IM 01T01B04-01E
IM 01T01B04-01E
3rd Edition
Yokogawa Electric Corporation
Blank Page
CONTENTS
CONTENTS
1. INTRODUCTION
Thank you for purchasing the YN53 electronic pressure IMPORTANT
transmitter.
Indicates that operating the hardware or software
The YN53 Pressure Transmitters are precisely cali- in this manner may damage it or lead to system
brated at the factory before shipment. To ensure correct failure.
and efficient use of the instrument, please read this
manual thoroughly and fully understand how to operate
the instrument before operating it.
1-1 IM 01T01B04-01E
1. INTRODUCTION
• Please confirm that voltages between the power - Reason of force majeure such as fires, earthquakes,
supply and the instrument before connecting the storms/floods, thunder/lightening, or other natural
power cables and that the cables are not powered disasters, or disturbances, riots, warfare, or
before connecting. radioactive contamination.
1-2 IM 01T01B04-01E
2. Checking the Instrument
defects are found, please contact your nearest Figure 2.1 Name Plate Example of JIS Flameproof Type
Yokogawa representative.
Table 2.2 Model and Suffix Codes 2.2 Storage
Model Suffix Codes Description The following precautions must be observed when
YN53 . . . . . . . . . . . . General use type storing the instrument, especially for a long period.
YN53G . . . . . . . . . . . . Flameproof type
Output signal -S. . . . . . . . . . . 4 to 20 mA DC (a) Select a storage area which meets the following
S. . . . . . . . . 5 to 20 kPa conditions:
A. . . . . . . . . 50 to 200 kPa • It is not exposed to rain or water.
B. . . . . . . . . 130 to 500 kPa
C. . . . . . . . . 0.25 to 1 MPa • It suffers minimum vibration and shock.
Capsule
(Span)
D. . . . . . . . . 0.5 to 2 MPa • It has an ambient temperature within the range of
E. . . . . . . . . 1.3 to 5 MPa
F. . . . . . . . . 2.5 to 10 MPa
⫺40 to 100⬚C.
G. . . . . . . . . 5 to 20 MPa (b) When storing the transmitter, repack it as nearly as
H. . . . . . . . . 13 to 50 MPa possible to the way it was packed when delivered
Flange material S. . . . . . . SUS316 stainless steel from the factory.
1. . . . . Rc1/4 female (c) If storing a transmitter that has been used, thor-
2. . . . . Rc1/2 female
Process connection 3. . . . . 1/4NPT female oughly clean the chambers inside the process
4. . . . . 1/2NPT female connector, so that no measured fluid remains in it.
Style code *A . . Style A Also make sure before storing that the amplifier
Option code / See Option codes unit and capsule assembly are securely mounted.
T0202E.EPS
2-1 IM 01T01B04-01E
3. GENERAL SPECIFICATIONS
3. GENERAL SPECIFICATIONS
Span and Range Limits: Exprosion Protected Type:
JIS flameproof type; Ex do IIB+H2 T4X
Measurement Measurement Maximum Note: In case of the ambient temperature exceeds 55⬚C,
Capsule use the heat-resistance cables with maximum
span range overpressure
allowable temperature of 70⬚C or above.
S 5 to 20 kPa 0 to 20 kPa 100 kPa
Mounting:
A 50 to 200 kPa ⫺100 to 200 kPa 400 kPa
2-inch pipe mounting
B 130 to 500 kPa ⫺100 to 500 kPa 1 MPa
Process Connections:
C 0.25 to 1 MPa ⫺0.1 to 1 MPa 2 MPa
Rc 1/4, Rc 1/2, 1/4 NPT, or 1/2 NPT female
D 0.5 to 2 MPa ⫺0.1 to 2 MPa 4 MPa
Electrical Connections:
E 1.3 to 5 MPa ⫺0.1 to 5 MPa 10 MPa
G 1/2 or 1/2 NPT female
F 2.5 to 10 MPa ⫺0.1 to 10 MPa 20 MPa
Bolt Material:
G 5 to 20 MPa ⫺0.1 to 20 MPa 40 MPa
SCM435
H 13 to 50 MPa ⫺0.1 to 50 MPa 75 MPa
T0301E.EPS
Wetted Parts Material:
Output Signal: Diaphragm; SUS316L
Two wire 4 to 20 mA DC output Flange; SUS316
Accuracy: Capsule gasket (O-ring); Fluorinated rubber
A to H capsule: ⫾0.2% of Span Fill Fluid:
S capsule: ⫾0.5% of Span Silicone oil
Repeatability: Amplifier Housing:
⫾0.02% of Span Cast aluminium alloy
Dead band: Polyurethane resin baked finish
⫾0.01% of Span Yellow Green (Munsell 5.0 GY3.6/1.3)
3-1 IM 01T01B04-01E
4 . INSTALLATION
4. INSTALLATION
IMPORTANT
F0401E.EPS
4-1 IM 01T01B04-01E
4 . INSTALLATION
4-2 IM 01T01B04-01E
5. WIRING
5. WIRING
The transmitter requires a DC power source. Connect Mounting flameproof packing adapter body
the wiring as shown in Figure 5.1. to conduit connection (see Figure 5.2)
1) Screw the flameproof packing adapter into the
terminal box until the O-ring touches the wiring port
CAUTION (at least 6 full turns), and firmly tighten the lock
nut.
For the wiring materials and wiring work for the 2) Insert the cable through the union cover, the union
transmitter, please read the “Installation and coupling, the clamp nut, the clamp ring, the gland,
Operating Precautions for JIS Flameproof the washer, the rubber packing, and the packing box,
Equipment” at the end of this manual. in that order.
3) Insert the end of the cable into the terminal box.
4) Tighten the union cover to grip the cable. When
Wiring Precautions tightening the union cover, tighten approximately
1) Avoid routing wiring near noise sources such as one turn past the point where the cable will no
high-capacity transformers, motors, or motor power longer move up and down.
supplies. Proper tightening is important. If it is too tight, a
2) For power wiring termination, crimp terminal lugs circuit break in the cable may occur; if not tight
with insulating sleeves (for 4 mm screws) are enough, the flameproof effectiveness will be
recommended. compromised.
3) So that the rainwater, etc. cannot enter the instru- 5) Fasten the cable by tightening the clamp nut.
ment through the electrical connection port, use a 6) Tighten the lock nut on the union cover.
watertight gland, thick electrical cable, flexible 7) Connect the cable wires to each terminal.
conduit and other such means when wiring.
4) The maximum load resistance between the transmit- Transmitter Input 1 to 5V DC
Distributor Receiving Instrument
ter and the distributor should be 600 ⍀ or less (for a
24 V DC power source). ⫹⫺
5) Grounding is always required for the proper opera-
Grounding
tion of transmitters. Follow the domestic electrical
1
requirement as regulated by each country. 2
WARNING
AC/DC
For JIS flameproof type, grounding should F0501E.EPS
satisfy Class D requirements (grounding resis-
Figure 5.1 Connection between Transmitter and Distribu-
tance, ⍀ or less). tor
Apply a non-hardening
6) There are ground terminals on both the inside and Packing box
sealant to the threads for
outside of the case. Either of there may be used. Rubber packing
Adapter body waterproofing.
7) Shielded cable is recommended for wiring. Washer
Gland Lock nut O-ring
CAUTION
Clamp ring
If the transmitter is flameproof and the ambient
temperature is 55⬚C or more, use cables having
a maximum allowable heat resistance of at least
Cable Clamp nut
70⬚C in consideration of the instrument’s gen-
Union cover Union coupling
eration of heat or the cables’ self-heating. Lock nut F0502E.EPS
5-1 IM 01T01B04-01E
6. BEFORE OPERATION
6. BEFORE OPERATION
6.1 Zero Adjustment CAUTION
pressure.
Input 1 to 5 V DC
Distributor Receiving Instrument
Check Terminals
AC/DC
F0601E.EPS
6-1 IM 01T01B04-01E
6. BEFORE OPERATION
6-2 IM 01T01B04-01E
7. MAINTENANCE
7. MAINTENANCE
Maintenance of the transmitter is easy due to its 4) Do not apply a pressure exceeding the equipment
modular construction. This chapter describes the rating.
procedures for calibration, adjustment, and the disas-
sembly and reassembly procedures required for 7.2 Calibration
component replacement.
Apply pressures corresponding to 0%, 25%, 50%, 75%,
Since the transmitters are precision instruments, and 100% of the measurement range. When doing this,
carefully and thoroughly read the following sections calculate the errors between the output obtained when
for proper handling during maintenance. the pressure is increased from 0% to 100%, and when
it is decreased from 100% to 0%, and verify that these
errors are within the accuracy specifications.
CAUTION
7-1 IM 01T01B04-01E
7. MAINTENANCE
Zero Adjustment
“⫺” Terminal
Span Coarse Adjustment Jumper
T. Z Potentiometer
(Temperature Zero Adjustment) Check Terminal
Note: Not necessary for adjustment.
7-2 IM 01T01B04-01E
7. MAINTENANCE
NOTE
Performing the insulation resistance and dielec-
tric strength tests too frequently may hasten
deterioration of the electronic parts. It is recom-
mended that these tests be performed only when
the transmitter is not operating properly, and it is
suspected that the cause of the problem lies in
the electronic circuitry (the amplifier unit).
7-3 IM 01T01B04-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
To meet flameproof requirements, equipment that can be (4) Path length of joint surface
termed “flameproof” must: On a joint surface, the length of the shortest path through
(1) Be certified by a Japanese public authority in accordance which flame flows from the inside to outside of the
with the Labour Safety and Health Laws of Japan and flameproof enclosure. This definition cannot be applied to
have a certification label in an appropriate location on its threaded joints.
case, and
(5) Gaps between joint surfaces
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and The physical distance between two mating surfaces, or
precautionary information furnished. differences in diameters if the mating surfaces are cylindrical.
2. Electrical Apparatus of Flame- Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are
proof Type of Explosion- determined by such factors as the enclosure’s internal
Protected Construction volume, joint and mating surface construction, and the
explosion classification of the specified gases and vapours.
Electrical apparatus which is of flameproof construction is
subjected to a type test and certified by the Japanese Ministry
of Labour aiming at preventing explosion caused by electrical
apparatus in a factory or any location where inflammable
gases or vapours may be present. The flameproof
1 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
2 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
CAUTION
3 EX-B03E
Blank Page