Professional Documents
Culture Documents
SPR3 EN TCD210147AB Modi 20211008 CATALOG W
SPR3 EN TCD210147AB Modi 20211008 CATALOG W
SPR 3 - ❶ ❷ ❸ ❹ ❺
❶ Rated load voltage ❹ Feedback control
1: 110 VACᜠ N: Normal control
3-Phase Slim
2: 220 VACᜠ F: Normal, feedback control (constant
3: 380 VACᜠ current / constant voltage / constant
4: 440 VACᜠ power)
Power Controllers
❷ Rated load current ❺ Fuse
Number: Rated load current (unit: A) N: None
F: Supports fuse
❸ Option output
N: Alarm output
T: Alarm output + RS485 comm. output
Product Components
• Product • Instruction manual
• 11-pin connector × 1 • Insulating barrier × 4
Software
Download the installation file and the manuals from the Autonics website.
■ DAQMaster
It is the comprehensive device management program for Autonics' products, providing
parameter setting, monitoring and data management.
Specifications
Model SPR3-1▭ SPR3-2▭ SPR3-3▭ SPR3-4▭
Control phase 3-Phase
110 VACᜠ 50 / 220 VACᜠ 50 / 380 VACᜠ 50 / 440 VACᜠ 50 /
Rated load voltage
60 Hz 60 Hz 60 Hz 60 Hz
Rated load current 25 / 35 / 50 / 70 / 100 / 150 A
Display method 3-digit 7segment LED
Operation / manual control indicator (green)
Indicators
Alarm / output / unit (V, A) indicator (red)
Current: DC 4 - 20 mA, voltage: 1 - 5 VDCᜡ, contact (non-voltage): ON / OFF,
Auto control input
contact (voltage): 5 - 12 VDCᜡ, communication: RS485
Manual control input External adjuster (10 kΩ), output control adjuster (OUT ADJ)
SPR3 Series
Digital input (DI) RUN / STOP selectable, AUTO / MAN selectable, RESET
Alarm output 250 VACᜠ 3 A, 30 VDCᜡ 3 A, 1c resistance load
CATALOG
RS485 comm. output Modbus RTU method
Rated load current 25 / 35 / 50 A: natural cooling
Cooling method
Rated load current 70 / 100 / 150 A: forced air cooling (with cooling fan)
Rated load current 25 / 35 / 50 A: ≈ 4.1 kg (≈ 4.9 kg)
Unit weight
Rated load current 70 A: ≈ 4.2 kg (≈ 5 kg)
(packaged)
Rated load current 100 / 150 A: ≈ 8.7 kg (≈ 9.7 kg)
For your safety, read and follow the considerations written in the instruction
Approval ᜢ
manual, other manuals and Autonics website.
The specifications, dimensions, etc. are subject to change without notice for product Control method Phase control Cycle control ON/OFF control
improvement. Some models may be discontinued without notice. Normal /
constant current feedback /
Control mode Fixed cycle -
constant voltage feedback /
constant power feedback
Resistance load, Resistance load,
Applied load Resistance load
Features
inductive load inductive load
Output range 0 to 98 % 0 to 100 % 0 / 100 %
Normal control: within ± 10 % F.S. of rated load voltage
• Slim and elegant design Phase control Constant current feedback control: within ± 3 % F.S. of rated load current
output accuracy Constant voltage feedback control: within ± 3 % F.S. of rated load voltage
• LED display allows real-time monitoring of control input, load voltage, load current, Constant power feedback control: within ± 3 % F.S. of rated load power
load power, load resistance, and heat-sink temperature
Power supply 100 - 240 VACᜠ ±10 % 50 / 60 Hz
• Stable control with feedback control (constant current, constant voltage, constant
Min. load current 1A
power) Rated load current 25 / 35 / 50 A: ≤ 14 VA
Power
• Communication output models available: RS485 (Modbus RTU) Rated load current 70 A: ≤ 22 VA
consumption
Rated load current 100 / 150 A: ≤ 32 VA
• Parameter configuration via PCs (RS485) : Free device management software Insulation
≥ 200 MΩ (500 VDCᜡ megger)
(DAQMaster) resistance
Dielectric strength Between input and power terminal: 2,000 VACᜠ 50 / 60 Hz for 1 min
• Various alarm functions (alarm output) : overcurrent, overvoltage, heater
Output leakage
disconnection, fuse break, heat-sink overheat, diode (SCR) error ≤ 10 mArms
currents
• Easy installation with mounting brackets Noise immunity ±2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
Memory retention ≈ 10 years (when using non-volatile semiconductor memory type)
• Easy fuse replacement and maintenance
0.75 mm double amplitude at frequency of 5 to 55 Hz (for 1 min) in
Vibration
• Inter phase insulating barrier included each X, Y, Z direction for 2 hours
Vibration 0.5 mm double amplitude at frequency of 5 to 55 Hz (for 1 min) in each
• High performance SCR (IXYS) diode (malfunction) X, Y, Z direction for 10 min
Ambient temp. -10 to 55 ℃, storage: -20 to 80 ℃ (no freezing or condensation)
Ambient humi. 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
ᜢ
-|Transparent Guide|-
Dimensions 13
11
• Unit: mm, For the detailed drawings, follow the Autonics website. 12 13
■ Rated load current 25 / 35 / 50 A U V W
105 01. Bracket [except rated load current 100 / 150 A model]
92.2 261 02. Indicator
68 4-Ø6 203.1
Indicator Function
6.8
200
Derating Curve
25
■ Rated load current 100 / 150 A ■ Rated load current 25 A ■ Rated load current 35 A
170
Load current [A]
158 326.5 25 35
140 4 - Ø 6.5 233.2
20 28
15 21
30
10 14
5 7
0 0
80 0 10 20 30 40 50 55 60 70 0 10 20 30 35 40 50 55 60 70
Ambient temp.[℃] Ambient temp.[℃]
80
270
210
50 70
40 56
30 42
25
20 28
10 14
0 0
0 10 20 25 30 40 50 55 60 70 0 10 20 30 35 40 50 55 60 70
Ambient temp.[℃] Ambient temp.[℃]
100 150
80 120
60 90
40 60
20 30
0 0
0 10 20 30 35 40 50 55 60 70 0 10 20 25 30 40 50 55 60 70
Ambient temp.[℃] Ambient temp.[℃]