Technical Write Up - IsOLCELL N2 Oxygen Reduction Fire Prevention System
Technical Write Up - IsOLCELL N2 Oxygen Reduction Fire Prevention System
Whatever media is in use, foam, water mist, sprinklers, gas or water they are being activated
after a fire has been detected. With the common and known methods fire is being fought only
reactively. Often the damage caused by the extinguishing media is worse than the damage
caused by the fire itself. Furthermore, there are many applications where the usage of water
or gas would be fatal in its consequence. Applications like e.g., Data Centres, Server Rooms,
Cold Stores, Paper Mills and many more. Whenever electricity comes into play the usage of
water could end in a total disaster. Huge storages like cold store could not be flooded from a
gas reservoir for example.
ISOLCELL aims to provide the optimal solution for most of the above-mentioned applications
to ensure absolute security by simply making the development of a fire impossible, replacing
traditional firefighting technologies.
“Completely eliminating the fire hazard and safeguarding people, buildings and its content is
possible with ISOLCELL’s N2 ORS oxygen depletion systems.”
The changed ratio has got the equivalent effect to human beings as a stay in high altitude or
when travelling by plane as the lower air pressure drives the molecules apart and the amount
of oxygen inhaled with every breath is less than in lower atmospheres.
The concept of the fire triangle
The generated and controlled atmosphere makes a fire impossible.
For a fire to ignite three elements are needed: Heat, combustibles and an oxidizing agent,
usually oxygen. The concept of the fire triangle.
When these elements are present and in the right mixture a natural fire will occur. A fire can
be prevented or extinguished by removing any one of these elements. Once a fire has
started, the exothermic chain reaction sustains the fire and allows it to continue until or
unless at least one of the elements of the fire is blocked.
The concept of traditional firefighting methods either deny the burning fire the oxygen it
needs or they lower the temperature of the fuel below the ignition point or by creating a
barrier of inert gases thus attacking the chemical reaction responsible for the fire.
With the N2 OXYGEN REDUCTION SYSTEM® we actively prevent the combustion process to
get started by uninterruptedly reducing the amount of oxygen.
Advantages of an Oxygen Reduction Fire The additional advantages of N2 ORS
Prevention System system
Flexibility
• Extensive customisation options
• Minimally invasive in the area to be
protected
• Silent
Economy
• Lower management and maintenance
costs
• Limited energy consumption
Operating principle
N2 ORS® in four simple steps
#Generate
This phase involves the generation of the oxygen-reduced atmosphere. All of Isolcell’s
technologies for producing this atmosphere are green systems in the true sense of the word:
they use only the air from the surrounding environment, without the addition of chemical
substances or additives.
#Releaser
The atmosphere created is released into the area to be protected using a distribution
network.
#Monitor
Using a special system called a ‘virtual grid’, a series of oxygen sensors analyse all of the
protected area and relay the results to the control panel, so that the atmosphere
is constantly analysed and monitored.
#Maintain
When an oxygen value other than the level desired is detected, the control panel activates
the generators of the oxygen-reduced atmosphere for the period required to restore the
defined values.
Thanks to the virtual grid and the rotation system, which is made possible because of
the modularity of the generators, the system is able to optimise energy consumption and
operating costs: in fact, the equipment alternates cyclically, thus limiting the hours of
operation and reducing wear and maintenance.
Areas of application of Oxygen Reduction Fire Prevention Systems
The N2 OXYGEN REDUCTION SYSTEM® is highly reliable, flexible, scalable and suitable for:
Archiving
Archives of all kind can perfectly be protected by ISOLCELL’s N2 ORS method as the risk of
fire can be eliminated completely.
Archives of all kind can perfectly be protected by ISOLCELL’s N2 ORS method as the risk of fire
can be eliminated completely. Sensitive documents, irreplaceable artefacts, paintings and
collections or precious materials that contribute to our global heritage are absolutely safe
once the oxygen depletion system is in place.
A large hospital in Italy has decided in favour of ADOX N2 OXYGEN REDUCTION system in
order to protect and preserve infinitely health records and medical documents. The archive
has got a size of 1000m2 and the shelf lengths holding these documents has got an
impressive length of 25 Kilometres.
Paper files
Film and data archives
Museums
Hospital warehouses
Libraries
Vaults/treasuries
Etc.
According to the article Clean Agents Fire Protection for Computer Rooms by Mark l. Robin,
the economic damage caused by a blackout of a computer network can exceed one million
dollars for each hour of downtime. Now more than ever, given the ever-increasing offer of
cloud-based services, it is vital to completely eliminate fire risk.
Data centres
Server rooms
Computer rooms
Server farms
Switch rooms
Shelters
Substations and transformer rooms
Etc.
Logistics
FIRE PROTECTION FOR AUTOMATED HIGH-BAY WAREHOUSES
Oxygen reduction fire prevention systems are the perfect solution for fully or half automated
warehouses. If it is an ambient temperature warehouse or a cold store, the method
eliminates the risk of fire completely thus also eliminating consequential damages a fire
would cause. For economic reasons more and more companies tend to manufacture and
store their products in a single facility, making an absolute and reliable fire prevention
indispensable
Reference project example:
A striking example is an automated warehouse near Parma, in Italy, with a volume of 161,000
m³, covering 4,600 m² and a capacity of 27,000 pallets, used to store plastic table utensils.
The particular characteristics of the product and the high calorific value of the plastic led the
company to look beyond traditional fire-fighting technologies (like e.g. sprinklers) and to turn
to the only concept of prevention. Despite the more than 500 storage and retrieval
movements per hour, the reduced-oxygen atmosphere is accurately being maintained and
constantly monitored to reliably eliminating the risk of fire.
Automated/intensives warehouses
ASRS warehouses (Automated Storage Retrieval System)
HBW (High-Bay warehouses)
Storage of hazardous materials
Cool stores, Freezer warehouses
Refrigerated warehouses
Food warehouses
Paper mills
Standard and regulations
How we make our system safe
On the basis of the applicable legislative provisions, all companies are required to comply
with the general principles for prevention in relation to health and safety. In this area, one
fundamental aspect is the functional safety of the products themselves, especially if used in
safety applications.
Our objective is to create high quality, reliable products, an essential requirement when
dealing with safety systems. For this reason, we rely on the evaluation and certification of our
products and systems by independent third parties.
Thanks to characteristics such as reliability, safety and exclusivity, we are in fact currently the
only company to hold a series of recognitions, namely approvals and certifications such as
the following:
ISOLCELL has been part of the work group for the establishment of the world regulations (ISO
20338:2019) for the oxygen reduction fire prevention as well as of the European standard (EN
16750:2017)
ISOLCELL OXYGEN-REDUCED ATMOSPHERE GENERATORS
The generation of an oxygen-reduced atmosphere through molecular separation is achieved
using ADOX® oxygen adsobers with VPSA (Vacuum Pressure Swing Adsorber) technology,
NIMOS nitrogen generators with PSA (Pressure Swing Adsorber) technology, or ISOSEP
membrane technology.
The following illustration shows the differences in the molecular separation process:
ADOX® systems (VPSA technology) are the most high-performance: these are modular
systems developed specifically for fire prevention using oxygen reduction and guarantee
greater safety, because they operate on the basis of redundancy. Thanks to its exclusive
technology, ADOX® is able to operate at low pressure, significantly reducing energy
consumption and wear.
This system is suitable for protecting medium-sized and large environments, optimising
operating costs and achieving a saving of up to 60% compared to previous technologies.
Characteristics of the ADOX® system
Unlike high-pressure systems (PSA or membrane), which require a series of elements
necessary for the compressed-air chain, ADOX® systems operate using low pressure and
thus consume less energy compared to the two other technologies and require less
maintenance. Furthermore, they are ready to use (plug & play) because they contain within
them everything they need to operate.
Modularity
ADOX® generators of self-extinguishing atmospheres are characterised by their modular
composition. This means that their production capacity can be increased at any time simply
through the addition of further modules. Improving the production capacity of these systems
achieves a better optimisation of work cycles and energy consumption and, because of the
redundancy system, more safety.
The figure represents an ADOX® oxygen adsorber made up of three independent modules.
In practice, it is like having three separate machines: if a module fails, the other two guarantees that the system
operates correctly.
The quietest in the class
To improve the working environment, we have also worked on the system’s acoustic
insulation, developing the sound-proof cabinet, providing shielding for the adsorber
produced by combining materials of the highest quality.
This solution has resulted in a significant reduction in noise, from 90 to < 64 dB(A)
(measurements of sound power taken and certified according to the UNI EN ISO 3744:2010
standard), thus obtaining the lowest level of noise in the category.
ISOSEP SERIES
ISOSEP - System using Membrane Technology
Comparison of technologies
The graphic showing the work performed by the three technologies illustrates their different
methods for separation of oxygen molecules from nitrogen molecules. Each of these
technologies is suitable for specific uses.
The following table illustrates the breakdown of initial and management costs for each
technology:
It is clear that a significant saving in energy costs, obtained through the use of the right
technology, can bring major benefits for the overall economy of the system. Among the
various alternatives, it is therefore important to choose the option that will provide the
greatest benefit over time.
CONTROL INDICATING EQUIPMENT (CIE) N2 ORS®
The heart of the system
The N2 ORS® control indicating equipment is the unit that manages the entire system. The
panel manages sampling from the virtual grid, ordering the activation and/or deactivation of
the integrated and interfaced equipment making up the system, according to scheduled
intervention plans. It also manages all control systems to avoid the undesired formation of
under-oxygenated atmospheres (compared to atmospheric values) in environments adjacent
to the areas to be protected, along with shut-off procedures when the pre-set oxygen
concentration thresholds are reached, and activation of alarms when needed.
Given the importance of the control indicating equipment in fire-prevention systems operating
using oxygen-depletion methodologies, it is regulated by specific requirements that impose a
series of characteristics associated with self-diagnostics and redundancy, and with a dual
power supply to guarantee operation of the system for at least 24 hours (according to the
standard to be followed), even where the primary electricity supply is absent.
The N2 ORS® control panel is certified SIL-3 according to the general requirement IEC 61508.
WEBSERVER N2 ORS®
Oxygen reduction system remote control
The system synoptics operate via web with an IP address and transform the data from the
control panel into intuitive graphics that be read immediately.
The specific operating conditions of the system (normal condition, fault condition, alarm
condition, etc.), including the corresponding switching operations, will be recorded and saved
so that they can be displayed.
Representation of the overlapping of the virtual grid, the sampling and analysis system and the
distribution system (©Isolcell).
2. Speed of response
avoids the spread of oxygen detected throughout the entire area
avoids the presence of non-uniform areas
3. Continuous analysis
facilitates the detection of any critical points, enabling intervention in
individual areas
reduces the quantity of oxygen-reduced air to be released into the
atmosphere
To ensure that a system achieves a particular SIL class, each element linked to a given safety
function must comply with the requirements determined for that SIL class: if even one of the
elements linked to a safety function were to be classified as a lower SIL class, the entire system
would be classified under the SIL class achieved by that element. ORS systems are broken down
into the following safety-related elements, with each being assigned a given SIL level:
Oxygen sensors
Control system
I/O modules
Oxygen-reduced atmosphere generators
Distribution valves
An analysis of the reliability of plant units, mechanisms or systems with safety implications
(namely those that present risks for people, the environment and property) is required more
and more often, for example by the recent ISO 20338:2019 standard. This is therefore an
effective and internationally recognised method of guaranteeing and demonstrating the safety
level of an ORS system. Extract from our IEC 61508:2010 certificate, which represents the
approach for obtaining SIL-3.