Professional Documents
Culture Documents
Coordinated Control of multi-FACTS To Enhance The Small Disturbance Stability of The Power System
Coordinated Control of multi-FACTS To Enhance The Small Disturbance Stability of The Power System
The H optimal design problem can be stated as to get a semi-positive definite solution P 0
follows: For a given augmented controlled object G s , The second step: construct H control law.
seeking feedback controller K s makes the closed-loop If the equation has semi-positive definite solution, we
name it P̂ , the H control law is
system stable and T zw s is minimum, that is
u B2T Pˆ x (t ) (9)
min Tzw ( s ) 0 (4)
K
Combined with the practical problems discussed in this X d1 ' X1 X2 X TCSC Xd2 '
Eq1 ' 1 Eq 2 ' 2
article, here are just a special case when D11 0 ,
PD1 X SVC V2 2 PD 2
C2 I , D21 0 , D22 0 . V11
1 ,2 ,1 ,2 , Pm1 , Pm2 , Pe1 , Pe2 are generator rotor angle, interference set are w(t ) [B, V1 , V2 ] (which means
rotational speed, mechanical power and electric power of the set the change of SVC as interference to TCSC), the
two generators. The control models of the TCSC and SVC matrixes are
are show as below:
0 0 0
1
X [u1 X ] (11) 1 1 1 1 1 B X1
TX A m2 ( ) PL10 cot 120 0 m2 ( ) PL10
TJ 1 TJ 2 TJ 1 TJ 2 X 1 X B X 1 X
1 0 0
1
B [u2 K A V B] (12) TX
TB
0 0 0
The power of the tieline is
1 1 X1 X 1 1 PL10 1
1 PL10
B1 m2 ( ) PL10 m2 ( ) m2 ( )
V1V2 sin(1 2 ) TJ 1 TJ 2 X 1 X B X 1 X TJ 1 TJ 2 V1 TJ 1 TJ 2 V2
PL1 (13)
0 0 0
X1 X 2 X TCSC B[ X1 ( X 2 X TCSC )]
The voltage of the bus which the SVC is tied on is
0
( X V1 ) 2 ( X 1V2 ) 2 2V1V2 cos 12 X 1 X
V (14) B2 0
X 1 X BX 1 X
PD1,PD2 are loads in the two areas. 1
Pe1 PD1 PL1 TX
(15) From (21), we can get the linear model of the system to
Pe 2 PD 2 PL 2
design the strategy of the TCSC, we can use the same
B. Linearization of system model method to design the control strategy of the SVC, the
difference are x(t ) [12 , f12 , B] ,
12 0 12
w(t ) [X , V1 , V2 ] and the change of loads shouldn’t
1 1 1 1 (16)
12 ( T Pe1 T Pe 2 ) ( T Pm1 T Pm 2 ) be ignored but calculated in the matrixes of A and B1.
J1 J2 J1 J2
IV.SIMULATION EXAMPLE
A. Introduction of the system
Figure 5 Electric power of the line
This article uses the software of PSASP (Power System between bus 8 and bus 9
Analysis Software Package) to simulate the four-generator Figure 6 shows the comparision of robust control SVC and
system, the original parameters of the four-machine system conventional control SVC when the TCSC is under
specific can be seen in [12]. In this article, the two AC conventional control.
lines between bus 7 and bus 8, are combined into one line,
and so are the two lines between bus 8 and bus 9. Single line
figure of the system is shown in Fig.3:
1 5 6 7 8 9 10 11 3
G1 G3
xTCSC
xSVC
2 4
G2 G4
SVC is paralleled on bus 8, TCSC is serried on the line Figure 6 Electric power of the line
between bus 8 and bus 9
between bus 8 and bus 9. In the process of
The following three conditions are compared in the
simplifying ,components between bus 7 and bus 9 are kept
simulation:
unchanged, other parts are equivalent to two machines. The
Situation 1 : The TCSC under conventional control and
two generators are connected to the bus 7 and bus 9, and TJ
SVC under robust control.
of the two generators are the sum of original generator 1, 2 Situation 2: The TCSC under robust control and SVC
and the sum of original generator 3, 4 separately. under conventional control.
B. The simulation results Situation 3: The TCSC under robust control and SVC
Small disturbance of the system is set as: there is a under robust control..
three-phase short circuit occurred between bus 5 and bus 6, The electric power of the line between bus 8 and bus 9 ,
which is near to bus 5. The fault occurred at 1s, and stops at and the voltage of bus 8 of the 3 situations are as Fig.7 and
1.05s. Fig .8:
The coefficients of robust control of TCSC (22) or
SVC(23), k1,k2,k3 change very little when m2 changes from
0.5 to 1, so we assure m2 to be 1 when we solve the robust
problem for system (21).
Figure 5 shows the comparision of robust control TCSC
and conventional control TCSC when the SVC is under
conventional control.
The conventional control of SVC is
KA
B U (24)
1 TA s
The conventional control of TCSC is
KI
X ( K P )P (25)
s Figure 7 Electric power of the line
between bus 8 and bus 9
VII. BIOGRAPHIES
Figure 10 Equivalent impedance of TCSC
Ye Tang , graduate student , Institute Of Power
It can be seen that in the situation three, the oscillation
System, Dept.Electrical Engineering, mainly
of the electric power of the AC line damps the fastest, and
the voltage stability of bus 8 is also the best. The adjustment research in power system automation.
of TCSC and SVC quickly quell in situation three. The
simulation curves show that the coordinated control of
FACTS----robust control used in this article is more
effective to improve small signal stability of the system
compared to conventional control.