Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3280618

Active Input–Voltage and Load–Current Sharing in Input-Series and Output-


Parallel Connected Modular DC–DC Converters Using Dynamic Input-Voltage
Reference Scheme

Article  in  IEEE Transactions on Power Electronics · December 2004


DOI: 10.1109/TPEL.2004.836671 · Source: IEEE Xplore

CITATIONS READS
277 1,274

3 authors, including:

Niall Mohan
Queen Margaret University
235 PUBLICATIONS   13,427 CITATIONS   

SEE PROFILE

All content following this page was uploaded by Niall Mohan on 28 October 2015.

The user has requested enhancement of the downloaded file.


1462 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

Active Input–Voltage and Load–Current Sharing


in Input-Series and Output-Parallel Connected
Modular DC–DC Converters Using Dynamic
Input-Voltage Reference Scheme
Raja Ayyanar, Member, IEEE, Ramesh Giri, and Ned Mohan, Fellow, IEEE

Abstract—This paper explores a new configuration for modular


dc–dc converters, namely, series connection at the input, and par-
allel connection at the output, such that the converters share the
input voltage and load current equally. This is an important step
toward realizing a truly modular power system architecture, where
low-power, low-voltage, building block modules can be connected
in any series/parallel combination at input or at output, to realize
any given system specifications.
A three-loop control scheme, consisting of a common output
voltage loop, individual inner current loops, and individual input
voltage loops, is proposed to achieve input voltage and load cur-
rent sharing. The output voltage loop provides the basic reference
for inner current loops, which is modified by the respective input
voltage loops. The average of converter input voltages, which is
dynamically varying, is chosen as the reference for input voltage
loops. This choice of reference eliminates interaction among
different control loops.
The input-series and output-parallel (ISOP) configuration is an-
alyzed using the incremental negative resistance model of dc–dc
converters. Based on the analysis, design methods for input voltage
controller are developed. Analysis and proposed design methods
are verified through simulation, and experimentally, on an ISOP
system consisting of two forward converters.
Index Terms—Input-series connection, input-series and output-
parallel (ISOP), load sharing, modular converter, voltage sharing.

I. INTRODUCTION

A FULLY modular power system architecture is envisioned


for dc–dc power conversion. In such an architecture, low-
power, low-voltage (input and output) building block dc–dc con-
verters can be connected in any combination, series or parallel, Fig. 1. Example of a fully modular power system architecture.
both at the output as well as at the input sides, to realize any
input–output specifications. Fig. 1 illustrates an example of a rating of 100 V, and providing a regulated 25-V output at a max-
5-kW power supply system operating from a 1000-V dc source imum current of 10 A. (Though not shown in the figure, required
and delivering a well regulated output voltage of 50 V at a max- level of redundancy may also be included.)
imum load current of 100 A. This system is implemented using The main advantages of the modular approach include: sig-
a total of 20 250-W power supplies, each with an input voltage nificant improvement in reliability by introducing desired level
of redundancy [1]–[5]; standardization of components leading
to reduction in manufacturing cost and time; power systems can
Manuscript received August 26, 2003; revised February 4, 2004. This be easily reconfigured to support varying input-output specifi-
work was supported by the Office of Naval Research (ONR) under Award cations; and possibly higher efficiency and power density of the
N00014-00-1-0928 and Award N00014-03-1-0802. Recommended by Asso-
ciate Editor P. M. Barbosa. overall system, especially with interleaving.
R. Ayyanar is with the Department of Electrical Engineering, Arizona State
University, Tempe, AZ 85287–5706 USA. A. Input–Parallel Connections
R. Giri is with Maxim Integrated Products, Sunnyvale, CA 94086 USA.
N. Mohan is with the University of Minnesota, Minneapolis, MN 55455 USA. Fig. 2 shows the four possible combinations of input-output
Digital Object Identifier 10.1109/TPEL.2004.836671 connections. Among these combinations, the input-parallel and
0885-8993/04$20.00 © 2004 IEEE
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1463

depends mainly on the drift region resistance, which is


roughly proportional to , where is the
break down voltage of the MOSFET [16]. Hence, “ ”
MOSFETs each with a voltage rating of ,
have a combined which is significantly lower
than the of a single MOSFET with a voltage
rating of .
2) MOSFETs can be used instead of insulated gate bipolar
transistors (IGBTs) for high input-voltage applications.
Hence, switching frequency, and therefore, power density
of such systems can be increased.
3) Input-series and output-parallel connection leads to
smaller conversion ratios for the individual converters,
Fig. 2. Four possible combinations of input–output connections. (a) Input especially for the popular low output voltage applications.
parallel and output series. (b) Input parallel and output parallel. (c) Input series
and output parallel. (d) Input series and output series. This leads to more efficient power conversion [5].
4) Possibility of interleaving to reduce filter ratings and im-
prove transient performance (similar to input-parallel con-
output-series (IPOS) connection is well known and is presently verters)
used in many applications requiring high output voltages. Stan- However, in spite of several advantages of input-series con-
dard dc–dc converters, with independent output voltage con- nection, not much research has been reported on this configu-
trollers, can be connected in series at the output achieving equal ration. In [17], input-series and output-parallel (ISOP) connec-
sharing of output voltage and input current. However, in order tion has been implemented for a two-converter system, using a
to obtain the advantages of modularity such as redundancy, a charge control scheme with input voltage feed forward. In [18]
common output voltage loop or an output-voltage share bus is a three-loop control scheme, including an input voltage loop,
required. A scheme based on common output voltage loop and for ISOP connection, is presented. This paper improves upon
individual inner current loops is discussed in [5]. the earlier work by the authors [18], by proposing a new refer-
The input-parallel and output-parallel (IPOP) connection has ence scheme for input voltage loop that minimizes interactions
been the subject of vigorous research recently, fueled by the among the control loops, and by providing detailed analysis and
requirement of low voltage and very high current outputs. The design methods based on incremental negative resistance model.
challenge here is to ensure equal sharing of load current (hence, An advantage of the proposed scheme is that standard converters
input currents also) among the modular converters, in spite of using popular current mode control (peak or average) can be
small differences in the power stage and control parameters of used, without the need for explicit average input current control
the different converters, and finite differences in the impedances or charge control, as in [17].
of interconnections. Several control schemes, such as many Direct series connection of devices such as MOSFETs and
droop schemes [6]–[8], master–slave scheme [9], [10], demo- IGBTs for high input voltage applications has also been inves-
cratic current share scheme [11]–[13], and frequency based tigated [19]. However, the advantages of modularity such as
current share scheme [4], have been proposed to ensure active scaling and reconfiguration, as well as interleaving to reduce
load current sharing among the parallel converters. Paralleling filter requirement, are easily achieved in series connected con-
techniques that do not require direct interconnection of control verter modules, than in series power devices.
circuits of the various modules have also been investigated
[14]. An excellent review and comparison of different methods
for IPOP connection are given in [15]. II. ISOP SYSTEMS
This paper investigates the ISOP connection, which is well
B. Input-Series Connections
suited for applications with high input voltages and high load
The ability to connect converters in parallel or series only currents. A main trend in switch mode power supplies is the re-
at the output does not result in complete modularity. Given the quirement of very low output voltages with very high currents.
wide variety of input sources possible, such as rectified utility With the proposed ISOP connection for such applications, the
voltage, batteries and fuel cells, the input voltage to a system conversion ratio for each converter, and therefore, the turns-ratio
can also vary widely for different applications. Hence, it is es- of the power transformer, is much smaller. This can result in
sential to develop converters that can be connected in series at smaller leakage inductances and other parasitic components,
the input [Fig. 2(c) and (d)] also, with dynamic input-voltage thus improving efficiency.
sharing capability. The feasibility of ISOP connection, even with finite differ-
Apart from considerations of modularity, the input-series ences in various converter parameters, can be verified by consid-
connection has many other advantages such as the following. ering power balance in individual converters, under steady-state.
1) Enables use of metal oxide semiconductor field effect Fig. 3 shows a numerical example of how input voltage as well
transistors (MOSFETs) with low voltage rating, which as output current can be shared equally, in the presence of pa-
are optimized for very low , leading to higher ef- rameter mismatches such as different turns-ratios for the power
ficiency. At higher voltages, the of a MOSFET transformers. Under steady state, the input currents of the two
1464 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

Fig. 3. Feasibility of input voltage and output current sharing with mismatched
Fig. 4. Divergence of input voltages in an ISOP system without input voltage
transformer turns-ratio.
control.

converters are equal due to the series connection. If the input individual converters depending on the error in input voltage
voltages are also maintained equal by control, then the input sharing, is required. It may be noted that input voltage sharing
powers of the two converters are equal. Therefore, by power bal- automatically ensures output load current sharing, without the
ance (neglecting losses), the output powers of the two converters need for a dedicated load current share controller.
are equal. Since, the parallel connection at the output ensures
that the output voltages are equal, the output currents are also au-
tomatically made equal. If the parameters of the two converters III. PROPOSED CONTROL SCHEME WITH DYNAMIC INPUT
are identical, the duty ratios will be equal; for any mismatch in VOLTAGE REFERENCE
the parameters such as turns-ratio of the transformer, the duty
Fig. 5 shows the proposed control scheme for ISOP connec-
ratios will differ to correct for the mismatch, as illustrated in
tion of forward converters (the reset windings for the trans-
Fig. 3. It should be noted, however, that the above discussion
formers are not shown, for clarity). The proposed scheme and
assumes that the converters operate stably in steady state. The
the analysis that follows are valid for any buck derived isolated
necessary condition for stable operation is discussed in the fol-
dc–dc converter. As seen, the scheme consists of three control
lowing sections.
loops to ensure equal input voltage and load current sharing.
A single output voltage loop, which is common to all the con-
A. Need for Input Voltage Controller verters, provides the initial current reference, to all the in-
dividual, inner current loops. The compensator for the output
It is easy to appreciate that standard converters, without any voltage loop is denoted as . Each converter also has an indi-
special input voltage or load current sharing controllers, when vidual input voltage loop, which adjusts the above current ref-
connected in ISOP combination, will not result in stable opera- erence to its inner current loop, based on the error between the
tion. This is similar to the case of the widely used IPOP connec- reference input voltage and the actual input voltage of the par-
tion, where, in the absence of a load current sharing controller, ticular converter. The inner current loop can be of either peak
even a small mismatch in parameters can lead to wide variations current mode or average current mode with a compensator
in the individual output currents of the converters. as shown in Fig. 5. The inner current loop controls the duty ratio
For the ISOP connection, it is important to note that even of the converter such that the output inductor current equals the
with load current sharing controllers, similar to those used in adjusted current reference, referred to as .
IPOP connection, stable operation is not achieved. For example, The input voltage reference is chosen to be the average of all
consider again the ISOP connection shown in Fig. 3, and as- the converter input voltages, as given in (1). Note that the con-
sume that the system has an output current sharing controller. If verter input voltage is defined as the voltage across the input
the input voltage of converter 1, for example, increases slightly capacitor of the corresponding converter. It takes into account
due to a disturbance, the output current sharing controller re- the resonance due to the input LC filter. In particular, the sum of
duces the duty ratio of this converter, in order to maintain its the converter input voltages (capacitor voltages) is not dynami-
current equal to that of the converter 2. This reduces the av- cally equal to the total system input voltage,
erage input current drawn by converter 1, leading to further
increase in its input voltage. This process leads to a runaway
condition, resulting in large voltage stress across converter 1,
eventually destroying it. Fig. 4 shows the simulated waveforms (1)
corresponding to an ISOP connection with a load-current-share
mechanism, but without an input-voltage controller. The two Other possible references for the input voltage loop are
series connected converters use current mode control, with a and a constant reference. As will be explained
common output voltage loop providing the current reference to in Section V, the main advantages of the dynamic input voltage
both converters. As seen in Fig. 4, in spite of the common cur- reference proposed in this paper are that it minimizes the inter-
rent reference, the input voltages diverge. Hence, a dedicated action among the different control loops and results in better
input voltage control loop, which adjusts the duty ratios of the transient performance.
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1465

Fig. 6. Equivalent circuit based on negative resistance model for an ISOP


system withN converters.

Fig. 6 shows the equivalent circuit used to analyze the


converter ISOP system. Each converter is modeled as an
equivalent negative resistance, , connected to an input LC
filter. In the actual system, the input voltage loop adjusts the
reference to the output inductor current. The inductor current
follows the reference with a small but finite response time,
which together with the change in duty ratio translates into a
change in the input current. The dynamics of the input current
depend on the bandwidth of the inductor current loop and
Fig. 5. Proposed three-loop control scheme with dynamic input voltage
N
reference for ISOP connection of “ ” modular converters. dynamic changes in the duty-ratio, . In the equivalent circuit of
Fig. 6, the correction mechanism is modeled as an ideal current
source, , connected directly across
IV. ANALYSIS BASED ON NEGATIVE RESISTANCE MODEL OF the input capacitor of each converter. After the scaling factors
DC–DC CONVERTER due to transformer turns-ratio and the steady-state duty ratio,
, are taken into account, this is a valid, close approximation
For the purpose of analyzing the stability and performance at frequencies less than the bandwidth of the inner current
of the input voltage loop, each converter can be modeled as an loop, and when the magnitude of the correction currents at the
equivalent incremental negative resistance as seen from the ter- input is relatively small. The validity of the equivalent circuit
minals of the input capacitor. The incremental negative resis- is confirmed by the excellent matching of simulation results
tance model of a dc–dc converter is discussed in detail, espe- obtained using the above equivalent circuit representation and
cially in the context of designing input filters and understanding those corresponding to the full circuit model as discussed in
their effects on the stability of the overall system, in [20] and detail in Section IV.B.
[21]. Regardless of whether current-mode control or voltage- The value of the incremental negative resistance, of
mode control is employed, the input terminals of the converter the converter depends on the operating load and input voltage.
exhibit negative resistance characteristics, since a positive in- While analyzing the stability of the system with input voltage
cremental change in input voltage results in a proportionate, but control, the worst-case condition is the maximum load current
negative incremental change in the input current. In the case and minimum input voltage. Hence, the value of the negative
of voltage-mode controlled converters, the negative resistance resistance used in the model of Fig. 6 is as given in
model is accurate for frequencies up to the bandwidth of the
output voltage loop. For current-mode controlled converters, the
frequency range extends up to the bandwidth of the inner cur-
(2)
rent loop. A more accurate model for the converter is a negative
resistance in parallel with a capacitance C that depends on the
above bandwidths [20]. However, since the bandwidth of the where, is the minimum specified input voltage to an in-
current loop is much higher than that of the input voltage loop dividual converter, and is the maximum output power of
here, the parallel capacitance is neglected. an individual converter.
1466 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

A. Derivation of Stabilizing Controller Gain, K For stable operation, should have the same sign
Referring to Fig. 6, let us define the following: as . Therefore, the condition for stability is given
by

(3a) (8)

(3b) This condition for the minimum gain for the proportional input
voltage controller is independent of the capacitance or ESR
(3c)
values of the input capacitors, and is strictly valid even if the
impedances of the input capacitors of different converters are
where is the constant gain of the input voltage controller.
significantly different. It may be noted that while ensures
The objective is to maintain the input voltages, as seen at the
stability, higher values of result in faster correction in input
input capacitor terminals, of all the converters equal to each
voltages after a disturbance. However, this faster response is at
other, and therefore, equal to . The necessary condition
the expense of increased switch currents. For the dynamic input
for stability of the system shown in Fig. 6, is that for an increase
voltage reference scheme, the value of is limited mainly
in any converter input voltage, for example, , relative to the
by the switch ratings. Selection of suitable is discussed in
average input voltage, , the input current drawn by the
Section IV-C.
converter, (which is the sum of the current through the
As mentioned earlier, in the actual system input voltage dif-
negative resistance model and the correction current) should in-
ferences are corrected by adjusting the output inductor currents
crease, relative to the average of the input currents drawn by all
of individual converters. The output inductor current and the ac-
the converters, , which is equal to . This en- tual correction current at the input are related by the turns-ratio
sures that the higher input current discharges appropriately of the power transformer, and the operating duty ratio. Con-
to reduce . sidering these two scaling factors, the value of minimum gain,
In terms of ac perturbation quantities, the condition is that for stability of the actual system is given by
should be in phase with . Note
that for ac analysis (9)

(4) where is the turns-ratio of the power transformer, and is


the steady state duty-ratio of the converter at the given operating
where, has a negative value given in (2). Also, the equiv- condition.
alent incremental negative resistance of each converter is as- It may be noted that though the paper has presented a scheme
sumed equal. From Fig. 6 with current mode control, it is possible to apply these principles
to voltage mode controlled converters as well. In this case, the
input voltage loop, instead of adjusting the current references,
will directly adjust the duty ratio of the individual converters.

B. Validation Through Simulation of a Two Converter System


Though (9) is valid for the general case of converters, for
(5) simplicity, further analysis, simulation and experimental results
in this paper are restricted to a two-converter ISOP system. The
Adding the expressions in (5) two-converter system is simulated using both the negative re-
sistance model, as well as the full large-signal average model,
in PSpice. The results match very closely, validating the anal-
ysis based on the simpler negative resistance model. The PSpice
schematic of the negative resistance model, similar to that of
Fig. 6, is shown in Fig. 7. The incremental negative resistance is
implemented by a controlled current source whose magnitude is
(6) inversely proportional to the converter input voltage. The input
capacitors are purposely made dissimilar in order to study the
performance of the proposed controller.
From (5) and (6) The schematic of the detailed, large signal average model is
shown in Fig. 8. The average model is obtained by replacing the
PWM switch of each converter by its ideal transformer model,
and . The turns-ratios of these ideal transformers
are dynamically varying and are equal to the instantaneous duty-
ratios, and , respectively, [22]. and are the power
(7)
transformers of the two converters with fixed turns-ratios. There
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1467

Fig. 9. Open loop gain for the input voltage loop.

For both the simulation models, the specifications of the


system and individual converters, and the values of components
used for power stage and controllers are the same as those of
the hardware prototype, which are detailed in Section VI.
For the two converter system

(10)

Fig. 7. PSpice schematic for a two-converter ISOP system based on negative (11a)
resistance model.

(11b)

For frequency domain simulation, in order to obtain a conve-


nient point for signal injection, the error voltage ,
referred to as , is considered as the variable to be controlled,
with the control reference being zero. By perturbing this refer-
ence, the frequency response plots of the two-converter system
can be obtained. This scheme is illustrated in the two schematics
shown in Figs. 7 and 8. In both the schematics, the open loop
transfer function for the input voltage control loop is given by
(12)

(12)

Fig. 9 shows the Bode plots of open loop gain , ob-


tained from both negative resistance model as well as full av-
erage model. The two models match very closely for frequen-
cies up to 10 kHz. As seen from the plots, the open loop gain
has an unstable pole (right half plane) at around 70 Hz. This
Fig. 8. PSpice schematic for a two-converter ISOP system based on full pole frequency is determined by the value of input capacitance
average model including the different control loops.
and the magnitude of the incremental negative resistance of the
converter. The gain, of the input voltage controller should be
is a common output voltage loop, individual average current chosen such that the closed loop gain defined in (13) is
mode inner current loops, whose references are adjusted by in- stable
dividual input voltage loops. The output voltage loop compen-
sator is designed to achieve a bandwidth of 5 kHz and the two (13)
inner average current loops are designed for a bandwidth of ap-
proximately 50 kHz. The structure of the compensators and the Fig. 10 shows the Bode plots of closed loop gain, for
values used are also shown in Fig. 8. different values of . As seen from Fig. 10, for ,
1468 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

Fig. 10. Closed loop Bode plots for the input voltage loop corresponding to stable and unstable values for gain, K .

Fig. 11. Bode plots corresponding to (v (S ))=(v (S )) at different values of gain, K.

the system is unstable, since the closed loop transfer function scheme will work well when the input dc voltage to the system
has an unstable pole (at around 20 Hz for this particular value is obtained by rectifying ac mains voltage.
of , where the magnitude drops at a rate of dB/decade Fig. 12 shows the time domain response in the individual
while the phase increases). For , the system is stable, input voltages when a step change of 20 V is applied to the
as seen from Fig. 10 (darker plots), thus validating the stability total system input voltage. Plots corresponding to both the neg-
conditions given in (8) and (9). ative resistance model and the full average model are shown.
The input voltage control loop has to correct for unbalances in As seen in Fig. 12(a), for , the system is unstable,
the individual converter input voltages caused by disturbances with the two converter input voltages diverging, resulting in a
such as a step change in total input voltage. Hence, a main run-away mode. For greater than, but close to , the
transfer function of interest for the input voltage control loop is system is stable, but it takes a long time for the correction in con-
, i.e., the response in the individual input verter input voltages, as shown in Fig. 12(b). For ,
voltages due to changes in the total system input voltage. This the two converter input voltages converge quickly as seen from
transfer function is obtained by keeping the reference to as Fig. 12(c). The oscillations in the individual input voltages in
zero, and perturbing the total input voltage. The corresponding Fig. 12 are due to the resonance in the input LC filters, and
Bode plots obtained using negative resistance model and full av- do not reflect on the stability margins of the input voltage con-
erage model are shown in Fig. 11, for three different values of troller. The objective of the input voltage controller is not to re-
. As seen, for , there is an unstable pole, which is duce these oscillations, but only to ensure that the total voltage is
eliminated at higher values of . Since, this is a response to dis- shared equally between the two converters. It may be observed
turbance input, the gain of the transfer function should be low that even in a single converter system the input voltage oscilla-
for better disturbance rejection, which is achieved by increasing tions occur for a step change in input voltage.
. Also, note that at 120 Hz the gain of the disturbance transfer Though in most applications the converters will be designed
function is low ( dB), which implies that the proposed to share the input voltage equally, it is possible to design the
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1469

Fig. 13. Response in converter input voltages when the reference for v 0
v changes from 0–10 V. Note that the commanded unequal sharing of input
voltages results in corresponding unequal load current sharing.

with higher values of . As discussed in Section V, the dynamic


reference scheme ensures that higher value of does not in-
terfere with output voltage loop. However, higher results in
larger switch currents momentarily, during input voltage distur-
bances. Since, in most designs, MOSFETs are usually chosen
with a significantly higher current rating than required (in order
to reduce ), it is possible to choose high values of .
The actual choice of depends on the expected tolerances in
the input capacitor values, the characteristic impedance of the
input LC filter and the magnitude of disturbance expected in the
total input voltage. The equivalent circuit of Fig. 6 will be useful
in selecting appropriate value for .

V. EFFECT OF INPUT VOLTAGE LOOP ON THE OUTPUT


VOLTAGE CONTROL
The main advantage of the dynamic reference scheme is that
the input voltage loop does not interfere with the dynamics of
output voltage control. The output voltage depends on the sum
of the individual output inductor currents. In the dynamic ref-
erence scheme, the sum of the adjustment currents is zero, i.e.,
. In particular, for the two-converter system,
. Since the contribution to the total output current
Fig. 12. Response in the individual converter input voltages to a step change from the input voltage control loop is zero, the output voltage is
of 20 V in total input voltage. (a) K = 0:8K . (b) K = 1:25K . (c) not affected by the input voltage correction. Hence, the output
K = 12K .
voltage controller can be designed without considering the
input voltage loop, and the design procedure is similar to that
input voltage loop such that the converters share the input
of a single converter system.
voltage at any other desired ratios too. By power balance, the
Fig. 14 shows the final output voltage and individual output
converter designed for lower input voltage will also provide
inductor currents, corresponding to a step change in the system
lower output current. Fig. 13 shows the response in input
input voltage. These simulation results correspond to the full
voltages when the reference to is changed from zero
average model shown in Fig. 8. As seen, the individual inductor
to 10 V. The gain, used for this simulation is . The
currents are adjusted to correct for the differences in the input
response time obtained corresponds well with the bandwidth
voltage, but in such a way that their sum is not affected. As a
of the closed loop Bode plots, similar to that shown in Fig. 10.
result, the change in output voltage is negligible (about 0.02%),
Fig. 13 also shows the output inductor currents (average model)
and is similar to the response of a single converter system to a
corresponding to the above command. As seen, the converters
step change in input voltage.
share the load currents in the same ratio as that of input voltage.

C. Selection of VI. EXPERIMENTAL RESULTS


From the above discussion, it is clear that should be at least The proposed control scheme is validated on a hardware pro-
higher than , and higher values of result in faster cor- totype comprising of two forward converters connected in ISOP
rection in the input voltages after a disturbance. Comparing the configuration. The specifications for the full system are:
plots Fig. 12 with different gains , the peak overshoot in the 1) input voltage: 160–200 V dc (to be shared equally by the
input voltage ( for the example considered) also decreases two converters);
1470 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

Fig. 14. Output voltage and output currents corresponding to step change in
total input voltage.

Fig. 15. Experimental waveforms: converter input voltages and output


inductor currents under steady state. (40 V/div, 2 A/div, and 10 s/div).

2) output voltage: 48 V dc;


3) maximum output current: 8 A (to be shared equally by the
two converters);
4) switching frequency: 170 kHz (each converter).
The values of the power stage components as well as the
compensators for the various control loops are same as those
shown in Fig. 8. Note that to verify the reliable operation and
Fig. 16. Response in individual input voltages for a step change of 20 V in
effectiveness of the proposed control scheme in the presence the total input voltage. (5 V/div and 0.5 ms/div). (a) K = 8K . (b) K =
of mismatches in the converter parameters, the input filter 12K .
capacitors of the two converters are purposely chosen to be
very different (33 and 66 F, respectively). The turns-ratios of step change in system input voltage. Fig. 17(a) shows the
the two power transformers are also not identical. Peak current output voltage in expanded (ac) mode, and as expected for the
mode control using UC2844 is employed for the individual dynamic reference scheme, the output is almost unaffected,
inner current loops. The two control integrated circuits (ICs) with the peak deviation less than 200 mV or 0.5%. The output
are synchronized, though this is not an essential requirement inductor currents corresponding to the above input change is
for the proposed control scheme. shown in Fig. 17(b). As seen, the increase in is compensated
Fig. 15 shows the individual input voltages and the inductor by decrease in .
currents of the two converters respectively, under steady state. Fig. 18 shows the response to step change of 2 A in the load
As seen, the input voltage as well as the load current is current. Fig. 18(a) shows that the change in individual input
shared perfectly equal by the two converters. Fig. 16 shows voltages corresponding to the step load change is small (less
the response in the converter input voltages to a step change of than 200 mV or 0.2%). The converters continue to stably share
20 V in the total input voltage of the system, corresponding to the voltages after the disturbance. Fig. 18(b) shows the output
two different values of gain, . As seen, higher gain results in voltage corresponding to the above step change in load. The
quicker correction in the converter input voltages. The results peak deviation is less than 0.5% and the output voltage recovers
match very closely with the simulation results shown in Fig. 12. within about 4 ms with an exponential response. The perfor-
Fig. 17 shows the response at the output side to the above mance is similar to that of a single converter system with cur-
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1471

Fig. 18. Response to a step change of 2 A in the load current. (a) Converter
Fig. 17. Response to 20-V step change in total input voltage. (a) Output input voltages (400 mV/div, 5 A/div, and 10 ms/div). (b) Output voltage
voltage (V 0 40 V/div, V 0 100 mV/div with ac coupling and 5 ms/div).
V 0
(200 mV/div in ac mode and 5 ms/div).
(b) Individual input voltages and individual inductor currents ( 10 V/div,
0 K
iL 2 A/div, and 0.5 ms/div). in both cases is 8 K .
VII. DISCUSSION
rent mode control. Hence, the presence of input voltage loop As discussed in Section I, input-series connection has several
with dynamic input voltage reference scheme, does not affect advantages in many applications. However, just as was done
the performance of the output voltage control loop. for its dual configuration—IPOP connection, concerted research
Fig. 19 shows the individual input voltages and the individual efforts are needed before the use of this configuration becomes
output currents during start-up of the system. Until the total widespread. This paper has only established the feasibility of
input voltage reaches the minimum specified value of 160 V, the ISOP connection, and proposed a simple control scheme to
the two converters do not regulate and operate at the maximum ensure input voltage sharing. Some of the main topics for future
duty ratio of 0.5. During this period, there is a slight mismatch in research in this area are outlined below.
the two individual input voltages, due to mismatch in the trans- True Modularity: The control scheme proposed in this
former turns-ratio of the two converters. After the total input paper has an output voltage loop that is common to all the
voltage increases above 160 V, the converters begin to regulate, converters. Therefore, the individual converter modules are not
and as seen, the input voltage control is able to ensure equal self-contained, and are not identical. The presence of a single,
input voltage sharing. central controller may compromise the reliability of the overall
1472 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 6, NOVEMBER 2004

rection currents is zero, and hence the input voltage correction


has no effect on the dynamics of output voltage control. This
allows the different control loops to be designed independently,
and also makes it possible to use large gains for input voltage
loop.
The stability analysis, controller performance and the sug-
gested design methods have been verified through numerical
simulation, both in frequency domain and in time domain. The
proposed scheme is also validated experimentally on an ISOP
system comprising of two forward converters and the results
have been presented extensively. More, concerted research ef-
forts are needed before the use of input-series and output-par-
allel configuration becomes widespread.

REFERENCES
[1] T. F. Wu, K. Siri, and C. Q. Lee, “Reliability improvement in parallel
connected converter systems,” in Proc. IEEE Industrial Electronics,
Control Instrumentation Conf. (IECON’91), vol. 1, 1991, pp. 429–434.
[2] L. Thorsell and P. Lindman, “Reliability analysis of a direct parallel
Fig. 19. Individual input voltages and individual output currents during startup connected n+1 redundant power system based on high reliable dc/dc
of the converters (40 V/div, 2 A/div, and 10 ms/div). modules,” in Proc. IEEE Int. Telecommunications Energy Conf. (INT-
ELEC’88), 1988, pp. 551–556.
[3] K. Siri, C. Q. Lee, and T. F. Wu, “Current distribution control for parallel
connected converters—Part I,” IEEE Trans. Aerosp. Electron. Syst., vol.
system. Hence, research is presently being done to develop 28, pp. 829–840, July 1992.
self-contained, identical modules that have individual output [4] D. J. Perreault, R. L. Selders, and J. G. Kassakian, “Frequency-based
voltage loops whose reference is adjusted by their respective current-sharing techniques for paralleled power converters,” IEEE
Trans. Power Electron., vol. 13, pp. 626–634, July 1998.
input voltage controller. [5] S. N. Manias and G. Kostakis, “Modular DC–DC convertor for high-
Protection Issues: In case of failure of a converter, it needs output voltage applications,” Proc. Inst. Elect. Eng., vol. 140, no. 2, pp.
to be isolated from the rest of the system. At the output side, 97–102, Mar. 1993.
[6] B. T. Irving and M. M. Jovanovic, “Analysis, design and performance
the protection is similar to that employed in IPOP configura- evaluation of droop current sharing methods,” in Proc. IEEE Applied
tion. However, at the input side, if the switch fails open, then Power Electronics Conf. (APEC’00), 2000, pp. 235–241.
the converter needs to be shorted, so that the rest of the system [7] J. W. Kim, H. S. Choi, and B. H. Cho, “A novel droop method for
converter parallel operation,” IEEE Trans. Power Electron., vol. 17, pp.
shares the total input voltage. Research is also needed to achieve 25–32, Jan. 2002.
hot-swapping capability for the converter modules. Another im- [8] J. S. Glaser and A. F. Witulski, “Output plane analysis of load-sharing in
portant issue is the isolation requirements for the power trans- multiple-module converter systems,” IEEE Trans. Power Electron., vol.
9, pp. 43–50, Jan. 1994.
formers, and for sensing the different converter input voltages. [9] Y. Panov, J. Rajagopalan, and F. C. Lee, “Analysis and design of N
Interleaving: Similar to IPOP connection, interleaving the parallel DC–DC converters with master–slave current control,” in Proc.
converters can result in significant reduction in the output ca- IEEE Applied Power Electronics Conf. (APEC’97), vol. 1, 1997, pp.
436–442.
pacitor current as well as the ripple in the input current of the [10] M. Jordan, UC3907 load share IC simplifies parallel power supply de-
system. sign, in Unitrode Applicat. Note U-129, 2004.
[11] K. T. Small, “Single wire current share paralleling of power supply,”
U.S. Patent 4 717 833, Jan. 1988.
VIII. CONCLUSION [12] V. J. Thottuvelil and G. C. Verghese, “Analysis and control design of
paralleled DC/DC converters with current sharing,” IEEE Trans. Power
Ability to connect isolated dc–dc converters in series at the Electron., vol. 13, pp. 635–644, July 1998.
input, with dynamic voltage sharing, is an essential step toward [13] M. M. Jovanovic, “A novel, low-cost implementation of ‘democratic’
realizing truly modular power system architecture. The input se- load current sharing of parallel converter modules,” IEEE Trans. Power
Electron., vol. 11, pp. 604–611, July 1996.
ries connection has other significant advantages such as the pos- [14] D. J. Perreault, K. Sato, R. L. Selders, and J. G. Kassakian,
sibility of using MOSFETs efficiently for high input-voltage ap- “Switching-ripple-based current sharing of paralleled power con-
plications, and smaller conversion ratios for low output voltage verters,” IEEE Trans. Circuits Syst. I, vol. 46, pp. 1264–1274, Oct.
1999.
applications. This paper has demonstrated input voltage and [15] S. Luo, Z. Ye, R. L. Lin, and F. C. Lee, “A classification and evaluation
load current sharing in converters connected in input-series and of paralleling methods for power supply modules,” in Proc. IEEE Power
output-parallel configuration. Electronics Specialists Conf. (PESC’99), 1999, pp. 901–908.
[16] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics: Con-
The proposed control scheme has an input voltage loop verters, Applications, and Design, 3rd ed. New York: Wiley, 2003, p.
adjusting the current reference provided by a common output 589.
voltage loop to the inner current loops. A simple proportional [17] J. W. Kim, J. S. You, and B. H. Cho, “Modeling, control, and design
of input-series–output-parallel-connected converter for high-speed-train
controller is sufficient for the input voltage loop. The minimum power system,” IEEE Trans. Ind. Electron., vol. 48, pp. 536–544, June
value of the gain for stability is determined by the incremental 2001.
negative resistance of the individual converters. The choice of [18] A. Bhinge, N. Mohan, R. Giri, and R. Ayyanar, “Series-parallel connec-
tion of DC–DC converter modules with active sharing of input voltage
dynamic input voltage reference, equal to the average of the and load current,” in Proc. IEEE Applied Power Electronics Conf.
individual converter input voltages, ensures that the sum of cor- (APEC’02), vol. 2, 2002, pp. 648–653.
AYYANAR et al.: ACTIVE INPUT-VOLTAGE AND LOAD–CURRENT SHARING 1473

[19] C. Gerster, “Fast high-power/high-voltage switch using series-con- Ramesh Giri received the B.S. degree from the
nected IGBTs with active gate-controlled voltage balancing,” in Proc. P.S.G College of Technology, Coimbatore, India, and
IEEE Applied Power Electronics Conf. (APEC’94), 1994, pp. 469–472. the M.S. degree from the Arizona State University,
[20] M. F. Schlecht. (2004) Input System Instability. SynQor Tempe.
Application Note: PQ-00-05-1. [Online]. Available: He has been a Switched Mode Power Supply
http://www.synqor.com/pdf/appnt_System_Instability.pdf Design Engineer in the industry for over 15 years.
[21] R. D. Middlebrook, “Input filter considerations in design and application He is currently a Corporate Applications Engineer
of switching regulators,” in Proc. IEEE Industry Applications Soc. (IAS) with Maxim Integrated Products, Sunnyvale, CA,
Meeting, 1976, pp. 366–382. and is responsible for defining power management
[22] V. Vorperian, “Simplified analysis of PWM converters using the model integrated circuits.
of the PWM switch: Part I—Continuous conduction mode,” IEEE Trans.
Aerosp. Electron. Syst., vol. 26, pp. 490–496, May 1990.

Raja Ayyanar (S’97–M’00) received the M.S. de- Ned Mohan (S’68–M’73–SM’91–F’96) is Oscar A.
gree from the Indian Institute of Science, Bangalore, Schott Professor of Power Electronics at the Univer-
India, and the Ph.D. degree from the University of sity of Minnesota, Minneapolis, where he has been
Minnesota, Minneapolis. since 1976. He has many patents and publications
He has been an Assistant Professor with Arizona in the field of power electronics. He coauthored
State University, Tempe, since August 2000. He Power Electronics: Converters, Applications and
has many years of industrial experience designing Design and authored Electric Drives: An Integrative
switch mode power supplies. His current research Approach and Advanced Electric Drives Analysis,
interests include topologies and control techniques Control and Modeling Using Simulink.
for modern dc–dc converters, new pulse—width Dr. Mohan received the Distinguished Teaching
modulation techniques for drives, and power elec- Award from the Institute of Technology, University
tronics applications in power systems. of Minnesota.

View publication stats

You might also like