Patterson Pump Company LTD: Model: 5x4x12 SSC Size: 5x4x12 Qty: 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Patterson Pump Company Ltd

Date :
Our Ref . : EGQ-7030
Subject. :
Item No. : A

Model: 5x4x12 SSC Size: 5x4x12 Qty: 1


OPERATING CONDITIONS
Service DIESEL FIRE PUMP
Liquid Handled WATER
Capacity M3/HR / GPM 170 / 750
Total Head M / FEET 92 / 301
Specific Gravity 1.0
Viscosity (CP) 1.0
Temperature C / F AMBIENT
NPSH - Available -
Vapour Pressure -
Suction Pressure -
Discharge Pressure -
Performance at : 3000 RPM
Efficiency % 77%
HP Rated / HP maximum 75 / 90
NPSH - Required Feet, at 150% capacity 23
Impeller Diam. Rated / Min / Max Inches 11-1/4 / 10 / 12
Pump Weight Lbs. -
Performance Curve Number A02-69285
A02-108280
MATERIAL OF CONSTRUCTION
Casing CAST IRON
Impeller BRONZE
Impeller Type ENCLOSED
Shaft STEEL
Sleeve BRONZE
Wear Plate BRONZE
Rotation CLOCKWISE
Lubrication GREASE
Base Plate Type STEEL
Coupling FLEXIBLE
Mechanical Seal or Packing SOFT PACKING
Discharge Flange Lbs. 125 #
Driver : CLARKE JU4H-UF34
Furnished by PATTERSON Enclosure -
Rating 115 HP Insulation -
Starting Method - Service Factor -
RPM 3000 Frame -
-
Temperature Starting System 12 V
sd
Q=750GPM @ H=301 FT
5x4x12SSC 750 301
3000 115 12
TORNATECH
UL /FM
CLARKE FIRE PUMP DRIVERS
HIGH SPEED MODELS
JU4H-UF14 JU4H-UF24 JU4H-UF34 JU4H-UF54

FM-UL-cUL APPROVED RATINGS BHP/kW


JU4H OPERATING SPEED (RPM)
MODEL 2800 3000
70 71
UF14 52 53
80 83
UF24 60 62
104 115
UF34 78 86
145 145
UF54 108 108

JU4H-UF54 ENGINE EQUIPMENT


OVERALL WIDTH
29.0 Heat Exchanger — (S) Tube & Shell Type, 60 PSI
[735] w/NPTF Connections
Instrument Panel — (S) English & Metric, Tachometer,
Air Cleaner — (S) Direct Mounted, Washable, Hourmeter, Water Temperature, Oil Pressure &
Indoor Service Two (2) Voltmeters
(O) Disposable, Drip Proof, Indoor Service Junction Box — (S) Integral with Instrument Panel;
(O) Outdoor Type For DC Wiring Interconnection to Engine Controller
Alternator — (S) 12V-DC, 42 Amps; With Belt Guard Lube Oil Cooler — (S) Engine Water Cooled,
(O) 24V-DC, 40 Amps; With Belt Guard Plate Type
Exhaust Protection — (S) Blankets on UF14,UF24; Lube Oil Filter — (S) Full Flow w/By-Pass Valve
• Metal Guards on Manifolds & Turbo on UF34, UF54 Lube Oil Pump — (S) Gear Driven, Gear Type
Exhaust Flex Connection — (O) SS Flex, NPT Manual Start Controls — (S) On Instrument Panel
Flywheel Housing — (S) S.A.E. #3 Overspeed Control — (S) Electronic w/Reset & Test
Flywheel Power Take Off — (S) 11.5" S.A.E. on Instrument Panel
Industrial Flywheel Connection Raw Water Solenoid Operation — (S) Automatic
• Drive Shaft & Guard — (O) Drive Shaft System
UF14, UF24 - 41 Series; UF34, UF54 - 51 Series from Engine Controller & from Emergency Local Control
• Falk Coupling — (O) Engine Half - UF14, Run-Stop Control — (S) On Instrument Panel With
UF24, UF34, & UF54-1070T10 Coupling Control Position Warning Light
Fuel Connections — (S) Fire Resistant Flexible Supply Run Solenoid — (S) 12V-DC Energized to Run
& Return Lines (O) 24V-DC Energized to Run
Fuel Injection System — (S) Stanadyne Direct Injection (O) 12V-DC Energized to Stop
Fuel Filter — (S) Primary Filter w/Priming Pump (O) 24V-DC Energized to Stop
Engine Heater — (S) 120 V-AC, 1500 Watt Starters — (S) Two (2) 12 V-DC (O) Two (2) 24 V-DC
(O) 240 V-AC, 1500 Watt Throttle Control — (S) Adjustable Speed Control,
Governor, Speed — (S) Constant Speed, Mechanical Tamper Proof
Water Pump — (S) Poly-Vee Belt Drive w/Guard
(S) – Standard Equipment (O) – Optional Equipment
LISTED meets
513Y
NFPA-20 FM approved
1333
Requirements
SPECIFICATIONS
JU4H Models
Item
UF14 UF24 UF34 UF54

Aspiration N T

Rotation* Clockwise (CW)

Weight - lb. (kg) 910 (413) 935 (424)

Compression Ratio 17.6:1 17.0:1

Displacement - cu. in. (l) 275 (4.5)

Engine Type 4 Stroke Cycle – Inline Construction

Bore & Stroke - in. (mm) 4.19 x 5.00 (106 x 127)

Installation Drawing D – 534

Wiring Diagram C07575 (DC Engine Wiring) C07651 (AC Heater Wiring)

Engine Series John Deere 4045 Series

Abbreviations: CW – Clockwise N – Naturally Aspirated T – Turbocharged


*Rotation viewed from Heat Exchanger / Front of engine
Engine intended for Indoor use or inside weatherproof enclosue only

† ENGINE RATINGS BASELINES


Engines are rated at standard SAE conditions of 29.61 in. (7521 mm) Hg barometer and 77˚F (25˚C) inlet air temperature [approximates
300 ft. (91.4 m) above sea level] by the testing laboratory (see SAE Standard J 1349).
A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall be made for diesel engines for each 1000 ft.
(305 m) altitude above 300 ft. (91.4 m).
A deduction of 1 percent from engine horsepower rating as corrected to standard SAE conditions shall be made for diesel engines for every
10˚F (5.6˚C) above 77˚F (25˚C) ambient temperature.
Note: Engines certified at any speed between 2800 & 3000 RPM. JU6H Engines cannot be operated below 2800 RPM.

CERTIFIED POWER AT ANY SPEED


Although FM-UL Certified BHP ratings are shown at specific speeds, Clarke
engines can be applied at any intermediate speed. To determine the intermediate
certified power, make a linear interpolation from the Clarke FM-UL certified power
curve. Contact Clarke or your Pump OEM representative to obtain details.

CLARKE
www.clarkefire.com Fire Protection Products
CLARKE Fire Protection Products, Inc. CLARKE UK, Ltd.
3133 E. Kemper Rd. Grange Works, Lomond Rd.
Cincinnati, Ohio 45241 Coatbridge, ML5-2NN
United States of America United Kingdom
Tel +1-513-771-2200 Fax +1-513-771-0726 Tel +44-1236-429946 Fax +44-1236-427274
Specifications and information contained in this brochure subject to change without notice.

C131122 11/04
  

SPECIFICATIONS FOR 
MODEL GPD DIESEL ENGINE DRIVEN 
FIRE PUMP CONTROLLER 
 
 
LISTING AND APPROVAL   Hand‐OFF‐Auto selector switch position 
The diesel engine driven fire pump controller   Actuation mode 
shall meet the latest NFPA 20 requirements, be   Type of controller 
listed with UL (in accordance with UL218 and   Method of shutdown 
CSA C22.2 No. 14 Industrial Control Equipment),   Time and date 
approved by FM Global (in accordance with   Pump room temperature (⁰F or ⁰C) 
approvals Class 1321/1323) and by the City of   System pressure in 5 different user 
New York for fire pump service.  selectable units of measure; 
  o PSI 
ENCLOSURE  o kPa 
The standard enclosure shall be NEMA type 2  o Bar 
(IP31) and suitable for wall mounting. Wall  o Feet of head 
mounting lugs shall be provided. The enclosure  o Meter of water 
shall incorporate a bottom entry gland plate for   
power and or engine connection entrance. The  The touch screen operator interface shall allow 
gland plate shall be field removable and meet  for the programming and display of: 
the same NEMA rating of the enclosure. Lifting   Cut‐In and Cut‐Out pressure settings 
lugs shall be provided.   Minimum run period timer  
   Sequential start timer  
 
OPERATIONAL COMPONENTS   Periodic test timer  
The diesel engine driven fire pump controller   
shall be supplied with a Hand‐OFF‐Auto selector  The user shall be able to select the language of 
switch installed behind a lockable breakable  operation on‐site. 
cover.   
  Contextual HELP screens shall be accessible to 
TOUCH SCREEN OPERATOR INTERFACE  the user while navigating through the operator 
The diesel engine driven fire pump controller  interface in the chosen language.   
shall be supplied with a 4.2” LCD color touch    
screen (HMI technology) operator interface  CONDITION AND ALARM VISUAL INDICATORS 
powered by an embedded microcomputer with  The touch screen operator interface shall 
software PLC logic. The operator interface’s  visually indicate the following alarms and 
touch screen shall allow navigation through the  differentiate the criticalness by color code: 
various operating screens. The following keypad   Engine run 
type pushbuttons shall be provided:   Main switch in Hand, Off or Auto  
 Crank from Battery #1    AC present / failure 
 Crank from Battery #2    Battery #1 and battery #2 failure 
 Stop   Battery charger #1 and battery charger #2 
 Run test  failure  
 Navigation   Low oil pressure 
 Help   High engine temperature 
 Home   Overspeed 
 Alarms   Fail to start 
 Settings/Configuration   Fail when running 
 History/Statistics   Periodic test 
The touch screen operator interface shall   System overpressure  
graphically display:   Water reservoir low 
 AC power present   Low system (discharge) pressure 
 Charger #1 and #2 charging mode   Periodic test cut‐in not reached  
 Battery #1 and #2 voltage and amperage   Run test solenoid valve check  
 System pressure   Faulty pressure transducer  
 Cut‐out and cut‐in pressure settings   Pump on demand 
 Starter #1 and #2 rest or cranking   Over pressure  
 Engine stopped / running   Under pressure  
 Type of starting cause   Low pump room temperature 
 Fuel solenoid valve energized / not   Low fuel level 
energized   
 Timers counting   
 

Effective date: February 1 2012     GPA‐SPE‐002/E Rev.0 
Supersedes:  new   
  

SPECIFICATIONS FOR 
MODEL GPD DIESEL ENGINE DRIVEN 
FIRE PUMP CONTROLLER 
 
 
   
CRANK CYCLE  SERVICE/FLOW TESTING CAPABILITIES 
The fire pump controller shall have a crank cycle  The diesel engine driven fire pump controller’s 
as follows:  touch screen operator interface shall have the 
‐ Crank from battery 1 for 15 seconds  capability of scheduling maintenance 
‐ Rest for 15 seconds  reminders. It shall also have the capability of 
‐ Crank from Battery 2 for 15 seconds  inputting pump flow test data, generate and 
This cycle shall repeat 3 times. A visual alarm  display the pump curve and store this 
“Fail TO Start” shall appear if the engine does 
not start after the completion of this cycle.  information in memory for the lifetime of the 
  controller. 
PRESSURE AND EVENT RECORDING   
The fire pump controller’s touch screen  CONNECTION FOR EXTERNAL DEVICES 
operator interface shall be capable of logging  The diesel engine driven fire pump controller 
pressure data and operational events with time  shall provide terminals for the connection for 
and date stamp. It shall be able to display the  the following external devices: 
last 500 operational events and display the  • Manual remote start device 
pressure data in text and/or graphic form.  • Automatic remote start device 
Under regular maintained operation, pressure  • Deluge valve start 
data and operational events can be stored in   
memory for up to 5 years. The data shall also be  ALARM CONTACTS FOR REMOTE INDICATION 
retrievable and downloadable to a flash  SPDT dry alarm contacts rated for 8A – 250VAC 
memory disk via the USB port accessible to the  for remote indication shall be provided for the 
user without having to open the controller  following conditions; 
door. General system information, events and 
alarms include the following:  • Engine run (x2) 
 Last service statistics   • Main switch in AUTO 
• Powered since   • Main switch in HAND or OFF 
• On time   • Common controller trouble (fail safe) 
• Engine last run  • Common engine trouble 
• Engine run time  • Common pump room alarm 
• Engine start count  Removable alarm contact terminals shall be 
• Minimum, maximum, average  provided. 
system pressure   
• Minimum, maximum, average  AUDIBLE ALARM 
pump room temperature  A 4” alarm bell rated for 85dB at 10ft (3m) shall 
 All time statistics  sound during boot up and internal 
• First power up  communication error. 
• First start up   
• On time  MANUFACTURER 
The diesel engine driven fire pump controller 
 Power statistics  shall be a Model GPD with ViZi Touch operator 
 Battery voltage readings with  interface as manufactured by Tornatech Inc. 
date stamp   
 Battery amperage readings with 
date stamp 
 
PRESSURE SENSING ‐ WETTED PARTS 
The diesel engine driven fire pump controller 
shall be supplied with a pressure transducer 
and run test solenoid valve assembly. The 
pressure sensing line connection to the 
pressure transducer shall be ½” FNPT. Provision 
for a redundant pressure transducer shall be 
provided. This assembly shall be rated for 
500psi working pressure (calibrated at 0‐300psi) 
and be externally mounted with a protective 
cover.   

Effective date: February 1 2012     GPA‐SPE‐002/E Rev.0 
Supersedes:  new   
Product Description
Diesel Engine Fire Pump Controller • FTA1100
„ Two manual crank push-buttons
„ Two 10 Amp battery chargers with 4 stage charg-
ing cycle, selectable AC voltage (110 / 220),
selectable DC voltage (12 / 24), and selectable
battery type (Lead Acid, Ni-Cad 9/18 Cell, Ni-
Cad 10/20 Cell)
„ Door mounted display/interface panel featuring
a 80 Character Vacuum Fluorescent Display,
Membrane Type User Control Push-buttons and
easy to read LED Indicators
„ MAIN SWITCH IN AUTO LED
„ ENGINE FAIL TO START LED
„ CHARGER MALFUNCTION LED
„ BATTERY #1 TROUBLE LED
„ BATTERY #2 TROUBLE LED
„ SYSTEM PRESSURE LOW LED
„ ENGINE RUNNING LED
„ ENGINE COOLANT TEMP HIGH LED
„ ENGINE OIL PRESSURE LOW LED
Description – Firetrol® combined automatic and „ ENGINE OVERSPEED LED
manual Mark II based diesel engine fire pump „ LOW FUEL LEVEL LED
controllers are intended for starting and monitoring „ Minimum Run Timer / Off Delay Timer
fire pump diesel engines. They are available for „ Daylight Savings Time Option
use with 12 or 24 volt negative ground systems „ Weekly Test Timer
using lead acid or Nickel-Cadmium batteries. The „ Engine Run Time Meter
controller monitors, displays and records fire pump „ Digital Pressure Display
system information. „ USB Host Controller and Port
„ Solid State Pressure Transducer
Approvals – Firetrol fire pump controllers are listed „ Data Log
by Underwriters’ Laboratories, Inc., in accordance „ Event Log (3000 events)
with UL218, Standard for Fire Pump Controllers, „ Simultaneous Display of Battery Voltages and
CSA, Standard for Industrial Control Equipment Charging Rates
(cUL), and approved by Factory Mutual. They are „ Disk Error Message
built to meet or exceed the requirements of the ap- „ Disk Near Full Message
proving authorities as well as NEMA and the latest „ Pressure Error Message
editions of NFPA 20, Installation of Centrifugal Fire „ Fail to Start Message
Pumps, and NFPA 70, National Electrical Code. „ Low Suction Pressure Message
„ Crank Cycle Status Indication (Displays Crank-
Standard Features – The following are included ing Battery, Number of Starting Attempts and
as standard with each controller: Crank/Rest Time Remaining)
„ Two pole AC line circuit breaker „ 300 psi (20.7 bars) wet parts (solid state pres-
„ Manual-Off-Auto selector switch sure transducer, solenoid valve, plumbing) for
„ Manual test push-button fresh water applications
„ High Speed Open Serial Communications Port
„ NEMA Type 2 enclosure
Specifications
Diesel Engine Fire Pump Controllers • FTA1100

Diesel Engine Fire Pump Controller LED Visual Indicators


The fire pump controller shall be a factory as- LED indicators, visible with the door closed, shall
sembled, wired and tested unit and shall conform to indicate:
all the requirements of the latest edition of NFPA 20, • Main Switch in Auto
Standard for the Installation of Stationary Pumps for Fire • Alarm
Protection and NFPA 70, National Electrical Code. • Engine Fail to Start
The controller shall be listed by Underwriters Labo- • Charger Malfunction
ratories, Inc., in accordance with UL218, Standard for • Battery #1 Trouble
Fire Pump Controllers, CSA, and Canadian Standards • Battery #2 Trouble
Association CSA-C22.2, Standard for Industrial Control • System Pressure Low
Equipment (cULus) and approved by Factory Mutual. • Engine Running
• Engine Coolant Temperature High
The controller shall be: • Engine Oil Pressure Low
• Engine Overspeed
12 Volt
24 Volt Data Logging
The digital display shall monitor the system and
The controller components shall be housed in a NEMA log the following data:
Type 2 (IEC IP11) drip-proof, wall mounted enclosure. • Motor Calls/Starts
• Total Engine Run Time
Operator Interface • Last Engine Run Time
The fire pump controller shall feature an operator • Last Engine Start
interface with user keypad. The interface shall monitor • Last High Water Temperature
and display motor operating conditions, including all • Last Low Oil Pressure
alarms, events, and pressure conditions. All alarms, • Last Low Fuel Level
events, and pressure conditions shall be displayed with • Last Battery Charger Failure
a time and date stamp. The display shall be a 4-line, • Last Battery Trouble
20-character, vacuum fluorescent, dot matrix type • Last Engine Overspeed
designed to allow easy viewing from all angles and in • Minimum Battery Voltages
all light conditions. The display and interface shall be • Maximum Battery Voltages
NEMA rated for Type 2, 3R, 4, 4X, and 12 protection and • Total Unit Run Time
shall be fully accessible without opening the controller • Minimum/Maximum System Pressure
door. The display and user interface shall utilize multiple
levels of password protection for system security. A Event Recording
minimum of 3 password levels shall be provided. The Memory - The controller shall record all opera-
display shall be capable of being programmed for any tional and alarm events to system memory. All events
language. shall be time and date stamped and include an index
number. The system memory shall have the capability
of storing 3000 events and allow the user access to
Digital Status/Alarm Messages the event log via the user interface. The user shall
The digital display shall indicate text messages for have the ability to scroll through the stored messages
the status and alarm conditions of: in groups of 1, 10, or 100.
• Engine Run • Sequential Start Time USB Host Controller - The controller shall have a
• Minimum Run Time • Crank/Rest Time - Cycle built-in USB Host Controller. A USB port capable of
/Off Delay Time • Remote Start accepting a USB Flash Memory Disk (aka: flash drive,
• Engine Fail to Start • System Battery Low thumb drive, memory stick, etc..) shall be provided.
• Low Suction Pressure • Printer Error The controller shall save all operational and alarm
• Drive Not Installed • Manual Engine Crank events to the flash memory on a daily basis. Each
• Disk Error saved event shall be time and date stamped. The total
• Disk Near Full amount of historical data saved shall solely depend
• Pressure Error on the size of the flash disk utilized. The controller
shall have the capability to save settings and values
The Sequential Start Timer, Minimum Run Timer/Off to the flash disk via the user interface.
Delay Timer and Crank/Rest time shall be displayed Serial Communications - The controller shall
as numeric values reflecting the value of the remaining feature a RS485 serial communications port for use
time. with 2 or 4 wire Modbus RTU communications.
Solid State Pressure Transducer A weekly test timer shall be provided as standard.
The controller shall be supplied with a solid state The controller shall have the ability to program the time,
pressure transducer with a range of 0-300 psi (0-20.7 date, and frequency of the weekly test. In addition, the
bar) ±1 psi. The solid state pressure switch shall be controller shall have the capability to display a preven-
used for both display of the system pressure and con- tative maintenance message for a service inspection.
trol of the fire pump controller. Systems using analog The message text and frequency of occurrence shall
pressure devices or mercury switches for operational be programmable through the user interface.
control will not be accepted. A Lamp Test feature shall be included. The user
The START, STOP and SYSTEM PRESSURE interface shall also have the ability to display the status
shall be digitally displayed and adjustable through of the system inputs and outputs.
the user interface. The pressure transducer shall be
mounted inside the controller to prevent accidental Battery Chargers
damage. The pressure transducer shall be directly The controller shall include two fully automatic, 200
pipe mounted to a bulkhead pipe coupling without amp hour, 4 step battery chargers. The chargers shall
any other supporting members. Field connections feature a qualification stage, in which the batteries are
shall be made externally at the controller coupling to examined by the charger to insure that they are not
prevent distortion of the pressure switch element and defective and are capable of accepting a charge. The
mechanism. battery charger shall feature:
• Selectable AC Power Voltage
Operation • Selectable Battery Voltage
A digitally set On Delay (Sequential Start) timer • Selectable Battery Type
shall be provided as standard. Upon a call to start, • Charge Cycle Reset Push-button
the user interface shall display a message indicating
the remaining time value of the On Delay timer. The controller shall be a Firetrol brand.
The controller shall be field programmable for
manual stop or automatic stop. If set for automatic
stopping, the controller shall allow the user to select
either a Minimum Run Timer or an Off Delay Timer.
Both timers shall be programmable through the user
interface.
The controller shall include an AC Power Loss
start timer to start the engine in the event of AC Power
failure.
The controller shall be fully programmable to al-
low up to 8 custom alarm messages to be displayed
on the user interface.

(919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA


SP1100-20 (06-11-07)
Patterson Pump Company Ltd
Date :
Inquiry No. : EGQ-7030
Proposal No. :
Item No. : B

Model: 5x4x12 SSC Size: 5x4x12 Qty: 1


OPERATING CONDITIONS
Service ELECTRIC FIRE PUMP
Liquid Handled WATER
Capacity M3/HR / GPM 170 / 750
Total Head M / FEET 92 / 301
Specific Gravity 1.0
Viscosity (CP) 1.0
Temperature C / F AMBIENT
NPSH - Available -
Vapour Pressure -
Suction Pressure -
Discharge Pressure -
Performance at : 2950 RPM
Efficiency % 77%
HP Rated / HP maximum 75 / 90
NPSH – Required, Feet at 150% capacity 23
Impeller Diam. Rated / Min / Max Inches 11-1/4 / 10 / 12
Pump Weight Lbs. -
Performance Curve Number A02-69286
A02-108280
MATERIAL OF CONSTRUCTION
Casing CAST IRON
Impeller BRONZE
Impeller Type ENCLOSED
Shaft STEEL
Sleeve BRONZE
Wear Plate BRONZE
Rotation CLOCKWISE
Lubrication GREASE
Base Plate Type STEEL
Coupling FLEXIBLE
Mechanical Seal or Packing SOFT PACKING
Discharge Flange Lbs. 125 #
ELECTRIC MOTOR
Furnished by PATTERSON Enclosure ODP
Rating 100 HP Insulation F
Starting Method Y-DELTA Service Factor 1.15
RPM 2950 Frame
Temperature - Power 3 / 50 / 380 V
sd
Q=750 GPM @ H=301 FT
5x4x12SSC 750 301

100 3 50 380 2950


TORNATECH
UL/FM
  

SPECIFICATIONS FOR 
MODEL GPY FULL SERVICE REDUCED VOLTAGE  
WYE‐DELTA OPEN TRANSITION STARTER 
        ELECTRIC FIRE PUMP CONTROLLER 
 
 
LISTING AND APPROVAL   One “Emergency Start” and run handle 
The electric fire pump controller shall meet the  mechanism latchable in the “ON” 
latest NFPA 20 requirements, be listed with UL  position 
(in accordance with UL218 and CSA C22.2 No.   
14 Industrial Control Equipment), approved by  TOUCH SCREEN OPERATOR INTERFACE 
FM Global (in accordance with approvals Class  The electric fire pump controller shall be 
1321/1323) and by the City of New York for fire  supplied with a 4.2” LCD color touch screen 
pump service.  (HMI technology) operator interface powered 
  by an embedded microcomputer with software 
STARTING METHOD  PLC logic. The operator interface’s touch screen 
The electric fire pump controller shall be a full  shall allow navigation through the various 
service combined manual and automatic type  operating screens. 
suitable for reduced voltage wye‐delta open  The following keypad type pushbuttons shall be 
transition starting of the electric fire pump  provided: 
motor.    Start  
   Stop 
SHORT CIRCUIT WITHSTAND RATING   Run test 
The short circuit withstand rating of the electric   Navigation 
fire pump controller shall be 100 kA RMS at   Help 
200V ‐ 480V or 50 kA RMS at 600V.    Home 
 Alarms 
ENCLOSURE   Settings/Configuration 
The standard enclosure shall be NEMA type 2.   History/Statistics 
The enclosure shall incorporate a bottom entry  The touch screen operator interface shall 
gland plate for power and or motor lead  graphically display: 
entrance. The gland plate shall be field 
removable and meet the same NEMA rating of   Voltage and amperage readings of all three 
the enclosure. Lifting lugs shall be provided.  phases simultaneously and independently 
  displayed with true RMS technology.  
POWER CIRCUIT COMPONENTS   Motor starting transition  
The electric fire pump controller shall be   Motor stopped / running 
supplied with the following power components:   Type of starting cause 
 Voltage surge arrestor   Actuation mode 
 Motor rated combination isolating switch   Type of controller 
and circuit breaker assembly. Both the   Method of shutdown 
isolating switch and circuit breaker shall   Time and date 
be rated not less than 115% of the motor   Pump room temperature (⁰F or ⁰C) 
full load current.   System pressure in 5 different user 
 The circuit breaker overcurrent sensing  selectable units of measure; 
shall be non‐thermal type, magnetic only.   o PSI 
 Locked rotor protector set to  o kPA 
automatically trip the circuit breaker  o Bar 
within 8 to 20 seconds at 600% of full  o Feet of head 
load current. The locked rotor protector  o Meter of water 
shall be factory calibrated, set and tested.    
 A wye‐delta open transition electric   The touch screen operator interface shall allow 
motor starter  for the programming and display of: 
   Cut‐In and Cut‐Out pressure settings 
OPERATIONAL COMPONENTS   Minimum run period timer  
The electric fire pump controller shall be   Sequential start timer  
supplied with the following externally flange   Periodic test timer  
mounted components approved to match the   
NEMA rating of the enclosure:  The user shall be able to select the language of 
 One common operating handle for both  operation on‐site. 
the isolating switch and the circuit   
breaker assembly mechanically  Contextual HELP screens shall be accessible to 
interlocked with the enclosure door to  the user while navigating through the operator 
prohibit access to the interior in the "ON"  interface in the chosen language.   
position.     

Effective date:      GPY‐SPE‐002/E 
Supersedes:     
  

SPECIFICATIONS FOR 
MODEL GPY FULL SERVICE REDUCED VOLTAGE  
WYE‐DELTA OPEN TRANSITION STARTER 
        ELECTRIC FIRE PUMP CONTROLLER 
 
 
CONDITION AND ALARM VISUAL INDICATORS  • Amperage between phases with date 
The touch screen operator interface shall  stamp 
visually indicate the following alarms and   
differentiate the criticalness by color code:  WETTED PARTS 
 Normal power phase reversal   The electric fire pump controller shall be 
 Normal power phase loss   supplied with a pressure transducer and run 
 Normal power loss   test solenoid valve assembly. The pressure 
 Locked rotor   sensing line connection to the pressure 
 Fail to start   transducer shall be ½” FNPT. Provision for a 
 Service required   redundant pressure transducer shall be 
 Undercurrent   provided. This assembly shall be rated for 
 Overcurrent   500psi working pressure and be externally 
 Under voltage   mounted with a protective cover.   
 Overvoltage   
 Phase unbalance   SERVICE/FLOW TESTING CAPABILITIES 
 Low water level  The electric fire pump controller’s touch screen 
 Low system (discharge) pressure  operator interface shall have the capability of 
 Periodic test cut‐in not reached   scheduling maintenance reminders. It shall also 
 Run test solenoid valve check   have the capability of inputting pump flow test 
 Faulty pressure transducer   data, generate and display the pump curve and 
 Pump on demand  store this information in memory for the 
 Over pressure   lifetime of the controller. 
 Under pressure    
 Low pump room temperature  CONNECTION FOR EXTERNAL DEVICES 
  The electric fire pump controller shall provide 
PRESSURE AND EVENT RECORDING 
The fire pump controller’s touch screen  terminals for the connection for the following 
operator interface shall be capable of logging  external devices: 
pressure data and operational events with time  • Manual remote start device 
and date stamp. It shall be able to display the  • Automatic remote start device 
last 500 operational events and display the  • Deluge valve start 
pressure data in text and/or graphic form.   
Pressure data and operational events shall be  ALARM CONTACTS FOR REMOTE INDICATION 
stored in memory for the lifetime of the  SPDT dry alarm contacts rated for 8A – 250VAC 
controller. The data shall also be retrievable and  for remote indication shall be provided for the 
downloadable to a flash memory disk via the  following conditions; 
USB port accessible to the user without having  • Power or phase failure and/or circuit 
to open the controller door. General system  breaker in open position 
information, events and alarms include the  • Phase reversal 
following:  • Pump run (X2) 
 Last service statistics   • Common pump room alarm 
• Powered since   • Common motor trouble 
• On time   Removable alarm contact terminals shall be 
• Motor last run  provided. 
• Motor run time   
• Motor start count  AUDIBLE ALARM 
• Minimum, maximum, average  A 4” alarm bell rated for 85dB at 10ft (3m) shall 
system pressure  sound during boot up and internal 
• Minimum, maximum, average  communication error. 
pump room temperature   
 All time statistics  MANUFACTURER 
• First power up  The electric fire pump controller shall be a 
• First start up  Model GPY with ViZi Touch operator interface 
• On time  as manufactured by Tornatech Inc. 
 Power statistics   
• Voltage between phases with date 
stamp 

Effective date:      GPY‐SPE‐002/E 
Supersedes:     
Product Description
Wye-Delta Open Transition Starting Electric • FTA1300
Fire Pump Controllers

„ Emergency Manual Run Mechanism to mechani-


cally close motor contactor contacts in an emer-
gency condition
„ Built-in Start and Stop push-buttons to bypass
automatic start circuits
„ Door mounted display/interface panel featuring
a 40 Character Vacuum Fluorescent Display,
Membrane Type User Control Push-buttons and
easy to read LED Indicators
„ Single handle Isolating Disconnect Switch/Circuit
Breaker mechanism
„ POWER ON LED
„ PUMP RUN LED
„ PHASE FAILURE LED
„ PHASE REVERSAL LED
„ LOW PRESSURE LED
„ DELUGE OPEN LED
„ INTERLOCK ON LED
„ TRANSFER SWITCH NORMAL LED (If unit
Description—Firetrol® FTA1300 Wye-Delta, Open ordered with Automatic Power Transfer Switch)
Transition Starting Fire Pump Controllers are used „ TRANSFER SWITCH EMERGENCY LED (If unit
with delta-wound squirrel cage motors. FTA1300 ordered with Automatic Power Transfer Switch)
controllers are of the open circuit transition type in „ EMERGENCY ISOLATING SWITCH OFF LED
which the motor circuit is opened during the transition (If unit ordered with Automatic Power Transfer
from start to run. The controller monitors, displays Switch)
and records fire pump system information. „ Minimum Run Timer / Off Delay Timer
Actuating the controller by the pressure switch, „ Daylight Savings Time option
START pushbutton or deluge valve contact closes „ Weekly Test Timer
the start contactor connecting the motor to the line „ Motor Acceleration Timer
in the wye connection. The motor will draw approxi- „ Elapsed Time Meter
mately 33% of its normal inrush current and develop „ Digital Pressure Display
approximately 33% of its normal starting torque. After „ USB Host Controller and Port
a time delay, the motor is automatically reconnected „ Solid State Pressure Transducer
in delta, applying full voltage to the motor windings.
„ Data Log
These controllers are recommended especially for
„ Event Log (3000 Events)
use with generator sets.
„ True RMS Metering with simultaneous 3 phase
display of amps and volts
Approvals—Firetrol fire pump controllers are listed
„ Disk Error message
by Underwriters’ Laboratories, Inc., in accordance
„ Disk Near Full message
with UL218, Standard for Fire Pump Controllers,
„ Pressure Error message
CSA, Standard for Industrial Control Equipment,
„ Motor Over 320% message
and approved by Factory Mutual. They are built to
„ Local Start message
meet or exceed the requirements of the approving
„ Remote Start message
authorities as well as NEMA and the latest editions
„ Emergency Start message
of NFPA 20, Installation of Centrifugal Fire Pumps,
„ Fail To Start message
and NFPA 70, National Electrical Code.
„ Undervoltage message
„ Overvoltage message
Standard Features—The following are included as
„ High Speed Open Serial Communications Port
standard with each controller:
„ NEMA Type 2 enclosure
„ Voltage surge protector
„ Main Disconnect Switch sized for connected mo-
tor horsepower and voltage
„ Fire pump Circuit Breaker
„ Motor contactor
„ Suitable for use as Service Equipment
Specifications FTA1000
Electric Fire Pump Controllers • -1900

Main Fire Pump Controller position without affecting the tripping characteristics
The main fire pump controller shall be a factory of the circuit breaker. The controller door shall have
assembled, wired and tested unit and shall conform a locking type handle and three point cam and roller
to all the requirements of the latest edition of NFPA vault type hardware. The circuit breaker trip curve
20, Standard for the Installation of Stationary Pumps adjustment shall be factory set, tested and sealed for
for Fire Protection and NFPA 70, National Electrical the full load amps of the connected motor. The circuit
Code. breaker shall be capable of being field tested to verify
The controller shall be listed by Underwriters Labo- actual pick up, locked rotor, and instantaneous trip
ratories, Inc., in accordance with UL218, Standard for points after field installation without disturbing incom-
Fire Pump Controllers, CSA, and Canadian Standards ing line and load conductors.
Association CSA-C22.2, Standard for Industrial Con-
trol Equipment (cULus), approved by Factory Mutual Operator Interface
and approved by the City of New York for fire pump The fire pump controller shall feature an operator
service. interface with user keypad. The interface shall moni-
tor and display motor operating conditions, including
Starting Method all alarms, events, and pressure conditions. All alarms,
The controller shall be of the combined manual events, and pressure conditions shall be displayed
and automatic type designed for: with a time and date stamp. The display shall be a 2-
Full Voltage Starting line, 20-character, vacuum fluorescent, dot matrix type
Solid State Soft Starting designed to allow easy viewing from all angles and in
Wye (Star)-Delta Open Transition Starting all light conditions. The display and interface shall be
Wye (Star)-Delta Closed Transition Starting NEMA rated for Type 2, 3R, 4, 4X, and 12 protection
Part Winding Starting and shall be fully accessible without opening the con-
Primary Resistance Reduced Voltage Starting troller door. The display and user interface shall uti-
Autotransformer Reduced Voltage Starting lize multiple levels of password protection for system
security. A minimum of 3 password levels shall be
of the fire pump motor having the horsepower, volt- provided. The display shall be capable of being pro-
age, phase and frequency rating shown on the plans grammed for any language.
and drawings. The controller components shall be
housed in a NEMA Type 2 (IEC IP11) drip-proof, wall Ammeter/Voltmeter
mounted enclosure. The fire pump controller operator interface shall
be capable of displaying true RMS digital motor
Withstand Ratings (Short Circuit Current Ratings) voltage and current measurements for all three
All controller components shall be front mounted, phases simultaneously. Displays requiring push-
wired and front accessible for maintenance. The mini- button and selector switches to toggle between
mum withstand rating of the controllers shall not be phases or current and voltage shall not be ac-
less than 100,000 Amps RMS Symmetrical at 200- cepted.
600 Volts*. If the available system fault current ex-
ceeds these ratings, the controllers shall be supplied Voltage and current shall be measured by True
with a withstand rating of 150,000 or 200,000 Amps RMS technology to provide the most accurate
RMS Symmetrical, as required. measurement for all sine waves, including non-
*Note: 100,000 Amp withstand rating not available in sinusoidal waveforms. Average responding meters
some larger horsepowers. Consult factory for will not be accepted.
details.

Isolation Switch and Circuit Breaker Digital Status/Alarm Messages


The controller shall include a motor rated combi- The digital display shall indicate text messages
nation isolating disconnect switch/circuit breaker, for the status and alarm conditions of:
mechanically interlocked and operated with a single, • Motor On • Sequential Start Time
externally mounted handle. When moving the handle • Minimum Run Time • Local Start
from OFF to ON, the interlocking mechanism shall / Off Delay Time • Remote Start
sequence the isolating disconnect switch ON first, and • Fail to Start • System Battery Low
then the circuit breaker. When the handle is moved • Under Voltage • Over Voltage
from ON to OFF, the interlocking mechanism shall • Locked Rotor Trip • Over Frequency
sequence the circuit breaker OFF first, and then the • Emergency Start • Motor Over 320%
isolating disconnect switch. • Drive Not Installed • Motor Overload
The isolating disconnect switch/circuit breaker • Disk Error • Printer Error
shall be mechanically interlocked so that the enclo- • Disk Near Full • Pressure Error
sure door cannot be opened with the handle in the
ON position except by a hidden tool operated defeater The Sequential Start Timer and Minimum Run Timer/
mechanism. The isolating disconnect switch/circuit Off Delay Timer shall be displayed as numeric values
breaker shall be capable of being padlocked in the reflecting the value of the remaining time.
OFF position for installation and maintenance safety,
and shall also be capable of being locked in the ON
LED Visual Indicators The START, STOP and SYSTEM PRESSURE shall
LED indicators, visible with the door closed, shall be digitally displayed and adjustable through the user
indicate: interface. The pressure transducer shall be mounted
• Power On • Emerg. Isolating Switch Open inside the controller to prevent accidental damage.
• Pump Running • Low System Pressure The pressure transducer shall be directly pipe mounted
• Alarm • Transfer Switch Normal to a bulkhead pipe coupling without any other support-
• Deluge Open • Transfer Switch Emergency ing members. Field connections shall be made exter-
• Phase Failure • Phase Reversal nally at the controller coupling to prevent distortion of
• Interlock On the pressure switch element and mechanism.
Data Logging Operation
The digital display shall monitor the system and A digitally set On Delay (Sequential Start) timer
log the following data: shall be provided as standard. Upon a call to start, the
• Motor Calls/Starts • Elapsed Motor Run Time user interface shall display a message indicating the
• Last Trip Currents • Elapsed Power On Time remaining time value of the On Delay timer.
• Last Breaker Trip • Maximum Run Currents The controller shall be field programmable for
• Minimum Voltages • Minimum Run Currents manual stop automatic stop. If set for automatic stop-
• Maximum Voltages • Last Motor Run Time ping, the controller shall allow the user to select either
• Last Phase Failure • Last Start Currents a Minimum Run Timer or an Off Delay Timer. Both
• Last Phase Reversal • Min/Max Frequency timers shall be programmable through the user inter-
• Min/Max Pressure face.
Event Recording
Memory - The controller shall record all operational
and alarm events to system memory. All events shall
be time and date stamped and include an index num-
ber. The system memory shall have the capability of
storing 3000 events and allow the user access to the
event log via the user interface. The user shall have
the ability to scroll through the stored messages in
groups of 1, 10, or 100.
USB Host Controller - The controller shall have a
built-in USB Host Controller. A USB port capable of
accepting a USB Flash Memory Disk (aka: flash drive,
thumb drive, memory stick, etc..) shall be provided.
The controller shall save all operational and alarm events
to the flash memory on a daily basis. Each saved
event shall be time and date stamped. The total amount
of historical data saved shall solely depend on the size
of the flash disk utilized. The controller shall have the
capability to save settings and values to the flash disk
via the user interface.
Serial Communications - The controller shall fea-
ture a RS485 serial communications port for use with
2 or 4 wire Modbus RTU communications.
Solid State Pressure Transducer
The controller shall be supplied with a solid state
pressure transducer with a range of 0-300 psi (0-20.7
bar) ±1 psi. The solid state pressure switch shall be
used for both display of the system pressure and con-
trol of the fire pump controller. Systems using analog
pressure devices or mercury switches for operational
control will not be accepted.


…XXXGJSFUSPMDPN…4BMFT0GGJDF$BSZ /$64"
SP1000-20 (05-03-07) ‹$6&2
Position Qty. Description Single Price
1 CR 10-14 A-FJ-A-E-HQQE Price on request

Note! Product picture may differ from actual product

Product No.: 96500974


Vertical, non-self-priming, multistage, in-line,
centrifugal pump for installation in pipe systems
and mounting on a foundation.

The pump has the following characteristics:


- Impellers and intermediate chambers are made of
Stainless steel DIN W.-Nr. DIN W.-Nr. 1.4301.
- Pump head and base are made of Cast iron.
- The shaft seal has assembly length
according to EN 12756.
- Power transmission is via cast iron split
coupling.
- Pipework connection is via DINflanges.

The motor is a 3-phase AC motor.

Liquid:
Liquid temperature range: -20 .. 120 °C
Liquid temp: 20 °C
Density: 998.2 kg/m³

Technical:
Speed for pump data: 2919 rpm
Actual calculated flow: 50.4 US GPM
Resulting head of the pump: 322 ft
Shaft seal: HQQE
Approvals on nameplate: CE

Materials:
Pump housing: Cast iron
EN-JL1030
ASTM A48-30 B
Impeller: Stainless steel
DIN W.-Nr. 1.4301
AISI 304

Installation:
Maximum ambient temperature: 60 °C
Max pressure at stated temp: 16 bar / 120 °C
16/-20 bar / °C
Flange standard: DIN
Pipe connection: DN 40
Pressure stage: PN 16
Flange size for motor: FF265

Electrical data:
Motor type: 132SC
IE Efficiency class: IE2
Efficiency class: Efficiency class 1

Printed from Grundfos CAPS 1/6


Position Qty. Description Single Price
Number of poles: 2
Rated power - P2: 5.5 kW
Power (P2) required by pump: 5.5 kW
5.5 kW
Mains frequency: 50 Hz
Rated voltage: 3 x 220-240 D/380-415 Y V
Rated current: 19,4/11,2 A
Starting current: 1070-1170 %
Cos phi - power factor: 0,88-0,84
Rated speed: 2910-2930 rpm
IE efficiency: IE2 87,0%
Motor efficiency at full load: 87,0-87,0 %
Motor efficiency at 3/4 load: 90-89,5 %
Motor efficiency at 1/2 load: 88-87 %
Enclosure class (IEC 34-5): 55 (Protect. water jets/dust)
Insulation class (IEC 85): F

Others:
Net weight: 94 kg
Gross weight: 116 kg
Shipping volume: 0.43 m3

Printed from Grundfos CAPS 2/6


Description Value H CR 10-14 3* 400 V, 50 Hz
Product name: CR 10-14 A-FJ-A-E-HQQE (ft)
Product No: 96500974
EAN number: 5700396212838 400

Technical:
Speed for pump data 2919 rpm 300
Actual calculated flow: 50.4 US GPM
Resulting head of the pump: 322 ft
Head max: 469 ft 200
Impellers: 14
Shaft seal: HQQE Q = 50.3 US GPM
Approvals on nameplate: CE H = 322 ft
100
Stages: 14 Pumped liquid = Water
Pump version: A Liquid temperature = 20 °C Eta pump = 67.4 %
Model: A Density = 998.2 kg/m³ Eta pump+motor = 60.3 %
0
0 5 10 15 20 25 30 35 40 45 Q(US GPM)
Materials: P
Pump housing: Cast iron (kW)
EN-JL1030 P1
ASTM A48-30 B P2
4
Impeller: Stainless steel
3
DIN W.-Nr. 1.4301
AISI 304 2
Material code: A 1 P2 = 4.54 kW
Code for rubber: E 0 P1 = 5.07 kW
134
Installation: 220
Maximum ambient temperature: 60 °C
Max pressure at stated temp 16 bar / 120 °C
16/-20 bar / °C
Flange standard: DIN
Connect code: FJ
391

Pipe connection: DN 40
Pressure stage: PN 16
Flange size for motor: FF265

Liquid:
300
Liquid temperature range -20 .. 120 °C
Liquid temp: 20 °C G 1/2 G 1/2
Density: 998.2 kg/m³

Electrical data:
760

Motor type: 132SC G 1/2 18 x 20.2


IE Efficiency class: IE2 ø39
Efficiency class: Efficiency class 1 ø114
Number of poles: 2 ø150
20

Rated power - P2: 5.5 kW


80

Power (P2) required by pump 5.5 kW ø110 4 x ø13.5


130
5.5 kW 178 215
Mains frequency: 50 Hz 280 256
Rated voltage: 3 x 220-240 D/380-415 Y V
Rated current: 19,4/11,2 A
Starting current 1070-1170 %
Cos phi - power factor: 0,88-0,84
Rated speed: 2910-2930 rpm
IE efficiency: IE2 87,0%
Motor efficiency at full load: 87,0-87,0 % +T +T +T

Motor efficiency at 3/4 load: 90-89,5 %


Motor efficiency at 1/2 load: 88-87 %
CONNECTED TO AMPLIFIER RELAY FOR CONTROL OF MAIN SUPPLY

Enclosure class (IEC 34-5): 55 (Protect. water jets/dust)


IEC TP211 THERMALLY PROTECTED WHEN THE THERMISTORS ARE

Insulation class (IEC 85): F


Motor protec: PTC TO AMPLIFIER

Motor No: 85D07417 RELAY


L1 L2 L3
THERMISTORS PTC ACCORDING TO DIN 44082

Others:
Net weight: 94 kg
Gross weight: 116 kg
Shipping volume: 0.43 m3 +T +T +T

TO AMPLIFIER
RELAY
L1 L2 L3

Printed from Grundfos CAPS 3/6


96500974 CR 10-14 50 Hz

H CR 10-14 3* 400 V, 50 Hz
(ft) Q = 50.3 US GPM
H = 322 ft
Pumped liquid = Water
Liquid temperature = 20 °C
Density = 998.2 kg/m³

400

300

200

100

Eta pump = 67.4 %


Eta pump+motor = 60.3 %
0
0 5 10 15 20 25 30 35 40 45 50 Q(US GPM)
P
(kW)
6

5 P1
P2
4

1
P2 = 4.54 kW
0 P1 = 5.07 kW

Printed from Grundfos CAPS 4/6


96500974 CR 10-14 50 Hz

134

220
391

300

G 1/2 G 1/2
760

G 1/2 18 x 20.2
ø39
ø114
ø150
20
80

ø110 4 x ø13.5
130
178 215
280 256

Note! All units are in [mm] unless others are stated.


Disclaimer: This simplified dimensional drawing does not show all details.

Printed from Grundfos CAPS 5/6


96500974 CR 10-14 50 Hz

+T +T +T

CONNECTED TO AMPLIFIER RELAY FOR CONTROL OF MAIN SUPPLY


IEC TP211 THERMALLY PROTECTED WHEN THE THERMISTORS ARE
TO AMPLIFIER
RELAY
L1 L2 L3

THERMISTORS PTC ACCORDING TO DIN 44082


+T +T +T

TO AMPLIFIER
RELAY
L1 L2 L3

Note! All units are in [mm] unless others are stated.

Printed from Grundfos CAPS 6/6


JP

Model
Jockey Pump Controller
Full voltage across the line starter
Solid State Controls with Digital
Standard Features: Operator Interface
• Solid state controls with digital iPD+
operator interface
• All adjustments on door front
• Visual indicators
• Manual motor run
• Automatic motor run
• System pressure
• Automatic mode
• Off mode
• Motor overload
• Pump start counter
• Elapsed time meter (hours / non-resettable)
• Timers
• Minimum run period timer
• Sequential start timer
• Operators
• OFF-AUTO pushbutton
• Start and stop pushbuttons
• NEMA 2 enclosure
• Pressure transducer
• Fuseless magnetic motor starter

The model JP jockey pump controllers are specifically


designed to control jockey pumps in order to
maintain the desired water pressure in fire pump
serviced systems. A jockey pump installation prevents
unnecessary starting of the fire pump due to small leaks
in the sprinkler system piping.
The standard power circuit consists of a horsepower
The model JP jockey pump controller is supplied with the rated disconnect switch, a thermo-magnetic motor
front door mounted, solid state controls with digital iPD+ protector and a motor contactor for across the line
operator interface. The iPD+ allows the user to set and adjust full voltage starting. Consult factory for other types of
all parameters required such as start and stop pressures, motor protection or starting methods available.
ON or OFF timers and units of measure (psi, bar, kPA, feet of
head, meter of head) without having to open the controller Individual models are specific to the voltage available
door. The iPD+ also continuously displays the system on site:
pressure and the start and stop pressure settings. LED visual • JP1: 120 V / Hp (kW) / single phase / 60Hz
indications include manual motor run, automatic motor • JP2: 220 to 240 V / Hp (kW) / single phase / 50 or 60Hz
run, system pressure above stop pressure setting, system • JP3: 208 to 600 V / Hp (kW) / three phase / 50 or 60Hz
pressure in-between start and stop pressure setting and SEISMIC COMPLIANT

system pressure below start pressure setting.


ICC-ES AC156
IBC 2015
CBC 2013
JP
Model
7

Operator Interface

2
1

5
4

9 8

6
6 - OFF-AUTO position pushbutton and visual
indication (LED)
7 - Horsepower rated door interlocked rotary
type disconnect switch
1 - High luminosity four digit digital display 8 - Fuseless magnetic motor starter with
2 - System status diagnostic LED’s for: thermo-magnetic motor protector and
i. Green: system pressure at or above cut-out horsepower rated contactor
value 9 - Pressure transducer with 0-600psi
ii. Yellow: system pressure between cut-in range and 316 stainless steel construction
and cut-out
iii. Red: system pressure at or below cut-in value
3 - Motor run LEDs (manual start or automatic start)
4 - Start and stop pushbuttons
5 - Navigation keypad
HOW TO ORDER: JPx - V / HP / Ph / Hz
Ex.: JP3 - 208 / 2 / 3 / 60

Americas Europe Middle East Asia


Tornatech Inc. USA Sales Tornatech S.P.R.L. Tornatech FZE Tornatech Pte Ltd.
Head Office Representatives Avenue Sabin 3 Warehouse RA08CC04 3 Soon Lee Street #05-33
7075, Pl. Robert-Joncas Toll Free: + 1 800 363-8448 1300 Wavre Jebel Ali North Pioneer Junction
Suite # 132 Cincinnati, Ohio Belgium PO Box 18435 Singapore 627606
Montreal, Canada Cell: + 1 513 307 6766 Tel.: + 32 (0) 10 84 40 01 Dubai, Tel.: + 65 6795 8114
H4M 2Z2 Birmingham, Alabama Fax: + 32 (0) 10 24 75 05 United Arab Emirates + 65 6795 7823
Tel.: + 1 514 334 0523 Cell: + 1 205 902 9331 Tel.: + 971 (0)4 887 0615 Fax: + 65 6795 3201
+ 1 800 363 8448 Latin America Fax.: + 971 (0)4 887 0604
Fax: + 1 514 334 5448 Sales Representative
Tel.: + 1 514 334 0523
Cell: + 1 514 945 4067

JP-BRO-002/E Rev.10 August 2015 Printed in Canada


tornatech.com
*The information contained in this brochure is subject to change without notice.
FTA550F Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Product Description

· Low Pressure indication


· Failed to start indication
· Main switch not in “Auto” alarm
· Pressure recording
· Event log (3000 events stored in controller
memory)
· Data log (including cycle counter)
· Door mounted display/user interface featuring
a 128 x 64 pixel backlit LCD Graphical Display,
Membrane Type User Controller Push-buttons
and LED indication for:
· Power ON
· Pump Running
· Alarm
· 2 lines of user selectable display information
Description—Firetrol® FTA550F XG Jockey Pump
Controllers are intended for use with fire pump
systems. They are used for pressure maintenance NOTE: FTA550F XG Jockey Pump Controllers are
in fire pump installations to prevent unnecessary only available in the voltage/horsepower
operation of the main fire pump. combinations shown below and with the op-
tions shown on the reverse side. For other
Approvals—Firetrol jockey pump controllers are combinations and options, see documen-
listed by Underwriters’ Laboratories, Inc., in ac- tation for FTA550E series XG Jockey Pump
cordance with UL508A, Standard for Industrial Controllers.
Controls, and CSA, Standard for Industrial Control
Equipment. They are built to meet or exceed the VOLTAGE 3-PHASE MAX HP Short Circuit
requirements of the approving authorities as well (50/60 Hertz) (MCP) Current Rating
as NEMA and the latest edition NFPA 70, National
Electrical Code. -H 200-208 7.5 30kA
-A 220-240 10 30kA
Standard Features—The following are included as -F 380-415V - WYE 15 30kA
standard with each controller: -B 440-480V - WYE 20 30kA
· NEMA Type 2/12 (IEC IP11/IP52) Polycarbonate -C 550-600V - WYE 20 18kA
enclosure (UL50E Construction)
· Horsepower rated motor circuit protector and VOLTAGE 1-PHASE MAX HP Short Circuit
starting contactor (50/60 Hertz) (MCP) Current Rating
· Suitable for use as service equipment
· HAND-OFF-AUTO selector switch -D 110-120 Volts 2 30kA
· Minimum run timer -T 200-208 Volts 3 30kA
· On-Delay timer -E 220-240 Volts 3 30kA
· Pump Restart Timer
· Control circuit transformer with 24VAC
secondary
· 0-300 psi (0-20.7 bar) stainless steel solid state NOTE: Firetrol Brand Jockey Pump controllers DO NOT
pressure transducer CONTAIN MERCURY filled pressure switches.
· Overpressure indication