Air Compressor Controller Unit

AR1710 Series: Screw Air Controller

User Manual
Version 92.9
AR1710 Series User’s Manual

 Read this direction for safety first…

Direction for safety

This direction is for using the product correctly so that you could be safe from danger or incident.

Please carefully keep this all direction.

 Please use eighth being attached to a dual safety device in case of using for controlling instruments
which could be effective to human life or property(e.g. : Controlling atomic energy, medical
instruments ,cars ,trains ,flights ,burners, amusement instruments or safety machinery).

 Please use with panel, there is a possibility getting an electric shock.

 Do not inspect or test with connecting power.

 Please connect after checking the terminal number when connecting power.

 Do not reorganize except mechanic from ARSIN ®


 Do not use outdoor .It would be a cause making the product life shorter.

 When connecting wires, please give a good screw on terminal. There is a possibility causing a fire with
bad connection.

 Please use in the proper performance zone. If you don’t there is a possibility making the product life
shorter or, causing a fire accident.

 Do not use a load which is exceeded proper value of opening and shutting capacity of a relay contact.
This will cause bad insulation, bad contact and bad connection.

 When cleaning, water or liquid including oil or prohibited, only clean with soft and dried cloth.

 Do not use in the place where there is inflammability gas, explosiveness gas, moisture a direct ray of
light, radiation, vibration and a shock.

 Please prevent from getting a dirt or leftover wire inside of this product.

 When connecting a sensor , please connect correctly after checking the polarity.

Some of the setting, size etc. on this manual could be changed without an advance notice.

2
AR1710 Series User’s Manual

1. OUTLINE

AR1710 is based on Micro Processor and the most advanced equipment for controlling electricity
conducting efficient operation of a screw air compressor.AR1710 is a system managing the compressor’s
operation intensively, saving energy through controlling of timing for capacity adjustment, preventative
and maintenance schedule. In the other word,AR1710 conducts the best operation(control)according to
the condition set up and operating circumstance.

 High reliability RISC MICOM


 240×128 graphic LCD
 Max. 30 events of running log storable (Non-volatile)-Easy preventative & maintenance and analysis for
trouble
 Automatic calculation and notice function for preventative & maintenance ,consumable parts exchange
information and expected schedule
 Automation of economical operation by embedded weekly timer

Unload Pressure: Pressure value under unload operation with closing intake valve on compressor.

Load Pressure: Pressure value under load operation with opening intake valve on compressor.

Auto Stop Delay: Compressor is stopped in case of continuous operation at unload operation during auto
stop delay time.

Stop Delay: Compressor is stopped after unload operation during manual stop delay time.

Start Delay: Delay time when compressor start load operation from starting.

3
AR1710 Series User’s Manual

1) Special advantages
AR1710 is a stable electronic control unit for screw air compressor which can provide users with running
log for integral control and management of the equipments. It adopts the method of digital process by high
efficiency RISC type microprocessor and occupies enough installation space and stability by unifying
module and control module. It provides convenience to let users know a status of operation at once
through display.

1-1) Noise solution


It is inevitable to figure for noise as an industrial controller. The digital input and output signal of AR1710 is
isolated, so it can not be allowed to flow external signal into the main board inside.CPU on main board
mounts HARDWARE WATCHDOG TIMER which can automatically recover from CPU down occurred by noise
per 32 msec., and BROWN-OUT function embedded in CPU inside supervises control power in real-time.

1-2) RISC TYPE MICOM


An assembler instruction in CPU can perform 7.3728Mbps, and logic for controlling written in CPU inside
needs about 1[m sec] based on 1 cycle. In this regard, sampling rate is about 10 times faster than the
existing controllers, so it has less probability of malfunction and more precise control.

1-3) Black Boxes: A recorder of operation status


It is possible for AR1710 to store maximum until 30 events of running log, so it is easy for preventative &
maintenance and Troubleshooting. Additionally, it is possible to verify the operation data at site occurs, so
it is helpful for users to know the reason of trouble and the status of equipment in real-time.

1-4) Display for operation status and/or maintenance (trip computer)


AR1710 has the display function for operation status, delay time and ready time by counting reversely, so
users can recognize the status of compressor at a glance. Also, it has the basic function to notify parts and
oil checking and exchanging schedule by calculating it automatically according to the information of
operation.

1-5) 240×128 graphic LCD (Wide Temperature Range Type: (-50 ~ +150°C).Display part of AR1710 adopts
240×128 graphic LCD for user’s easy operation and recognition.

1-6) Minimization

It is possible to minimize compressor by occupying a small space due to unifying design of control part and
display part.

1-7) Scalability

It provides users with RS485 port, MODBUS RTU standard protocol and MMI software and automatic
interface.

4
AR1710 Series User’s Manual

2) Basic specification

2-1) General Specification

Power Conditions Input Power AC12V 50/60Hz


Power Consumption Max 4.0 VA

2-2) CPU & LCD

CPU AT mega 128,16MHz


CPU , LCD
LCD 240×128 pixel, LED Backlight

2-3) Digital Input &Output

Input Type Opto -Isolation


Digital Input Number of Input 8 Points(1 Common)
Signal Power 12V DC
Output Type Relay Contact
Digital Output Number of Output 8 Points(1 Common)
Relay Contact Type 250Vac,10Amper

2-4) Analog Input & Output

Temp. Sensor NTC 2 Points


Analog Input 4~20 mA 2 Points
(Internal Sensor Power 12V)
Correction of Software
Deviation
-- --
Analog Output -- --
-- --

2-5) Communication Specifications

Type RS485(Half-Duplex) 1 Channel


Modbus RTU
Speed 4800,9600,19200,38400 BPS
Communication (default 9600)
Parity None, Data 8 bit, Stop 1,bit
Distance Max. 1.2Km
Recommended Cable BELDEN 9842 or 8761

2-6) Installation Circumstance

Place Indoor
Field Conditions Operating Temp. -10~60°C
Storage Temp. -30~80°C
Operation Humidity (No condensation) 5~95%

5
AR1710 Series User’s Manual

2. Input / Output Specification

1) Digital Input Signal

Pin Name Function Active state


10 Com Input Common Terminal
11 Rmt Remote Input Signal Remote (close)
12 Rot Rotation Fault Signal Alarm(close)
13 Motor Motor Bimetal Fault Signal Alarm(close)
14 Fan Fan Bimetal Fault Signal Alarm(close)
15 PSW Pressure Switch Signal Alarm(close)
16 EMS Emergency Stop Signal Alarm(close)
17 TSW Thermo Switch Signal(Motor) Alarm(close)
18 Oil Oil Level Sensor Signal Alarm(close)

2) Power Output Signal

Pin Name Function Active state


33 Com Power Common Terminal
34 MF3 Multi Function Output # 3 Output(NO)
35 MF2 Multi Function Output # 2 Output(NO)
36 MF1 Multi Function Output # 1 Output(NO)
37 Fan Fan Motor Output Output(NO)
38 Valve Solenoid Valve Output Output(NO)
39 Norm Normal Contactor Output Output(NO)
40  Rectangular Contactor Output Output(NO)
41 Y Star Contactor Output Output(NO)

3) Analog Input Signal


Pin Name Function Type Range
19 Temp Oil Temperature Sensor (1) Pt1000 -50~150 C
20 Temp Oil Temperature Sensor (2) Pt1000 -50~150 C
21 Temp Air Temperature Sensor (1) Pt1000 -50~150 C
22 Temp Air Temperature Sensor (2) Pt1000 -50~150 C
23 +12V Oil Pressure Transmitter (+) 4~20mA Settable
24 Out Oil Pressure Transmitter (-) 4~20mA Settable
25 +12V Air Pressure Transmitter (+) 4~20mA Settable
26 Out Air Pressure Transmitter (-) 4~20mA Settable

6
AR1710 Series User’s Manual

BELDEN 9842 standard cable is recommendable

6) Power Supply Inputs


Pin Name Function

6,7 Auxiliary Supply AC12V

8,9 Main Supply AC12V

7
AR1710 Series User’s Manual

7) Current measurement

Pin Name Function Active state


27 CT1 Current Sampling L1 Loop circuit
28 CT1 Current Sampling L1 Loop circuit
29 CT2 Current Sampling L2 Loop circuit
30 CT2 Current Sampling L2 Loop circuit
31 CT3 Current Sampling L3 Loop circuit
32 CT3 Current Sampling L3 Loop circuit

100/5….500/5 Ratio

8
AR1710 Series User’s Manual

Constitution
1) Dimensions and panel Cut-Out Information front view:

2) Back view:

9
AR1710 Series User’s Manual

1-1) Basic Constitution


Display part specification: 240×128 Graphic LCD

1-2) Operation part

Reset: Reset when trip occurred

1-3) Program setup part

Enter switch: selection of setup program or value

Downward Switch: Moving down to setup program or value

Upward switch: Moving up to setup program or value

Menu switch: Opening menu for setup

Escape switch: Returning to the previous menu or initial screen

2) Display for Operation Status

10
AR1710 Series User’s Manual

2) Operation Button Function

Start Select Start


The equipment starts when pushing start button.

Stop Select Stop


The equipment stops when pushing stop button.

Reset Reset when trip


The trip reset automatically doesn’t need to push
reset button.
Enter Entering to programming / enter to new menu

Up/Down Upward(Increase)and/or Download (Decrease)

Escape Exit from current menu

3) Status display lamp

RED Error occurred in system

Yellow It’s the time for system to be serviced or warning in progress

GREEN Power supply applied

4) Display Explanation

L Operating Mode : Local


R Operating Mode : Remote
N Operating Mode: Network
W Schedule Program Enabled
GOOD Normal Operation
Mainten Need to be Serviced
S_DOWN Shut down Trip
FAULT Fault Occurred
Inhibit Unable to be run by an inhibition cause

11
AR1710 Series User’s Manual

5. Menu Constitution

1) Main Screen Constitution Type

STATUS STATU S
OPERATION Delivery Air Temp : 150 C
RUNNING LOG Delivery Pressure : 0.0Bar
SCHEDULE Oil Pressure : 0.0C
MAINTENANCE Oil Temperature : 150C
SHUTDOEN Differential Press. : 0.0Bar
WARN MODE Total Run Hours : 00379h
START INHIBIT
COMPRESSOR

TEST MODE
CONFIGURATION
CONTRAST
MOTOR SETTING
SYSTEM DATE-TIME

12
AR1710 Series User’s Manual

STATUS
OPERATION Unload Pressure : 0.2 Bar
RUNNING LOG Load Pressure : 6.0 Bar
SCHEDULE Auto Stop Delay : 10 Min
MAINTENANCE Stop Delay : 05 Sec
SHUTDOEN Start Delay : 05 Sec
WARN MODE Drain Time[On] : 05 Sec
Drain Time[Off] : 05 Min
START INHIBIT
COMPRESSOR

STATUS
OPERATION RUNNING LOG
RUNNING LOG
#00 1391/01/07 08:05
SCHEDULE
Oil High Pressure
MAINTENANCE
#01 1391/02/08 12:05
SHUTDOEN
1```````

Emergency Stop .p
WARN MODE
#02 1301/02/07 21:05
START INHIBIT
Emergency Stop .p
COMPRESSOR
#03 1301/03/07 20:15
Main Motor Fault .p

13
AR1710 Series User’s Manual

STATUS
OPERATION
RUNNING LOG
SCHEDULE
SCHDULE .
MAINTENANCE Sunday On : 08:00
SHUTDOEN
WARN MODE Sunday Off : 17:00
START INHIBIT
COMPRESSOR Monday On : 08:00
Monday Off : 17:00
Tuesday On : 08:00
Tuesday Off : 17:00
Wednesday On : 08:00
Wednesday Off : 17:00

Thursday On:
17:00 : 08:00
Thursday
08:00 Off : 17:00
Friday On : 08:00
Friday Off : 17:00
Saturday On : 08:00
Saturday Off : 17:00

14
AR1710 Series User’s Manual

STATUS
OPERATION
RUNNING LOG
SCHEDULE
SHUTDOEN MAINTENANCE .
MAINTENANCE
WARN MODE Dust Filter : : 1000h
START INHIBIT
Suction Filter : 1000h
COMPRESSOR
Oil Filter : 1000h
Lub. Oil Filter : 1000h
Cooler Cleaning : 1000h
Overhaul : 5000h

.
.
.
.
.
.

15
AR1710 Series User’s Manual

1)Menu construction

STATUS OPERATION RUNNING LOG SCHEDULE


00: Delivery Air Temp. 00: Unload Pressure 00: Event #1 00: Sun: Start ~ Stop
01: Delivery Press. 01: Load Pressure 01: Event #2 01: Mon: Start ~ Stop
03:Oil Pressure. 02: Auto Stop Delay 02: Event #3 02: Tue: Start ~ Stop
04: Oil Temperature. 03: Stop Delay . 03: Wed: Start ~ Stop
05: Differential Pres. 04: Start Delay 04: Thu Start ~ Stop
.|
06:Total Run Hours 05: Drain Time [On]
31: Event #32 05: Fri: Start ~ Stop
06: Drain Interval [Off]
06: Sat: Start ~ Stop
07: Cooling Fan Run
08: Cooling Fan Stop
09: LCD Backlight Mode

ALARM MODE
MAITENANCE SHOUTDOWN
00:Delivery Temp.
00: Dust Filter 00:Delivery Temp. High High START INHIBIT
01: Suction Filter 01:Delivery Press. High 01:Delivery Press. 00:Delivery Temp.
High Low
02: Oil Filter 02:Oil Rec. Temp. High
02:Oil Rec. Temp. 01:Delivery Press.
03: Lub. Oil Change 03:Oil Rec. Press. High High High
04: Cooler Cleaning 04:Diff-Pressure High 03:Oil Rec. Press. High
05: Overhaul
04:Diff-Pressure High

16
AR1710 Series User’s Manual

COMPRESSOR VSD MODE* TEST MODE CONFIGURATION


00: Y-Delta Transfer 00:VSD Control Mode 00:Manual Test Mode 00: Master Password
Time Setup
01:Maximum Speed 01:Multi Function N1
01: Load Delay Time 01: Trip/Alarm
02:Minimum Speed 02: Multi Function N2 HistoryDelete
02: Reload Delay Time
03:Optimum Speed 03: Multi Function N3 02: Operation History
03: Diff-Press. Detect Delete
Delay 04:Unloaded Speed 04: Multi Function N4
03: Reverse Phase Signal
04: Load Command 05:Speed Command (Hz)
05:Main Motor MAIN 04: Oil Rec. P-Sensor Use
Mode 06: Speed Command
(mA) 06:Main Motor STAR 05:Oil Rec. T-Sensor Use
05: Starting Command
Mode 07:Proportional Band(P) 07:Main Motor DELTA 06:Deliovery Press.
Correction
06: Power Return 08:Integral Time(I) 08:Load Solenoid
Restart Valve 07:Oil Rec. press.
09:Dead Band Correction
07: Network ID 09:Invertal Control*
10:Jerk Control Ratio 09:Delivery Temp.
08: Network BPS 10:Delivery Press. Cporrection
11:Max.Inverter RPM Retrans*
10:Oil Rec. Temp.
Correction
12:Max.Inverter
Frequency 11:Min. Delivery Press.
12:Max. Delivery Press
13:Min Oil Rec. Press
14:Max. Oil Rec. Press.
DIAGNOSTIC 15:Multi Function 1

00:SELF TEST 16:Multi Function 2

01:B1 Input 17:Multi Function 3

02: B2 Input
03:B3 Input
04:B4 Input
06: B3 4mA
07: B3 20 mA
08:B4 4mA
09: B4 20mA
10:Y1 4mA
11:Y1 20mA
12:Y2 4mA
13:Y2 20mA

16:ADC F/T

17:DAC F/T

17
AR1710 Series User’s Manual

10-1) Trip Message

Description Detect condition


1 System Fault In case of unexpected change of the value of parameter
2 Emergency Stop Sensing [Digital Signal Input : Emergency Stop] : ON

Reset
[Digital Signal Input : Emergency Stop] : OFF
3 Fan Motor O.L. Sensing [Digital Signal Input : Fan Motor O.L] : ON

Reset
[Digital Signal Input : Fan Motor O.L] : OFF
4 Delivery Sensing
Delivery Pressure ≥ [Shutdown: Delivery Pressure High]
Pressure High
Reset
Delivery Pressure < [Shutdown: Delivery Pressure High] - 0.5bar
5 Delivery Sensing
Delivery Temp. ≥ [Shutdown: Delivery Temp. High]
Temp. High
Reset
Delivery Temp. < [Shutdown: Delivery Temp. High] - 5℃
6 Oil Rec. Oil
Sensing
Rec. Pressure ≥ [Shutdown: Oil Rec. Pressure High]
Pressure High
Reset
Oil Rec. Pressure < [Shutdown: Oil Rec. Pressure High] – 0.5bar
7 Oil Rec. Oil Rec. Temperature ≥ [Shutdown: Oil Rec. Temp. High]
Sensing
Temp. High
Reset
Oil Rec. Temperature < [Shutdown: Oil Rec. Temp. High] - 5℃
8 Diff-Pressure Sensing
(Oil Rec. Pressure–Delivery Pressure) ≥
High [Alarm Mode: Diff-Press. High] & Delivery Air Temperature > 50℃

Reset
(Oil Rec. Pressure–Delivery Pressure.) < [Alarm Mode: Diff-Press.
High] - 0.1bar
9 Brow down Time Sensing Oil Rec. Pressure > [Start Inhibit : Oil Rec. Pressure High] in case of exceeding
Over of [Operation :
Reset
Blow down Delay Time] during brow down check sequence
10 Delivery Reset In case of occurrence of error on delivery Pressure sensor (disconnection)
P-Sensor
Sensing
In case of normal condition of delivery Pressure sensor
11 Delivery Sensing
Reset
In case of occurrence of error on delivery temp. sensor (disconnection )
T-Sensor In case of normal condition of delivery temp. sensor
12 Oil Rec. Sensing In case of occurrence of error on oil rec. pressure sensor (disconnection )
P-Sensor Fault Reset
In case of normal condition of oil rec. pressure sensor
13 Oil Rec. Sensing In case of occurrence of error on oil rec. temperature sensor
T-Sensor Fault (disconnection)
Reset
In case of normal condition of oil rec. temperature sensor

18
AR1710 Series User’s Manual

※ Fault message occurred is reset by pushing [Reset] button after solving related reason.

10-2) Alarm Message

Item Description Detect condition


1 Oil Filter Sensing
[Digital Signal Input : Oil Filter High] : ON
High
Reset
[Digital Signal Input : Oil Filter High] : OFF
2 Air Filter Sensing
[Digital Signal Input : Air Filter High DP] : ON
HighDP
Reset
[Digital Signal Input : Air Filter High DP] : OFF
3 Oil Rec. Sensing [Digital Signal Input : Oil Reclaimer High Press.] : ON
Press. High
Reset
[Digital Signal Input : Oil Reclaimer High Press.] : OFF
4 Delivery Sensing Delivery Pressure ≥ [Alarm Mode : Delivery Pressure High]
Pressure
High Reset
Delivery Pressure < [Alarm Mode : Delivery Pressure High]-0.5bar
5 Delivery Sensing
Delivery Temp. ≥ [Alarm Mode : Delivery Temp. High]
Temp. High
Reset
Delivery Temp. < [Alarm Mode : Delivery Temp. High]-5℃
6 Oil Rec. Oil Rec. Pressure ≥ [Alarm Mode : Oil Rec. Pressure High]
Sensing
Press. High
Reset
Oil Rec. Pressure < [Alarm Mode : Oil Rec. Pressure High]- 0.5bar
7 Oil Rec. Oil Rec. Temperature ≥ [Alarm Mode : Oil Rec. Temperature High]
Sensing
Temp. High
Reset
Oil Rec. Temperature < [Alarm Mode : Oil Rec. Temperature High]-5℃
8 Diff- Sensing (Oil Rec. Pressure –Delivery Pressure) ≥
Pressure [Alarm Mode: Diff- Pressure High] & Delivery Air Temp. >50℃
High Reset
(Oil Rec. Press. –Delivery Press.) < [Alarm Mode: Diff- Pressure High]-0.1bar
9 RTC Stop Sensing
RTC is not working, (Sensible during scheduled operation)
Alarm
Reset
RTC is in ordinary operation, (necessary to reset the time)
※ Occurred alarm message is automatically reset in case of reset condition

19
AR1710 Series User’s Manual

6. Wiring Diagram

20