAL GRAY Q.D.E. G22 PLAIN SHEET GUTTER/ 4" THK CHB WALL,100MM X 1200MM FIBRE CEMENT BOARD WOOD
1 CHARCOAL GRAY PAINT, OR ANY EQUIVALENT APPROVED BY THE
ARCHITECT
3 FLASHING, OR ANY APPROVED EQUIVALENT BY THE ARCHITECT 5 GRAIN PLANKS, PAINTED TEAK BROWN, OR ANY EQUIVALENT
APPROVED BY THE ARCHITECT
7 SEE SCHEDULE OF DOORS AND WINDOWS (SHEET A8)

GREY ASPHLAT SHINGLES WITH G24 PLAIN SHEET UNDERSHEETING ON 4" THK CHB WALL, 100MM X 1200MM FIBRE CEMENT BOARD WOOD GRAIN 4" THK CHB WALL, SMOOTH PLASTERED, PAINTED VENETIAN FINISH,
4" THK CHB WALL, SMOOTH PLASTERED, PAINTED WITH SEMI GLOSS
2 WHITE, OR ANY EQUIVALENT APPROVED BY THE ARCHITECT 4 2"X3" CEE PURLINS, OR ANY APPROVED EQUIVALENT BY THE
ARCHITECT
6 PLANKS, PAINTED ASH GRAY, OR ANY EQUIVALENT APPROVED BY THE
ARCHITECT
8 POLISHED, TOP WITH ACRYLIC EMULSION (SMOOTH POLISHED
CONCRETE LOOK)
ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
FRONT ELEVATION Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING REAR ELEVATION
A5
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 05 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
1 2 3 4 5 6 7
2 1 3 7 5 7 6 7 2 3 7 5 3

APEX OF ROOF - "A" @ 6.22M

1.76m
APEX OF ROOF - "B" @ 5.05M

0.49m 0.92m
APEX OF ROOF - "C" @ 4.76M

APEX OF ROOF - "D" @ 4.32M

1.06m
APEX OF ROOF - "E" @ 4.03M

0.39m
0.32m
6.22m
APEX OF ROOF - "F" @ 3.04M

5.17m
DOOR AND WINDOWS LINE @ 2.45M
A A
A A

2.40m
W

3.39m

2.75m
S S S S 10 S S
F F

W W

0.80m
W
DOOR AND WINDOWS LINE @ 0.30M 3 5 12

0.29m
DOOR AND WINDOWS LINE @ 0.00M

01 L E F T S I D E E L E V A T I O N
A-06 A-09 SCALE 1:60

7 6 5 4 3 2 1
8 7 1 3 7 7 2 3 4 7 5 3

APEX OF ROOF - "A" @ 6.22M

1.76m
APEX OF ROOF - "B" @ 5.05M
0.49m 0.92m

APEX OF ROOF - "C" @ 4.76M

APEX OF ROOF - "D" @ 4.32M

0.85m
APEX OF ROOF - "E" @ 4.03M
0.39m
0.32m

6.22m
APEX OF ROOF - "F" @ 3.04M
5.17m

DOOR AND WINDOWS LINE @ 2.45M

F F F F
1.33m

3.60m
W
3.04m

9
D
3
1.15m

DOOR AND WINDOWS LINE @ 0.30M


DOOR AND WINDOWS LINE @ 0.00M

02 R I G H T S I D E E L E V A T I O N
A-06 A-09 SCALE 1:60

D E S I G N A T I O N S
LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS LEGEND SPECIFICATIONS
4" THK CHB WALL, SMOOTH PLASTERED, PAINTED WITH SEMI GLOSS PRE PAINTED CHARCOAL GRAY Q.D.E. G22 PLAIN SHEET GUTTER/ 4" THK CHB WALL,100MM X 1200MM FIBRE CEMENT BOARD WOOD
1 CHARCOAL GRAY PAINT, OR ANY EQUIVALENT APPROVED BY THE
ARCHITECT
3 FLASHING, OR ANY APPROVED EQUIVALENT BY THE ARCHITECT 5 GRAIN PLANKS, PAINTED TEAK BROWN, OR ANY EQUIVALENT
APPROVED BY THE ARCHITECT
7 SEE SCHEDULE OF DOORS AND WINDOWS (SHEET A8)

GREY ASPHLAT SHINGLES WITH G24 PLAIN SHEET UNDERSHEETING ON 4" THK CHB WALL, 100MM X 1200MM FIBRE CEMENT BOARD WOOD GRAIN 4" THK CHB WALL, SMOOTH PLASTERED, PAINTED VENETIAN FINISH,
4" THK CHB WALL, SMOOTH PLASTERED, PAINTED WITH SEMI GLOSS
2 WHITE, OR ANY EQUIVALENT APPROVED BY THE ARCHITECT 4 2"X3" CEE PURLINS, OR ANY APPROVED EQUIVALENT BY THE
ARCHITECT
6 PLANKS, PAINTED ASH GRAY, OR ANY EQUIVALENT APPROVED BY THE
ARCHITECT
8 POLISHED, TOP WITH ACRYLIC EMULSION (SMOOTH POLISHED
CONCRETE LOOK)
ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
RIGHT SIDE ELEVATION Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING LEFT SIDE ELEVATION
A6
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 06 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
7 6 5 4 3 2 1 DESIGNATIONS
LEGEND SPECIFICATIONS
5 1 2 4 1 2 1 2 2 1 5
4" THK CHB WALL, SMOOTH
PLASTERED EGGSHELL WHITE PAINT
1 FINISH, OR ANY APPROVED
EQUIVALENT BY THE ARCHITECT

SEE SCHEDULE OF DOORS AND


2 WINDOWS

3
4"THK LAMINATED MARINE BOARD FOR

U T I L I T Y S P A C E
3 MODULARS, OR ANY APPROVED
ALTERNATIVE BY THE ARCHITECT

4" THK CHB WALL, 600MM X 600MM

0.15m
RECESSED CEILING LINE @ 3.44M
BOT. OF 2ND ROOF BEAM @ 3.30M
4 CERAMIC NON SKID TILES, OR ANY

0.85m
APPROVED EQUIVALENT BY THE
ARCHITECT
TOP OF WINDOWS AND DOORS @ 2.45M

PRE PAINTED CHARCOAL GRAY Q.D.E.

2.40m
3.00m

2.99m
5 G22 PLAIN SHEET GUTTER, OR ANY

3.44m
3.30m

1.65m
APPROVED EQUIVALENT BY THE
NICHED WALL
ARCHITECT

BOT. OF WINDOWS @ 0.80 M GREY ASPHLAT SHINGLES WITH G24


0.50m

0.50m
PLAIN SHEET UNDERSHEETING ON
FINISHED FLOOR LINE @ 0.30 M BEDROOM - 2 TOILET BEDROOM - 1 MASTER BEDROOM
6 2"X3" CEE PURLINS, OR ANY
0.30m

0.30m
NATURAL GRADE LINE @ 0.00 M APPROVED EQUIVALENT BY THE
ARCHITECT

01 CROSS SECTION THRU- "A"


A-07 A-09 SCALE 1:60

A' A B C D E F G H I J
6 4 3 1 2 1 2 2 6 1 2 2 2 5

U T I L I T Y S P A C E

1.13m 0.15m
BOT. OF 1ST ROOF BEAM @ 4.30 M

DROP OF HIGH CEILING @ 4.14 M

1.28m
BOT. OF 2ND ROOF BEAM @ 3.30 M

0.15m
DROP CEILING LINE @ 3.00 M

TOP OF WINDOWS AND DOORS @ 2.45M

0.74m

4.29m
3.00m

2.71m
3.30m

2.74m

0.75m
0.88m
FINISHED FLOOR LINE @ 0.30 M TOILET BEDROOM-1 HALLWAY LIVING AREA DINING AREA KITCHEN
0.30m

0.30m
0.26m

NATURAL GRADE LINE @ 0.00 M

02 CROSS SECTION THRU- "B"


A-07 A-09 SCALE 1:60

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
CROSS SECTIONS Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING A7
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 07 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
1.40m 2.22m
0.66m 0.66m 2.14m
2.87m 1.00m 1.00m 0.88m 0.71m 0.71m 0.71m
1.02m 1.81m 0.10m 0.72m 0.10m 0.92m 0.80m
0.97m 0.34m 1.12m 0.34m 0.15m 0.62m 0.15m
0.41m

0.10m

0.15m

0.15m
0.34m

0.27m
1.14m
1.04m
1.02m
S S S S S

1.65m
1.30m
2.25m
1.51m

2.15m

2.15m

2.15m

2.15m
F

2.11m

2.11m
1.81m

1.81m
0.10m
1.84m

0.77m

0.77m

0.97m

0.50m

0.50m
0.34m

0.15m

0.15m
0.10m
FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE

LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION:
ENTRANCE PORCH OFFICE LIVING AREA, ALL INTERIOR ROOMS, LIVING AREA, DINING AREA, MAID'S DINING AREA
KITCHEN TOILETS QUARTER
1 1 2 12 3 1
D SPECIFICATIONS:
D SPECIFICATIONS:
D SPECIFICATIONS:
D SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS:
1 DECORATIVE PIVOT DOOR WITH PAINTED WOOD PLANKS, PAINTED
2 SINGLE LEAF, 6MM GLASS DOOR,
3 DECORATIVE SINGLE LEAF DOOR,
4 DECORATIVE SINGLE LEAF DOOR,
1 2-6MM THK. DOUBLE SLIDING GLASS WINDOW IN
2 3-6MM THK. DOUBLE SLIDING GLASS WINDOW IN
POLISHED TEAK, WITH FIXED GLASS SIDE PANEL OR ANY EQUIVALENT WITH LEVER TYPE DOOR HANDLE WITH PAINTED WOOD PLANKS, WITH PAINTED WOOD PLANKS, UPVC WINDOW SLIDING FRAME AND UPVC JAMB UPVC WINDOW SLIDING FRAME AND UPVC JAMB
APPROVED BY THE ARCHITECT PAINTED POLISHED TEAK, OR ANY PAINTED POLISHED TEAK, OR ANY
APPROVED EQUIVALENT APPROVED EQUIVALENT

3.97m 1.05m 0.80m


0.73m 2.40m 0.73m 2.72m 0.95m 0.75m
2.64m

2.97m

0.37m
0.29m
A A A A 0.72m 0.72m 0.72m 0.72m
1.18m

0.65m 0.63m 0.63m 0.65m

A A

0.22m

0.35m
0.30m
0.26m
A
2.35m

F
S S S S

1.65m

1.65m
F

2.47m

1.39m

1.29m
1.17m

F F

1.80m
0.50m

0.50m
0.49m

FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE

LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION:

MASTER BEDROOM MASTER'S T&B BEDROOM 1 BEDROOM 2, POWDER


1 1 1 2 OFFICE 2 ROOM,
T&B 2

W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS:


3 6MM THK CLEAR FIX GLASS WITH 2- SIDE AWNING AND FIX GLASS WINDOWS, IN UPVC WINDOW FRAME AND UPVC
4 4-6MM THK. CLEAR GLASS ON UPVC AWNING WINDOW
5 4-6MM THK. DOUBLE SLIDING GLASS WINDOW IN UPVC WINDOW SLIDING
6 6MM THK CLEAR GLASS,
7 6MM THK. CLEAR GLASS
WINDOW JAMB, OR ANY APPROVED EQUIVALENT BY THE ARCHITECT FRAME IN UPVC WINDOW JAMB FRAME AND UPVC JAMB ON UPVC FIX WINDOW ON UPVC AWNING
FRAME WINDOW FRAME IN UPVC
WINDOW JAMB

01 SCHEDULE OF DOORS AND WINDOWS


A-08 A-09 SCALE 1:60

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
SCHEDULE OF DOORS AND Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING WINDOWS
A8
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 08 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
1.51m
1.59m 3.87m 2.26m 0.83m 1.43m
0.79m 0.76m 0.99m 0.95m 0.95m 0.99m 1.13m 1.13m 0.71m 0.71m

0.37m

A A

1.18m
A

0.29m
0.34m
A A

0.47m
F F F F

2.35m

1.62m
S S

2.47m

1.33m
1.18m
F

1.76m
1.64m

0.49m

0.49m
FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE FINISH FLOOR LINE

LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION: LEGEND: UNITS: LOCATION:
MASTER'S WALK-IN-CLOSET KITCHEN T&B 1 MASTER BEDROOM BEDROOM 2

1 1 1 2 1
W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS: W SPECIFICATIONS:
8 2-6MM THK. CLEAR GLASS ON UPVC AWNING
9 4-6MM THK CLEAR GLASS, ON FIX UPVC WINDOW FRAME, IN UPVC WINDOW JAMB OR ANY APPROVED
10 2-6MM THK. CLEAR GLASS ON UPVC AWNING WINDOW
11 1-6MM THK CLEAR GLASS, ON 12 2-6MM THK. DOUBLE SLIDING GLASS WINDOW IN
WINDOW FRAME IN UPVC WINDOW JAMB BY THE ARCHITECT FRAME IN UPVC WINDOW JAMB UPVC AWNING WINDOW FRAME, UPVC WINDOW SLIDING FRAME AND UPVC JAMB
1-6MM THK CLEAR GLASS ON
UPVC FIX WINDOW FRAME, IN
UPVC WINDOW JAMB

01 SCHEDULE OF DOORS AND WINDOWS


A-09 A-09 SCALE 1:60

ARCHITECT PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
SCHEDULE OF DOORS AND Date Remarks
ENGINEERING SERVICES
AR. HARRIS MARK V. CANAKAN PROPOSED TWO-STOREY RESIDENTIAL BUILDING WINDOWS
A9
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 09 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
IAPOA NO.: PLACE: PLACE: CHECKED BY: Date :
CONSTRUCTION NOTES
A. GENERAL C. MASONRY AND CONCRETE BLOCKS

1. THESE NOTES CONTAIN GENERAL INFORMATION AND ARE NOT COMPLETE FOR CONSTRUCTION 1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT NOT TO 12 THK. EXPANSION JOINT
WITH MASTIC FILLER 1-Ø16 VERT. BARS DOWEL TO MATCH
PURPOSES. CONTRACTOR SHALL VERIFY INFORMATION GIVEN HERE WITH THE SPECIFICATIONS EXCEED 80 PCF. FOR LOAD BEARING TYPE, TYPE CONCRETE BLOCKS, A MINIMUM
AND OTHER DOCUMENTS AND BRING ANY CONFLICTS TO THE ATTENTION OF THE ENGINEER COMPRESSIVE STRENGTH f'm = 3.50 MPa (500psi) SHALL BE DEVELOPED. CHB WALL CHB VERT. BARS
BEFORE BEGINNING AFFECTED WORK. THE ENGINEER WILL RESOLVE ANY SUCH CONFLICTS. 2. PROVIDE 1-Ø16 VERTICAL BARS AT CORNERS, INTERSECTIONS, END OF WALLS AND EACH WHERE DEPRESSED
FOR SIZE AND SPACING 300 SLAB OCCURS
2. BEFORE FABRICATION AND/OR CONSTRUCTION ALL DIMENSIONS SHALL BE VERIFIED AND SIDE OF OPENINGS.

(DOWEL)
OF HOR. & VERT. BARS
(TYP.)

DOWEL
COORDINATED WITH ARCHITECTURAL, ELECTRICAL, PLUMBING AND MECHANICAL DRAWINGS. 3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200 MM) ON EACH SIDE OF MASONRY SEE CONSTRUCTION NOTES.

400

400
WALL OPENING. 1-Ø16 VERT. BARS
3. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE METHODS OF CONSTRUCTION, UNLESS SO STATED. 4. WALL REINFORCEMENTS SHALL BE AS FOLLOWS.

250
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PROTECT THE STRUCTURES,
WALL THICKNESS VERTICAL REINFORCEMENT HORIZONTAL REINFORCEMENT FOR SIZE AND SPACING
ADJACENT PROPERTY, WORKMEN AND OTHER PERSONS DURING ALL PHASES OF CONSTRUCTION. OF HOR. & VERT. BARS
6 IN. (150 MM) Ø12 @ 600 MM Ø10 @ 600 MM SEE CONSTRUCTION NOTES. 6-Ø10 BARS (AS SHOWN)
4. THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACING AND SHORING FOR ALL
4 IN. (100 MM) Ø12 @ 600 MM Ø10 @ 600 MM OPENING OR END WALL Ø10 BOTT. BARS @300 O.C.
STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE STABILITY DURING ALL PHASES CHB WALL 400
OF CONSTRUCTION. 5. REINFORCING BARS SHALL BE LAPPED A MINIMUM OF 30 BAR DIAMETERS WHERE SPLICE
DOWELS FROM FOOTING OR SLABS SHALL EXTEND INTO THE BLOCK WALL A MINIMUM OF
5. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
30 BAR DIAMETERS. REBARS TO BE PROPERLY TIED W/ G.I. WIRE. CORNER WALL
B. CONCRETE & REINFORCEMENT D. FOUNDATION

1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING CODE OF 1. FOUNDATION DESIGN WAS BASED ON ASSUMED ALLOWABLE SOIL BEARING CAPACITY CHB WALL R.C. COLUMN OR WALL
AMERICAN CONCRETE INSTITUTE (ACI-318). OF 4150 PSF (200 KPa). THE CONTRACTOR SHALL VERIFY SOIL CONDITION AT SITE & SHALL
DOWEL TO MATCH
NOTIFY STRUCTURAL ENGINEER IF ACTUAL SOIL PROPERTY APPEARS WEAKER TO THAT ASSUMED. 1-Ø16 VERT. BARS DOWEL BARS TO MATCH
2. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY CHB VERT. BARS
CHB HOR. BARS
EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMPS AS FOLLOWS. 2. FOUNDATION SHALL REST ON NATURAL SOIL UNLESS OTHER WISE NOTED BY THE ENGINEER.
12 THK. EXPANSION JOINT
NO PART OF FOUNDATION SHALL REST ON FILL. 12 THK. EXPANSION JOINT 300
WITH MASTIC FILLER
LOCATION 28 DAYS STRENGTH MAX. SIZE AGGREGATE MAX. SLUMP WITH MASTIC FILLER
3. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION HAVE BEEN COMPLETED (TYP.)

DOWEL
(CRASHED ROCK)

400
FOUNDATION AND PRIOR TO CONCRETING TO CONFIRM THE DESIGN SOIL BEARING CAPACITY.
3000 PSI (20.7 MPa) 3/4 IN. (19 MM) 4 IN. (100 MM)
E. LAP SPLICE AND HOOKS FIN. FLR. LVL.

(DOWEL)
COLUMNS 3000 PSI (20.7 MPa) 3/4 IN. (19 MM) 4 IN. (100 MM)

250
400
1. ALL BARS FOR BEAMS AND COLUMNS SHALL BE LAPPED WITH A LENGTH OF 50XBAR DIAMETER.
SUSPENDED BEAMS & SLABS 3000 PSI (20.7 MPa) 3/4 IN. (19 MM) 4 IN. (100 MM) FOR SIZE AND SPACING
2. ALL BARS FOR SUSPENDED SLAB SHALL BE LAPPED WITH A LENGTH OF 40XBAR DIAMETER.
OF HOR. & VERT. BARS 6-Ø10 BARS (AS SHOWN)
SLAB ON GRADE 3000 PSI (20.7 MPa) 3/4 IN. (19 MM) 4 IN. (100 MM) 400
3. NO MORE THAN 50% OF THE BARS SHALL BE SPLICED WITHIN THE REQUIRED LAP LENGTH. SEE CONSTRUCTION NOTES. Ø10 BOTT. BARS @300 O.C.
(DOWEL) 400
ALL OTHERS 3000 PSI (20.7 MPa) 3/4 IN. (19 MM) 4 IN. (100 MM) 4. 90° HOOKS WITH 12 X BAR DIAMETER EXTENSION (SPECIFICALLY FOR BEAMS) SHALL BE
3. ALL REINFORCING BARS SHALL CONFORM TO ASTM SPECS GRADE 40 (275 MPa) FOR 12Ø & SMALLER BARS ANCHORED INTO THE FAR-FACE OF THE COLUMN.
INTERSECTION WALL INTERSECTING R.C. COL. OR WALL
AND GRADE 40 (275 MPa) FOR 16Ø TO 25Ø BARS.
F. STANDARD CONSTRUCTION DETAILS
4. IN GENERAL THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING TYPICAL CONNECTION DETAIL OF MASONRY WALL TYPICAL CHB FOOTING DETAILS
REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS OTHERWISE SHOWN MAIN REINFORCEMENT H ( WHERE APPLICABLE )
OR NOTED.

t OR 1/4 D
CROSS-TIE HOOPS
5. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS.

t
SLEEVES FOR UTILITY
SUSPENDED SLABS

350mm. MAX.
3/4 IN. (19 MM) PIPES MAX. 1/5 D
SLAB ON GRADE 1 1/2 IN. (38 MM) D
WALLS ABOVE GRADE 1 IN. (25 MM) FOR SIZE AND SPACING

H
10
BEAM STIRRUPS AND COLUMN TIES 1 1/2 IN. (38 MM) PROVIDE 3-Ø10 EXTRA STIRR. OF HOR. & VERT. BARS

d
EACH SIDE OF SLEEVES

m
WHERE CONCRETE IS EXPOSED TO SEE CONSTRUCTION NOTES

in
TYP. DET. FOR SLEEVES

(DOWEL)
EARTH BUT POURED AGAINST FORMS 2 IN. (50 MM) THRU CONCRETE BEAM
WHERE CONCRETE IS DEPOSITED DOWEL BARS TO MATCH

400
DIRECTLY AGAINST EARTH FAR FACE OF COLUMN CHB VERT. BARS
3 IN. (75 MM)
6. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE WITH REGARDS TO PLACING JOINT HOOP SPACE @ "2Sh" WHEN 2-Ø12 TOP BARS

(HOOPS)
W/ TABLE 1 (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWN THERE ARE BEAMS HAVING WIDTH OF

200
OF BEAM REINFORCEMENT.

D
ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. AT LEAST ONE-HALF THE COLUMN 2-Ø12 BOTT. BARS
7. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED & WIDTH & DEPTHS NOT LESS THAN Ø12x1000 LONG AT

JOINT REINF.
(HOOPS)
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. THREE QUARTERS OF THE DEEPEST MID-DEPTH OF SLAB
LAP SPLICE LENGTH: SECTION
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, BEAM THAT FRAME INTO FOUR AT EACH CORNER
AT ANY LEVEL NO MORE THAN
H (CLEAR HEIGHT OF COL.)

EQUIPMENT'S AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, SIDES OF THE COLUMN. ALL OTHER
ALTERNATE BARS SHOULD BE 1-Ø12 TOP &
ELECTRICAL, AND MECHANICAL DRAWINGS.

(HOOPS)
CONDITIONS USE HOOPS @ "Sh" CENTERS. 200 (MIN) 200 (MIN)
SPLICED. MIN. DISTANCE BET. BOTT. BARS

D
9. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS
TWO ADJACENT BARS SPLICES
IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP FOG SPRAYING, CURING
COMPOUNDS OR OTHER APPROVED METHODS. SHALL BE 600mm.

COLUMN TIES AS
Ø10 STIRRUPS
WITHIN CENTER

400
10. STRIPPING OF FORMS AND SHORES: L FOR COL. BAR SPLICES SEE TABLE @ 150 O.C.
HALF OF "H"

FOUNDATION 24 HRS. OF MIN. LAP SPLICE LENGTH OF


SUSPENDED SLAB EXCEPT WHEN L/4
COLUMN REINFORCEMENT
ADDITIONAL LOADS ARE IMPOSED 8 DAYS CHB WALL SLAB 38mm
TOP BARS @ SUPPORT (CONT.)
OPENING CLEAR
WALLS 18 HRS. (SEE COLUMN DETAILS FOR
REQ'D. BOTT. BARS @ SUPPORT

(HOOPS)
BEAMS 14 DAYS HOOPS AND TIES SPACING)
OPENING

D
1-Ø16 VERT.
11. DEVELOPMENT LENGTH (Ld) OF REINFORCING STEEL BARS SHALL BE AS FOLLOWS:
JT. REINF.

BARS TYPICAL

400
SIZE OF BARS (mm) DEVELOPMENT LENGTH (mm)

JOINT REINF.
10 375 (HOOPS) ALL CONCRETE REINF. DETAIL SHOULD
CONF. REINF. TIES LAT. TIES

12 440 BE DONE IN ACCORDANCE WITH ACI IN TWO WAY SLAB EXTEND


16 590 DETAILING MANUAL 1980 PUB-66. FIN. FLR. LVL. BARS UP TO BEAM SUPPORT
20 BOTTOM BARS
730 0.165L SPLICE
(HOOPS)

AT MID SPAN
25 920 OMIT TRIMMER BARS WHERE
D

28 0.22L EXTRA TOP BARS OPENING IS FRAMED BY BEAM


1030 ELEVATION
@ SUPPORT
32 1170
IF THE DEPTH OF CONCRETE CAST IN ONE LIFT BENEATH THE BARS EXCEEDS TYP. DETAIL OF COL. LAP SPLICE TYPICAL COLUMN ELEV. SHOWING TYP. DET. OF LINTEL BEAM AT CHB WALL OPENING TYP. SLAB OPENING DET.
300 mm, INCREASE THE ABOVE LENGTHS BY 1.40. & EXT. GIRDER TO COL. CONNECT. DOWELS AND TIES SPACING

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
CONSTRUCTION NOTES Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING CONSTRUCTION DETAILS
S1
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 10 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
A' A B C D E F G H I J K
28.85m
12.35m 11.03m 5.47m
2.05m 3.60m 3.63m 3.07m 3.60m 2.70m 4.73m

C2F2 C2F2 C2F2 C2F2


SC FTB FTB FTB
1

3.44m
WF-1

FTB
FTB
FTB
5.50m

S-1 S-1
C2F2 C2F2 C1F1 C1F1
SC WF-1 SC WF-1 FTB FTB FTB
2 BED BARS
SPACED @

FTB

FTB
60CM B.W. O.C.

C2F2 C1F1 C2F2 C1F1


SC FTB FTB FTB FTB
3

FTB
FTB

5.35m
S-1 S-1 S-1
3.19m
14.40m

WF-1
FTB

FTB

7.76m
S-1

FTB

16.20m
C1F1 C2F2 C1F1 C1F1
SC WF-1 SC FTB FTB FTB FTB
4
0.76m

SC
WF-1

FTB
FTB
2.51m

FTB
8.90m

WF-1

2.41m
FTB

S-1
1.75m

C2F2 C1F1 C2F2 C1F1 C1F2 C1F1 C1F1 C2F2


FTB FTB FTB FTB FTB SC FTB FTB
5 S-1 S-1 S-1 S-1

WF-1

FTB
FTB
3.20m

FTB

WF-1
FTB

FTB
WF-1 WF-1

5.00m
FTB

FTB
S-1 S-1 S-1
C2F2 C2F2 C2F2 C2F2 C2F2
WF-1
6 FTB FTB FTB

WF-1
FTB

C2F2 C2F2 C2F2 C2F2


FTB
7 1.54m 1.96m
FTB FTB

3.60m 3.20m 3.50m 3.60m 2.70m 2.10m 2.63m 5.47m


13.90m 12.90m
26.80m

01 F O U N D A T I O N L A Y O U T P L A N
S-02 S-08 SCALE 1:70

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
FOUNDATION LAYOUT PLAN Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
S2
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 11 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
SCHEDULE OF FOOTINGS SCHEDULE OF COLUMNS
DIMENSION DEPTH REINFORCEMENTS
MARK REINFORCEMENT REMARKS MARK DIMENSION
X (mm) Y (mm) t (mm) d (mm)
VERTICAL BARS TIES

F1 1000 1000 250 8-16mm R.BARS B.W. 1500 ISOLATED C1 200mm X 300mm 8 - 16 mm Ø 10 mm Ø spaced @ 4-50mm, 4-100mm, 4-150mm, REST 200mm O.C

F2 800 800 250 6-12mm R.BARS B.W. 1200 ISOLATED C2 200mm X 300mm 4 - 16 mm Ø 10 mm Ø spaced @ 4-50mm, 4-100mm, 4-150mm, REST 200mm O.C

SC-1 150mm x 150mm 4 - 12 mm Ø 10 mm Ø spaced @ 200mm O.C. EQUALLY

SCHEDULE OF BEAMS
C1 C2 SC
DIMENSION (mm) REINFORCEMENTS
MARK

GROUND FLOOR

GROUND FLOOR

GROUND FLOOR
DEPTH WIDTH LOC. SUPPORTS MIDSPAN STIRRUPS

ROOF BEAM

ROOF BEAM

ROOF BEAM
TOP 2 - 12mm 2 - 12mm

TO

TO

TO
RB 300 200 10mm DRB SPACED @ 150mm O.C. EQUALLY
BOTTOM 2 - 12mm 2 - 12mm

TOP 2 - 12mm 2 - 12mm


FTB 300 200 10mm DRB SPACED @ 200mm O.C. EQUALLY
BOTTOM 2 - 12mm 2 - 12mm
SECTION 200 X 300 SECTION 200 X 300 SECTION 150 X 150
VERT. BARS 8 - 16MM Ø VERT. BARS 4 - 16MM Ø VERT. BARS 4 - 12MM Ø
COLUMN 1 SET 10MM Ø COLUMN 1 SET 10MM Ø COLUMN 1 SET 10MM Ø
CL CL CL
TIES 4 @50, 4 @100, 4 @150, REST @ 200 TIES 4 @50, 4 @100, 4 @150, REST @ 200 TIES @ 200mm O.C. EQUALLY
JOINT TIES 10MM Ø @ 100MM O.C. JOINT TIES 10MM Ø @ 100MM O.C. JOINT TIES 10MM Ø @ 100MM O.C.
.200

CENTERLINE OF
COLUMN
Y BARS
COLUMN

50mm COVER

.300
EXTERIOR INTERIOR INTERIOR CENTERLINE OF
COLUMN COLUMN COLUMN COLUMN
SUPPORT SUPPORT SUPPORT
X BARS
03 TYPICAL BEAM CROSS SECTION
S-03 S-08 SCALE 1:10

01 T Y P I C A L B E A M D E T A I L S 10mmØ VERTICAL
S-03 S-08 SCALE NTS
BAR SP. @ 0.60m
1" THK. PLASTER
WITH SMOOTH 05 TYPICAL FOOTING PLAN
10MM THK. 100MM THK SLAB ON FINISH S-03 S-08 SCALE 1:10

COMPACTED GRADE W/ 10MM Ø REBAR


GRAVEL BASE SP. @ 400MM O.C. B.W. FIN. FLOOR LINE

SEE COLUMN DETAIL &


SCHEDULES

.400 .400
FOOTING REINF. (VARIES)

FIN. FLOOR LINE 10mmØ HOR. BAR IN


EVERY 3 LAYERS OF CHB 4" THK.
.100

GRAVEL BASE
.200

12mmØ BOTTOM
.100

GRAVEL BASE BARS SP. @


FIN. GRADE LINE 300mm O.C.

3 - 10mmØ 4" THK. GRAVEL BASE


BOTTOM BARS 100 mm THK.
GRAVEL BASE

04 WALL FOOTING SECTION 06 TYPICAL FOOTING SECTION


S-03 S-08 SCALE NTS S-03 S-08 SCALE 1:10
02 S L A B O N F I L L D E T A I L S
S-03 S-08 SCALE NTS
GENERAL NOTES: A.) USE GRADE 33 REBARS A.) USE GRADE 33 REBARS
B.) USE 3000 PSI CONCRETE B.) USE 3000 PSI CONCRETE

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
SCHEDULE OF FOOTINGS Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
SCHEDULE OF COLUMNS
SCHEDULE OF BEAMS
TYPICAL BEAM DETAILS
S3
LOCATION MR. FRANCIS J T. ESCOBILLO SLAB ON FILL DETAILS
REG. NO.: P.T.R. NO.: TYP. BEAM CROSS SECTION REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH WALL FOOTING SECTION
TYP. FOOTING PLAN T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 12 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: TYP. FOOTING SECTION PLACE: CHECKED BY: Date :
A' A B C D E F G H I J K
28.85m
12.35m 11.03m 5.47m

RB-1 RB-1 RB-1 RB-1


1

3.44m
RB-1

RB-1

RB-1
5.50m

RB-1
RB-1 RB-1 RB-1
2

RB-1

RB-1

RB-1
RB-1 RB-1 RB-1 RB-1
3

5.35m
RB-1

RB-1

RB-1
3.19m

RB-1

7.76m
16.20m

16.20m
RB-1 RB-1 RB-1 RB-1 RB-1
4

12.76m
2.51m
8.90m

2.41m
RB-1

RB-1

RB-1

RB-1

RB-1

RB-1
RB-1 RB-1 RB-1 RB-1
5
3.20m

RB-1

RB-1

RB-1

RB-1

RB-1

5.00m
5.00m
RB-1

RB-1
RB-1
6 RB-1 RB-1 RB-1 RB-1
1.80m

7 RB-1 RB-1 RB-1

3.60m 3.20m 3.50m 3.60m 4.80m 2.63m 5.47m


2.05m 13.90m 12.90m
28.85m

01 R O O F B E A M L A Y O U T
S-04 S-08 SCALE 1:70

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ROOF BEAM LAYOUT Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
S4
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 13 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
A' A B C D E F G H I J
24.73m
10.30m 14.43m
1.50m 5.17m 3.62m 1.56m 3.59m 3.73m 4.00m 1.55m

ROOF - B LINE

1.45m
2.24m

2 GIRT GIRT GIRT


1.47m

3 GIRT GIRT

HT-3

HT-3

HT-3
11.62m

11.62m
HT-1

HT-1

HT-2
5.45m

10.17m
8.54m

GIRT GIRT GIRT GIRT GIRT


5
1.62m

GUTTER GUTTER
0.83m

GUTTER

6
ROOF - C LINE
1.50m 5.17m 5.19m 2.54m 1.05m 3.72m 4.00m 1.55m
7 14.40m 10.33m
24.73m

01 R O O F F R A M I N G L A Y O U T - A
S-05 S-08 SCALE 1:70

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ROOF FRAMING LAYOUT - "A" Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
S5
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 14 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
A' A B C D E F G H I J K
27.36m
14.56m 12.80m
1.00m 3.00m 2.58m 3.70m 3.22m 1.05m 3.98m 3.00m 3.00m 2.82m

2"x3" G.I. CEE PURLINS

1 GIRT GIRT GIRT GIRT

4.48m
ROOF -B

HT-7
HT-6

2.50m
HT-7

HT-7

HT-7
HT-5

HT-5
HT-4

HT-5
8
T-
7.68m

H m
77
3.
2 HT-7

3.00m
3

10.21m
HT-7
16.60m

3.00m
3.54m

4
HT-7

1.71m
5
5.38m

HT-9

HT-9

HT-9

HT-9

HT-9
ROOF -C

ROOF - E LINE
GIRT GIRT GIRT
6

1.00m
7
2"x3" G.I. CEE PURLINS

0.95m 3.00m 3.00m 3.00m 1.60m


11.55m ROOF - F LINE

01 ROOF FRAMING LAYOUT - B&C


S-06 S-08 SCALE 1:70

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ROOF FRAMING LAYOUT B Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
ROOF FRAMING LAYOUT C
S6
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 15 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
0.05m
2" X 3" X 2MM THK.
0.60m
STONE SHINGLES ON G22 RECTANGULAR TUBE 2"x3" G.I. CEE PURLINS SP. @ 600MM O.C.
0.24m
PLAIN SHEET 8.78m

2" X 2" X 1.5MM 2" X 3" X 2MM THK. CEE

0.59m
ANGLE BAR, CLEATS PURLINS

2.13m

HT-10

HT-10

HT-10
6.23m

6.23m
0.03m
0.10m
0.18m

4.10m
0.28m
0.14m
GIRT GIRT
GUTTER GUTTER

4.36m 6.04m 3.28m 1.13m

3" DIA PVC PIPE 02 ROOF FRAMING LAYOUT - D


DOWNSPOUT 3" DIA. DOME ROOF DRAIN S-07 S-08
S-07 SCALE 1:50

6.65m
2.83m 2.78m 1.05m
2"x3"
G.I. CEE PURLINS SP.
@ 600MM O.C.
01 GUTTER INSTALLATION DETAILS
S-07 S-07
S-08 SCALE 1:6
3.40m

1.05m
GIRT GIRT

2"x4" RECTANGULAR
STEEL TUBE RAFTERS

HT-11

HT-11

5.18m

7.28m
2.36m

2"x4" RECTANGULAR
STEEL TUBE RAFTERS
GUTTER

4.72m

GIRT GIRT
2.36m

1.05m
GUTTER

04 ROOF FRAMING LAYOUT - E


4.54m S-07 S-08 SCALE 1:50
2"x4" RECTANGULAR
STEEL TUBE RAFTERS

03 ROOF FRAMING LAYOUT - F


S-07 S-08 SCALE 1:50

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ROOF FRAMING LAYOUT- "D" Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
ROOF FRAMING LAYOUT- "E"
ROOF FRAMING LAYOUT- "F" S7
MR. FRANCIS J T. ESCOBILLO GIRT DETAIL
LOCATION GUTTER INSTALLATION DETAILS
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 16 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
2"X2"X4MM ANGLE BAR WEB
2"X2"X6MM ANGLE BAR
2"X2"X4MM ANGLE BAR WEB 2"X2"X6MM ANGLE BAR TOP AND BOT CHORD
1.50m
TOP AND BOT CHORD 1.50m 1.00m 2"X2"X4MM ANGLE BAR WEB
1.37m 8.47m 1.00m
1.00m 10.75m 2"X2"X6MM ANGLE BAR
1.37m 1.00m
1.00m
1.37m
1.37m
1.00m
1.00m
TOP AND BOT CHORD
1.00m 1.48m
1.50m 0.97m 11.50m
1.50m 0.97m
0.97m
0.97m
0.97m
0.95m
0.97m

2.22m
0.99m
2.01m

2.00m

1.52m

1.24m
1.50m

0.54m
1.36m 1.36m 1.36m 1.36m 0.96m 0.96m 0.96m 0.96m 0.96m 0.94m 0.96m 0.98m
0.99m 0.99m 0.99m 0.99m 0.99m 0.99m 0.99m 0.99m
5.45m 7.68m 7.92m

02 HALF TRUSS - 1 (2 SETS) 02 HALF TRUSS - 2 (1 SET) 03 HALF TRUSS - 3 (3 SET)


S-05 S-08
S-08 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50

2"X2"X4MM ANGLE 2"X2"X6MM ANGLE BAR 2"X2"X4MM ANGLE


2"X2"X4MM ANGLE 2"X2"X6MM ANGLE BAR 2"X2"X6MM ANGLE BAR
BAR WEB TOP AND BOT CHORD BAR WEB
BAR WEB TOP AND BOT CHORD TOP AND BOT CHORD
7.68m 0.97m
1.43m 4.50m
1.43m 6.71m
1.43m 1.43m
1.43m 1.43m 1.16m
0.99m 1.43m 1.16m
0.99m
1.43m 0.99m 2.19m

1.09m

1.09m
0.66m

0.66m
0.66m
1.42m 1.43m 1.43m 1.43m
1.42m 1.42m 1.43m 1.43m 1.19m 1.16m 1.16m
5.70m
5.70m 3.51m

04 HALF TRUSS - 4 (1 SETS) 05 HALF TRUSS - 5 (3 SETS) 06 HALF TRUSS - 6 (1 SETS)


S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50

2"X2"X4MM ANGLE 2"X2"X6MM ANGLE BAR


BAR WEB TOP AND BOT CHORD
2"X2"X4MM ANGLE
2"X2"X6MM ANGLE BAR 2"X2"X4MM ANGLE
BAR WEB 2"X2"X6MM ANGLE BAR
TOP AND BOT CHORD BAR WEB
TOP AND BOT CHORD
2.50m 3.78m
0.87m 4.40m
0.75m 0.75m 0.92m 0.87m
1.00m 0.93m 0.92m 0.87m
1.00m 0.87m 0.91m

0.81m
0.88m
0.78m

0.50m
0.66m

0.66m
0.86m 0.86m 0.86m 0.86m
0.75m 0.75m 0.93m 0.92m 0.92m 3.45m
1.50m 2.77m

07 HALF TRUSS - 7 (7 SETS) 08 HALF TRUSS - 8 (1 SETS) 09 HALF TRUSS - 9 (5 SETS)


S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50

2 - 2" x 2" x 3mm THK. 2" x 2" x 2.5mm THK.


2"X2"X4MM ANGLE 2 - 2" x 2" x 3mm THK. ANGLE BAR FOR ANGLE BAR FOR TOP ANGLE BAR FOR
2"X2"X4MM ANGLE BAR WEB AND BOTTOM CORD BRACES
2"X2"X6MM ANGLE BAR TOP AND BOTTOM CORD
BAR WEB 5.99m TOP AND BOT CHORD
1.25m
1.25m
1.25m 5.20m

VERIFY ON ACTUAL
1.25m 0.65m
0.99m
0.65m 0.65m
0.65m 0.65m
0.65m 0.65m
0.65m
1.44m

0.99m

0.97m
0.49m

〜0.60m 〜0.60m 〜0.60m 〜0.60m


VERIFY ON ACTUAL
1.25m 1.25m 1.25m 1.25m 0.65m 0.65m 0.65m 0.65m 0.65m 0.65m 0.65m 0.65m
5.00m 5.20m

HALF TRUSS - 8 (HT-8)

10 HALF TRUSS- 10 (3 SETS) 11 H A LF TR U SS - 1 1 ( 2 S ET S) 12 T Y P . G I R T D E T A I L


S-08 S-08
S-05 SCALE 1:50 S-08 S-08
S-05 SCALE 1:50 S-08 S-08 SCALE 1:50

CIVIL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
HALF TRUSS DETAIL Date Remarks
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
S8
LOCATION MR. FRANCIS J T. ESCOBILLO
REG. NO.: P.T.R. NO.: REG. NO.: P.T.R. NO.:
HKARCHIANDENGGSERVICES@GMAIL.COM
T.I.N. NO.: DATE:
LOWER LAMBAYONG, TAMPAKAN, SOUTH
T.I.N. NO.: DATE : DESIGN BY: ACAD by : O. Gepte 17 24
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: PLACE: CHECKED BY: Date :
3" DIA. PVC PIPE SERIES 1000

3" DIA. PVC PIPE SERIES 1000 3" DIA. PVC PIPE SERIES 1000

3" DIA. PVC PIPE SERIES 1000


G
U
3" DIA. PVC PIPE SERIES 1000
G

T
U
U

T
T
T

E
T

3" DIA. PVC PIPE SERIES 1000


R
R
E
R

G U T T E R
3" DIA. PVC PIPE SERIES 1000
G

G
U

3" DIA. PVC PIPE SERIES 1000


U
T

T
T

3" DIA. PVC PIPE SERIES 1000

T
E

E
R

R LEGEND

MARK DESCRIPTION MARK DESCRIPTION MARK DESCRIPTION MARK DESCRIPTION


G
U
T
T
E

M
R

00
10
S
IE
ER
S
E
P IP
C
PV
I A.
D
3"

MASTER PLUMBER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
STORM DRAINAGE PLAN
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING GENERAL CONDITIONS
INSTALLATION P1
MR. FRANCIS J T. ESCOBILLO PLUMBING NOTES
LOCATION
LEGEND
HKARCHIANDENGGSERVICES@GMAIL.COM LOWER LAMBAYONG, TAMPAKAN, SOUTH
DATE:
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE:
M

2" DIA. PVC PIPE SERIES 800, VSTR


2" DIA. PVC PIPE SERIES 800, VSTR

2" DIA. PVC PIPE SERIES 800


2" DIA. PVC PIPE SERIES 800

2" DIA. PVC PIPE SERIES 800, SVTR


2" DIA. PVC PIPE SERIES 800, SVTR
2"
D IA.
PV
CP
IPE
SE

2" DIA. PVC PIPE SERIES 800, SVTR


RIE
S8
00

2" DIA. PVC PIPE SERIES 800

MASTER PLUMBER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ENGINEERING SERVICES SANITARY DRAINAGE LAYOUT
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
SANITARY DRAINAGE ISOMETRIC P2
MR. FRANCIS J T. ESCOBILLO LAYOUT
LOCATION

HKARCHIANDENGGSERVICES@GMAIL.COM LOWER LAMBAYONG, TAMPAKAN, SOUTH


DATE:
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE:
" DIA. PN20 PPR PIPE
4
3
E
3
4 " DIA. PN20 PPR PIPE

P
I
P
R
P

LUPON, DAVAO ORIENTAL


P

+63930-566-1663 | 09303832711
0
1 /2 " DIA. PN20 PPR PI PE
" DIA. PN20 PPR PIPE

2
4
3

ENGINEERING SERVICES

HKARCHIANDENGGSERVICES@GMAIL.COM
HK ARCHITECTURAL AND
P
.
3
" DIA. PN20 PPR PIPE

A
4

" DIA. PN20 PPR PIPE


3
4
3

I
4 " D I A . P N 2 0 P P R P I P E
E

1 /2 " DIA. PN20 PPR PI PE

D
P
I

"
P

3
4
R
P
P
0
2
N

DATE:
P

PLACE:
MASTER PLUMBER
.

3
4 " D I A . P N 2 0 P P R P I P E
A
I
D
"
3
4

3
4 " DIA. PN20 PPR PIPE
" DIA. PN20 PPR PIPE
3
4

1
2" DIA. PN20 PPR PIPE

LOCATION

COTABATO
PROJECT TITLE
1
2" DIA. PN20 PPR PIPE

1
2" DIA. PN20 PPR PIPE
M

1
2" DIA. PN20 PPR PIPE

1
2" DIA. PN20 PPR PIPE
1
2" DIA. PN20 PPR PIPE
1 " D I A . P N 2 0 P P R P I P E

LOWER LAMBAYONG, TAMPAKAN, SOUTH


PROPOSED TWO-STOREY RESIDENTIAL BUILDING
OWNER
1
2" DIA. PN20 PPR PIPE

1
2" DIA. PN20 PPR PIPE
1
2" DIA. PN20 PPR PIPE

MR. FRANCIS J T. ESCOBILLO


LAYOUT
1
2" DIA. PN20 PPR PIPE
1
2" DIA. PN20 PPR PIPE
1
2" DIA. PN20 PPR PIPE
SHEET CONTENT
WATER DISTRIBUTION LAYOUT

WATER DISTRIBUTION ISOMETRIC

1
2" DIA. PN20 PPR PIPE
M
M

REPUBLIC ACT 9266, ARTICLE IV, SECTION 33


REVISIONS

P3
SHEET NO.
MASTER PLUMBER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
ENGINEERING SERVICES SEPTIC VAULT DETAILS
PROPOSED TWO-STOREY RESIDENTIAL BUILDING CATCH BASIN DETAILS
SYSTEM CALCULATION P4
LOCATION MR. FRANCIS J T. ESCOBILLO

HKARCHIANDENGGSERVICES@GMAIL.COM LOWER LAMBAYONG, TAMPAKAN, SOUTH


DATE:
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE:
GENERALNOTESANDSPECIFICATION C
R
ICU
TI DESCR
P
IT
O
IN X
U
T
R
E
SIF B
RE
AK
ER
A
NT
G
I NOO
.F E
ZS
IR
W
EI E
ZS
IC
O
T
ND
U
I KAIC
NO. Q
Y
T
. V
O
T
L AV
- A
N
M
G
R
A
P
EIT
R
E N
G
R
A
C
IT
B POLES
2-3.5 MM. SQ. THHN WIRE (LINE)
1.0 ALL ELECTRICAL INSTALLATION HEREIN AND OTHER RELATED WORK TO BE 1 LIGHTING OUTLET 20 220 2000 9.09 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
DONE ON THIS BUILDING SHALL CONFORM IN ACCORDANCE WITH THE 2 LIGHTING OUTLET 13 220 1300 5.91 20 AMP 2
2-3.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
PROVISIONS AND CODE STANDARD OF THE FOLLOWING: 2-3.5 MM. SQ. THHN WIRE (LINE)
3 LIGHTING OUTLET 20 220 2000 9.09 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
2-3.5 MM. SQ. THHN WIRE (LINE)
1.1 LATEST EDITION OF PHILIPPINE ELECTRICAL CODE (PEC/NEC) 4 LIGHTING OUTLET 25 220 2500 11.36 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10

1.2 REPUBLIC ACT 7920 OTHERWISE KNOWN AS NEW ELECTRICAL 5 LIGHTING OUTLET 12 220 1200 5.45 20 AMP 2
2-3.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10 COMPUTATION OF LOADS
ENGINEERING LAW 6 LIGHTING OUTLET 20 220 2000 9.09 20 AMP 2
2-3.5 MM. SQ. THHN WIRE (LINE)
20 MM. DIA. PVC PIPE 10
1-2.0 MM. SQ. THHN WIRE (GROUND)
1.3 NATIONAL BUILDING CODE
7 ACU OUTLET 1 HP 1 220 920 4.18 30 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
20 MM. DIA. PVC PIPE 10
Load Computation PB
1.4 FIRE CODE OF THE PHILIPPINES 1-2.0 MM. SQ. THHN WIRE (GROUND)

1.5 EXISTING LOCAL UTILITY COMPANY 8 ACU OUTLET 1 HP 1 220 920 4.18 30 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10 It = 156.27 +(10x0.25) = 158.77 Amps.
1.6 EXISTING CITY/ MUNICIPALITY ORDINANCE, AND THE 9 ACU OUTLET 1 HP 1 220 920 4.18 30 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
20 MM. DIA. PVC PIPE 10
1.7 REQUIREMENTS OF THE BUREAU OF LABOR STANDARDS
1-2.0 MM. SQ. THHN WIRE (GROUND)
2-5.5 MM. SQ. THHN WIRE (LINE)
Use 2-60mmsq THW wire + 1- 14 mmsq TW wire in a 40 mm dia. RMC pipe
10 ACU OUTLET 1 HP 1 220 920 4.18 30 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10

2.0 ELECTRICAL INSTALLATION HEREIN SHALL BE DONE UNDER THE DIRECT 11 CABLE TV 1 220 180 0.82 20 AMP 2
2-3.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
175 AT MCCB, 2P, 240V
2-3.5 MM. SQ. THHN WIRE (LINE)
SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. THE 12 CONVENIENCE OUTLET 9 220 1620 7.36 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
ELECTRICAL ENGINEER SHALL BE RESPONSIBLE IN INTERPRETATION OF THE 13 ACU OUTLET 1 HP 1 220 920 4.18 30 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
20 MM. DIA. PVC PIPE 10
COMPUTATION OF LOADS MAIN FEEDER LINE
1-2.0 MM. SQ. THHN WIRE (GROUND)
DESIGN INTENT, PLANS AND SPECIFICATIONS AND THE REQUIRED STANDARD
OF ELECTRICAL CODE. 14 RANGE 1 220 2500 11.36 30 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10 It = 156.27+113.27 +(12x0.25) = 218.03 at 0.8 d.f. Amps.
2-5.5 MM. SQ. THHN WIRE (LINE)
15 RANGE 1 220 2500 11.36 30 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
Use 2-125mmsq THW wire + 1- 22 mmsq TW wire in a 65 mm dia. RMC pipe
3.0 AS REQUIRED BY NEW ELECTRICAL ENGINEERING LAW (RA 7920) FOR 200A 16 REF 1 220 1500 6.82 20 AMP 2
2-5.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
MAIN AND ABOVE CAPACITY, CONTRACTOR SHALL HAVE PCAB LICENSE WITH
8 1440 6.55
2-3.5 MM. SQ. THHN WIRE (LINE) 225 AT MCCB, 2P, 240V
17 CONVENIENCE OUTLET 220 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
SPECIALTY IN ELECTRICAL WORKS (S-EE) CATEGORY.
2-3.5 MM. SQ. THHN WIRE (LINE)
18 CONVENIENCE OUTLET 8 220 1440 6.55 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
4.0 SERVICE ENTRANCE TO THE BUILDING SHALL BE THREE PHASE (3Ø), 4-WIRE, 19 SPARE 20 AMP 2
2-3.5 MM. SQ. THHN WIRE (LINE)
1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
60HZ, 230V, THROUGH TRANSFORMER BANK. IF TO BE AIR CONDITIONED. 2-3.5 MM. SQ. THHN WIRE (LINE)
20 SPARE 20 AMP 2 1-2.0 MM. SQ. THHN WIRE (GROUND) 20 MM. DIA. PVC PIPE 10
USE : 2- 80mm2 THW COPPER WIRE
4.10 SINGLE PHASE (1P) IF NO A/C.
O
TA
T
L 121
7.1
A IN 50 MM Ø RSC PIPE
PROVIDE: 1- 200 AT/2P, 240V, 60HZ ACB AS MAIN FEEDER PROTECTION
2 COMPUTATION OF LOADS
E-02 E-03 SCALE NTS
5.0 MATERIALS AND EQUIPMENT TO BE USED (BALLAST, FLOURESCENT TUBE,
WIRING DEVICES, CIRCUIT BRAKERS, CONDUIT AND PIPES, ENCLOSURES,
WIRES AND CABLES, ETC.) SHALL HAVE IMPORTED COMMODITY CLEARANCE
(ICC) LABEL FOR FOREIGN MADE PRODUCTS AND P.S. MARK FOR LOCAL IN 1 SCHEDULE OF LOADS
NATURE OF THE BUREAU OF PRODUCT STANDARD (BPS). E-02 E-03 SCALE NTS

6.0 PROVIDE GROUNDING WIRE TO ALL OUTLETS AND LIGHTING CIRCUITS. ALL
FAULT CALCULATION VOLTAGE DROP CALCULATION
NON-CURRENT CARRYING METAL PARTS SHALL BE GROUNDED AND BONDED
INCLUDING FENCE AND GATES.

7.0 ALL PANEL BOARDS, MAIN DISTRIBUTION PANEL, ETC. SHALL HAVE GROUNDING M
BUS FOR BRANCH CIRCUITS AND SUB-FEEDER GROUNDING SYSTEM, MAIN
GROUNDING SYSTEM SHALL BE BONDED TO THE NEAREST METAL WATER PIPE IN
SERVICE.

8.0 MOUNTING HEIGHTS FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL BE AS
FOLLOWS:

8.1 LIGHTING SWITCHES --------------------------------1.4M. ABOVE FLOOR FINISH


8.2 CONVENIENCE OUTLET -----------------------------0.4M. ABOVE FLOOR FINISH
8.3 TERMINAL BOX OF FCU THERMOSTAT ---------1.4M. ABOVE FLOOR FINISH
8.4 TELEPHONE OUTLET --------------------------------0.4M. ABOVE FLOOR FINISH
8.5 PANELBOARDS AND CABINETS ------------------1.4M. ABOVE FLOOR FINISH
8.6 PHOTO ELECTRIC BYPASS SWITCH -------------1.4M. ABOVE FLOOR FINISH
8.7 MOTOR CONTROL AND ECB -----------------------1.4M. ABOVE FLOOR FINISH
8.8 MANUAL TRANSFER SWITCH ----------------------1.4M. ABOVE FLOOR FINISH
8.9 AIR CONDITIONED SWITCH ------------------------1.8M. ABOVE FLOOR FINISH
9.0 WIRING METHOD SHALL BE AS FOLLOWS:

9.1 SERVICE ENTRANCE RISER ----------INTERMEDIATE METALLIC


CONDUIT (IMC)
9.2 SERVICE LATERAL ---------------------POLYVINYL CHLORIDE (PVC)
WITH CONCRETE
ENCASEMENT
9.3 LIGHTING AND POWER SYSTEM ----POLYVINYL CHLORIDE (PVC)
9.4 TELEPHONE SYSTEM ------------------POLYVINYL CHLORIDE (PVC)
9.5 ALL VIBRATING EQUIPMENT --------LIQUIDTIGHT FLEXIBLE METAL
CONDUIT
9.6 JUNCTION BOX TO ---------------------FLEXIBLE CONDUIT (METAL)
LIGHTING FIXTURE

10.0 LIGHTING FIXTURES WITH FLUORESCENT TUBE SHALL HAVE


THERMAL PROTECTOR HIGH-POWER FACTOR BALLAST (PRE-HEAT).

11.0 MECHANICAL EQUIPMENT WITH HIGH VIBRATION MOVEMENTS


SHALL HAVE METAL FLEXIBLE CONDUIT CONNECTION FROM MOTOR
TERMINAL BOX TO OVERCURRENT DEVICE ENCLOSURE (ECB).

12.0 PRIOR TO ITS MOUNTING AND TERMINATION OF LIGHTING


FIXTURES, WIRING DEVICES, EQUIPMENT, ETC. CONTRACTOR WILL
ENGAGE WITH THE CONSULTANT OR OWNER REPRESENTATIVE THE
FOLLOWING FIELD ACCEPTANCE TEST AND MATERIAL INSPECTION:

12.1 BRANCH CIRCUITS AND SUB-FEEDER INSULATION RESISTANCE


TEST MEASUREMENT
12.2 POLARITY TEST ON WIRING DEVICES
12.3 GROUND RESISTANCE TEST MEASUREMENT
12.4 MATERIALS QUALITY INSPECTION AS REQUIRED IN THE ABOVE
SPECIFICATION
12.5 GROUND WILL RESISTANCE TEST MEASUREMENT FOR
LIGHTING SYSTEM

THE FIELD ACCEPTANCE TEST SHALL BE DONE OR PERFORM BY A


QUALIFIED INDEPENDENT TESTING AGENCY.

13.0 NO CHANGE AND MODIFICATION SHALL BE MADE WITHOUT THE


CONSULTANT/ DESIGNER WRITTEN CONSENT.

14.0 ALL WORKS SHALL BE EXECUTED IN A WORKMANSHIP MANNER


AND SHALL PRESENT A NEAT AND ORDERLY ACCEPTANCE. ALL
WIRING SHALL BE CONCEALED AS MUCH AS POSSIBLE.
3 RISER DIAGRAM
E-02 E-03 SCALE NTS

ELECTRICAL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
GENERAL NOTES
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING RISER DIAGRAM

SCHEDULE OF LOADS AND


E1
LOCATION MR. FRANCIS J T. ESCOBILLO
COMPUTATIONS
LOWER LAMBAYONG, TAMPAKAN, SOUTH FAULT AND VOLTAGE DROP
HKARCHIANDENGGSERVICES@GMAIL.COM
+63930-566-1663 | 09303832711
DATE:
COTABATO CALCULATION
LUPON, DAVAO ORIENTAL
PLACE:
6wW
6wD

9wD
9wW

B C B C LS

6
PB
LF

SC1, D1, E1 1
B
C 1
A1 F1
A F1
C1 C1
D1 D1

A1 A1
E1 E E E E
F1 F1
C1 C1 A1 EF
D 1
D 1 SA1,B1 A1 SF1 5
PB
UP

SE GL
Q
1 1
C C Y Y Y
W W T T
SC1, D1, E1 SY

CABINET BELOW
4
PB

U R E

X Q
T V T
C S
O D
P P
W W
O T T R
SW,X ST,U,V Q
SP 2
PB 3
PB E
B SO SQ,R,S

D D Q
N D
D
SN F
CABINET BELOW
N
SM SI SF,G
C SD 1 F
L F SA,B,C PB

F I I G G G
M M SL SI
SK CABINET BELOW

M M K G G G
L
B SL A A
SJ

C B C B J SH
A A G H
G G
H
SF,G F
A A

F F F F

ELECTRICAL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
LIGHTING LAYOUT
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
E2
LOCATION MR. FRANCIS J T. ESCOBILLO

HKARCHIANDENGGSERVICES@GMAIL.COM LOWER LAMBAYONG, TAMPAKAN, SOUTH


DATE:
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE:
6wW
6wD

9wD
9wW
R O O F L I N E

LS

SHELVES
LF

SHO BATH TUB EF

STORAGE
SLIDING CABINET
TABLE

SLIDING CABINET

SHELVES
CABINET

STORAGE
LAV
WC
EF
BAY BENCH

UP
13

TV MODULAR CABINET

OVEN
14 GL

PREP AREA
10 11 SINK
SHELVES

12

ISLAND COUNTER
TV MODULE

TABLE 15

SHELVES
SLIDING CABINET
RANGE
BAY BENCH

PREP AREA
SLIDING CABINET
BED

SHELVES

TV MODULAR CABINET

BREAKFAST NOOK
16

SHELVES
SLIDING CABINET

09 REF

SHELVES SHELVES

17
EF SHELVES
NICHED WALL

WC

SHO LAV
SLIDING CABINET

18
SHELVES

CONSOLE TABLE

PUGON
CABINET
SLIDING CABINET

DOUBLE DECKER
SLIDING CABINET

TABLE

M
0M SHELVES SLIDING CABINET
90
LAV D =1
TABLE
TABLE

08 07 SINK
WC

SHELVES BAY BENCH EF

SHO.

REF
DOUBLE DECKER
WC
EF SHELVES

ELECTRICAL ENGINEER PROJECT TITLE OWNER SHEET CONTENT REPUBLIC ACT 9266, ARTICLE IV, SECTION 33 REVISIONS SHEET NO.
HK ARCHITECTURAL AND
POWER LAYOUT
ENGINEERING SERVICES
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
E3
LOCATION MR. FRANCIS J T. ESCOBILLO

HKARCHIANDENGGSERVICES@GMAIL.COM LOWER LAMBAYONG, TAMPAKAN, SOUTH


DATE:
+63930-566-1663 | 09303832711
LUPON, DAVAO ORIENTAL
COTABATO
PLACE: