Professional Documents
Culture Documents
Energy Consumption Guide
Energy Consumption Guide
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
atkins
On
23/02/2018
BEST PRACTICE
PROGRAMME
ENERGY EFFICIENT BUILDINGS
CONTENTS
1 INTRODUCTION 3
3 PASSIVE DESIGN 7
5 HEATING 11
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
6 VENTILATION 15
7 LIGHTING 16
FURTHER INFORMATION 18
REFERENCES 18
2
ENERGY EFFICIENT BUILDINGS
1 INTRODUCTION
3
ENERGY EFFICIENT BUILDINGS
INTEGRATED DESIGN
Multi-residential projects should be designed so Energy assessments can also be used to set
that passive design elements (chapter 3), insulation minimum design standards. Performance targets
(chapter 4), heating and ventilation systems can be set in terms of energy use or running costs
(chapters 5 and 6), and lighting (chapter 7) work (either per unit floor area, or per bedspace). In
together. Integrated design ensures that comfort some accommodation Standard Assessment
conditions are optimised at minimum cost and Procedure (SAP)[4] targets can be used.
minimum energy consumption.
The SAP is one of the principal methods of
Making energy efficiency an integral part of the assessing energy performance. Others include
design process ensures that appropriate energy computerised energy modelling and detailed
features are included as the design proceeds and computer simulation.
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
4
ENERGY EFFICIENT BUILDINGS
design for little or no extra cost. capital cost but payback periods can be attractive.
In some cases the payback period will be within
The insulation standards for gas and electric the design tolerance of the institution, but in
heating were chosen because: others the additional capital cost needs to be
■ they are easy to implement by tried and carefully compared with energy cost savings.
tested means
■ computer analysis shows them to offer
optimum cost effectiveness
■ they will reduce energy consumption, running
costs and carbon dioxide emissions further Figure 1 Bar chart showing
than required by 1995 Building Regulations. relative heating fuel savings
for each specification
25% 33%
saving saving
Heating energy consumption (cost)
5
ENERGY EFFICIENT BUILDINGS
■ Low energy lights in communal areas, corridors etc ■ Condensing gas or oil-fired boiler
■ Low energy lights throughout
For electric heating
■ Ground floors with 100 mm of insulation
■ Walls with, for example, 100 mm fully filled
cavities and lightweight blockwork
■ Roofs with 250 mm of insulation
■ Double glazed windows
■ All doors and windows draughtstripped
■ Automatic charge control on storage heaters
Table 1 Typical options for ■ Fan assisted storage heaters in large rooms
basic and higher energy ■ Low energy lights in communal areas, corridors etc
efficiency specifications
Heating Lead condensing gas boiler and thermostatic Lead condensing gas boiler and thermostatic
radiator valves radiator valves
Typical capital costs £378 additional cost per bed £916 additional cost per bed
Typical annual energy £48 saving per bed £63 saving per bed
costs/savings and payback** Payback: 8 years Payback: 14 years
Typical annual CO2 8 kg/m2 floor area 10.5 kg/m2 floor area
emissions (kg/m2)
*Note that boiler efficiency depends on the oversizing ratio. For this example a boiler size to heat load ratio of 3:1 is assumed, giving an overall efficiency of 64%
for the basic package and 72% with the lead condensing boiler.
**Based on fuel costs – gas 1.5p/kWh, electricity 7.5p/kWh
Table 2 Typical costs and savings for basic and higher specifications
6
ENERGY EFFICIENT BUILDINGS
3 PASSIVE DESIGN
Although conservatories can provide useful solar gain, they are not in general
energy saving features.
7
ENERGY EFFICIENT BUILDINGS
PASSIVE DESIGN
SOLAR GAIN
Shading should be provided where glare and
overheating may be a problem, for example in
conservatories or highly glazed communal living
areas. External shading on south façades can cut
out high summer sun and allow low winter sun to
enter the building. But in most cases internal
blinds will provide an adequate solution.
✓
A more detailed analysis of the required window
area is available in the CIBSE Window Applications
Manual[6] and the Lighting and
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
✗
Figure 4 Raising the position
of windows increases the DAYLIGHTING
penetration of daylight Daylighting reduces lighting costs and provides
a pleasant environment. The need for sufficient
window area, however, must be balanced against
the desire for privacy. If residents feel exposed in
a room they may draw curtains and switch on
lights, causing energy consumption to rise. Venetian
blinds can aid privacy while still admitting daylight.
8
ENERGY EFFICIENT BUILDINGS
Filling cavity walls with insulation is one of the construction will improve the thermal responsiveness of the building.
most cost-effective options. Fully filled cavity walls
will resist rain penetration except in very severe
exposure areas, mainly found in the west of WINDOWS
Britain. Maps are available which divide the UK The Building Regulations set acceptable window
into zones according to exposure to wind-driven areas as a percentage of floor area. Window areas
rain. It is important to take local conditions can be increased, but higher performance windows
into account and calculate a driving rain index will then be required, incurring higher costs.
using BS8104[9]. Further guidance on whether
walls are suitable for cavity fill can be found in the Gaps of up to 20 mm between panes are
DOE’s Good Practice Guide 26, ‘Cavity wall recommended in double glazed units to minimise
insulation in existing housing’[10]. heat loss. However, the larger the gap the higher the
cost of the window, and gaps of 12 mm usually
Timber framed constructions can be well insulated provide an acceptable level of thermal insulation.
at low cost. Other constructions, such as partial fill
and wide internal insulating blockwork, can produce When selecting double glazing, specify:
well-insulated walls although costs may be higher. ■ units to BS 6262 fitted in accordance with the
Constructions other than fully filled cavities should Glass and Glazing Federation Manual[13].
allow a minimum 50 mm clear residual cavity. ■ units ‘kite marked’ to BS 5713
■ trickle ventilators in the top of the frame
Care should be taken to avoid insulation products (unless full mechanical ventilation is
made with ozone-depleting chemicals (page 3). provided)
■ thermal breaks, if metal frames
ROOFS, CEILINGS AND FLOORS are used
For pitched roofs, at least 200 mm of insulation is ■ draughtstripped frames
recommended, laid in two layers, one between the appropriate for the
joists and the second across the joists to prevent exposure rating.
thermal bridging. A gap at the eaves allows
ventilation and prevents condensation. If
necessary, battens should be used to raise access
walkways above the insulation.
Figure 6 Good
For most types of flooring, insulation of 100 mm insulation levels
thickness gives a good standard. A method for the are essential in
calculation of ground floor U-values is given in an energy efficient
BRE IP 3/90[11]. building
9
ENERGY EFFICIENT BUILDINGS
Care homes
Day rooms with large areas of wall and roof glazing are present in many care
THERMAL BRIDGING
Heat loss from thermal bridging occurs where one
element of a building is more poorly insulated, and
homes. As these rooms are usually heated and constantly occupied it is worth thus colder, than the other parts. Thermal bridges
considering installing a higher standard of glazing to improve thermal are also associated with condensation. This usually
performance and the comfort of residents[12]. occurs around windows, doors, and at the
junctions between external walls, floors and roofs.
✓ AIR LEAKAGE
Background air leakage should be minimised and
controllable ventilation provided by means of
Figure 7 Good detailing is purpose-designed openings (see page 15).
important to avoid thermal bridging
The main air leakage paths in dwellings are:
■ joints around components, eg windows
Typical air leakage ■ gaps between one building element and another
paths ■ holes where services pass through the
construction.
10
ENERGY EFFICIENT BUILDINGS
5 HEATING
oil-fired wet systems are listed in table 3. If the hot water, such as in care
base load of the development is large enough, Heating systems must be sized to meet reasonable homes, centralised plant
combined heat and power (CHP) plant may be maximum demand using one of the proven heat may be a more efficient
considered[17]. A community heating system may loss calculation methods. Oversizing leads to option.
be an efficient and cost-effective option. inefficient operation and unnecessary capital cost.
Electrical heating equipment is cheap to install and Whichever system is chosen, it is important to
maintain, but running costs and environmental ensure that the controls are accessible and easily
impact reduce its attractions. However, in some understood by those operating them.
circumstances it may be a viable option. As well as
its low capital cost, ease of installation and low Further information on choosing a heating system
maintenance requirements, electric storage heating can be obtained from the DOE’s Good Practice
needs no central plant and billing residents is easy. Guide 182[18].
Advantages Disadvantages
Radiators ■ Flexible layout of boiler and ■ Care must be taken to ensure that
emitters touch temperatures are not too
■ Relatively cheap to install high. (Particularly important in care
■ Low maintenance homes as the elderly are more
■ Occupants familiar with system susceptible to burns)
from domestic use
Table 3 Advantages and disadvantages of alternative emitters for wet heating systems
11
ENERGY EFFICIENT BUILDINGS
HEATING
Care homes
Space heating in care homes can be in use for up to 24 hours per day during the Most boilers lose efficiency when operated at part
heating season. The additional capital cost of providing this heat as efficiently as load. The solution is correct sizing and, instead of
possible, by installing condensing boilers for example, can often be recouped in a single large boiler, the use of multiple, smaller
5 years through reductions in fuel bills[12]. units which improves system reliability by
enabling some heating to be supplied if one boiler
fails. If multiple boilers are used, the lead boiler
HEATING PLANT should be condensing.
Whether heating and domestic hot water is
supplied from a central boiler house or a series of Condensing boilers are also suitable for single
local decentralised units will depend on site boiler installations and for variable or low
characteristics and other factors (see table 4). temperature circuits, particularly if the return water
temperature is less than 55˚C.
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
Advantages Disadvantages
Central boiler house ■ Easy maintenance as there is only one ■ Failure could cause major disruption
main plant area ■ Increased capital costs for boiler house etc
■ Provides flexibility to run multiple boiler ■ Increased capital costs due to larger pipework
installation at near 100% output giving good distribution
operating efficiencies ■ Less control for local user
■ Possibility of heat recovery or CHP ■ Additional plant room space (cupboards etc)
installation for zone control
■ Simplified fuel supply ■ Energy loss from distribution mains and
additional pump power
■ Difficult to meter the supply for individual
payment
Decentralised boilers ■ No main boiler house and associated flue ■ Individual fuel supplies must be provided
required ■ Large number of units to service
■ Small boilers make less noise and usually do
not need forced ventilation
■ Increased user control to determine on/off
times of heating system
■ Failures create only local disruption
12
ENERGY EFFICIENT BUILDINGS
HEATING
13
ENERGY EFFICIENT BUILDINGS
HEATING
Care homes
different areas of a building.
Heating in care homes will usually be centralised. Staff will generally be thermostats, averaging several units through an
responsible for adjusting the heating system in response to residents’ requests. intelligent controller or building energy
Some local temperature control, such as room thermostats or TRVs, may be management system (BEMS). Secondary local
worthwhile for extra control[12]. control relies on thermostatic radiator valves
(TRVs) or dampers for finned tube emitters.
Zone 2
Zone 3
Time controls Time switch Time switch and optimised start Frost and condensation protection
Occupancy sensors
14
ENERGY EFFICIENT BUILDINGS
6 VENTILATION
For further information, refer to BRE IP13/94[24] Further details can be obtained from BRE Digest 398[26]
15
ENERGY EFFICIENT BUILDINGS
7 LIGHTING
16
ENERGY EFFICIENT BUILDINGS
failed building up to meet its targets, and early Comprehensive and accessible manuals are
identification and correction of potential problems required for each aspect of a building and its
is vital. services. The components installed and the
operating instructions and standard control
COMMISSIONING settings for all services equipment must be clearly
Infiltration rate tests and infrared thermographic and accurately communicated. Cross referencing
surveys enable straightforward and accurate with layout and schematic drawings is also
checking of the design and construction standard required to aid full understanding of the
of any heated building. design intent.
17
ENERGY EFFICIENT BUILDINGS
FURTHER INFORMATION
REFERENCES
18
ENERGY EFFICIENT BUILDINGS
REFERENCES
[13] Glass and Glazing Federation. Glass and London, DOE, 1995
Glazing Federation Manual. London, GGF [26] Building Research Establishment.
[14] National House-Building Council. Good Continuous mechanical ventilation in
Practice Guide: thermal insulation and dwellings: design, installation and operation.
ventilation. London, NHBC, 1991. BRE Digest 398. Garston, BRE, 1994
[15] Building Research Establishment. [27] Chartered Institution of Building
Thermal insulation – avoiding risks (second Services Engineers. Code for interior
edition). BRE 262. Garston, BRE, 1994. lighting. London, CIBSE, 1994
[16] Department of the Environment. [28] Department of the Environment. Energy
Minimising thermal bridging in new efficient lighting – a guide for installers.
buildings. Good Practice Guide 174 (GPG 174). Good Practice Guide 199 (GPG 199). London,
London, DOE, 1996 DOE, 1996
[17] Department of the Environment. Small-
scale combined heat and power for buildings.
Good Practice Guide 176 (GPG 176). London,
DOE, 1996 FURTHER READING
[18] Department of the Environment.
Heating system option appraisal – a manager’s Guides listed on these pages from the Department
guide. Good Practice Guide 182 (GPG 182). of the Environment’s Energy Efficiency Best
London, DOE, 1996 Practice programme are available from BRECSU
[19] The Boiler (Efficiency) Regulations. No. 3083, (contact details on back cover).
energy conservation. London, HMSO, 1993
[20] Chartered Institution of Building Good Practice Guide
Services Engineers. Applications manual 3: 73 Energy efficient house design – exploiting
condensing boilers. AM3. London, CIBSE, 1989 solar energy
[21] Health and Safety Executive. The control
of legionellosis including legionnaire’s disease. General Information Report
HS(G) 70. Sheffield, HSE, 1991 27 Passive solar estate layout
19
Licensed copy from CIS: atkins, Atkins Plc, 23/02/2018, Uncontrolled Copy.
The Government’s Energy Efficiency Best Practice programme provides impartial, Energy Consumption Guides: compare energy use in
authoritative information on energy efficiency techniques and technologies in industry and specific processes, operations, plant and building types.
buildings. This information is disseminated through publications, videos and software,
Good Practice: promotes proven energy-efficient techniques
together with seminars, workshops and other events. Publications within the Best Practice
through Guides and Case Studies.
programme are shown opposite.
New Practice: monitors first commercial applications of new
Visit the website at www.energy-efficiency.gov.uk energy efficiency measures.
Call the Environment and Energy Helpline on 0800 585794
Future Practice: reports on joint R&D ventures into new
For further specific information on: energy efficiency measures.
Buildings-related projects contact: Industrial projects contact:
General Information: describes concepts and approaches
Enquiries Bureau Energy Efficiency Enquiries Bureau yet to be fully established as good practice.
BRECSU ETSU
Fuel Efficiency Booklets: give detailed information on
BRE Harwell, Oxfordshire
specific technologies and techniques.
Garston, Watford WD25 9XX OX11 0RA
Tel 01923 664258 Tel 01235 436747 Introduction to Energy Efficiency: helps new energy managers
Fax 01923 664787 Fax 01235 433066 understand the use and costs of heating, lighting, etc.
E-mail brecsuenq@bre.co.uk E-mail etsuenq@aeat.co.uk © CROWN COPYRIGHT FIRST PRINTED MARCH 1997