Professional Documents
Culture Documents
Headway BWMS - Technical Manual
Headway BWMS - Technical Manual
(Short manual for basic knowledge, for all details read the full manual)
This documentation is short manual for basic knowledge, for more details please read the User Manual.
Table of Contents
1 Overview .................................................................................................................................................. 4
4 Troubleshooting ..................................................................................................................................... 21
4.1 Filter & FCB Alarms ................................................................................................................. 21
4.1.1 Filter Differential Pressure High Alarm ......................................................................... 21
4.1.2 Filter Motor Error Alarm ................................................................................................ 25
4.1.3 Back-Flushing Pump Error Alarm .................................................................................. 26
4.2 EUT & PE Alarms ..................................................................................................................... 27
4.2.1 EUT temperature communication fail Alarm ................................................................. 27
4.2.2 EUT temperature high Alarm ......................................................................................... 27
4.2.3 EUT leak sensor Alarm ................................................................................................... 28
4.2.4 EUT Pressure Switch Alarm ........................................................................................... 29
2 / 54
4.2.5 EUT Power Communication Fail Alarm ........................................................................ 30
4.2.6 EUT Power “ON” Error Alarm....................................................................................... 33
4.2.7 EUT Power in Manual Mode Alarm ............................................................................... 33
4.2.8 EUT Power Abnormal Alarm ......................................................................................... 34
4.3 MU & MCB Alarms .................................................................................................................. 36
4.3.1 TRO Communication Alarm........................................................................................... 36
4.3.2 TRO Status: No Intake Water Alarm .............................................................................. 36
4.3.3 TRO Status: Purge Is Slow Alarm .................................................................................. 37
4.3.4 TRO Status: Purge Is Clogged Alarm ............................................................................. 37
4.3.5 TRO Pressure Abnormal Alarm...................................................................................... 37
4.3.6 Salinity Meter Communication Fail Alarm .................................................................... 38
4.3.7 Salinity low (below 0.85 PSU) Alarm ............................................................................ 38
4.4 NU Alarms ................................................................................................................................. 39
4.4.1 Low Level (Neutralization Unit) Alarm ......................................................................... 39
4.4.2 Low Level (Neutralization Unit) Alarm ......................................................................... 39
4.4.3 NU Pump dry run protection........................................................................................... 40
4.4.4 NU Pump Error Alarm .................................................................................................... 40
4.5 Flow meter Alarms .................................................................................................................... 41
4.5.1 Flow meter Communication Alarm ................................................................................ 41
4.5.2 High Flow Rate Alarm .................................................................................................... 41
4.5.3 Low Flow Rate Alarm .................................................................................................... 41
4.6 Valves Alarms ............................................................................................................................ 42
4.6.1 Filter Angle Valve (FV2) Communication Fail Alarm................................................... 42
4.6.2 FV2 Error Alarm ............................................................................................................. 42
4.6.3 Valve 1/2/3/4/5/6 Alarm ................................................................................................. 43
4.7 CL、PDU、RC & MCB Alarms .............................................................................................. 43
4.7.1 CL Lost Power Alarm ..................................................................................................... 43
4.7.2 Emergency Switch is Pressed Alarm .............................................................................. 43
4.8 Operation & Processing Alarms ................................................................................................ 44
4.8.1 Repair / Maintenance Alarm ........................................................................................... 44
4.8.2 Emergency ON / Bypass ON Alarm ............................................................................... 44
4.8.3 Ballast TRO Low And High Alarm or Ballast TRO Adjust Overtime Alarm................ 44
5 Notes ...................................................................................................................................................... 54
3 / 54
1 Overview
The BWMS is single treatment, this means the ballast water is fully treated during ballasting. The ballast
water can be Sea water / Brackish water / Fresh water.
When the ballast mode is selected, the water is treated by a 50-micron filter and the EUT. The EUT uses
the process Electro Catalysis to form a large amount of Hydroxyl radicals (∙OH). These Hydroxyl
radicals (OH) exist for a short amount of time, during this time they will react with the (micro) organisms
which are left in the ballast water and kill them. A by-product of the Electro-Catalysis process is a small
amount of TRO (Chlorines) which is measured by the Monitor Unit. The TRO target value is between 1.8
ppm and 2.2 ppm and is used to regulate the current output to the EUT.
When the de-ballast mode is selected, the ballast water goes directly overboard, only the TRO value will
be measured. The TRO value during de-ballasting must be lower than 0.1 ppm. If the TRO value exceeds
0.1 ppm the Neutralization Unit will start automatically and inject to “Sodium Thiosulfate Pentahydrate”
to neutralize the TRO.
4 / 54
2 System Operation
The screen above you see on the control unit (CL) or on the remote-control panel (RC) when you
turn on the power distribution unit (PDU) and press start on the control unit (CL).
PIPE
This screen shows the general flow diagram of the Ballast Water Management System. When
the system is active you can see the following data on this screen:
System Mode, Valve Status, TRO Value, Flow, EUT Power and Current, Salinity, GPS data
and when the Back-Flushing / Neutralization / Ballast-pump is active.
In this screen you can choose additional modes, generally this will be the “repair” mode.
ALARM
This screen shows the “Real Time Alarms”, “Historical Alarms” and “Warnings” This screen
includes a “Help” function which is useful for trouble shooting.
5 / 54
LOG
This screen shows the “Operation log”, “Data record” and “Valve log”
The log is saved on a SD card inside the screen.
INFO
This screen shows several topics (System principle, Ballast On/Off, De-Ballast On/Off,
By-pass On/Off, Maintenance MU/NU, how to copy the log files, Company info.
SETTING
Here you can see the general configuration for your BWMS. (Settings can only be viewed!)
Here you can make a copy of the log files.
6 / 54
2.3 De-Ballasting Process
7 / 54
2.5 Coping the System Log
Step Operation
Plug a USB disk(lower than 8GB and file system is“FAT32”) into the USB port located on
Turn on the power of the Power Distribution Unit and the Control Unit.
The system will make a copy to the SD card automatically and will mention at information
if the copy was successful. (in normal situations)
Than power off the system and take out the USB card,
4
If you no use the USB card ,put the SD card in a computer and copy the excel files
5 Important: Do not delete files from the SD card.
In case of a re-occurring alarm or problem these logs can be send to Headway.
6
We can analyses the log and send our recommendations
8 / 54
2.6 Parameter Setting
Step Operation
1 Turn on the power of the Power Distribution Unit and the Control Unit.
9 / 54
3 System Maintenance
The raw water flow into the filter from the inlet, through the filter screen, then flow out from the
outlet.
As the accumulation of various contaminants inside the screen, the filtration channel is blocked.
And the differential pressure between inlet and outlet increases gradually. When the pressure
reaches to the pre-set value, the system will start the stroke motor and booster pump automatically.
Meanwhile, the shaft with driving device and suction nozzle will rotate and move back and forth
horizontally inside the screen. And at the same time, the cleaning device and the shaft run
synchronously. And the movements are correspondingly. At the premise without interrupting
producing water, it can run the cleaning function by a small part of the product water. The cleaning
water flows through the filter screen, together with the impurities from the filter screen. And they
10 / 54
are quickly inhaled into the dirt collector by the nozzle, sent to the shaft, and finally discharged from
the drain.
After one cleaning process, the pressure differential is down. All the parts recover to the initial state.
And the system will go back to the normal operation state again.
When the filter is running properly, there is no need to wash the filter element manually. The
element will be cleaned during the automatic back flushing.
If the intervals of the automatic back flushing get shorter, this indicates that the filter element is
blocked more and more by impurities.
If the pressure difference keeps on raising to the pre-set alarm value, the filter element needs to
be washed manually.
Note
11 / 54
Steps for replacing the filter element
Step Operation
1 Power off the system, drain the water, disconnect the cables.
12 / 54
6 When the cover is lifted (See view A)
7 Loosen 2 M8 screws (item4) so the ring (item5) falls down to shaft sleeve (item6)
8 If the ring (item5) is on the shaft sleeve (item6), tighten (2)M8 screws (item4).
13 / 54
Remove the bolts around filter top cover to remove top cover and move out driving
12
shaft.
When the filter element is being cleaned with a high-pressure water gun, the
14
pressure must not exceed 60 bar and the distance between the nozzle of the water
gun and the filter element must not be less than 200 mm
17 Before installation check the filter element, if there is any damage replace this part.
18 Put everything back together in a reverse order and restart the system.
19 Make sure the limit switches are correctly mounted and connected!
Generally, after the filter has worked for 300 hours or once a year, the drain must be opened. In
this way big impurity particles inside the lower shell of the filter will flush out.
When the slag is being removed, the vent at the upper shell of the filter must be opened. After
the slag is removed, the vent can be closed.
14 / 54
3.1.3 Filter Maintenance(HMT-F)
When the filter is running properly, there is no need to wash the filter elements manually. The
elements will be cleaned during the automatic back flushing.
this indicates that the filter elements are blocked more and more by impurities. If the pressure
difference keeps on raising to the pre-set alarm value,
(pressure difference > 0.6 bar = start back flushing, pressure difference >1.5 bar = overpressure
alarm)
STEPS FOR CLEANING OR REPLACING THE FILTER ELEMENTS (see drawings below)
15 / 54
The first oil change must be done after about 2000 hours or 3 years at the longest.
The following oil changes must be done every 3 year or every 10000 hours.
16 / 54
3.2 Monitoring Unit Maintenance
The MU is a very important part of the BWMS, all the feedback from the MU is used by the BWMS
to make the right adjustments so it works correctly.
During the commissioning of the BWMS a lot of time is spent for the correct adjustment of the MU,
so don’t change the settings, if the MU is not working properly contact the manufacturer.
17 / 54
3.2.2 Replacing the Indicator Reagent
1 Open the MU
Take out the reagent kit. Open it and take one small white bottle and one brown
2
DPD tube.
3 Open the small white bottle and add 100 ml deionized water, close it and shake it.
4 Open the small white bottle and add one brown DPD tube, close it and shake it.
Open the small white bottle and add deionized water until it is filled up to the bottle
5
neck.
Steps Operation
When a reagent kit is ordered, it contains 1 buffer and 4 indicator bottles. Take the
1
big buffer bottle and add 400 ml deionized water, close it and shake it.
2 Open the MU
18 / 54
3.3 Neutralization Unit Maintenance
When the NU is running properly, there is no need for maintenance. After you receive an alarm
“Low Level Alarm (Neutralization Unit)”, the NU must be refilled.
Steps Operation
Get the right amount of Sodium Thiosulfate Pentahydrate (see list below), open the
1 feeding port cover of the NU, put all the Sodium inside the NU and close the feeding
port cover.
2 Check if the freshwater supply valve to the NU is open.
Press “mixing”, the NU will automatically add fresh water until the right level is
3 reached, the NU will mix the Sodium Thiosulfate Pentahydrate and the water for 10
minutes.
19 / 54
Size old NU Amount Sodium BWMS Model Size new NU Amount Sodium
20 / 54
4 Troubleshooting
⑤Turn off the power of the backflushing pump (QF12 in PDU) and power on
the system. After the control unit is started, you can see that the Filter Control
Box is already working. Press the Manual backflushing button and repeat the
automatic cleaning of the filter element more than 5 times;
After the above operation, the sewage needs to be discharged:
(1). Turn on QF12(for back flushing pump) in the PDU, turn off QF52(for
cleaning pump), turn on the power of the backflushing pump, and turn off the
cleaning pump at the same time
(2). Open the manual valve of the backflushing pipeline, press the manual
backflushing button after the system is powered on, discharge most of the
sewage through the sewage pipe, and discharge the remaining sewage in the
filter from the slag outlet into the sewage well;
Restore the power supply of the QF52 cleaning pump, open the filter outlet
manual valve to the preset optimal flow position (about 5%-20%) to start
ballasting according System reduced flow operation.
If the filter still has a high-pressure difference after cleaning with clean water,
you can choose to soak the filter element directly with oxalic acid. The soaking
time is generally about 2 to 6 hours. Generally, oxalic acid is selected as
H2C2O4.2H2O≥99.5%
If the above mechanical and electrical faults have been eliminated and the
pressure difference continues to rise, it may be that the filter element
Remark
is blocked and the filter element needs to be stopped for self-cleaning
or manual cleaning.
4.1.2 Filter Motor Error Alarm
Spares:
Remark
4.1.3 Back-Flushing Pump Error Alarm
Remark
4.2 EUT & PE Alarms
Solution:
Remark
Description: The seawater temperature inside the EUT is too high (above 45 degree)
Special Tools:
1,If the EUT is installed horizontal and higher than the ballast tanks, falling water can
cause the EUT to not be completely filled with water.
①In many cases backpressure can be created with valve HMV 1 or a valve to the
ballast tanks to make sure the EUT is completely filled all the time.
②During installation also measures should have been taken to make sure the EUT is
completely filled all the time.
Solution:
2,Flow is too low
①Find the reason for the low flow and make sure the flow is adjusted to system
capacity.
3,Temperature sensor
①Check the sensor, if it is broken replace it.
Remark
Description: The EUT leak sensor detects water or leak sensor is broken
Special Tools:
1,The sealing parts of the EUT anodes are aging.
①Make sure the BWMS is completely powered off. Open the cover of the EUT. Check
the origin of the leakage and replace relevant parts.
2,The leak sensor
①Check the sensor, if it is broken replace the sensor.
3, The leak sensor needs coil protection
Solution:
Remark
4.2.4 EUT Pressure Switch Alarm
Solution:
ERP NO. Name type Quantity Remark
Spares:
Remark
2,If there is a serial port tool on board, you can detect the data of 94,95, and the baud rate is 9600.
If you don't have serial port tools, please check the EUT power REMOTE/PANEL lamp for flicker, as
follows: If flicker, it can be preliminarily determined there is data communication.
Solution:
3,When checking item 2, if there is no power in the Control Box of PE, it is necessary to check the power
supply of the PE and the internal condition of the PE at this time.
(1) For EUT power supply query, please refer to the following drawing: (it also attached in PDU)
(2) If the 440VAC power supply of PE is normal, it is necessary to check the internal 150W
switching power showed below,pls check its input and output are normal.
4,If the above inspections are normal, it may be caused by the program of Control Unit(this possibility is
very low), which needs the assistance of professional boarding.
5,In the above inspection, if any device is found damaged, please refer to the following ERP application
parts; When replacing, record the wires number mark then replace it directly.
Remark
4.2.6 EUT Power “ON” Error Alarm
Remark
Remark
Sample cuvette has No flow in Monitor Check the drain pipe. If this one is blocked there
slow purge (PURG) Unit drain pipe will be slow or no purge
Sample cuvette has no No flow in Monitor Check the drain pipe. If this one is blocked there
purge (NPRG) Unit drain pipe will be slow or no purge
The control unit does Loose wire Check the cable connections to see if they are
not detect the signal. (signal line) correct and reliable.
Information is displayed Make a copy of the log and send it to the
Other faults
on the salinity meter. manufacturer if problem remains
Loose wire Check the cable connections to see if they are
(power supply) correct and reliable.
If the Monitor Unit (MU) is Ex-Proof the Monitor Unit
No information is Control (MUC) controls the power supply. The
Power supply
displayed on the salinity start-up time for the MUC is 18 minutes. For the
interrupted
meter. Ex-Proof MU it is important to have air supply
to create the necessary overpressure in the MU.
Make a copy of the log and send it to the
Other faults
manufacturer if problem remains
Salinity is low Salinity is low If the ballast water has a salinity below 3 PSU the flow
should be regulated to the “standard flow”.
(the “standard flow” is mentioned in “settings”)
If a mixing pump is installed and the salinity is below
0.85 PSU it will start to add seawater (with a high
salinity) from a storage tank to the ballast pump
(intake) until ballasting is stopped. The amount of
seawater which is mixed can be regulated with a
discharge valve behind the mixing pump. If the salinity
in the ballast water is above 0.85 PSU after mixing the
seawater this alarm will disappear.
4.4 NU Alarms
The liquid level in the Refill the neutralization unit with Sodium Thiosulfate
neutralizer has reached Pentahydrate.
the low level For right amount see maintenance NU
Check the cable connections to see if they are
Neutralization unit has The liquid level is correct and reliable.
Low level alarm alright but there is alarm
anyway The level sensor or floater is broken, if so replace
relevant parts.
Make a copy of the log and send it to the
Other faults
manufacturer if problem remains
Flow is lower than the Adjust backpressure and regulate flow to system
minimum system Backpressure too high capacity with valve HMV1
capacity The filter is clogged, start the backflush cycle or
clean the elements
Loose wire Check the cable connections to see if they are correct
(signal line) and reliable.
The control unit does
Loose wire Check the cable connections to see if they are correct
not detect the signal.
(power supply) and reliable.
The angle valve is not
Valve FV2 does not Check valve, make sure there is hydraulic or air supply
working
open or close to open the valve
Valve broken Replace broken parts
Loose wire Check the cable connections to see if they are correct
The angle valve (signal line) and reliable.
position is not correct. Loose wire Check the cable connections to see if they are correct
During Ballast-On this (power supply) and reliable.
valve should be open at Valve FV2 does not Check valve, make sure there is hydraulic or air supply
least 30% but it is not. open or close to open the valve
Valve broken Replace broken parts
4.6.3 Valve 1/2/3/4/5/6 Alarm
Power failure No power Check the power supply and restart the BWMS.
Something is wrong
with the BWMS but The Emergency On Fix the problems with the BWMS and select
Ballasting or De- button is selected normal operation again.
Ballasting is needed
4.8 Operation & Processing Alarms
Something is wrong
with the BWMS but The Emergency On Fix the problems with the BWMS and select normal
Ballasting or button is selected operation again.
De-Ballasting is needed
4.8.3 Ballast TRO Low And High Alarm or Ballast TRO Adjust
Overtime Alarm
Claim: Ballast TRO Low And High Alarm or Ballast TRO Adjust Overtime Alarm
1,TRO Low alarm (ballast)
Description: 2,TRO High alarm(ballast)
3,TRO2 High alarm(Deballast)
Special
Tools:
1,First of all, make sure that TRO reagent is not expired, so as not to guarantee,
replace the new reagent.
Attention: Once mixed, the indicator reagent has an expected life of 90 days if kept
Solution: under 25°C and 30 days if kept under 40°C.
2,Run and check the unit equipment, check the water intake in the reaction room,
check whether the flow rate of CLX is OK, details as follows:
3, The above is the setting of TRO . There is also a manual valve at the outlet of the
monitoring unit to improve the pressure in the monitoring unit and manual valve in
CLX, so that TRO can get water better. If have “TRO status: No intake water
alarm”, reduce the outlet valve opening. Meanwhile, do not forget to clean the water
pipe and TRO filter screen in the monitoring unit.
4, After finish last step, if also have alarm, remove the inlet manual valve to make
sure the water can flow out from the inlet pipe.
5, Confirm the below 4 electromagnetic valves is OK. And confirm the drain water for
sample is normal. If sampling water is obstructed, Open the screw, keep the Seal
Ring well, and please note that the electromagnetic valves water direction.
6, After this, can try step2 again and run BWTS again.
7,To observe whether the TRO meter cuvette can be filled with water during detectio
n. During normal operation the TRO METER will run through a timed cycle. A
simplified cycle will consist of the following sequences:
✓ Flushing – continuous sample flow
✓ Purging – PURGE valve opens
✓ Zeroing – no flow with cuvette full
✓ Adding Reagents – one pulse of the reagent pump
✓ Mixing with sample – sample flow pulses in
✓ Reading resulting sample – no flow with cuvette full
✓ Purging – PURGE valve opens to remove reacted sample
If an error occurs, a message is posted to the message queue on the LCD screen.
Different message description as follow:
8,Make sure that the reagents can be injected into the cuvette.
If reagents fail to flow or Prime it may be due to a clog in either the tubing or at a
check valve. To alleviate this you may have to flush the system with Chlorine Free
water, preferably deionizer water.
9,If the above operation is no problem and TRO value is stable above 1.0,you can set as follow:
LOW SALINITY(TRO) EMERGENCY PROCEDURE
1) Turn on the power of the Power Distribution Unit and the Control Unit;
2) Press the button ”setting” e log in with user ”Hdw” and password ”Hdw”;
3) Take a picture of the setting page (commissioning setting);
You can add 50A in current valve ,for example: Initial Current 700 A change to 750A.
When next time you can add 50A from 750A to 800A
4) Press the hidden button at the top right corner for 2-3 seconds
5) Increase the value of “Flow-to-Current ratio” adding 5%, i.e. if “Flow-to-Current” is set at 70%,
please change it to 75.0%;
6) Press the button “Back and press Sure to Save”;
7) Press the button “Save Date to HMI internal storage”;
8) Click “Sure” to save.
9) It is necessary to change the same setting in control unit and in the remote control unit.
Please run the system for ballasting operation and record the following data.
SW temp. = ____ °C
Salinity = ____ ppt
TRO = ____ ppm
Flow rate = ____ m3/h
EUT: ____ V , ____ A
It is necessary to run the system with this setting for at least 10 minutes, so in case TRO LOW alarm is
activated during this range of time, please stop the system and start it again.
After 10 minutes running with this setting, if TRO LOW alarm is activated again, please follow the
steps 1-9 again, increase the value of “Flow-to-Current ratio” adding 5% more and start the system for
ballasting operation. The same data requested above should be recorded.
The maximum value of “Flow-to-Current ratio” is 120%.
The maximum value of “Initial Current” is Max Current*80%.
Remark
(1) OPEN JRC the setting screen, press and 3 seconds, in JRC’s Main
Menu chose”0”as follows:
Solution:
(2) move up and down to chose” 0” Equip SET”,press enter,as follows:
Special
Tools:
1,Power off to shut down the system.
Solution:
2,Press to unplug the HMI SD card of both local and remote HMI,and make a mark to separate
local or remote.
3,Plug the two SD cards to computer,and back-up all the files to computer.
4,After back-up, delete all the files in incomplete SD card and copy the files in intact SD to the
incomplete one.
5,Plug the two SD cards to HMI ,and power on to check if the LOG recovered.
6,Any queries please contact us,thanks!
Note: If you need to replace the program files in the SD card, please directly delete the folder and
file, and copy the new files into it, do not format, format the SD card will scrap it!!
注意:如果需要更换卡中的文件,请直接把文件夹和文件删除,并复制新文件进去,一定不
要格式化,格式化后 SD 卡就报废了!!
5 Notes