CONTENTS
1. Specifications..........................................................................................................2 2. Outline and Dimensions .........................................................................................6 3. Operation ..............................................................................................................12 4. Wiring Diagram.....................................................................................................28 5. Refrigerant Cycle..................................................................................................32 6. Control Block Diagram .........................................................................................33 7. Electric Circuit Diagram........................................................................................34 8. Trouble Shooting...................................................................................................36 9. Key Components of Electronic Circuit .................................................................62 10. Disassembly Instructions .....................................................................................65 1) Indoor Unit ........................................................................................................65 2) Outdoor Unit .....................................................................................................68 3) Exploded Diagram (Indoor Unit)......................................................................71 4) Exploded Diagram (Outdoor Unit)...................................................................79 5) Control Box Assembly......................................................................................87
1. SPECIFICATIONS
DSB-070L
MODEL ITEM Function Class Power Capacity W Btu/h Dehumidification Running Current Electrical Data Power Input Starting Current Type Compressor Model Capacitor Indoor Unit Fan Motor Type Capacitor Motor Model Number Refrigerant (R-22) Control Charge Q'ty Type Connection OD (Liquid/Suction) Dimensions (W x H x D) Net Weight in(mm) mm kg 1/4 (6.35) 750 x 245 x 174 7.0 1/2 (12.7) 654 x 549 x 256 34 g Cross flow fan 1.0F 400VAC IC-8417DWKF5A Capillary 800 Flare l/h A W A DSB-070L Cooling T AC 220~ 240V/ 50Hz 2,051 7,000 0.89 2.9 680 18 Rotary QB 125PL 12B 25F/370VAC Outdoor Unit Propeller fan 1.8F 400V IC-9625DWLF5A
DSB-091L
MODEL ITEM Function Class Power Capacity W Btu/h Dehumidification Running Current Electrical Data Power Input Starting Current Type Compressor Model Capacitor RBB090A001 25F / 370VAC Indoor Unit Fan Motor Type Capacitor Motor Model Number Refrigerant (R-22) Control Charge Q'ty Type Connection OD (Liquid/Suction) Dimensions (W x H x D) Net Weight in(mm) mm kg 1/4 (6.35) 750 x 245 x 174 7.0 1/2 (12.7) 654 x 549 x 256 34 g Cross flow fan 1.0F 400VAC IC-8417DWKF5A Capillary 1,000 Flare l/h A W A DSB-091L Cooling T AC 220~240V/ 50Hz 2,637 9,000 1.15 4.2 920 21 Rotary QK 164PN12F 30F / 370VAC Outdoor Unit Propeller fan 1.8F 400V IC-9630DWLF5A
DSB-121L/122L
MODEL ITEM Function Class Power Capacity W Btu/h Dehumidification Running Current Electrical Data Power Input Starting Current Type Compressor Model Capacitor Division Fan Motor Type Capacitor Motor Model Number Refrigerant (R-22) Control Charge Q'ty Type Connection OD (Liquid/Suction) Dimensions (W x H x D) in(mm) mm 1/4 (6.35) 925 x 285 x 194 654 x 549 x 256(After) Net Weight kg 9.7 34 1/2 (12.7) 666 x 552 x 264(Before) g Indoor Unit Cross flow fan 1.0F 400VAC IC-8428DWKG7C Capillary 1,300 Flare l/h A W A DSB-121L/122L Cooling T AC 220~240V/ 50Hz 3,507 12,000 1.53 5.7 1,250 34 Rotary RCB 120A001 25F/ 400VAC Outdoor Unit Propeller fan 3.5F 400VAC IC-9430DWLC5B
DSB-240L
MODEL ITEM Function Class Power Capacity W Btu/h Dehumidification Electrical Data Running Current Power Input Type Compressor Model Capacitor Division Fan Motor Type Capacitor Motor Model Number Refrigerant (R-22) Control Charge Q'ty Type Connection OD (Liquid/Suction) Dimensions (W x H x D) Net Weight in(mm) mm kg 3/8 (9.52) 1080 x 298 x 200 14.7 5/8 (15.9) 872 x 675 x 325 64 g Indoor Unit Cross flow fan 2F 400VAC IC9430DWKG7A Capillary 2,050 Flare l/h A W DSB-240L Cooling T AC 220~240V/ 50Hz 7,030 24,000 3.2 13.4 2,400 Recipro AWG5530EXC 45F/ 400VAC Outdoor Unit Propeller fan 5F 400VAC 05ME986DERC
Plate Mounting
Connecting Pipe
REMOTE CONTROLLER
750
REMOCON
1 INDOOR UNIT
Plate Mounting
DSB-070L/DSB-091L
245
174
Connecting Pipe
406 925
Plate Mounting
REMOTE CONTROLLER
REMOCON
DSB-121L/122L
Filter - L
Filter - R
194
285
Connecting Pipe
REMOCON
1080
8
DSB-240L
Filter-L
Filter-R
Panel Top
Guide Support
DSB-070L/DSB-091L/DSB-121L/DSB-122L(After)
Foot Handle
2 OUTDOOR UNIT
Outlet
549
654
Service Valve
Foot Cushion
Inlet
Inlet AIR
264 334
Panel Top
Cabinet Back
DSB-121L/122L(Before)
666
552 572
10
Inlet
323
380
Cabinet Side
Service valve
DSB-240L
873
699
11
3. OPERATION
1 PARTS OF NAME AND FUNCTION
DSB-070L/DSB-091L
Indoor Unit
Lamp Antibacterial Filter Fan Direction (Up, Down) Remote Controller Receiver
Air Outlet
Power Plug
REMOTE CONTROLLER
Remote Controller
12
DSB-121L/122L
Indoor Unit
Electrostatic Filter
Air Inlet
Deodorizing Filter
Antibacterial Filter
Air Outlet
Power Plug
Remote Controller
TE MO RE R LLE RO NT CO
13
DSB-070L/DSB-091L
Switch Panel
EMR. REMOCON
s There is a switch panel at inside of Front Panel. At the time of operating, open the Front Panel.
ON (Red) Lights when the operation is going on. Air clean (Green) Timer (Yellow) Lights during the time reservation mode. Quick (Red)
Emergency switch can be used when the remote controller is lost or Testing. Remote switch is usually used by remote controller.
14
DSB-121L/122L
Switch Panel
EMERGENCY REMOTE
There is a switch panel at inside of Front Panel. At the time of operating, open the Front Panel.
ON
AIR CLEAN
QUICK
TIMER
Emergency switch can be used when the remote controller is lost or testing.
ON (Red)
Lights when the operation is going on.
Timer (Yellow)
Lights during the time reservation mode.
Quick(Red)
15
DSB-240L
Switch Panel
REMOCON EMERGENCY
EMERGENCY REMOCON
ON (Red) Lights-on during the operation Air clean (Green) Lights-on during the operation
Timer (Yellow) Lights-on during the time of reservation mode. Quick (Red) Lights-on during the time of Quick Mode.
s There is a switch panel at inside of Front Panel. At the time of operating, open the Front Panel.
Emergency switch can be used when the remote controller is lost or Testing. Remote switch is usually used by remote controller.
16
DSB-070L/DSB-091L/DSB-121L/DSB-122L(After)
Outdoor Unit
Connection Wire
Connecting Pipe
Drain Hose
Air Outlet
17
DSB-121L/DSB-122L(Before)
Outdoor Unit
Air Inlet (side Back)
AIR
Connection Wire
Drain Hose
NOTE:
How to remove Top Panel
1. Loosen the screw at left and right side. 2. Push the three parts op Front and Back sides like figure orderly. 3. Unhook the locking parts of Top Panel.
The front locking parts The back locking parts
FRONT SIDE
BACK SIDE
18
DSB-240L
Drain Hose
Air Outlet
Connection Pipe
19
2 REMOTE CONTROLLER
DSB-070L/DSB-091L/DSB-121L/DSB-122L/DSB-240L
AUTO
ON/OFF Button Press to turn the unit on or off. TEMPERATURE Buttons Press to raise or lower the desired temperature.
MODE FAN SPEED FAN DIR.
FAN SPEED Button Press to select the fan speed (High " ", Middle " ", Low " "). MODE Button Press to cycle through the modes (Auto/Quick/Cooling/Fan/Dry) SLEEP Button Press to set the unit for the sleep mode. TIMER ON/OFF Button Press to set the unit of or on time. (0.5, 1, 1.5, 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 16, 20, 24hr) TIMER ENTER/CANCEL Button Press to enter a timer setting or to cancel timer setting
SLEEP TIMER
ON/OFF
ENTER/ CANCEL
TURBO/MILD
REMOTE CONTROLLER
COVER Slide down to access most of the remote buttons. Slide down further to access the battery compartment.
20
AUTO
FAN Indicators Lights to indicate the fan speed. NATURAL Indicator Lights to indicate the speeds simulating a loreeze.
TIMER Indicators (Include sleep) Lights to indicate the timer function mode. TEMPERATURE & RESERVATION TIME lndicator Lights to indicate the temperature or time.
Replacing Batteries
Open the cover after pressing the arrow direction and pulling out.
RE MOT E CO NT RO LL ER
+
RE MOT E CO NT
21
RO LL ER
4 DESCRIPTION OF FUNCTIONS
OFF-Timer
If you set time in OFF-Timer Mode, the unit will stop at the set time.
ON OFF
SET Time
HOUR
ON-Timer
If you set time in ON-Timer Mode, the unit will run at the set time.
Unit ON
SET Time
HOUR
-1C
0C +1C (COOLING)
(RT-DT)
(3) During the time of test operating, Fan (Indoor, Outdoor) and Compressor is running regardless of room temperature.
Buzzer
If the Indoor Unit Display receive the signal of Remote Controller, you can hear the signal "beep " or "beep, beep". (1) In the case of receiving ON/OFF signal-"beep" "beep" (2) And so on-"beep"
22
(4) Automatic Operation If the unit is set in 'AUTO' mode, the unit operates automatically according to the room temperature to keep the room temperature comfortable.
(COOLING)
H M L 0C (D.T) 1C 2C (R.T-D.T)
23
Sleep Mode
(1) When you are going to sleep, select sleep switch and the unit controls the room to the desired temperature. (The unit will not operate after 4 hour) (2) For changing the temperature.
DT +0.5C +0.5C
+0.5C
0.5
1.0
HOUR
(COOLING CYCLE)
(3) To cancel sleep mode, press the SLEEP button again or press the MODE button once.: the SLEEP indicator will disappear in the display.
Emergency Operation
(1) When the remote controller is lost, damaged or the battery is discharged, the Emergency operation can be used to run the unit. (2) The setting conditions of Emergency operation are as follows. Operation mode: Quick Preset temperature:18C: Cooling Fan speed: High You cannot operate with remote controller.
ON OFF
ON Set speed
Auto Mode
(1) In Auto Mode After the indoor fan is operated for 20 seconds in the Auto Mode the unit will operate automatically by selecting operating Mode according to the room temperature (RT: Room temperature) ROOM TEMPERATURE OPERATING MODE Cooling Dehumidifier Cooling FLAP POSITION Cooling Position Cooling Position Cooling Position
(2) Selecting Operating Mode Again Room temperature meets desired temperature and the compressor stops running over 30 minutes, then the unit selects operating Mode again.
25
Dehumidification Mode
1 Desired temperature < Room temperature
Outdoor Fan, Compressor : ON Indoor Fan : Low speed 2 Desired temperature Room temperature Compressor : 3 min/ON, 5 min/OFF Fan Speed : low speed 3 Room temperature 18C Compressor : OFF Fan speed : Low speed
Up/Down
Fixed
26
Self-Diagnostic Function
The control will contain diagnostic test to verify the integrity of the system. (1)Error Code Display Pattern 1 ON LAMP: Blink
LED BLINK PATTERN CASE NOTE
0.5s 8s
I/D coil sensor open or short O/D coil sensor open or short
Do not woorking
1 times blink
Continuously workiug
27
OUTDOOR UNIT
INDOOR UNIT
LED PCB
RED
RED
BLK
BLK
4. WIRING DIAGRAM
BLUE
COMP 1 1 2 3
DSB-070L/DSB-091L/DSB-121L/DSB-122L
CAPACITOR YEL FAN COMPRESSOR C HERM BLU YEL/GRN BRN S RED BRN
1 2 3 4 5 6 7 8
23
BRN C R
ORG RED
BLU
BLK
YEL
1 2 3 4 5
SWING MOTOR
28
OUTDOOR
BLK H RED RED BRN S FAN MOTOR CAPACITOR DUAL FAN C HERM ORG 1 8 4 0 6 2 L POWER RELAY RED BLU YEL/GRN Y N RED BLU RED BLU Y N BLU BLU RL1 WHT
INDOOR
PCB TRANS RED RA RED TH.
CN6 CN9
BLK
CN2
IDC TH.
LED PCB 1 2 3 4 5 6 7 1
CN1
COMPRESSOR
S C R
RED
WHT
CN4
CN3
RA TH. : ROOM AIR THERMISTOR IDC TH. : INDOOR COIL THERMISTOR ORG YEL PNK BLU RED BLU C
CN13
BRN BLU RA TH. : ROOM AIR THERMISTOR IDC TH. : INDOOR COIL THERMISTOR
SWING MOTOR
DSB-240L
29
FUSE
CONTROL PCB
CN1
Indoor Unit
Outdoor Unit
DSB-091L
PART NAME Fan Motor Fan Motor Capacitor Fuse Transformer Stepping Motor Terminal Block Compressor Outdoor Unit Fan Motor Dual Capacitor Terminal Block PART CODE 3108003800 3106900300 5FVLB3152L 5EPV050120 3108003900 3108912301 3RC0020KE0 3107101900 3108004100 3109502010 3109502030 3108912301 SPEC. IC-8417DWKF5A 1.0uF 400VAC 250V 3.15A 230V 50Hz GSP-24SW-061 SN-DBW-05P RBB100A001 QK185PN13F IC-9630DWLF5A 1.8+30F 400VAC 1.8+35F 400VAC SN-DBW-05P QUANTITY 1 1 1 1 1 1 1 1 1 1 1 1 REMARK
Indoor Unit
DSB-121L/122L
PART NAME Fan Motor Fan Motor Capacitor Fuse Transformer Stepping Motor Terminal Block Compressor Fan Motor Dual Capacitor Terminal Block PART CODE 3108001220 3106900300 5FVLB3152L 5EPV050100 3108000100 3108912301 3100030CE0 3108000800 3109500700 3108912301 SPEC. IC-8428DWKG7C 1.0uF 400VAC 250V 3.15A 220V/18V MP28GA (L=400mm) SN-DBW-05P RCB150A001 IC-9430DWLC5A 3.5+25F 400VAC SN-DBW-05P QUANTITY 1 1 1 1 1 1 1 1 1 1 REMARK
Indoor Unit
Outdoor Unit
30
DSB-240L
PART NAME Fan Motor Fan Motor Capacitor Fuse Transformer Stepping Motor Terminal Block Compressor Fan Motor Dual Capacitor Terminal Block PART CODE 3108007500 3106902400 5FVLB3152L 5EPV050120 3108007600 3108912320 3100068201 3108007400 3109508100 3108912320 SPEC. IC-9430DWKG7A 2.0uF 400VAC 250V 3.15A 230V/50Hz GSP-24RW-062 SN-DBW-062 AWG-5530EXC OSME986DERC 230/50 5/45F 400VAC SN-DBW-4P QUANTITY 1 1 1 1 1 1 1 1 1 1 REMARK
Indoor Unit
Outdoor Unit
31
5. REFRIGERANT CYCLE
INDOOR UNIT Evaporator
Connecting pipe
Accumulator Compressor
Capillary tube
Condenser
Dryer
Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter. Model Name
Contents
DSB-070L
DSB-121L
DSB-240L
Capillary Tube
Charge Quantity
800 g
1,000 g
1,300 g
2,050g
32
Remote Emergency
Signal receiver
Operation
SLEEP REMOCON Circuit for signal receiver A/D converter Beeper MICRO CONTROLLER lnitialization Clock generation DC5V DC power supply DC12V
STEPPING MOTOR ON/OFF COMPRESSOR ON/OFF
Transformer
AC220V 50Hz
Relay RL1
TRIAC
Stepping Motor
33
1
Indoor Unit Fan Motor
2 3
N
I.D.C
SWING MOTOR
TERMINAL BLOCK
S
TRIAC RL1 COMP. RELAY
TRANSFORMER
Remote Controller
34
Description
1. After the power ON/OFF button is pressed once, the relay and triac are turned ON or OFF per the remote control setpoint. TRIAC is controlled per the fan speed selection. RELAY is controlled per the operation mode selection.
2. If the power ON/OFF button is pressed once more, the relay and triac are turn off and the unit stops operation.
3. The unit turns on or off according to the temperature set point by sensing the room air temperature through thermistor.
4. If the fan speed selection is set to the auto position, the fan speed is automatically controlled according to the temperature differance between room temperature and temperature set point.
5. If you press the ON/OFF button during operating the unit, Relay and LED is OFF and the unit is OFF.
35
Trouble
Is the unit display normal? Is the power applied to the unit YES YES
NO
NO YES
8. TROUBLE SHOOTING
Is the power normal? check the voltage between L & N of terminal block NO YES
NO
Does the compressor run normally? YES Indoor unit does not run(note 1) Is the unit display mormal? YES Check the failure code according to the self diagnostic (note 2) NO NO
press the power ON/OFF button on remote controller YES NO Normal Does the beeper beep two times? check the connecting point of magnetic contactor YES NO
NO
Place the switch position to the "Remote" and then Check it once more
YES
Does control PCB status LED repeat one second "on and off"? NO Is the display all off? YES control PCB fault Micom or reset IC fault
YES
YES
Check the connector on display PCB connected to control PCB Check the display PCB itself
Check the remote signal receiver Check the connection between signal receiver and control PCB
36
Note 1) 1 Neither indoor unit nor outdoor unit runs. Check the following points first. (There are following case in normal operation) a. Is the timer mode set the "timer ON". b. Is the timer mode set the "timer-OFF" and the time had passed? 2 Neither outdoor fan nor compressor runs while indoor fan runs. Check following points first. (There are following cases in normal operation) a. Is the temperature set point suitable? b. Has the 3 minutes time guard for compressor operated?
Self-Diagnostic Function
Error Code 1 When the compressor do not run. i) Check the voltage between L and Y of terminal block. (Indoor Unit, Outdoor Unit) ii) Check connecting wire of indoor unit and outdoor unit. iii) Check relay RL1 on power P .C.B 2 Check fixing of indoor coil thermistor. 3 Check the GAS LEAKAGE of the pipe.
37
Rating voltage Check the voltge between L and Y of terminal block under 90%
Rating voltage more than 90% Check the indoor unit display is the display all off? No Self Diagnostic function is ON Yes No Check according to self Diagnostic function No
Yes Press the ON/OFF switch of Remote Control Is the indoor unit display all off?
Pull out the power plug and then insert the power plug after 5 second
38
Rating Voltage more than 90% Open or short Check the winding resistance of Indoor unit fan motor Normal Check the fan motor capacitor Change of fan motor
Run again
No
Normal
Run again
39
Rating voltage Check the voltge between L and Y of outdoor unit terminal under 90%
40
Rating voltage more than 90% Rating voltage Check the voltge between L and Y of outdoor unit terminal less than 90% Check the connecting wire between indoor and outdoor.
Rating voltage more than 90% Check the wiring of outdoor unit NG Change the control P .C.B
Open or Short
41
43
DSB-121L/DSB-122L
44
45
No IC5 IC6 L1 OSC PCB PT1 R-OPT R1 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R2 R20 R21 R23 R24 R25 R26 R27 R28 R29 R3 R30 R31 R32 R38 R4 R5 R6 R7 R8 R9 RA1 RA2 RA3 RL1 RL1 RL2 RL3 SCRW T1 TEST TR1 VAR WSHR
PART CODE 1KA7042P-1KD65004AP 52C1374001 4850103610 3104398102 1TLP560J-3104810000 RD-4K101JRN-4K1272F RN-4K1272F RD-4K102JRD-4K562JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K562JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K102JRD-4K103JRD-4K102JRD-4K102JRD-4K102JRS01F121JRD-4K102JRD-2K102JRD-4K331JRD-4K331JRD-4K331JRN-4K1272F RA8K5103JRA8K4103JRA8K3103J5SC0101220 5SC0101128 5SC0101128 5SC0101128 7122401211 TSM3JZ47-3108804300 TKRC102M-D15G561K-3106002900
PART NAME IC RESET IC DRIVER COIL RESONATOR PCB CONTROL IC PHOTO COUPLER RESISTOR OPTION R CARBON FILM R METAL FILM R METAL FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R M-OXIDE FILM R CARBON FILM RESISTOR R CARBON FILM R CARBON FILM R CARBON FILM R METAL FILM RESISTOR ARRAY RESISTOR ARRAY RESISTOR ARRAY RELAY RELAY SW RELAY SW RELAY SCREW TAPPING TRIAC WAFER TR VARISTOR WASHER
SPEC KIA7042P 5L KID65004AP 130UH 3A CST8.00MTW,8MHZ 160.5*140*1.6T.1(42) TLP 560J NOTE OPTION TABLE 1/4 100 OHM J 1/4 12.7K OHM F 1/4 12.7K OHM F 1/4 1K OHM J 1/4 5.6K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 5.6K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 10K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1W 120 OHM J 1/4 1K OHM J 1/2W - 1K 1/4 330 OHM J 1/4 330 OHM J 1/4 330 OHM J 1/4 12.7K OHM F 6A 103J 5A 103J 4A 103J UKH-12SP CS11-12SH 1C 1P CS11-12SH 1C 1P CS11-12SH 1C 1P T2S TRS 4*12 MFZN SM3JZ47 YF254S-02 KRC 102-M (TAPPING) 15G561K/350V 3*6
Q'TY UNIT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 EA EA EA EA EA EA ST EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA
REMARK
070LH,091LH,240LH 070LH,091LH,240LH
240L/LH
46
47
No R2 R20 R21 R22 R23 R26 R3 R32 R33 R34 R4 R5 R6 R7 R8 R9 RA1 RA2 TEST TR1 TR2
PART NAME R CARBON FILM R METAL FILM R CARBON FILM R METAL FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM R CARBON FILM RESISTOR ARRAY RESISTOR ARRAY WAFER TRANSISTOR TR
SPEC 1/4 10K OHM J 1/4 12.7K OHM F 1/4 330 OHM J 1/4 12.7K OHM F 1/4 330 OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 1/4 1K OHM J 6A 103J 4A 103J YF254S-02 KTC3198Y-(1815Y) KRC 102-M (TAPPING)
Q'TY UNIT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA
REMARK
122LH,181LH 122LH,181LH
181L/LH 181L/LH
48
082H,102H,122H
122LH,181LH 122LH,181LH
49
50
Power Supply(1)
VAR D1 D2 CC1 D4 POWER TRANS CE1 + D3 104 35V 1000F IC2 7812 VI VO G
5V
CC2
CE2 +
CC3
CE3 +
104
25V 470F
104
16V 100F
DESCRIPTION
DC Power Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Relay, Triac Driving Photo Triac, Buzzer Driving Swing, Sweep Motor. AC voltage of secondary Power Transformer is rectified by Bridge Diode, and it is filtering by Main Condensor CE1. Filtered DC voltage is about +18V, is regulated +12V DC by Regulator IC7812. And it is regulated +5V DC by Regulator IC7805. VAR is serge filter and CC1, CC2, CC3 is Noise filter.
Oscillator(2)
DESCRIPTION
Oscillatory Frequency drive Micom, it is made up 8MHz resonator oscillatory Freqency. Ocillatory wave is as following Fig 2-1.
VDD-10%
VSS+10%
Fig 2-1
51
Sensor(3)
Room temperature and Evaporator temperature Sensor Input
070LH,091LH 182LH, 240LH 330 O/C SENSOR R8 23 CN10 CN9 I/C SENSOR ROOM SENSOR R10 12.7KF R11 12.7KF R7 330 25 R6 330 CC5 103 R9 12.7kF CC7 103 103 CC6 24 MICOM
DESCRIPTION
Number 24, 25 of Micom is Terminal of A/D convertor Input. Room temperature and Evaporator temperature is sensing by change of Thermister Resistance, Micom is put in 5V by ratio between R10 (12.7K) and R11 (12.7K). Relation between temperature and voltage is following Table 3-1. CC5, 6 is Noise filter.
Table 3-1
52
Triac Driving(4)
12V N 2 AC 220V L SN1 0.1F 120Ohm TO MOTOR
TLP561 PT1
L1 1 130H 3A
DESCRIPTION
Number 38 Terminal of Micom is put out Pulse Output, by way of Buffer it is driving Photo Triac is supplied Trigger Signal. Trigger Test of Triac is detected Zero Cross Part of AC input and it is triggered from Zero Cross part to Time delay part according to Fan Speed. (Ref. Fig 4-1) SN1 is Snubber.
AC220V
TRIGGER LOW SPEED LOW SPEED MEDIUM SPEED MEDIUM SPEED HIGH SPEED HIGH SPEED
MOTOR INPUT
Fig 4-1
53
Remote Controller(5)
DESCRIPTION
Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Number 33, which is gotten fid of Carrier (38KHz) from Receive Module. Signal Wave repeat third as following Fig 5-1. But in Secondary Wave Custom Code is Reversed Face.
9ms
4.5ms
16bit
24bit
8bit
16bit
0.56ms
0.56ms
LEADER CODE
CUSTOM CODE
DATA CODE
CHECK SUM
TAILER
1.12ms bit 0
Fig 5-1
Selecting Mode(6)
(SELECT S/W INPUT, OUTPUT)
5V
DESCRIPTION
There are Mode according to SW position as following Table 6-1. According as port of fixed Micom is Low, the unit is operating as following Table 6-1. POSITION OPEN GND MODE REMOCON EMERGENCY
Table 6-1
54
5V
VDD 42 41 MICOM 40 39
CC11 104
OSC 8MHz
19 20 21 VSS
22
CC13 104
DESCRIPTION
MICOM Power is supplied 5V at Number 42 using VDD, Number 19, 20 Vsing Oscillator, CC13 is noise filter.
55
Reset(8)
MICOM R13 5.6K 1K 7042P IC5 CE4 4.7uF/50V CC9 10.3 R12 18
DESCRIPTION
Voltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect Power ON and Voltage less than 4.25V, and then send Reset Signal.
t
DELAY TIME FOR POWER ON H RESET
L POWER ON
56
Function Selecting(9)
CA3 F3 104Z 41 40 39 MICOM F5 104Z CA1 1K 1K R17 14 1K R16 1K R15 RA2 16 CA2 28 15 27 26 1K R29 1K 1K R24 R23 29 1K 6A 103J RA1 R28 R25 R36 heat/low R35 cool/low R34 heat/high R33 cool/high R37 monitoring R32 1K R31 1K R30 1K RA3 4A 103J JS5 MILD/HIGH JS4 HEAT/COOL RA3
DESCRIPTION
Selecting function is as following table 9-1. RWhen power source is put at fist, Funtion selection input is recognized. And when the unit is running the microcomputer ignore variation of funtion selection input. JS1 MILD FAN FUNCTION HIGH COOL 070 091 MODEL 122/240 181 SHORT OPEN SHORT OPEN JS2 SHORT OPEN OPEN SHORT JS4 OPEN JS5 SHORT OPEN
Buzzer Driving(10)
VCC 12V
DESCRIPTION
MICOM KID 65004 34 6 11 R4 1K BZ1
Micom 34 Terminal put out Buzzer Driving Pulse, its output is driving Buzzer through Buffer. Ocillatory Frequency of buzzer is selected by internal Micom. This unit is setting at 4KHz.
57
D6
R2 5.6K
CC4 103
DESCRIPTION
It defect Zero Cross part of Trans output voltage, Transistor TR1 is used to put in the Micom. Detail Driving is as following Fig 11-1. R19 is Resistance to limit current.
AC18V
DETECT POINT
Fig 11-1
58
DESCRIPTION
There are one Stepping Motor for Flap (up and down) and it is used 4 face Drive Method. It is driving as following Fig 12-1. (Ring Count Method of 8 Status)
(Normal Rotating)
Fig 12-1
(Reversed Rotating)
59
Is it normal?
No
ERROR
Is it normal?
No
ERROR
v (w) No
Is it normal?
ERROR
No
ERROR
Is it normal?
60
No
ERROR
Is it normal
No
ERROR
TIMER display?
No
ERROR
No
ERROR
Is it normal?
No
ERROR
No
ERROR
No
ERROR
TEST OK!
61
VDD 42
4 P74(SI) (INT5/STOP)P20 39 5 P73(SCK) 6 P72(PDO/PWM) 7 P71(INT4) P17 38 P16 37 (TC2)P15 36 Indoor Unit Motor Driving
8 P70(INT3/TC3) (PPG)P14 35 9 P07 10 P06 LED Driving 11 P05 12 P04 Emergency Mode Function S/W 13 P03 14 P02 15 P01 16 P00 17 TEST Reset Curcuit Oscillation 18 RESET 19 XIN 20 XOUT 21 (VASS)VSS (DVO)P13 34 (INT2/TC1)P12 33 (INT1)P11 32 (INTO)P10 31 (AIN7)P67 30 (AIN6)P66 29 (AIN5)P65 28 (AIN4)P64 27 (AIN3)P63 26 (AIN2)P62 25 (AIN1)P61 24 (AIN0)P60 23 VAREF 22 Temperature Sensor Input Function S/W Buzzer Driving Remocon Input Comp Relay Driving Zero Crosing Detect
62
KID65004AP
COMMON INPUT
10.5K 3K 7.2K
OUTPUT
GND
(Equivalent Circuit)
(Top View)
OUTPUT
1 2 3
2.7 K 1.4 K 28K
6K
2K 0.19K
30pF Fin 2 is ground for Cose 221A. Case is ground for Case 1.
500 6K 1K 5K
5K
GND
INPUT
40 pF
OUTPUT
20K
29K
20K
GND
(Equivalent Ciircuit)
63
2 GND
OUTLINE
64
Fig 2
3. Removing the Control Box. (Fig 3) 1 Remove room and coil thermistors. 2 Disconnect the fan motor lead wire from connection at the Control PCB. 3 Disconnect the stepping motor lead wire from connection at the Control PCB. 4 Remove the select switch from connection at the Control PCB. 5 Loosen a screw for fixing ground wire. 6 Remove the Control Box
Fig 3
4. Removing the Drain Pan. (Fig 4) 1 Disconnect the Body drain hole. (left and right Body) 2 Disconnect three hook and remove the Drain Pan.
Fig 4
5. Removing the Indoor Evaporator. (Fig 5~6) 1 Remove one screw for fixing indoor Evaporator at the Body. 2 Remove the hook for fixing Bracket Pipe at the back of Body. 3 Remove Indoor Evaporator.
Fig 5
6. Removing the Cross Flow Fan. (Fig 7) 1 Remove set screw for fixing Motor shaft. 2 Remove Cross Flow Fan.
Fig 6
65
DSB-121L/DSB-122L
PROCEDURES 1. Stop the Air conditioner and disconnect the power cord from the wall outlet. Fig 1 2. Removing the Insert Grille and Frame Grille. (Fig 1~2) 1 Draw up the Insert Grille and remove it. 2 Loosen two special screw for fixing the Cover Ter-Block. 3 Loosen three screw at the Body. 4 Remove the Frame Gille. PHOTOS
Fig 2
3. Removing the Control Box. (Fig 3) 1 Remove room and coil thermistors. 2 Disconnect the fan motor lead wire from connection at the Control PCB. 3 Disconnect the stepping motor lead wire from connection at the Control PCB. 4 Remove the select switch from connection at the Control PCB. 5 Loosen a screw for fixing ground wire. 6 Remove the Control Box
Fig 3
4. Removing the Drain Pan. (Fig 4) 1 Disconnect the Body drain hole. (left and right Body) 2 Disconnect three hook and remove the Drain Pan.
Fig 4
5. Removing the Indoor Evaporator. (Fig 5~6) 1 Remove three screw for fixing indoor Evaporator at the Body. 2 Remove the hook for fixing Bracket Pipe at the back of Body. 3 Remove Indoor Evaporator.
Fig 5
6. Removing the Cross Flow Fan. (Fig 7) 1 Remove set screw for fixing Motor shaft. 2 Remove Cross Flow Fan.
Fig 6
66
DSB240L
PROCEDURES 1. Stop the Air conditioner and disconnect the power cord from the wall outlet. Fig 1 2. Removing the Insert Grille and Frame Grille. (Fig 1~2) 1 Draw up the Insert Grille and remove it. 2 Loosen one screw for fixing the Cover Ter-Block. 3 Loosen two screw at the Frame Grille. 4 Remove the Frame Grille. PHOTOS
Fig 2
3. Removing the Control Box. (Fig 3) 1 Remove room and coil thermistors. 2 Disconnect the fan motor lead wire from connection at the Control PCB. 3 Disconnect the stepping motor lead wire from connection at the Control PCB. 4 Remove the select switch from connection at the Control PCB. 5 Loosen a screw for fixing ground wire. 6 Remove the Control Box
Fig 3
4. Removing the Drain Pan. (Fig 4) 1 Disconnect the Body drain hole. (left and right Body) 2 Disconnect three hook and remove the Drain Pan.
Fig 4
5. Removing the Indoor Evaporator. (Fig 5~6) 1 Remove the hook for fixing Plate mounting at the back of Body. 2 Remove Indoor Evaporator.
Fig 5
6. Removing the Cross Flow Fan. (Fig 7) 1 Remove set screw for fixing Motor shaft. 2 Remove Cross Flow Fan.
Fig 6
67
2 OUTDOOR UNIT
DSB-070L/DSB-091L/DSB-121L(After)
PROCEDURES 1.Stop the air conditioner and disconnect the wire from Indoor Unit to Outdoor Unit. PHOTOS
2. Disassemble the case. (Fig 1~2) 1 Remove the Top Panel. (Loosen thirteen screw) 2 Remove the Front Cabinet. (Loosen six screw) 3 Remove the Side Cabinet. (Loosen seven screw) 4 Remove the Guide Support. (Loosen two screw)
Fig 1
3. Removing the Propeller Fan. (Fig 3) 1 Loosen the Nut for fixing the Propeller Fan. 2 Remove the Plain Washer. 3 Remove the Propeller Fan.
Fig 2
4. Removing the Motor ODU. (Fig 4) 1 Loosen four screw at Bracket Motor. 2 Disconnect the wire at Control Panel and remove Motor ODU.
Fig 3
5. Removing the Dual Capacitor. (Fig 5) 1 Disconnect the wire at Control Panel. 2 Loosen a screw at Clamp Capacitor. 3 Remove the Dual Capacitor.
Fig 4
6. Removing the Over load Protector. (Fig 6~7) 1 Loosen a Hex Nut at Terminal Cover. 2 Remove the Terminal Cover. 3 Remove the wire at Over load Protector. 4 Remove the Over load Protector.
Fig 5
Fig 6
Fig 7
68
DSB-121L (Before)
PROCEDURES 1.Stop the air conditioner and disconnect the wire from Indoor Unit to Outdoor Unit. PHOTOS
2. Disassemble the case. (Fig 1~2) 1 Remove the Top Panel. (Loosen thirteen screw) 2 Remove the Front Cabinet. (Loosen six screw) 3 Remove the Side Cabinet. (Loosen seven screw) 4 Remove the Guide Support. (Loosen two screw)
Fig 1
3. Removing the Propeller Fan. (Fig 3) 1 Loosen the Nut for fixing the Propeller Fan. 2 Remove the Plain Washer. 3 Remove the Propeller Fan.
Fig 2
4. Removing the Motor ODU. (Fig 4) 1 Loosen four screw at Bracket Motor. 2 Disconnect the wire at Control Panel and remove Motor ODU.
Fig 3
5. Removing the Dual Capacitor. (Fig 5) 1 Disconnect the wire at Control Panel. 2 Loosen a screw at Clamp Capacitor. 3 Remove the Dual Capacitor.
Fig 4
6. Removing the Over load Protector. (Fig 6~7) 1 Loosen a Hex Nut at Terminal Cover. 2 Remove the Terminal Cover. 3 Remove the wire at Over load Protector. 4 Remove the Over load Protector.
Fig 5
Fig 6
Fig 7
69
DSB-240L
PROCEDURES 1.Stop the air conditioner and dis connect the wire from in door unit to out door unit. PHOTOS
2. Disassemble the case. (Fig 1~2) 1 Remove the Top Panel. (Loosen two screw and remove six hook) 2 Remove the Front Cabinet. (Loosen four screw and four hook) 3 Remove the Side Cabinet and Back Cabinet. (Loosen eight screw)
Fig 1
3. Removing the Propeller Fan. (Fig 3) 1 Loosen the screw for fixing the motor bracket. 2 Remove the Plain Washer. 3 Remove the Propeller Fan.
Fig 2
4. Temove the panel control. (Fig 4) 1 Disconnect the wire at control panel. 2 Loosen a screw at panel control. 3 Remove the parts on panel control.
Fig 3
5. Remove the partition panel. (Fig 5) 1 Loosen four screws at bracket motor. 2 Disconnect the wire at control panel.
Fig 4
6. Removing the Over load Protector. (Fig 6) 1 Remove the cocondenser 2 Loosen three volts at compressor. 3 Remove the compressor.
Fig 5
Fig 6
70
71
72
DSB-121L/DSB-122L
73
74
I NO 15, 15-11, 16, 26, 28 Will be changed depend on export destination & buyer requirements.
75
77
78
79
80
81
DSB-121L(Before)
82
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 21-1
PART CODE 3100300501 3106000900 3102100800 3108134AE0 3100030CE0 7400208411 7392800011 3100014100 3100015100 3105400700 3105400800 7347602011 3100020600 3100020700 3100014200 3100800600 3104503800 3100601901 3108000800 3101801000 3100015400 3104201301
PART NAME PAN BASE COMP BOLT FOOT GROMMET COMPRESSOR ASS'Y WASHER PLANE NUT LOCK CONDENSER ASS'Y BRACKET SERVICE ASS'Y SERVICE VALVE SERVICE VALVE BOLT HEX PIPE DISCHARGE ASS'Y PIPE SUCTION ASS'Y FILTER ASS'Y CABINET BACK PLATE PARTITION BRACKET MOTOR MOTOR ODU FAN PROPELLER PANEL CONTROL ASS'Y PANEL CONTROL
SPEC
REMARK
M8 X L46.5 MFZN SECC EPDM RCB120A001 M8.4 X 0.D22 X T1.6 M8 X P1.25 MFZN
M6 X L20 MFZN C1220T C1220T C1220T ABS or AES SBHG1 SBHG1 IC-9430DWLC5A ABS+G.F20%
83
PART CODE 3109500700 3101201100 3108900900 3103800300 3101202000 7111301611 7112403011 3100800701 3100800501 3104201201 3101401900 3104201100 3102600300 3102100700 7112401211 7112402011 3106001600 7112401614 7S422X40B1 7112401214
PART NAME CAPACITOR DUAL CLAMP CAPACITOR TERMINAL BLOCK LOCK TWIST CLAMP CORD TAPPING SCREW TAPPING SCREW CABINET SIDE CABINET FRONT PANEL ORIFICE COVER GRILLE PANEL TOP HANDLE FOOT CUSHTON TAPPING SCREW TAPPING SCREW SPECIAL SCREW TAPPING SCREW SPECIAL SCREW TAPPING SCREW
Q'TY 1 1 1 1 1 1 3 1 1 1 1 1 1 4 19 4 1 4 4 12
SPEC 3.5+25F 400VAC SBHG1 323-HDS103 DATL-250 NYLON TIS PAN 3 X 16 MFZN TIS TRS 4 X 30 MFZN ABS or AES ABS or AES P.P ABS or AES ABS or AES ABS or AES NBR T1S TRS 4 X 12 MFZN T1S TRS 4 X 20 MFZN T2 4 X 16 MFNI LOCKING T1S TRS 4 X 16 MFNI+PVC/W TT2 TRS SE 4 X 12 MFZN TIS TRS 4 X 12 MFZN+PVC/W
REMARK
84
23 6
16-3 16-1
2 24
DSB-240L
21
85
86
9 8 5
2 0 1
87
DSB-070L/DSB-091L
No 1 2 3 4 5 6 7 8 9 10 PART CODE 3100054400 3108912300 5EPV050120 3106900300 3104896300 3101300100 3102797610 3102797910 3102704000 3102704500 PART NAME CONTROL PCB ASSY TERMINAL BLOCK TRANSFORMER CAPACITOR SH.M.B SENSOR ID ASSY POWER CORD ASSY HARNESS HARNESS HARNESS HARNESS Q'TY 1 1 1 1 1 1 1 1 1 1 SN-DBW-03P DWA-220B 220V 50/60Hz 1.0F 400VAC PTM-KD43C-D2 16A 250V I/D COMP I/D EARTH POWER LED PCB SPEC REMARK
88
DSB-121L/DSB-122L
H3 H1
H2
6 2
5
S H3
1 4
89
DSB-121L/DSB-122L
No 1 2 3 4 5 6 7 8 H1 H2 S H3 PART CODE 3100503101 3100054400 3108054200 3103400300 3101395060 3108901230 5EPV050100 3106900300 3102797610 3102797500 3104896300 3102794000 PART NAME CONTROL BOX CONTROL PCB ASS'Y LED PCB ASS'Y KNOB RESET SWITCH POWER CORD ASS'Y TERMINAL BLOCK TRANS FORMER CAPACITOR SH.M.B HARNESS I/D COMP HARNESS LED PCB SENSOR ID ASS'Y HARHESS POWER Q'TY 1 1 1 1 1 1 1 1 1 1 1 1 PTM-KD-43C-D2 SN-DBW-03P DWA220A-50/60Hz 1.0F 400VAC SPEC P .P+G.F 20% FR-1 FR-1 ABS BUYER REMARK
90
DSB-240L
12
7 4 6 9
5 10
8 11
91
DSB-240L
No 1 2 3 4 5 6 7 8 9 10 11 12 PART CODE 3104300830 3101200400 3106902400 3102797910 3102714400 3102704410 3102704010 3102702200 3102704430 3104896300 3108912320 5EPV050120 PART NAME CONTROL PCB ASSY CLAMP POWER CORD CAPACITOR SH.M.B HARNESS EARTH HARNESS CAPACITOR HARNESS COMP SIGNAL HARNESS POWER HARNESS TH3 HARNESS OD SIGNAL SENSOR ID ASSY TERMINAL BLOCK TRANSFORMER Q'TY 1 1 1 1 1 1 1 1 1 1 1 1 SPEC 240LH(A), 240LH(B) DA-5N 2.0MF 400V GREEN/YELLOW L170mm DSB-240L, LH CAPACITOR UL1015#18 UL1015#16 TH-3-1 UL1015#18 NTM-KD43C-D1D2 L450, L330 SB-DBW-4P DWA-220B REMARK
92