Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

6FM150-X

Shenzhen Center Power


12V 150Ah(10hr)
Tech.Co.Ltd,.

Overview
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is
absorbed by separators and plates and thus immobilized. Should the battery be accidentally
overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape
thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is,
therefore, maintenance-free, leak proof and usable in any position.

Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid

General Features Battery Specification


Positive and negative plates in lead-calcium-tin alloy;
Performance Characteristics
Stable Quality&High Reliability;
Nominal Voltage 12V
Sealed Construcrion;
Number of cell 6
Long Service Life;
Design Life 10 years
Maintenance-Free Operation;
Nominal Capacity 77℉(25℃)
Low Pressure Venting System; 10 hour rate (15.0A, 10.8V) 150Ah
Low Self Discharge; 5 hour rate (27.0A, 10.5V) 135Ah
U.L.Component Recognition; 1 hour rate (102A, 9.6V) 102Ah
Six months shelf life at 20℃; Internal Resistance
Design life 10 years Fully Charged battery 77℉(25℃) ≤4.5 mOhms
Self-Discharge
3% of capacity declined per month at 20℃(average)
Operating Temperature Range
Discharge -20~60℃
Charge -10~60℃
Storage -20~60℃
Max. Discharge Current 77℉(25℃) 1000A(5s)
Dimensions and Weight Short Circuit Current 2700A
Charge Methods: Constant Voltage Charge 77℉(25℃)
Length(mm / inch) 482 / 18.98
Cycle use 2.40-2.45VPC
Width(mm / inch) 170 / 6.69
Maximum charging current 45.0A
Height(mm / inch) 240 / 9.45 Temperature compensation -30mV/℃
Total Height(mm / inch) 240 / 9.45 Standby use 2.20-2.30VPC
Approx. Weight(Kg / lbs) 48.4 / 106.7 Temperature compensation -20mV/℃
* Weight deviation: ± 5%
Discharge Constant Current (Amperes at 77oF25oC)
End Point
482±2 170±1 Volts/Cell 10min 15min 30min 45min 1h 3h 5h 10h
1.60V 360 288 169 123 102 44.5 28.8 15.5
1.65V 327 214 162 120 99.0 44.2 28.2 15.4
1.70V 313 210 160 118 96.3 43.8 27.6 15.2
1.75V 288 198 156 114 93.4 43.4 27.0 15.1
1.80V 264 186 150 110 90.5 41.4 26.5 15.0

Discharge Constant Power (Watts at 77oF25oC)


End Point
Volts/Cell 10min 15min 30min 45min 1h 2h 3h 5h
1.60V 637 542 333 243 192 111 84.5 55.4
1.65V 614 504 304 235 186 109 83.9 54.1
1.70V 566 469 300 229 181 108 83.3 53.2
1.75V 532 444 294 224 177 106 82.1 52.1
1.80V 498 425 289 221 175 104 80.8 51.0

(Note)The above characteristics data are average values


obtained within three charge/discharge cycles not the mimimum
values.All data shall be changed without notice,Vision reserves
the right to explain and update the information contained hereinto.

Shenzhen Center Power Tech.Co.Ltd,. STOCK CODE: 002733 www.vision-batt.com


6FM150-X
Shenzhen Center Power
12V 150Ah(10hr)
Tech.Co.Ltd,.

Constant Current Discharge Constant Power Discharge


1000 1000

Wattage(W)
100 100
Current(A)

10 10

1 1
1 10 100 1000 10000 1 10 100 1000 10000
1.60V 1.65V 1.70V 1.60V 1.65V 1.70V
Time/mins Time/mins
1.75V 1.80V 1.75V 1.80V

Charged

Current

Voltage
Volume
Constant voltage charging
characteristic (0.25CA,25 ℃)
(%) (XCA) (V)
12.0 140

120 0.25
15.0 Charged Volume
100 0.20
15.0 A 14.0 Charge Voltage
43.8 A 27.0 A 80
9.6 0.15
320 A 125 A 102 A 60 13.0
0.10
40 12.0
20 0.05
11.0 Charging Current
0 0
0 2 4 6 8 10 12 14 16 18 20
Charging time (hours)

Self-discharge characteristic
Relationship between
(V/CELL)
(V/12V)

charging voltage and temperature


(V/6V)
(V/8V)

(V/4V)

100

90
Capacity(%)

15.6 10.4 7.8 5.2 2.6

Cycl 80
15.0 10.0 7.5 5.0 2.5 e Us
e
14.4 9.6 7.2 4.8 2.4 70

STANDB
13.8 9.2 6.9 4.6 2.3 Y USE 60
℃ ℃ ℃
13.2 8.8 6.6 4.4 2.2 50

-10 0 10 20 30 40 50 60 40
0 2 4 6 8 10 12 14 16 18 20
Ambient temperature (℃)
Storage time: months

120
Life characteristics of Standby use Cycle service life in relation to depth of discharge
120

100 100
Capacity(%)

80 80
Capacity(%)

60 60
100% D.O.D. 50% D.O.D. 30% Depth of discharge
Testing conditions:floating voltage:2.27 to 2.30V Cell
ambient temperature: 25°C(77°F)
40
40

20
20

0 200 400 600 800 1000 1200 1400


0 1 2 3 Number of cycles(cycles)
Life(year)

Temperature effects on float life Temperature effects on capacity


120

100
C
0.05
80 0.1C
Capacity (%)
Life(years)

. C
0.2
60

40 1.0C
2.0C
20

0
o
-20 -10 0 10 20 30 40 50
Temperature( C) Temperature (°C )

Shenzhen Center Power Tech.Co.Ltd,. STOCK CODE: 002733 www.vision-batt.com