Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

IEEE PES ISGT ASIA 2012 1569536277

Coordinated control of multi-FACTS to enhance the


small disturbance stability of the power system
Ye Tang1 Wei Hu1 Yang Huang1 Fei Xu1 Rui Min1
1) Department of Electrical Engineering, Tsinghua University, Bei Jing, China

Abstract--The widespread application of FACTS will be an variable-based multivariable PI controller parameters


obvious tendency with the development of power system, as tuning method[5], the batch method[6] , the multi-objective
FACTS have the ability to optimize power flow, reduce the hybrid evolutionary algorithm[7] and so on. The second
network loss, increase power system damping, improve voltage
stability and so on. Therefore , there is particular urgent needs
way completely abandons the conventional control
to study the coordinated control of the multiple FACTS in the strategies of FACTS and reformulate new control strategies
system. This article uses the robust control method to control according to the target, the target can be set as improving
the TCSC and SVC in a system, the power system is system transient stability or small signal stability. Methods
equivalent to a two-machine system, all-state equations of the of energy function [8], adaptive fuzzy damping control[9]
system can be written according to the generator equations and and robust nonlinear control[10] are used to achieve the
flow equations, from which we can solve the robust problem
and get the control law of FACTS. The robust control
target.
strategy of FACTS is simulated by the software of PSASP on Robust control theory based on all-state equations of the
a power system of 4 generators, and the results show that the system achieves the optimization goal of the whole system.
Robust control strategy can improve the small signal stability In published reports, robust control was used to achieve
of the system. coordination control mostly on the single machine infinite
bus system[11] or to study coordinated control of FACTS
Index Terms--Linear robust control, small signal stability, and the generator excitation. In this paper, robust control
TCSC, SVC theory is used to control a TCSC and a SVC, large grid is
equivalent to a two-machine system, one TCSC is serried
I.INTRODUCTION between the two-machine system, in which the SVC is
The power grid of China has entered the era of paralleled. All-state equations of the system can be written
developing ultra-high voltage (UHV) and large according to the generator equations and flow equations ,
interconnected power system. The interconnection of from which we can solve the robust problem and get the
national grid has greatly increased the complexity of the grid control law of TCSC , the SVC is control by voltage of the
structure and the difficulty in operation. In addition, the bus as usual ,but the control strategy of TCSC involves the
development of smart grid brings operators more challenges influence of SVC. The new control strategy is verified by
to run the grid. The future smart grid needs more flexible PSASP.
and reliable control methods to improve the flow
distribution, reduce network losses, raise the level of system II.INTRODUCTION OF LINEAR ROBUST CONTROL
damping and improve the system voltage stability and so on. Linear robust control is all named linear H  control.
Individual FACTS device is fast and reliable in H norm is an energy gain index from the interference
improving the operation state of the local power grid, and signal to the evaluation signal. H  control is a method to
using the coordinated control of multiple FACTS devices makes the H  norm of interference signal to the evaluation
can provide an optimization control of the entire grid or signal minimum and reduce the effect of interference and
parts of the grid. With the extensive application of FACTS increase the system robust stability.
devices, the problem of interaction and coordination control
of FACTS devices is acquiring an increasingly important A. Standards problem of linear robust control
position[1]. Figure 1 shows the system, u is the output of the
There are two ways in studying multi-FACTS controller, y is the input of the controller , w is the
coordination and optimal control. One way is based on the interference signal (or auxiliary signal). z is the control
interaction effect of multiple FACTS devices. The modal object (or evaluation signal). The transfer function matrix
analysis method[2], the relative gain matrix analysis from the input signal u, w to the output signal z, y is called
method[3], singular value decomposition method and the augmented controlled object. K(s) is the controller.
Gramm determinant-based analysis method[4] can be used
to quantify the extent of interaction of FACTS devices. And
researchers then plan the installation location or optimize
the control parameters of FACTS devices using the

National Twelfth Five-Year Plan Fund support, Project “WAMS-based


FACTS coordination control technology”(Funding No.:2011BAA01B02)

1 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded
 z
 x( t )  Ax ( t )  B1w( t )  B2 u( t )
 
G( s ) (6)


z( t )  Cx ( t )
u y Where x( t ) is n -dimensional state vector, u( t ) is
K (s) the r -dimensional control vector, w( t ) is the p
dimension disturbance variable, A, B,C is the
Figure 1 H  standard design problem system diagram
corresponding dimension matrix.
System model is:
Linear H control problem of system (6) is: given
x  Ax  B1 w  B 2 u
  0 , design a state feedback controller U  KX , makes
z  C 1 x  D11 w  D12u (1)
y  C 2 x  D21 w  D22u the corresponding closed-loop system internally stable, and
w(  )  L2 [ 0, ) , if the initial of system is X ( 0 )  0 , the
Where x is a n-dimensional state variable, w is
r -dimensional vector, u is p -dimension, z is response z( t ) of the system (6) satisfy the following

m -dimension, y is the q -dimensional signal vector. inequality


 2  2
Transfer function matrix G (s) is :
0 z( t ) dt    w( t ) dt
0
(7)
G11( s ) G12 ( s )
G( s )    Where  reflects the level of interference suppression
G 21( s ) G 22 ( s )
 A B1 B 2  (2) of the closed-loop system.
 C 1 D11 D12  Linear H control problem has the following solving
C 2 D21 D22  steps:
The closed-loop transfer function from w to z is The first step: solve the feedback matrix;
solve the equation
T zw ( s )  LFT ( G( s ), K ( s ))
(3) 1
 G11  G12 K ( I  G 22 K ) 1 G 21 AT P  PA  PB1 B1T P  PB2 B2T P + C T C  0 (8)
 2

The H  optimal design problem can be stated as to get a semi-positive definite solution P  0
follows: For a given augmented controlled object G s  , The second step: construct H control law.
seeking feedback controller K s  makes the closed-loop If the equation has semi-positive definite solution, we
name it P̂ , the H control law is
system stable and T zw s   is minimum, that is
u   B2T Pˆ  x (t ) (9)
min Tzw ( s )    0 (4)
K

III.ROBUST CONTROL OF THE POWER SYSTEM


And the H sub-optimal design problem can be
described as: For a given augmented controlled object G s  A. Power system model
and (   0 ) , Seeking feedback controller K s  makes Consider the two regional power system (Complex
the closed-loop system internally stable and Tzw ( s ) systems can be simplified to two-machine system through
satisfies: the network equivalence and generator equivalence.), TCSC
and SVC is installed on the contact line. Equivalent circuit
T zw ( s ) 
 (5)
diagram is shown in Fig.2 :
B. The solution of linear robust control PL1 PL 2

Combined with the practical problems discussed in this X d1 ' X1 X2 X TCSC Xd2 '
Eq1 ' 1 Eq 2 '  2
article, here are just a special case when D11  0 ,
PD1 X SVC V2 2 PD 2
C2  I , D21  0 , D22  0 . V11

Inspect system consisting of the following state space


equation and output equation
Figure 2 The equivalent two-machine system schematic

2 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded
Use the generator second-order model, that is, voltage Pm1  Pe10 , Pm2  Pe 20 ,and PL1   PL 2 ,if we ignore the
behind the transient impedance of the generator Eq' and change of loads, (19) becomes
the mechanical power Pm are constant. Ignore the damping  12  0 f12
of the generator, the system robust model can be written as: 
 1 1 (20)
 1  0 (1  1) f12   m2 ( T  T )PL1
  J1 J2

   1 (P  P ) To design the control strategy of TCSC, If (13) is linearized


 1 TJ 1 m1 e1 near the operation point, then (20) becomes
 (10)
  2  0 (2  1)  x (t )  Ax (t )  B1 w (t )  B2u1 (t )
(21)
 
1  z (t )  Cx (t )
2  ( Pm 2  Pe 2 )
 TJ 2 In (21), state variables are x(t )  [12 , f12 , X ] , the

1 ,2 ,1 ,2 , Pm1 , Pm2 , Pe1 , Pe2 are generator rotor angle, interference set are w(t )  [B, V1 , V2 ] (which means
rotational speed, mechanical power and electric power of the set the change of SVC as interference to TCSC), the
two generators. The control models of the TCSC and SVC matrixes are
are show as below:  
 
 0 0 0 
1
X  [u1  X ] (11)  1 1 1 1 1  B  X1 
TX A   m2 (  ) PL10  cot 120 0 m2 (  ) PL10 
 TJ 1 TJ 2 TJ 1 TJ 2 X 1  X   B  X 1  X  
 
1  0 0 
1

B  [u2  K A V  B] (12)  TX 
TB
 0 0 0 
The power of the tieline is 
 1 1 X1  X  1 1 PL10 1

1 PL10 
B1  m2 (  ) PL10 m2 (  ) m2 (  )
V1V2 sin(1  2 )  TJ 1 TJ 2 X 1  X   B  X 1  X  TJ 1 TJ 2 V1 TJ 1 TJ 2 V2 
PL1  (13) 
 0 0 0


X1  X 2  X TCSC  B[ X1 ( X 2  X TCSC )]
The voltage of the bus which the SVC is tied on is  
0 
( X V1 ) 2  ( X 1V2 ) 2  2V1V2 cos 12 X 1 X   
V  (14) B2   0 
X 1  X   BX 1 X   
PD1,PD2 are loads in the two areas. 1 
Pe1  PD1  PL1  TX 
(15) From (21), we can get the linear model of the system to
Pe 2  PD 2  PL 2
design the strategy of the TCSC, we can use the same
B. Linearization of system model method to design the control strategy of the SVC, the
difference are x(t )  [12 , f12 , B] ,
 12  0 12
 w(t )  [X , V1 , V2 ] and the change of loads shouldn’t
 1 1 1 1 (16)
12  ( T Pe1  T Pe 2 )  ( T Pm1  T Pm 2 ) be ignored but calculated in the matrixes of A and B1.
 J1 J2 J1 J2

In which: C. solving the control problem


12  1   2  ( 10   20 ) After setting C and m2, we can use the method of part II
(17) to solve the linear robust problem for system (21) to get the
12  1   2  ( 10   20 ) feedback:
Assume both sides of the generators are coherent, so u1  k112  k2 f12  k3 X (22)
12  m112
The control block for TCSC is shown in figure 3.
f12  m2 12 (18)
inertia Limiting
m1  m2 1 12
k1
link link X0
S X max

1 ,2 is the phase angle of generator voltage, m1 and m2 are 1


f12 k2  
unknow, then (16) becomes 1  TX s X
X min
 m1
 12  m 0 f12  0 f12 k3
 2
 (19) Figure 3 Control block for TCSC
 f  ( 1 P  1 P )  ( 1 P  1 P )
1 Use the same method to get the control strategy of SVC,

 m2
12
TJ 1
e1
TJ 2
e2
TJ 1
m1
TJ 2
m2
u2  k112  k2 f12  k3 B (23)
Ignore the influence from governors in both areas, then The control block for SVC is shown in figure 4.

3 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded
1 12
k1
S Inertia Limiting
link link
f12 k2 Bmax B0
1
V KA  
 1  TB s
B B
 Vref Bmin
k3
Figure 4 Control block for SVC

IV.SIMULATION EXAMPLE
A. Introduction of the system
Figure 5 Electric power of the line
This article uses the software of PSASP (Power System between bus 8 and bus 9
Analysis Software Package) to simulate the four-generator Figure 6 shows the comparision of robust control SVC and
system, the original parameters of the four-machine system conventional control SVC when the TCSC is under
specific can be seen in [12]. In this article, the two AC conventional control.
lines between bus 7 and bus 8, are combined into one line,
and so are the two lines between bus 8 and bus 9. Single line
figure of the system is shown in Fig.3:

1 5 6 7 8 9 10 11 3
G1 G3
xTCSC

xSVC

2 4

G2 G4

Figure 4 the single line figure of four-machine two-region systems

SVC is paralleled on bus 8, TCSC is serried on the line Figure 6 Electric power of the line
between bus 8 and bus 9
between bus 8 and bus 9. In the process of
The following three conditions are compared in the
simplifying ,components between bus 7 and bus 9 are kept
simulation:
unchanged, other parts are equivalent to two machines. The
Situation 1 : The TCSC under conventional control and
two generators are connected to the bus 7 and bus 9, and TJ
SVC under robust control.
of the two generators are the sum of original generator 1, 2 Situation 2: The TCSC under robust control and SVC
and the sum of original generator 3, 4 separately. under conventional control.
B. The simulation results Situation 3: The TCSC under robust control and SVC
Small disturbance of the system is set as: there is a under robust control..
three-phase short circuit occurred between bus 5 and bus 6, The electric power of the line between bus 8 and bus 9 ,
which is near to bus 5. The fault occurred at 1s, and stops at and the voltage of bus 8 of the 3 situations are as Fig.7 and
1.05s. Fig .8:
The coefficients of robust control of TCSC (22) or
SVC(23), k1,k2,k3 change very little when m2 changes from
0.5 to 1, so we assure m2 to be 1 when we solve the robust
problem for system (21).
Figure 5 shows the comparision of robust control TCSC
and conventional control TCSC when the SVC is under
conventional control.
The conventional control of SVC is
KA
B  U (24)
1  TA s
The conventional control of TCSC is
KI
X  ( K P  )P (25)
s Figure 7 Electric power of the line
between bus 8 and bus 9

4 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded
V.SUMMARY
Coordination control of FACTS has become a hot topic.
Robust control is widely used as a global control method. In
this paper, robust control is used to get coordination control
of TCSC and SVC , in the process, the power system is
equivalent to two-generator system which includs one TCSC
and one SVC. We deduce the state equations of the
two-generator system from the generator equations and flow
equations, and then use the feedback liberalized robust
control method to design the FACTS control law of the
system.
This article simulate the robust control law in the
four-generator system by PSASP. Simulation results show
Figure 8 Voltage of bus 8 that the robust control of FACTS can improve the small
signal stability of the system more compared to
Then we compared the change of SVC’s equivalent conventional control.
admittance and TCSC’s equivalent impedance in the
situation three situation, results are shown in Fig.9 and VI. REFERENCES
Fig.10 :
[1] Yijia Cao, Jia Tao, “Research progress on interaction and coordinated
control among FACTS controllers”, Proceedings of the CSU- EPSA, Vol.
20 No . 1, pp. 1-8, Feb.2008.
[2] JC.Passelergue, N.Hadjsaid, “An efficient index to deal with
interaction phenomena of FACTS devices in power systems”, Power
System Technology, Volume: 1, pp. 401 – 405, 1998.
[3] Zhenyu Zou, “Research on interaction analysis and coordinated
control of the multiple FACTS controllers in power system”, Ph.D.
dissertation, College of Electrical Engineering , Zhejiang University, 2006.
[4] Mingxing Gu, “Study on the interactions and coordination of
the multiple FACTS controllers in power system”, M.SC. Dissertation,
Dept. Electrical Engineering Nanjing University of Science & Technology,
2010.
[5] Haifeng WANG, Min LI, Heng CHEN, “Multivariable control design
of multi-functional unified power flow controller”, Proceedings of the
CSEE, Vol. 20 No. 8, pp. 51-55, Aug . 2000.
[6] Xiao Guo, “The study of interactions between PSS and SVC”, M.SC.
Dissertation, Dept. Electrical Engineering, Guangxi University , 2006.
Figure 9 Equivalent admittance of SVC [7] Lin Zhang, “Research on interactions analysis and control strategy
multiple FACTS controllers in power system”, Ph.D. dissertation, College
of Electrical Engineering , Zhejiang University, 2007.
[8] Ning Ke, Jianshe Su, “Simulation study of TCSC and SVC to
improve transient stability of transmission system”, Automation of electric
power systems, Vol.28. No.1, pp.20-23, Jan. 2004.
[9] Fangcheng Lu, “Research on TCSC control schemes for damping the
low frequency oscillation of power systems”, Ph.D. dissertation,
Department of Electric Engineering, North China Electric Power University,
1999.
[10] Xiachen Teng, “Research on robust nonlinear coordinated control
for SVC、TCSC and generator excitation”, M.SC. Dissertation, Dept.
Electrical Engineering, Xi an University of Science & Technology, 2009.
[11] Xiaorong Xie, Wenjin Cui, “Coordinated control of STATCOM and
generator Excitation”, Automation of electric power systems, pp.19-22,
Mar.10 , 2004
[12] Prabha Shankar Kundur , Power systems stability and control (in
Chinese), Beijing, 2001 , p. 548.

VII. BIOGRAPHIES
Figure 10 Equivalent impedance of TCSC
Ye Tang , graduate student , Institute Of Power
It can be seen that in the situation three, the oscillation
System, Dept.Electrical Engineering, mainly
of the electric power of the AC line damps the fastest, and
the voltage stability of bus 8 is also the best. The adjustment research in power system automation.
of TCSC and SVC quickly quell in situation three. The
simulation curves show that the coordinated control of
FACTS----robust control used in this article is more
effective to improve small signal stability of the system
compared to conventional control.

5 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded
Wei Hu, associate professor, Institute Of Power
System, Dept.Electrical Engineering, mainly
research in power system coordination and control.

Lei Chen, assistant researcher, Institute of Power System, Dept.Electrical


Engineering , mainly research in power system dynamic analysis and
control.
Fei Xu, associate professor, Institute Of Power System, Dept.Electrical
Engineering , mainly research in power system automation, renewable
energy and wind power.
Rui Min, graduate student , Institute Of Power System, Dept.Electrical
Engineering , Mainly research in power system simulation and
coordinated control.

6 on September 21,2020 at 10:19:10 UTC from IEEE Xplore. Restrictions apply.


Authorized licensed use limited to: Universidade Estadual de Campinas. Downloaded

You might also like