Professional Documents
Culture Documents
Class, Type, Protection and Electricity Safety ME
Class, Type, Protection and Electricity Safety ME
Class, Type, Protection and Electricity Safety ME
Anaesthesia
Electricity and Magnetism
David Sanders, Bruce McCormick*
*Correspondence Email: Bruce.McCormick@rdeft.nhs.uk
STATIC ELECTRICITY
You may occasionally notice a click of energy when
shaking someone’s hand; this is due to build up of
static charge by contact of our shoes on the carpet.
The click is due to discharge of the static charge on
contact with the other person. Static is a stationary
collection of electrical charge that can be positive
or negative. It is usually formed as a result of charge
separation between dissimilar materials. Items are said
Figure 1. Electricity explained as an analogy to fluid flow to become charged, and a potential difference is created
representing stored potential energy. This energy can be David Sanders
released or discharged as sparks, which has implications Consultant Anaesthetist
in theatre, particularly when using flammable agents
such as ether. Bruce McCormick
Consultant Anaesthetist
CURRENT ELECTRICITY
Royal Devon and Exeter
Current describes moving electrical charge that flows
NHS Foundation Trust
around circuits and is described by Ohm’s law:
Barrack Road
Current, I = Voltage, V Exeter
Figure 2. Conventional electric current flow and electron Resistance, R Devon EX2 5DW
flow (or commonly rearranged as: V = IR) UK
MAGNETISM
Theory
Magnetic force is a fundamental natural force (like gravity) and, as
such, is not easily explained. Magnetic poles are always paired and
are usually described as north or south. Magnetic fields are classically
described in terms of lines of flux, which show the direction of the
magnet field at any particular point. Materials can be:
• Ferromagnetic – they are strongly attracted into a magnetic field,
become magnetic while in the field and remain so after the field
is removed,
Figure 4. The Wheatstone Bridge. When R1/R2 = R3/R4, no current • Paramagnetic – they are weakly attracted into a magnetic field,
flows through the meter (I) and the ‘bridge’ is said to be ‘balanced’. • Diamagnetic – they are weakly repelled form a magnetic field.
The transducer (RT ) is connected in place of R1 and a variable resistor
(RV) replaces as R3. The transducer is zeroed by adjusting RV until there
is no current flow through I. A change in the transducer’s resistance
unbalances the circuit and causes a current to flow through the meter.
The amount that the variable resistor must be changed to restore the
bridge to balance (i.e. no flow at I), can be used to calculate the resistance
change at the transducer and therefore the pressure change to which the
transducer has been exposed
Inductance
Inductance arises in circuits with alternating or oscillating currents.
As the current reverses, the associated magnetic field (see above) in a
coil or loop of wire waxes and wanes. The fluctuating magnetic field
induces a current in the same wire in the opposite direction to original Figure 11. Schematic diagram of a defibrillator. The charging voltage
current, which is in opposition to the original change (Lenz’s Law). is approximately 5000V and the total current delivered is up to 35A. The
stored energy of the capacitor is ½CxV2
Inductance is proportional to rate of change of current (i.e. the AC
frequency) and the number of turns in the coil. Hence the resistance
Monophasic and biphasic defibrillators (Figure 12)
to current flow (the impedance – see below) is frequency dependent.
In many countries biphasic defibrillators have replaced monophasic
dibrillators. They require lower energy levels to achieve defibrillation
Impedance
and the risk of damage to the cardiac muscle is therefore less. Smaller
This is a fundamental concept in AC circuits and signal processing,
capacitors are required and batteries have longer life.
describing the opposition to the passage of current. Impedance is
analogous to resistance in DC circuits and, like resistance, is measured
AMPLIFIERS
in ohms. Impedance is given the symbol, Z.
The magnitude of impedance depends upon a complex relationship Principles
between the signal frequency and the capacitance, inductance and An amplifier increases the power of an electrical signal – the output
resistance of circuit. It is the frequency dependence of impedance that signal is proportional to input but of greater magnitude. The ratio
makes it possible to build circuits which present high impedance to between output and input is the amplification factor or gain, with
one range of frequencies and low impedance to others - this is the the power gain expressed in decibels (dB). Voltage gain is the ratio of
basis of electronic filters. input signal voltage to output voltage.
The extent of the burn is governed by the relationship: There are three classes of secondary protection (Table 2):
Burn = current x time Equipment should only become hazardous if two faults are present
simultaneously, for example a short to the case and a broken earth lead.
area
The result of a ‘two fault’ state such as this would be a live enclosure
Other risks of diathermy: - if touched current will flow to earth through the patient or a staff
member. This is prevented by regular servicing and testing for both
• A potential source of ignition risking fires or explosions.
types of fault separately, aiming to detect a single fault condition before
• Direct coupling of current - the user accidentally activates the the second fault occurs.
generator while the active electrode is near another metal
instrument. The secondary instrument will then become Prevention of microshock
energised. Microshock is hazardous when there is a low impedance piece
CONCLUSION
Electricity is now available in most theatres around the world and
many of the technologies available for patient care, monitoring and
safety rely upon it. Whilst many anaesthetists will not seek a detailed
understanding of the circuitry within their equipment, some basic
knowledge is essential to minimise any risks of harm to the patient
by inadvertent exposure to electrical current. This is particularly
important where the facilities for regular servicing are stretched or
Figure 19. Labels identifying classes of equipment used in contact with unavailable, when the ability to keep equipment safe and functional
patients is the responsibility of the anaesthetist.